ICP DAS USA DFS2H318J2A, DFS2A324J2A, DFS2A318J2A, DFS2H324J2A User Manual

Cooling Model
DFS2A318J2A DFS2A324
J2A
Heat Pump
DFS2H DFS2H
318J2A 324J2A
R-22
51302618919-A 0606
DFS2A/H 2 X 09, 2 X 12
Duct Free Systems
Installation, Start-Up and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS................................1
GENERAL...........................................................1-4
INSTALLATION ................................................4-11
Indoor Unit Installation ........................................4
Outdoor Unit Installation .....................................6
Power Supply .......................................................7
Leak Test ............................................................... 7
START-UP ........................................................... 11
System Checks................................................... 11
CARE AND MAINTENANCE............................... 11
Outdoor Units .....................................................11
Indoor Units ........................................................11
To Clean the Indoor Unit Front Panel ............... 11
To Clean Indoor Coil .......................................... 11
Air Filters for Indoor Units ................................ 11
SERVICE ............................................................. 11
TROUBLESHOOTING....................................12-15
Page
Consult local building codes and National Electrical Code (NEC, U.S.A.) for special installation requirements.
Max. cable length. Total voltage drop should not exceed 1V. Therefore max. length:
For #18 AWG 24.3 Feet (7.4 m) For #16 AWG 37.7 Feet (11.5 m) For #14 AWG 50.0 Feet (18 m)
Use only type "G" or "C" fuses. Use single length power cable without extension. Allow sufficient space for airflow clearance on condensing units for wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2 for minimum required distances between unit and walls or ceilings.
Indoor and outdoor units should be installed at a Minimum length of 10 ft. apart. Maximum line length of 50 ft. and vertical separation of 30 ft.
Do not install indoor units near a direct source of heat such as direct sunlight, steam or flame.
CAUTION
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be per­formed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equip­ment.
Follow all safety codes. W ear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
WARNING
Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect. There may be more than one disconnect switch. Electrical shock can cause personal injury.
GENERAL
These instructions cover the installation, start-up and servic­ing of DFC2A/DFC2H outdoor and DFF2A/DFF2H indoor units cool­ing only and heat pump duct free systems. See Table 1 for parts included. See Tables 2 and 3 for Physical Data.
Do not bury more than 36 in. of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. vertical rise to the valve connections on the outdoor units. If more than the rec­ommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refriger-ant slugging and could possibly damage the com­pressor at start-up.
TOP (min.) 2" (0.6m)
LEFT (min.) 6" (0.15m)
FRONT (min.) 2" (0.6m)
REAR (min.) 6" (0.15m)
RIGHT (min.) 2" (0.6m)
System Requirements
IMPORTANT: The Indoor units & the inter units cable voltage is 30 VDC.
IMPORTANT: Each refrigerant line must be insulated Separately. See line sizing requirements in tabel 2.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc. Printed in Israel
Fig. 1 — 38BCC/BCQ 018, 024 Outdoor Unit Clearances
Pg 1
1
Table 1 — Parts List — High Wall Units
ITEM QTY DIAGRAM
Mounting Bracket 2 X 1
Long Screws 2 X 8
Outdoor Sensor
Connecting Cable 2 X 1
Absorption Cushions 4
DFF2A/DFF2H 09, 12
(Available for HEAT PUMP ONLY)
Electric Terminals 2 X 8
2 X
Remote Controller 1 Mounting
Mounting Bracket Bracket with 2 screws
Remote Controller 2 X 1
and Batteries
Insulation for indoor Fittings 2 X 1
Owner's Manual 2 X 1
ECONOMY
TURBO-JET
1
Wall mounted Receiver RTX (OPTIONAL)
(Not included)
2
Table 2 - Physical Data - Cooling Only
INDOOR UNIT 2 X DFF2AH09J1A 2 X DFF2AH12J1A
COOLING CAPACITY (Btuh) 2 X 9,000 2 X 11,400
SEER 13.0 13.0 SYSTEM CHARGE (Ib)* 2 X 2.4 2 X 3.1 MOISTURE REMOVAL (pt/hr) 2 X 2.6 2 X 4.5 AIRFLOW (3 Speeds)
High / Med. / Low Cfm DIMENSIONS LxHxW (in.) 32 3/32x10 15/64x7 9/32 32 3/32x10 15/64x7 9/32 REFRIGERANT TYPE R-22 R-22 NET WEIGHT (Ib) 2 X 19.0 2 X 19.0
OUTDOOR UNIT DFC2A318J2A DFC2A324J2A
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft) NOMINAL LINE SIZING
Mixed Phase...Suction (in.) COMPRESSOR TYPE Panasonic-2R13S126A6F Panasonic-2P17SR126B1A DIMENSIONS LxHxW(in.) NET WEIGHT (Ib) 226 228 METERING TYPE Piston (Accurator) Piston (Accurator) LEGEND SEER — Seasonal Energy Efficiency Ratio *Units are shipped with a factory charge based on 25 ft of refrigerant lines.
2 X 350 / 2 X 280 / 2 X 220 2 X 370 / 2 X 280 / 2 X 220
30/30/50 30/30/50
1/4...1/2 1/4...1/2
35.5 X 49.5 X 12.6 35.5 X 49.5 X 12.6
INDOOR UNIT 2 X DFF2HH09J1A 2 X DFF2HH12J1A
COOLING CAPACITY (Btuh) 2 X 9,000 2 X 11,400
SEER 13.0 13.0 HEATING CAPACITY (Btuh) 17,200 23,600
HSPF 7.7 7.7 SYSTEM CHARGE* (Ib) 2 X 2.4 2 X 3.1 MOISTURE REMOVAL (pt/hr) 2 X 2.6 2 X 4.5 AIRFLOW (3 Speeds)
High / Med. / Low Cfm DIMENSIONS LxHxW (in.) 32 3/32x10 15/64x7 9/32 32 3/32x10 15/64x7 9/32 REFRIGERANT TYPE R-22 R-22 NET WEIGHT (Ib) 2 X 19.0 2 X 19.0
OUTDOOR UNIT DFC2H
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft) NOMINAL LINE SIZING
Mixed Phase...Suction (in). COMPRESSOR TYPE Panasonic-2R13S126A6F Panasonic-2P17SR126B1A DIMENSIONS LxHxW (in.) SHIPPING WEIGHT (Ib) 226 228 METERING TYPE Piston (Accurator) Piston (Accurator)
LEGEND
HSPF - Heating Seasonal Performance Factor SEER - Seasonal Energy Efficiency Ratio
*Units are shipped with a factory charge based on 25 ft of refrigerant lines. NOTE: Standard Ambient Operating Limitations - 55 °F to 125 °F (12.7 °C to 51.6 °C).
Table 3 - Physical Data - Heat Pump
2 X 350 / 2 X 280 / 2 X 220 2 X 370 / 2 X 280 / 2 X 220
318J2A DFC2H324J2A
30/30/50 30/30/50
1/4...1/2 1/4...1/2
35.5 X 49.5 X 12.6 35.5 X 49.5 X 12.6
3
6" (0.15m)
min.
8"
(0.2m)
min.
6'-8'3"
(1.8-2.5m)
8"
(0.2m)
min.
Fig. 2 — Indoor Unit Clearances
INSTALLATION
Plan the installation carefully to avoid component failures
and make installation easier.
Indoor Unit Installation
REFRIGERANT LINE ROUTING — The refrigerant lines may be routed in any of the four directions shown in Fig. 3.
INSTALL THE MOUNTING BRACKET
1. Carefully remove the mounting bracket, which is connected to the back of the indoor unit's base with screws.
2. Position the mounting bracket on the wall and level it using a spirit level (see Fig. 2 for minimum required clearance distances).
3. Mark the four drilling holes on the wall, as they appear in Fig. 4.
4. Drill the holes, insert the wall plugs and use four long screws to attach the mounting bracket to the wall.
5. Check that the bracket is leveled and securely fastened to the wall.
DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER-UNIT CONNECTIONS-
To make the connections between the indoor and outdoor units, drill a 2.5-in. hole through the wall for the refrigerant lines, drain­age hose and control cable passage as shown in Fig. 5.
1. Mark the center of the hole to be drilled according to the refrigerant line routing used and dimensions shown in Fig.
4.
2. Make sure to drill outwards and downwards, so that the opening in the outside wall is at least 1/2" lower than the opening on the inside.
3. Make sure the drainage hose is at the bottom side of the hole.
4 . If refrigerant line route no. 1,2 or 4 are used, use a small
saw blade to carefully remove the corresponding plastic covering on the side panel.
5. Run the outdoor sensor cable, electrical cable, refrigerant lines, and drainage tube through the hole.
6. Fill the remaining wall hole gap with an appropriate sealant material.
2
3
1
4
Fig. 3 — Refrigerant Lines
Fig. 4 — Mounting Bracket DFF2A/DFF2H 09, 12
2.5-IN.
Fig. 5 — Drill Holes
4
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
FUSE
AUTO/OFF
FILTER RESET
SERVICE LED
POWER/AIRCOND
TIMER
FUSE
AUTO/OFF FILTER RESET
SERVICE LED
AUTO/OFF FILTER RESET
SERVICE LED
WIRE THE INDOOR UNIT
1. Strip the cables back 1/4 inch.
2. Remove the unit's front panel by lifting the lower part and pulling it gently outward and upward. See Fig. 6.
3. Remove the two screws from the control box cover and take off the cover. See Fig. 7. Save the screws to reassemble.
NOTE: In general wiring the indoor unit does not require the removal of the grille frame but in case of need do as follow:
4. Remove the two screws from the air discharge opening. Save the screws to reassemble. See Fig. 7A.
Pull downwards and outwardston the bottom of the grille and gently raise the frame of the top of the unit.
Once all covers are off, mount the unit onto the wall mounting bracket. See Fig. 8 .
NOTE: Leave covers off until after the Making Drainage Con­nections section.
Route the interconnecting unit's electric cable and the outdoor sensor cable towards the lower right hand corner of the indoor unit.
Make sure that the wires are connected in accordance with the wiring diagram on the inside of the unit front cover or within this instruction manual.
Secure the control cables to the strain relief.
For heat pump systems only, connect the outdoor sensor TH3 to its mating black terminal. See Fig. 9.
REASSEMBLE
1. Connect the display connector to the display panel printed circuit board.
2. Put the control box cover and grille frame back on using the appropriate screws (Steps 3 and 4 of Wire the Indoor Unit section). Put the grille insert back on.
Fig. 6 — Remove Grille Insert
Fig. 7 — Remove Control Cover
CAUTION
Make sure that all wires and screws are firmly fastened. Loose wires or connections can cause damage and present a fire hazard.
MAKE DRAINAGE CONNECTIONS
1. Connect the unattached end of the drainage tube to the drainage hose outlet.
2. Seal the drainage connection to prevent leakage.
3. Make sure there are no kinks, "U" bends or flattened sections in the tube.
4. Check that the drainage functions properly. Fill the pan below the unit's coil with water and observe that it freely drains out.
5. Make sure the drainage hose is at the bottom side of the wall through-hole (see Fig. 5).
Standard Dip Switches status from the factory
Model-2 X12 DIP Switches location
Models-2 X 09 DIP Switches location
Model-2 X12 DIP Switches location
Models-2 X09 DIP Switches location
HEAT PUMP
(on the Control Box side)
HEAT PUMP
(on the Control Box side)
COOLING ONLY
(on the Control Box side)
COOLING ONLY
(on the Control Box side)
Fig. 9 — Outdoor Sensor Connection
Fig. 7A - Remove the screws from the air
discharge opening.
Mount the indoor unit on the mounting bracket
1
2
Gently push with the arrow direction
Fig. 8 — Indoor Unit Mounting
Inter unit
terminal block
30VDC
Display
Connection
TH1 TH2
TH3
(Heat Pump Only)
Inter unit cable clamp
5
Loading...
+ 10 hidden pages