ZT-2053 - 14-channel DI Module with Counters- QuickStart (Sep/2017)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1 -310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
1
ZT-2053
ZigBee Wireless Module with 14 Digital Input
Channels
Quick Start Guide
Product Website:
https://www.icpdas-usa.com/zt_2053
Introduction
The ZT-2053 offers 14 digital input channels which can be used for either dry or
wet contact. Its effective distance for dry contact is up to 500 meters. All channels
are able to be used as 16-bit counters. The ZT-2053 includes 14 LED indicators to
display the channel status as well as 4 kV ESD protection and 3750 Vrms intramodule isolation. Users can easily to configure the module address, protocol,
checksum, ZB-PID and ZB-channel settings using a combination of rotary and DIP
switches.
1
What’s in the Shipping Package?
The shipping package contains the following items:
ZT‐2053 DIO Device ANT‐124‐05 Quick Start
![](/html/8e/8e0b/8e0b31f6ce6a434259ba41995db5d6abf54043877eb7061bd11315e7848c06f0/bg2.png)
ZT-2053 - 14-channel DI Module with Counters- QuickStart (Sep/2017)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1 -310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
2
2
Preparing the Device
1. Refer the chapter 3. to configure the DIP switch of ZT-2053 I/O device.
2. Install the ZT Configuration Utility to configure the ZT-2053 coordinator. CD:
\Napdos\ZigBee\ZT_Series\Utility
http://ftp.icpdas.com/pub/cd/usbcd/napdos/zigbee/
zt_series/utility
3. Power Supply: +10 ~ +30 V
DC
3
Setting up the ZT‐2053 DIO Device
3.1 Introduction to the Configuration Parameters
A. “Pan ID” parameter is the group identity for a ZigBee network, and must the same
for all devices in the same ZigBee network.
“Address/Node ID” parameter is the individed identity of a specific the ZigBee
module, and must be unique for each device connected the same ZigBee network.
B. “RF Channel” parameter indicates the radio frequency channel, and must be set to the
same value as other modules on the same ZigBee network.
Channel
※
RF channels 0x04, 0x09, 0x0E or 0x0F are recommended because they do not overlap
with the Wi-Fi frequencies based.
802.11b/g Channel (North America)
802.15.4 Channel
C. Protocol/Application Mode:
![](/html/8e/8e0b/8e0b31f6ce6a434259ba41995db5d6abf54043877eb7061bd11315e7848c06f0/bg3.png)
ZT-2053 - 14-channel DI Module with Counters- QuickStart (Sep/2017)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1 -310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
3
When implementing custom programs based on different protocols, the following
application modes are recommended in order to ensure
communicatible
User Program Protocol
DCON
Modbus RTU
Modbus TCP
ZT-2053 I/O
![](/html/8e/8e0b/8e0b31f6ce6a434259ba41995db5d6abf54043877eb7061bd11315e7848c06f0/bg4.png)
4
Rotation Switch and DIP Switch
The configuration of ZT-2053 series can be adjusted by using the external rotary
switch and the DIP switches. The ZT-2053 device should only be rebooted once the
configuration is complete.
DIP Switch to the ZT‐2042/ZT‐2043/ZT‐2053/ZT‐2055
Protocol Pan ID
ON
DIP Switch to the ZT‐2053/ZT‐2060
ZT-2053 - 8-channel DI DAQ module - QuickStart (Nov/2016)
ICP DAS USA, In c. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
Protocol
Pan ID
4