ICPDAS UA-5000 User Manual

ICP DAS CO., LTD.
UA-5000 Series User Manual
IIoT Communication Server
ICP DAS CO., LTD. All Rights Reserved.
www.icpdas.com
2
Warranty
All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, starting from the date of delivery to the original purchaser.
Warning
ICP DAS Inc., LTD. assumes no liability for damages consequent to the use of this product. ICP DAS Inc., LTD. reserves the right to change this manual at any time without notice. The information furnished by ICP DAS Inc. is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS Inc., LTD. for its use, or for any infringements of patents or other rights of third parties resulting from its use.
Copyright and Trademark Information
© Copyright 2015 by ICP DAS Inc., LTD. All rights reserved worldwide.
Trademark of Other Companies
The names used for identification only maybe registered trademarks of their respective companies.
License
The user can use, modify and backup this software on a single machine. The user may not reproduce, transfer or distribute this software, or any copy, in whole or in part.
Technical Service:
Please contact local agent or email problem-report to service@icpdas.com . For more product information, please refer to www.icpdas.com .
Technique: Sun Chen; Translation & Edition: Eva Li/Janice Hong ; R&D Dept., ICP DAS CO., LTD.
V.1.0.0 , Aug. 2015
UA-5000 Series User Manual V.1.0.0 ICP DAS
3
Table of Contents
1. UA-5000 IIoT Communication Server ........................................................................................................ 5
1.1. Introduction ...................................................................................................................................... 5
1.2. Function Features ............................................................................................................................. 6
1.3. Hardware Specifications ................................................................................................................... 7
1.4. Software Specifications ..................................................................................................................... 8
1.5. Appearance ....................................................................................................................................... 9
2. Quick Start ............................................................................................................................................... 11
2.1. Link to UA-5000 Web-based UI ....................................................................................................... 11
2.2. Add Variables in the Variable Table ................................................................................................ 15
2.3. Start a Built-in MQTT Broker ........................................................................................................... 18
2.4. Set Up the Driver, Virtual Device and Service ................................................................................. 19
2.4.1. Set up the Driver ................................................................................................................. 20
2.4.1.1. Example of the Modbus Driver settings................................................................ 20
2.4.1.2. Example of the MQTT Driver settings ................................................................... 24
2.4.2. Set Up the Virtual Device .................................................................................................... 28
2.4.2.1. Example of the PID settings .................................................................................. 28
2.4.3. Set Up the Service ............................................................................................................... 31
2.4.3.1. Set up the OPC UA Service .................................................................................... 31
2.4.3.2. Example of the MQTT Service ............................................................................... 31
2.5. Start the RunTime ........................................................................................................................... 36
3. System Functional Description ................................................................................................................ 37
3.1. System Management ...................................................................................................................... 37
3.1.1. System Information ............................................................................................................. 37
3.1.2. Main system setting ............................................................................................................ 38
3.1.3. MQTT Broker Setting ........................................................................................................... 39
3.1.4. Save the System Management settings .............................................................................. 39
3.2. Variable Setting ............................................................................................................................... 40
3.3. Driver ............................................................................................................................................... 42
UA-5000 Series User Manual V.1.0.0 ICP DAS
4
3.3.1. Modbus Master ................................................................................................................... 42
3.3.1.1. RTU ........................................................................................................................ 43
3.3.1.2. TCP ........................................................................................................................ 46
3.3.2. MQTT ................................................................................................................................... 49
3.4. Virtual Device .................................................................................................................................. 52
3.4.1. PID ....................................................................................................................................... 52
3.5. Service ............................................................................................................................................. 54
3.5.1. OPC UA ................................................................................................................................ 54
3.5.1.1. Redundancy Settings ............................................................................................. 54
3.5.1.2. Security ................................................................................................................. 55
3.5.2. MQTT ................................................................................................................................... 56
4. Technical Reference Websites ................................................................................................................. 59
OPC UA ...................................................................................................................................................... 59
MQTT ........................................................................................................................................................ 59
Modbus ..................................................................................................................................................... 59
UA-5000 Series User Manual V.1.0.0 ICP DAS
5
1. UA-5000 IIoT Communication Server
This chapter introducts the UA-5000 and its functions, software/hardware specifications...
1.1. Introduction
The UA-5000 is a series of data acquisition controller and also an IIoT communication server by ICP
DAS (IIoT: Industrial Internet of Things). The UA-5000 built-in OPC UA Server and MQTT Client
Service support a variety of common industrial communication protocols. Its RISC-based CPU
architecture has the advantages of small size and low power consumption that lets this series can
be placed in a small space to fit variety of rooms, equipment and case environment. In the
hardware, it provides a variety of communication interfaces, such as Gigabit Ethernet, USB, RS-232
and RS-485… ports to connect diverse devices.
Applying OPC UA can integrate the I/O products of ICP DAS with the third-party devices, import
the data information to the SCADA, database or decision-making systems for the back-end
management, and satisfy the reliability, interoperability and security needs of the industrial
automation system. Using MQTT communication can bridge the system with the Internet of
Things (IoT) to meet the current trend of the smart internet.
UA-5000 Series User Manual V.1.0.0 ICP DAS
6
1.2. Function Features
Web-based UI
With the Web-based User Interface, users can log in and configure the controller via a normal web browser that only need a mobile device or computer with web browsing capabilities.
OPC UA Server: IEC 62541 Standard
The OPC UA Server certified by the OPC Foundation can assist the integration for the local-end devices, actively upload data to the application system, and support to across the multiple platforms.
PID Logic Operation
The PID function can dynamically combine the remote I/O devices for the PID logic control to provide temperature control and case field solutions.
Support Modbus TCP/RTU Master
Through the controller's RS-485, RS-232 and Ethernet ports can connect to the Modbus TCP/RTU Slave devices. Build systems with scalability and flexibility to meet the diverse application needs and expansion at any time.
MQTT Broker Inside
Compliance with MQTT v3.1.1 protocol. Support MQTT message distribution management. Users do not need to build Broker system when using MQTT communications.
Support MQTT Protocol
Support MQTT to allow the IoT devices communicating with the OPC UA system and the UA-5000 conducting the data acquisition and management; and also can convert and publish the devices' data under the UA-5000 to the IoT system.
UA-5000 Series User Manual V.1.0.0 ICP DAS
7
1.3. Hardware Specifications
Model
UA-5231
UA-5241
System Software
OS
Linux Kernel 3.2.14
Embedded Service
SFTP server, Web server, SSH
CPU Module
CPU
AM3352, 720 MHz
DDR3 SDRAM
512 MB
Flash
256 MB
FRAM
64 KB
Expansion Flash Memory
microSD socket with one 4 GB microSD card (support up to 32 GB microSDHC card)
RTC (Real Time Clock)
Provide second, minute, hour, date, day of week, month, year
64-bit Hardware Serial Number
Yes, for Software Copy Protection Dual Watchdog Timers
Yes
LED Indicators
4 LEDs (Power, Running and 2 user defined LEDs)
Rotary Switch
Yes (0 ~ 9)
VGA & Communication Ports
VGA & Communication Ports
Yes, resolution: 640 × 480, 800 × 600, 1024 × 768, 1280 x 720
Ethernet RJ-45 x 1
RJ-45 x 2
10/100/1000 Based-TX ( Auto-negotiating, Auto MDI/MDI-X, LED indicators)
USB 2.0 (host)
1
Console Port
RS-232 (RxD, TxD and GND); Non-isolated
ttyO2
RS-485 (Data+, Data-); Non-isolated
ttyO4
RS-232 (RxD, TxD and GND); Non-isolated
ttyO5
RS-485 (Data+, Data-); 2500 VDC isolated
Mechanical
Dimensions (W x L x H)
91 mm x 132 mm x 52 mm
Installation
DIN-Rail Mounting
Environmental
Operating Temperature
-25 ~ +75°C
Storage Temperature
-30 ~ +80°C
Ambient Relative Humidity
10 ~ 90% RH (non-condensing)
Power
Input Range
+12 ~ +48 VDC
Consumption
4.8 W
UA-5000 Series User Manual V.1.0.0 ICP DAS
8
1.4. Software Specifications
Model
UA-5000 Series
OPC UA
OPC UA Server
OPC Unified Architecture: 1.02 Core Server Facet Data Access Server Facet Method Server Facet Client Redundancy Facet UA-TCP UA-SC UA Binary User Token User Name Password & X509 Certificate Security Policy
None
Basic128Rsa15
• Sign
• Sign & Encrypt
Basic256
• Sign
Sign & Encrypt
Modbus Master
Modbus TCP
To read or control the devices that support standard Modbus TCP Slave protocol. Recommend to keep the maximum number of devices within 100 connections.
Modbus RTU
A max. of 3 ports: ttyO2, ttyO4, ttyO5 to connect other Modbus RTU Slave devices (e.g. M-7000). Recommend no more than 32 devices per port for better communication quality.
MQTT
MQTT Client
Connect the MQTT Broker to read/control the devices supporting the MQTT protocol.
MQTT Service
Connect the MQTT Broker to externally read/control the devices supporting other protocols that linking with the UA-5000 series.
MQTT Broker
Compliance with MQTT v3.1.1 protocol. Support MQTT message distribution management. Recommend to keep the connection number of Client within 400.
Virtual Device
PID Function
Combine the remote I/O devices for the PID logic control system.
UA-5000 Series User Manual V.1.0.0 ICP DAS
9
1.5. Appearance
UA-5000 Series User Manual V.1.0.0 ICP DAS
10
UA-5000 Series User Manual V.1.0.0 ICP DAS
11
2. Quick Start
This chapter describes the process of creating a UA-5000 project, including how to connect to the UA-5000 web-based UI via a browser, set web functions step-by-step, and complete a project.
2.1. Link to UA-5000 Web-based UI
The following steps will show you how to connect to the UA-5000 web interface.
Using the UA-5000 Utility (named UA-5000utility.exe) at the path of the companion CD (i.e.,
CD:/UA-5000/Utility/). Please copy this file to your PC, and then run it to connect the device.
Step 1
Run the UA-5000 Utility (file name: UA-5000utility.exe).
UA-5000 Series User Manual V.1.0.0 ICP DAS
12
Step 2
Add a connection item and give a name for it.
Step 3
Mouse double-click on the name you created (or single-click and then click the Connect button), this utility will search and list all devices over the network.
1
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
13
Step 4
Click the device name you want to connect to, and then click the Connect button. It will connect to the UA-5000 web interface via the default browser.
Step 5
A login dialog box will appear, entering your user name and password, and then click OK. The factory default user name and password are root.
2
1
UA-5000 Series User Manual V.1.0.0 ICP DAS
14
Finish
After logging into the web interface, you can see the main configuration screen.
UA-5000 Series User Manual V.1.0.0 ICP DAS
15
2.2. Add Variables in the Variable Table
The following steps will show you how to add variables in the variable table.
Step 1
Click Variable Setting on the left to open the setting page.
Step 2
Click Add to add the needed variable.
UA-5000 Series User Manual V.1.0.0 ICP DAS
16
Step 3
Enter all related information for this variable and then click OK.
Now that your variable is set up.
UA-5000 Series User Manual V.1.0.0 ICP DAS
17
Step 4
Repeat the previous steps to add more wanted variables.
Step 5
Click the Save button to save the settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
18
2.3. Start a Built-in MQTT Broker
Step 1
Click System Management on the left tree-menu, and then click the MQTT Broker Setting tab in the right panel.
Step 2
Click Start to execute the Broker. When it marked in gray that means the Broker is running.
UA-5000 Series User Manual V.1.0.0 ICP DAS
19
2.4. Set Up the Driver, Virtual Device and Service
This article will describe the Driver, Virtual Device, and Service settings.
The user can also refer the Chapter 3 : System Function Description to view all features, properties and configuration notice on each setup item mentioned as follows.
Section 3.3 Driver Section 3.4 Virture Device Section 3.5 Service
All features follow the task-oriented and hierarchical architecture as the logical design. First of all, the user can add a connection task depends on device properties, and add the related command or the item table. Finally, you can complete two-level or three-level settings.
Description of the tool button:
: Add a task, command, or item. : Delete a task, command, or item. : Modify a task, command, or item.
Command
Task
Item Table
Item Table
UA-5000 Series User Manual V.1.0.0 ICP DAS
20
2.4.1. Set up the Driver
The Driver setting is divided into the Modbus Driver setting and the MQTT Driver setting.
2.4.1.1. Example of the Modbus Driver settings
In this example, we use Modbus TCP protocol to conduct the Modbus Driver setting. The user can also refer the Chapter 3 - System Function Description - Section 3.3 Driver to view all features, properties and configuration notice for each item mentioned in this section.
Step 1
Add all needed variables in the variable table. (See Section 2.2)
Step 2
On the tree menu to the left, click Driver > Modbus Master > TCP, and add a connection task.
1
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
21
Step 3
In the Task table, add a Modbus command and enter all parameters.
Step 4
After completing it, you can see this two-level (Task > Command) table.
1
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
22
Step 5
Then, you can choose a proper variable for a Modbus Address in the Item table.
Step 6
Repeat the previous steps to set up this table.
UA-5000 Series User Manual V.1.0.0 ICP DAS
23
Step 7
Save all settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
24
2.4.1.2. Example of the MQTT Driver settings
In this case, we will describe how does the MQTT Driver of UA-5000 series (i.e., UA-5231) communicate with the MQTTdevice. The user can also refer the Chapter 3 - System Function Description - Section 3.3 Driver to view all features, properties and configuration notice for each item mentioned in this section.
Step 1
Add all needed variables in the variable table. (See Section 2.2)
Step 2
Click Driver > MQTT on the left tree-menu to open the MQTT Driver page.
UA-5000 Series User Manual V.1.0.0 ICP DAS
25
Step 3
Add a MQTT Driver task. Enter task name and Broker settings, and then click OK.
Step 4
In the Item table, click Add to add variable and edit its topic.
1
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
26
Step 5
Enter the needed parameters, and then click OK.
Step 6
Now, you have successfully added this item.
UA-5000 Series User Manual V.1.0.0 ICP DAS
27
Step 7
Follow the previos steps to add several settings.
Step 8
Save the settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
28
2.4.2. Set Up the Virtual Device
Including the PID setting.
2.4.2.1. Example of the PID settings
In this section, we will describe the PID settings. The user can also refer the Chapter 3 - System Function Description - Section 3.4 Virture Device to view all features, properties and configuration notice for each item mentioned in this section.
Step 1
Add all needed variables in the variable table. (See Section 2.2)
Step 2
Set up the driver for the corresponding physical I/O. (See Section 2.4.1)
Step 3
Click on Virtual Device > PID to set up the PID.
UA-5000 Series User Manual V.1.0.0 ICP DAS
29
Step 4
Add one PID setting.
Step 5
Set up all parameters.
1
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
30
Step 6
Save all settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
31
2.4.3. Set Up the Service
The Service setting is divided into the OPC UA Service and the MQTT Service.
2.4.3.1. Set up the OPC UA Service
The OPC UA Server is a system service and enabled by default. When the user assign variables in the Driver and Virtual Device panels, the configuration for the OPC UA Server will also be done, that is, no more settings to do.
2.4.3.2. Example of the MQTT Service
The UA-5000s MQTT Service is used to convert other Drivers data into the MQTT message. Using a user-defined topic as an index to receive the data sending from other MQTT devices.
The following steps will show you the way to convert the Modbus Master Drivers data into the MQTT message. The user can also refer the Chapter 3 - System Function Description - Section 3.5
Service to view all features, properties and configuration notice for each item mentioned in this
section.
Step 1
Add all needed variables in the variable table. (See Section 2.2)
UA-5000 Series User Manual V.1.0.0 ICP DAS
32
Step 2
Set up the Modbus Driver, and assign variables to the Driver. (See Section 2.4.1)
Step 3
Set up the MQTT Service. Click Service > MQTT on the left.
Step 4
Add a task for this MQTT service. After completing it, click OK.
1
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
33
Step 5
Click the Add button under the Task tab you added before.
Step 6
In the pop-up Add dialog box, enter the needed variable and parameters. Then, click OK.
UA-5000 Series User Manual V.1.0.0 ICP DAS
34
Step 7
Now, you have successfully added this item.
Step 8
Repeat the previous steps to add several items.
UA-5000 Series User Manual V.1.0.0 ICP DAS
35
Step 9
Save all settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
36
2.5. Start the RunTime
This section will describe how to start the UA-5000 seriess RunTime.
When the user finish the project setting and want to start the system runtime, simply switch to the Main System Setting page in the System Management panel, and then click Start.
While Start is marked in gray, it means the system is running.
UA-5000 Series User Manual V.1.0.0 ICP DAS
37
3. System Functional Description
In the chapter, we will explain all functions and parameters on the following topics that listed in the UA-5000s Web UI (as the figure below).
3.1. System Management
This section will describe how to use the System Management function and save all settings. It includes the System Information, Main System and MQTT Broker settings.
3.1.1. System Information
To display or modify the system information.
Function items
Description
Default
IP Address
The IP address of the UA-5000.
System value
Netmask
The mask address of the UA-5000.
System value
Host Name
The host name of the UA-5000.
System value
User Name
The login name for the UA-5000s Web UI.
Password
The login password for the UA-5000s Web UI.
Date
Time/Time zone setting, NTP network time synchronization.
System value
UA-5000 Series User Manual V.1.0.0 ICP DAS
38
3.1.2. Main system setting
To display or modify the current status for the main system setting.
Function items
Description
Default
Main System status
Display the current status of the main system and allows switching this function.
Stop Run at startup
Whether to run at startup.
Uncheck
UA-5000 Series User Manual V.1.0.0 ICP DAS
39
3.1.3. MQTT Broker Setting
To display or modify the current status for the MQTT Broker setting.
Function items
Description
Default
MQTT Broker status
Display the current status of the Broker and allows switching this function.
Start Port
MQTT Brokers COM port.
1883
Run at startup
Whether to run at startup.
Uncheck
3.1.4. Save the System Management settings
Click the Modify button to save the currnt settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
40
3.2. Variable Setting
This section will describe how to add, edit and delete variables in the variable table, and then save the settings.
Description of the tool button:
: Add a variable : Delete the selected variable
: Edit the selected variable
1. In the Variable Table, you can add, edit and delete variables (as the figure below).
2. Add/Edit the variable.
Function items
Description
Default
Name
Variable name.
Name
Attribute
Variable attribute. Options : Read, Write, Read_Write
Read
Data Type
Variable data type. Options: Bool, Short, Unsigned Short, Long, Unsigned Long, Float, Double, String
Bool Size
Variable size. If this value is greater than 1, this variable will be declared as an array.
1 Description
Write a note for this variable.
UA-5000 Series User Manual V.1.0.0 ICP DAS
41
3. Click Ok to complete the setting.
4. Click “Saveto save the current settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
42
3.3. Driver
This section will describe the Driver setting and all related parameters for the UA-5000 series. This topic includes the Modbus Master (RTU and TCP) and the MQTT items.
3.3.1. Modbus Master
The following article will show you how to set up the Modbus Master Driver which is divided into RTU and TCP protocols.
Description of the tool button:
: Add a task, command, or item. : Delete a task, command, or item. : Modify a task, command, or item.
UA-5000 Series User Manual V.1.0.0 ICP DAS
43
3.3.1.1. RTU
This section will show you the way to add, edit, and delete the Modbus RTU Master Driver in the RTU page.
1. Edit the RTU task.
The Task settings:
Function items
Description
Default
Task Name
Give a task name.
Task1
Polling Rate
Set a time interval for the command.
500
Serial Settings
Port
Choose a serial port number. Please check which RS-232/485 port is in use. Note: The wrong setting will cause the communication error.
TtyO2 Baud Rate
Choose a baud rate. Make sure the modules baud rate is correct. Note: The wrong setting will cause the communication error.
115200
Data Bits
The number of bits used to represent one byte of data.
8
Parity
Choose one way for the parity checking. Options: None, Even, and Odd.
None Stop Bit
Choose the number of stop bit.
1
UA-5000 Series User Manual V.1.0.0 ICP DAS
44
2. Configure the command under the task tab.
The Command settings:
Function items
Description
Default
Command Name
Give a command name.
Command1
Function Definition
Data Model
Choose the data type for the Modbus command.
02 Input Status(1x)
Slave ID
Set the Slave ID of the UA-5000. (Range: 1 ~ 247)
1 Start Address
The start address of the Modbus command.
0
Length
The number of the Modbus address.
10
Timeout
Set the timeout value for the module.
500
UA-5000 Series User Manual V.1.0.0 ICP DAS
45
3. Set up the Variable and Swap items in the command tab.
Function items
Description
Default
Address
Modbus address.
Auto arrange
Variable
Choose the variable you set before. (See 3.2 Variable Setting)
Data Type
After selecting the variable, its data type will automatically display. (Not editable)
Swap
To swap 4-byte or 8-byte data into Low-to-High/High-to-Low order values.
True (enable) False (disable)
4. Click Save to save current settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
46
3.3.1.2. TCP
This section will show you the way to add, edit, and delete the Modbus RTU Master Driver in the TCP page.
1. Edit the TCP task.
The Task settings:
Function items
Description
Default
Task Name
Give a task name.
Task1
Polling Rate
Set an interval time for each command.
500
Ethernet
IP
The IP address of the connected device.
127.0.0.1
Port
The port number for Modbus TCP.
502
UA-5000 Series User Manual V.1.0.0 ICP DAS
47
2. Configure the command under the task tab.
The Command settings:
Function items
Description
Default
Command Name
Give a command name.
Command1
Function Definition
Data Model
Choose the data type for the Modbus command.
02 Input Status(1x)
Slave ID
Set the Slave ID of the UA-5000. (Range: 1 ~ 247)
1 Start Address
The start address of the Modbus command.
0
Length
The number of the Modbus address.
10
Timeout
Set the timeout value for the module.
500
UA-5000 Series User Manual V.1.0.0 ICP DAS
48
3. Choose the variable and the swap options in the command tab.
Function items
Description
Default
Address
Modbus address.
Auto arrange
Variable
Choose the variable you set before. (See 3.2 Variable Setting)
Data Type
After selecting the variable, its data type will automatically display. (Not editable)
Swap
To swap 4-byte or 8-byte data into Lo-to-Hi / Hi-to-Lo order values.
True (enable) False (disable)
4. Click Save to save the current settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
49
3.3.2. MQTT
This section will show you the way to add, modify, and delete the MQTT driver in the MQTT page.
Description of the tool button:
: Add a task, command, or item. : Delete a task, command, or item. : Modify a task, command, or item.
1. Edit the MQTT task.
The Task settings:
Function items
Description
Default
Task Name
Give a task name.
Task1
Broker Setting
IP
The IP address of the Broker.
Syatem value
Port
The Broker port.
1883
Keepalive
Keepalive time.
60
UA-5000 Series User Manual V.1.0.0 ICP DAS
50
2. Configure the variable and related parameters under the MQTT task tab.
The settings:
Function items
Description
Default
Variable Name
Choose a variable which pre-defined in the variable table.
Data Type
Not editable. It will show the data type of a variable.
System value
Attribute
Not editable. It will show the variable attribute.
System value
Publish Topic
The topic of sending data or publishing messages.
Publish Qos
The Quality of Service (Qos) levels. 0: Delivering a message at most once. 1: Delivering a message at least once. 2: Delivering a message at exactly once.
2
Subscribe Topic
The topic of receiving data or subscribing messages.
Subscribe Qos
The Quality of Service (Qos) levels. 0: Delivering a message at most once. 1: Delivering a message at least once. 2: Delivering a message at exactly once.
2
Retain
Whether to store a broker message. (0: No ; 1: Yes)
0
UA-5000 Series User Manual V.1.0.0 ICP DAS
51
3. Click Save to save the current settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
52
3.4. Virtual Device
This Virtual Device function allows the user to simulate various devices with the real I/O by using the PID tuning function. This article includes the PID function.
3.4.1. PID
This section will show you the way to add, modify, and delete the virtual PID device in the PID page. Proportional-Integral-Derivative control is the most widely used in industrial control systems. A regulator which is controlled in accordance with Proportional, Integral and Derivative is called PID contol for short, also called PID regulator. When the user cannot fully grasp or measur parameters of the control system, the PID regulator is the best solution.
Description of the tool button:
: Add a task, command, or item. : Delete a task, command, or item. : Modify a task, command, or item.
1. Configure a task in the PID Device page.
The settings:
Function items
Description
Default
PID Name
Give a PID task name.
Task1
UA-5000 Series User Manual V.1.0.0 ICP DAS
53
2. Configure related parameters for the PID device in the Task tab.
Function items
Description
Default
PV(Input)
Choose a predefined float variable as the input parameter.
Auto Tune
True: Auto-tuning PID parameters for your system. False: Tuning PID parameters manually.
True Sample Time
Set the samping time.
500
Setvalue
The target value for PID control.
0
Controller mode
DIRECT: Set it as positive output value. REVERSE: Set it as reverse output value.
DIRECT Kp
Set the Proportional gain.
1.0
Ki
Set the Integral gain.
1.0
Kd
Set the Derivative gain.
1.0
MV(Output)
Choose a preset floating variable as output.
Max
Set the upper-limit value for the variable.
0
Min
Set the lower-limit value for the variable.
0
3. Click Save to save the current settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
54
3.5. Service
This section will describe how to configure the Service funtion. It includes the OPC UA and MQTT items.
3.5.1. OPC UA
This section will show you the way to configure the Redundancy and Security settings.
3.5.1.1.Redundancy Settings
Function items
Description
Default
Redundancy Support
Mode
Select the redundant mode.
System value
Local Host
IP
Display the IP address of the active OPC UA Server.
System value
Server Name
Display the active OPC UA Server name. Not editable.
ICPDAS_OPC_UA_Server
Port
The TCP port number of the active OPC UA Server.
48010
Activate Driver
Check: Driver will run at system startup. Uncheck: Driver will run if a network is available.
Uncheck
Redundant Server
IP
The IP address of the redundant OPC UA Server.
Server Name
Display the redundant OPC UA Server name. Not editable.
ICPDAS_OPC_UA_Server Port
The TCP port number of the redundant OPC UA Server.
48010
UA-5000 Series User Manual V.1.0.0 ICP DAS
55
3.5.1.2. Security
Function items
Description
Default
User Identity Tokens
Enable Anonymous
Check: Allow clients to use anonymous access . Uncheck: No anonymous login.
Check
Enable User Password
Check: Allow to log in with username/password. Uncheck: Not supported this way.
Uncheck
Enable Certificate
Check: Allow to log in with certificates Uncheck: Not supported this way.
Uncheck
Click Save to save the OPC Ua settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
56
3.5.2. MQTT
This section will show you the way to add, modify, and delete an MQTT task in the MQTT Service page.
Description of the tool button:
: Add a task, command, or item. : Delete a task, command, or item. : Modify a task, command, or item.
1. Configure a task in the MQTT Service page.
The settings:
Function Items
Description
Default
MQTT Setting
Prefix
Set up the prefix for the MQTT topic.
System value
Name
Give a task name.
Task1
Scan Rate
Set an update frequency for the task data. (Unit: ms)
1000
Dead Bend
Give a deadbend value for updating a float signal. (Unit: %)
0
Will Topic
Enter the title of a disconnect notice.
Will
Enter a disconnect notice.
Connection Setting
IP
Set the Brokers IP address.
System value
Port
Set the Broker port.
1883
Keepalive
Set a time to check whether or not the connection to the Broker is working. (Unit: second)
60
UA-5000 Series User Manual V.1.0.0 ICP DAS
57
2. Configure the variable, topic and related parameters in the MQTT task item.
Settings:
Function items
Description
Default
Variable Name
Choose a variable in the pre-defined variable table.
Data Type
Not editable. It will show the data type of a variable.
System value
Attribute
Not editable. It will show the variable attribute.
System value
Subscribe Topic
The topic of receiving data or subscribing messages.
Subscribe Qos
The Quality of Service (Qos) levels. 0: Delivering a message at most once. 1: Delivering a message at least once. 2: Delivering a message at exactly once.
2
Publish Topic
The topic of sending data or publishing messages.
Publish Qos
The Quality of Service (Qos) levels. 0: Delivering a message at most once. 1: Delivering a message at least once. 2: Delivering a message at exactly once.
2
UA-5000 Series User Manual V.1.0.0 ICP DAS
58
3. Click Save to save current settings.
UA-5000 Series User Manual V.1.0.0 ICP DAS
59
4. Technical Reference Websites
OPC UA
https://opcfoundation.org/
MQTT
http://mqtt.org/
Modbus
http://modbus.org/
Loading...