ICP DAS tM-P8, tM-PDW8 User Manual

Features
tM-PDW8: Dry Contact Source-type Digital Inputs
Wet Contact Source- or Sink-type Digital Inputs
Photocoupler Isolation
Dry Contact and Wet Contact Selectable via Wire Connections
All Channels Can Be Used As 16-bit Counters
Dual Watchdog
Cost-eff ective
tM-PDW8tM-P8
8-channel Isolation Digital Input Module
Introduction
The tM-P8 off ers 8 channels for digital input, each of which features photocoupler isolation. In addition, digital input can be either sinkor source-type using wire connections and all channels can be used as 16-bit counters. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided. The tM-PDW8 off ers 8 channels for digital input, catering for both dry and wet contact, with an eff ective distance for dry contact of up to 500 meters. All channels not only feature Photocoupler isolation, but can also be used as 16-bit counters. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.
Applications
• All Kinds of On/Off Control
• Industrial Automation
• Industrial Machinery
• Building Automation
• Food and Beverage Systems
• Semiconductor Fabrication
• Control Systems
Dimensions (Units: mm)
27
10.2
19
52
System Specifications
Model tM-P8 tM-PDW8
CPU Module
Watchdog Timer
Isolation
Intra-module Isolation 3750 V
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power
EFT (IEC 61000-4-2)
LED Indicators
Status 1 x Power and Communication
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
Protocol DCON, Modbus/RTU, Modbus/ASCII
Power
Reverse Polarity Protection Yes
C
onsumption 0.2 W Max. 0.43 W Max.
Powered from Terminal Block
Mechanical
Dimensions (W x L x H) 52 mm x 98 mm x 27 mm
Installation DIN-Rail Mounting
Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +75 °C
Humidity 10 ~ 95% RH, Non-condensing
Yes, Module (2.3 seconds), Communication (Programmable)
DC
±4 kV Contact for Each Terminal ±8 kV Air for Random Point
Yes, 10 ~ 30 V
DC
35.4
23
6.6
Left Side View Front View
98
I/O Specifications
Model tM-P8 tM-PDW8
Digital Input/Counter
Channels 8
Type
Wet Contact, ON Voltage Level Wet Contact, OFF Voltage Level Dry Contact, ON Voltage Level Dry Contact, OFF Voltage Level
Max. Counts 65535 (16-bit)
Frequency 100 Hz
Min. Pulse Width 5 ms
Input Impedance 10 KΩ, 0.5 W
Overvoltage Protection ±70 VDC
Wet Contact, Sink/Source
+3.5 VDC ~ +50 VDC
+1 VDC Max.
- Close to GND
- Open
Wet Contact (Sink, Source) + Dry Contact (Source) Wet Contact, Sink/Source
ICP DAS CO., LTD Website: http://www.icpdas.com Vol.
2021.3
1/2
Internal I/O Structure
tM-P8
+5V
EEPROM
DI.COM DIO
tM-PDW8
EEPROM
+5V
+5V
DI.COM
DIO
INIT
Embedded
Controller
RS-485
Interface
Power
Regulator
+5V
DATA+
DATA-
+Vs
GND
Frame
Ground
INIT
Embedded
Controller
RS-485
Interface
Power
Regulator
+5V
DI6
DI7
DATA+
DATA-
+Vs
GND
Frame
Ground
Pin Assignments
tM-P8
tM-PDW8
Wire Connections
Model tM-PDW8
Input Type ON State Readback as 1 OFF State Readback as 0
Close to GND Open
Dry Contact
DI.GND
+S5 V
DI.GND
+5V
DI6
+5V
DI7
DI.GND
GND1
+S5 V
To other
DIx
channels
DIx
Model tM-P8 / tM-PDW8
Input Type ON State Readback as 1 OFF State Readback as 0
OPEN or <1 V
DIx
-+
Wet Contact
(Sink)
+3.5 ~ +50 V
DIx
-+
DC
10K
To other
10K
channels
DC
DI.COM
OPEN or <1 V
DIx
-+
Wet Contact
(Source)
DI.COM
+3.5 ~ +50 V
DIx
-+ To other
DI.COM
channels
DI.COM
Ordering Information
tM-P8 CR 8-channel Isolation DI (Wet) Module (RoHS)
tM-PDW8 CR 8-channel Isolation Digital Input (Dry, Wet) Module (RoHS)
To other channels
DC
10K
To other channels
DC
10K
To other channels
ICP DAS CO., LTD Website: http://www.icpdas.com Vol.
2021.3
2/2