Introduction
The SG-3016 is a voltage input to voltage or current output signal conditioning module. It has 3000Vdc three-way isolation for input, output and power. And can change the input/output range via internal configuration switches.
The SG-3016 has an LED display to show whether the SG-3016 is functioning correctly and
has three VRs (Zero, Span, Exci) to calibrate the input/output range accuracy.
The bandwidth of the SG-3016 is typically 600Hz. It’s easy to mount the SG-3016 on a standard DIN rail and can operate in environments with wide temperature range.
Specifications Voltage Specifications:
Electrical input: ±10mV, ±20mV, ±30mV, ±50mV, ±100mV Excitation voltage: 1 ~10Vdc (20mA max.)
Voltage output:
Bipolar: ±5V, ±10V Unipolar: 0~5V, 0~10V Output impedance: <50
Current output:
Current: 0~20mA Current load resistor:0~500 (Source)
General
Three-way isolation: 3000Vdc Accuracy: ±0.1% of full range
Bandwidth: 600Hz (typical)@-3dB Operation temperature range:-25°C75°C Storage temperature range:-30°C85°C
Supply Voltage
Input Range: 10~30Vdc Consumption: 1.44W (voltage output)
1.74W (current output)
configure
The terminal wiring for the SG-3016 is shown in Figure A. Positive power terminals pin’s 7 and 9 are internally connected, as are negative pins 10 and 12. Power can be connected through the adjacent modules, making wiring much easier. The SG-3016 uses a power input range of 10~30Vdc. Table 1 and table 2 show the switch positions used to configure the input and output range. The I/O configuration switches are located inside the module. And can be accessed by removing the DIN-rail bracket covers by sliding them in the direction shown in Figure B.
Ver1.305/18/2005,~2~
Range (SW2)
SG3016
Input Range
1 2 3 4 5
±10mV
±20mV
±30mV
±50mV
±100mV
Factory default setting
Range (SW1) Range (SW2)
SG3016
Output Range
1 2 3 4 5 6 6 7 8
±10V
±5V
0~10V
0~5V
0~20mA
Factory default setting
◆:ON
Table 1: Input range setting (SW2)
◆:ON
Table 2: Output range setting (SW12)
Ver1.305/18/2005,~3~
Configuration of SW1 1 2
Voltage Output
3 4
Current Output
ON Unipolar Output
5
OFF Bipolar Output ON
Internal Gain2 :2
6
OFF
Internal Gain2 :1
Configuration of SW2
1
Input:±10mV
2
Input:±20mV
3
Input:±30mV
4
Input:±50mV
5
Input:±100mV
6
Internal Gain1 :0.5
7
Internal Gain1 :1
8
Internal Gain1 :2
Block Diagram
Table 3: Configuration of SW1 and SW2
Ver1.305/18/2005,~4~
Calibration Procedure
1. Refer to figure C to adjust the offset value.
(1) Connect pin7 to the +24Vdc and connect pin 10 to GND.
(2) Connect pin8 and pin 11 to the meter.
(3) Use wire to connect pins 1 and 2.
(4) Changing the SW1 and SW2 depends on your input/output range. Watch the value of
the meter and adjust the VR2 (ZERO) value to the minimum value of this range.
2. Refer to figure D to adjust the gain value.
(1) Connect pin7 to the +24Vdc and connect pin 10 to GND.
(2) Connect pin8 and pin 11 to the meter.
(3) Connect pins 1 and 2 to input source.
Ver1.305/18/2005,~5~
(4) Changing the SW1 and SW2 depends on your input/output range. Watch the value of
the meter and adjust the VR3 (SPAN) value to the maximum value of this range.
3. Refer to figure E to adjust the excitation voltage value.
(1) Connect pin7 to the +24Vdc and connect pin 10 to GND.
(2) Connect pins 4 and 6 or pins 5 and 6 to the meter.
(3) Watch the value of the meter and adjust the VR1 (EXCI) value to the 1~10Vdc of this
range.
The default value is 10Vdc