
I-7017(F)C, M-7017C Quick Start Guide
Warranty
All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date
of delivery to the original purchaser.
Warning
ICP DAS assumes no liability for damages resulting from the use of this product. ICP DAS reserves the right to change this
manual at any time without notification. The information furnished by ICP DAS is believed to be accurate and reliable.
However, no responsibility is assumed by ICP DAS for its use, or for any infringements of patents or other rights of third
parties resulting from its use.
Packing List

Modbus Table (M-7017C only)
10129 ~
10136
00129 ~
00136
Over/under range status of channel 0
to 7 for 4 ~ 20mA or 0 ~ 20mA ranges
30001 ~
30008
40001 ~
40008
Analog input value of channel 0 to 7
Firmware version (low word)
Firmware version (high word)
Module address, valid range: 1 ~ 247
Bits 5:0
Baud rate, 0x03 ~ 0x0A
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bit
10: even parity, 1 stop bit
11: odd parity, 1 stop bit
Modbus response delay time in ms,
valid range: 0 ~ 30
Host watchdog timeout value, 0 ~
255, in 0.1s
Channel enable/disable, 00h ~ FFh
Host watchdog timeout count, write 0
to clear
Protocol, 0: DCON, 1: Modbus RTU
Filter setting, 0: 60Hz rejection, 1:
50Hz rejection
1: enable, 0: disable host watchdog
Modbus data format, 0: hex, 1:
engineering
Host watch dog timeout status, write
1 to clear host watch dog timeout
status
Reset status, 1: first read after
powered on, 0: not the first read after
powered on
Read module firmware version
Read all analog input data
Read analog input data of each channel (<=16 channel)
Read analog input data of each channel (>16 channel)
If you want to know the detail DCON protocol, please check it from CD or web
CD path: \\napdos\7000\manual\
Web: ftp://ftp.icpdas.com/pub/cd/8000cd/napdos/7000/manual/

Module test and configuration
Step 1: INIT switch Operation
1. Find out the INIT switch( back of the module),
and turn to INIT.
2. Reboot the module
Step 2: Install & Run DCON Utility
1. Please Install DCON Utility first
You can find the software in the CD.
CD path:
<Driver>:\napdos\driver\dcon_utility\
Web link:
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/
2. Run DCON utility
Step 3: Set search configuration & search module
Step 4: Select Module for testing and configuration
1. Click “COM Port”
2. Assign the communication information and click
“OK”
Refer converter Port Number
DCON for I-7000
Modbus RTU for M-7000
3. Click “Search” and select “Start Searching”
Software will search the modules from COM Port
4. Click “Search“ and select “stop searching”
Manual stop when the modules searched
Note:
When no module can be searched, please check the
wire and communication information
Double click “select module”

Step 5: Configuration Settings & Channel Settings
Depends on signal
sources
Step 6: Change to normal mode and keep the settings
1. Turn the INIT Switch to Normal.
2. Reboot the module
Trouble Shooting
Q1. How to do when forgot module address or baud rate?
Please turn to INIT mode, and run DCON Utility to search.
The module supports DCON protocol at the INIT mode.
And the address is 0. The communication setting is “9600,N,8,1”.
Q2. How to configure the I-7000 and M-7000 modules?
ICP DAS provide DCON Utility to configure I-7000 and M-7000 modules.
Please download the last version from: http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/
Q3. I-7017(F)C & M-7017C are the current input modules. Do they need external resistors for the measurement?
No, please refer internal I/O structure.
There is a 125Ω resistor inside for each channel.
Q4. How to calibrate the analog input module?
Usually it is not necessary to calibrate the analog input module.
However, in case you need to perform this operation, we provide a function to calibrate the module.
Please refer to user manual 1.10.
Notice:
1. Please update DCON Utility to version 5.2.3 or more.
2. Keep the module running more than 30 minutes to warm-up.
Q5. How to programming with I-7000 or M-7000 by C#, VB, VC?
ICP DAS I-7000 and M-7000 series both support DCON protocol. And Only M-7000 series supports Modbus protocol.
For DCON protocol, please download SDK and Demo from:
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_dll_new/
For Modbus protocol, please refer this web link:
http://www.icpdas.com/products/PAC/i-8000/modbus.htm
If there is any other question, please feel free to contact us. Email: service@icpdas.com
Website: http://www.icpdas.com.tw/contact_us/contact_us.html