ICPDAS GW-7553 Quick Start User Manual

Quick Start User Guide
1. Introduction
This manual introduces the GW-7553's basic setting and operating quickly, the user can refer to the user manual in the ICP DAS companion CD-ROM (Path: “CD:\profibus\gateway\gw-7553\manual\gw-7553 user manual.pdf”). This manual helps users to understand about the GW-7553 module and application. In the following examples the CIF50-PB PROFIBUS Master card from Hilscher is used. The configuration and communication is done by the program “SyCon” provided by Hilscher.
Application example of PROFIBUS to Modbus TCP
In this example the GW-7553 acts as a Modbus TCP Slave device. When the GW­7553 module receives a write DO Modbus command from PC’s Ethernet Port, the GW-7553 module can send the message to the input data area of PROFIBUS Master station. When the GW-7553 module receives a read DI Modbus command from PC’s Ethernet Port, GW-7553 module can refer to the output data area of PROFIBUS Master station to produce response message and send it to PC’s Ethernet Port.
2. Hardware configuration
Ethernet connectionRS-232 connectionPower connection
GW-7553 PROFIBUS/Modbus TCP Gateway
GW-7553 PROFIBUS/Modbus TCP Gateway Quick Start (Version 1.10, May/2012) PAGE:1
PROFIBUS connection
Here we recommend users to use the standard PROFIBUS cable and connector (DB9 male). It is only needed to use D-type connector via PROFIBUS cable to connect PROFIBUS Master station and GW-7553 module. PROFIBUS Master station and GW-7553 module belong to terminal equipments in this example, thus we need to enable the terminator resistor in the D-type connector.
Address setting
The GW-7553 is a slave device of PROFIBUS DP protocol. The station address of GW-7553 can be set by DIP switch. The DIP switch can be seen by open the cover, as shown in the below. The range of DIP switch is 0~126, here we set GW-7553 module’s DIP switch to 1.
LED status indicator
LED Status Description
flash
When the GW-7553 is a Modbus Slave device and receiving query message form Modbus Master device, PWR led will flash.
on
Power supply is ok. The firmware has loaded.
PWR
off Power supply has failed.
ERR
flash
When the GW-7553 connects with the utility tool, it will flash fast (flash once about 55ms). When the GW-7553 has diagnostic message, it will flash slowly (flash once about 220ms).
DIP switch (SW1)
Station
address
1 2 3 4 5 6 7 8
1 1 0 0 0 0 0 0 0
10 0 1 0 1 0 0 0 0
31 1 1 1 1 1 0 0 0
Note: 1=>ON, 0=>OFF
GW-7553 PROFIBUS/Modbus TCP Gateway Quick Start (Version 1.10, May/2012) PAGE:2
on
The
connection is error with PROFIBUS Master device or
PROFIBUS system configuration is not correct.
off
PROFIBUS system configuration is correct. It is normal operation.
on
Data exchange mode. It is normal operation.
RUN
off GW-7553 module is not in data exchange mode.
3. Establish connection with GW-7553
Before establish the connection between DP-Master and GW-7553, users should obey the following steps first.
1. First, users must load the electronic device description file (GSD file) of the GW-7553 into the DP-Master.
2. And then set the parameters and configurations.
3. Finally change your DP-master from offline state to operate state. The GW-7553 will be initialized. If there is no error occurs, GW-7553 proceeds into data exchange state. At the meantime, if there is any error occurs, GW-7553 will return to wait for parameterization.
4. S
oftware configuration
GSD file
Please copy the GSD file (IPDS0C0D.gsd) and the bitmap file (ICP_7553. bmp, GW_7553.bmp) from the CD of the GW-7553 module into the Profibus configuration tool.
File->CopyGSD
(Directory: --> CD:\profibus\gateway\gw-7553\gsd\)
the example of how to load GSD file
Here, we use the hilscher CIF50-PB PROFIBUS communication interface to show how to load GW-7553’s GSD file step by step.
GW-7553 PROFIBUS/Modbus TCP Gateway Quick Start (Version 1.10, May/2012) PAGE:3