ICPDAS GW-2139M User Manual

User Manual
Version 1.0.0 February 2019
GW-2139M
(BACnet MS/TP to Modbus TCP Gateway)
Written by Ives Shen
Copyright © 2019 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
Table of Contents
1. General Information ............................................................................................................ 4
1.1 BACnet MS/TP Introduction ............................................................................................ 4
1.2 Modbus TCP Introduction ............................................................................................... 4
1.3 About GW-2139M ................................................................ ................................ ........... 5
1.4 Features .......................................................................................................................... 6
1.5 Specifications .................................................................................................................. 7
2. Hardware .............................................................................................................................. 8
2.1 Size (Unit : mm) .............................................................................................................. 8
2.2 Appearance ..................................................................................................................... 9
2.3 LED Indicator ................................................................................................................ 10
3. Getting Started With GW-2139M ....................................................................................... 11
3.1 Wiring Preparation ........................................................................................................ 11
3.2 GW-2139M Utility ................................................................ ................................ .......... 12
3.3 How to update the firmware .......................................................................................... 16
GW-2139M (Modbus TCP to BACnet MS/TP Gateway) User Manual Version 1.0.0 Page3
Copyright © 2019 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
Important Information
Warranty
All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning from the date of delivery to the original purchaser.
Warning
ICP DAS assumes no liability for any damage resulting from the use of this product.ICP DAS reserves the right to change this manual at any time without notice. The information furnished by ICP DAS is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS for its use, not for any infringements of patents or other rights of third parties resulting from its use.
Copyright
Copyright @ 2018 by ICP DAS Co., Ltd. All rights are reserved.
Trademark
Names are used for identification purpose only and may be registered trademarks of their respective companies.
Contact us
If you encounter any problems while operating this device, feel free to contact us via mail at: service@icpdas.com . We guarantee to respond within 2 working days.
GW-2139M (Modbus TCP to BACnet MS/TP Gateway) User Manual Version 1.0.0 Page4
Copyright © 2019 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
1. General Information
1.1 BACnet MS/TP Introduction
BACnet is a data communications protocol for Building Automation and Control Networks.
BACnet Master Slave Token Passing (MS/TP) protocol is used to relay and exchange
information between building devices. BACnet MS/TP is a based on BACnet standard protocol
SSPC-135, Clause 9. BACnet MS/TP is a peer-to-peer, multiple master protocol based on token
passing. A token is information packets in the form of a pulse signal that is passed between
devices on a network. BACnet MS/TP is exclusive to BACnet and can be implemented using the
EIA-485 signaling standard. This is a shielded twisted-pair (STP) LAN operating at speeds from
9600 bit/s to 76800 Kbit/s. This LAN type is particularly suitable for single controller and low cost
communications.
1.2 Modbus TCP Introduction
MODBUS/TCP is a variant of the MODBUS family of simple, vendor-neutral communication
protocols intended for supervision and control of automation equipment. Specifically, it covers the
use of MODBUS messaging in an “Intranet” or “Internet” environment using the TCP/IP protocols.
The most common use of the protocols at this time are for Ethernet attachment of PLC’s, I/O
modules, and gateways to other simple field buses or I/O networks.
GW-2139M (Modbus TCP to BACnet MS/TP Gateway) User Manual Version 1.0.0 Page5
Copyright © 2019 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
1.3 About GW-2139M
GW-2139M is a network gateway allowing Modbus TCP client devices to be accessed
BACnet MS/TP network as a BACnet MS/TP master. The BACnet Master Slave Token Passing
(MS/TP) protocol is used to relay and exchange information between building devices.
GW-2139M contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV)
gives you flexibility in mapping Modbus TCP registers to any combination of BACnet objects.
BACnet interoperability building blocks (DS-RP-A, DS-RPM-A, DS-WP-A, DS-WPM-A,
DM-DDB-A, DM-DOB-A, DM-DCC-A, DM-RD-A) are Supported. All the data transfer is
configurable using ICPDAS Utility.
GW-2139M (Modbus TCP to BACnet MS/TP Gateway) User Manual Version 1.0.0 Page6
Copyright © 2019 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
1.4 Features
Read/Write standard BACnet objects via Modbus Configurable BACnet MS/TP master Configurable Modbus TCP server Simple data translation allows you to manipulate data Supports BACne AI, AO, AV, BI, BO, BV, MSI, MSO, MSV Object Types Supports Modbus DI, DO, AO, AI Types BACnet object properties mapping configured via Modbus register Isolated COM : RS-485 Provide LED indicators Built-in Watchdog 4KV ESD Protection