Features
Built-in Web Server
Web HMI
Support for both Modbus TCP and Modbus UDP Protocols
Communication Security
2-port Ethernet Switch for Daisy-Chain Topology
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
I/O Pair Connection
Built-in I/O
ET-7018Z
PET-7018Z
ET-7218Z
PET-7218Z
Thermocouple Input: 10 Channels
DO: 6/3 Channels
Ethernet I/O Module with 10-ch Thermocouple Inputs,
6/3-ch DO
Introduction
The “Z” version is another milestone in the development of the thermocouple series and is a testament to the excellence of ICP DAS products.
The ET-7018Z/PET-7018Z/ET-7218Z/PET-7218Z is specifically designed for extremely accurate thermocouple measurement and features automatic
cold-junction compensation for each channel to ensure temperature output consistency and stable temperature output in the field. Current input
and voltage input are both supported. Another feature is that its ten input channels can be individually configured for different kinds of analog input.
Open thermocouple detection and ESD/EFT/Surge protection mechanisms are also included. The six/five digital output channels can be set as alarm
outputs with short-circuit protection and overload protection.
System Specifi cations
Model ET-7018Z PET-7018Z ET-7218Z PET-7218Z
Software
Built-in Web Server Yes
Web HMI Yes
I/O Pair Connection Yes
Communication
Ethernet Port 1 x RJ-45, 10/100 Base-TX 2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE - Yes - Yes
Protocol Modbus TCP, Modbus UDP
Security ID, Password and IP Filter
Dual Watchdog Yes, Module (0.8 seconds), Communication (Programmable)
LED Indicators
for System Running
for Ethernet Link/Act Yes
for DI/DO status - Yes
for PoE Power - Yes - Yes
2-Way Isolation
Ethernet 1500 V
I/O 2500 V
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power Line ±2 kV for Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line ±2 kV for Power Line
Power
Reverse Polarity Protection Yes
Powered from Terminal Block 10 ~ 30 V
Powered from
C
onsumption 2.0 W (Max.) 3.0 W (Max.) 3.1 W (Max.) 3.3 W (Max.)
Mechanical
Dimensions (L x W x H) 123 mm x 72 mm x 35 mm 120 mm x 76 mm x 38 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 to +75°C
Storage Temperature -30 to +80°C
Humidity 10 to 90% RH, Non-condensing
PoE
DC
DC
- Yes, IEEE 802.3af, Class1 - Yes, IEEE 802.3af, Class1
- 1500 V
12 ~ 48 V
DC
Yes
DC
12 ~ 48 V
DC
DC
-
12 ~ 48 V
DC
ICP DAS CO., LTD Website: http://www.icpdas.com Vol.
2021.01
1/5
I/O Specifi cations
Model ET-7018Z PET-7018Z ET-7218Z PET-7218Z
Thermocouple Input
Channels 10 (Diff erential)
+/-15 mV, +/-50 mV, +/-100 mV, +/-500 mV, +/-1 V, +/-2.5 V
Sensor Type
Thermocouple (J, K, T, E, R, S, B, N, C, L, M, and L
Individual Channel Confi guration Yes
Resolution 16-bit
Sampling Rate 10 Samples/Second (Total)
Accuracy +/-0.1% of FSR or better
Zero Drift +/-0.5 μV/°C
Span Drift +/-25 ppm/°C
Over Voltage Protection 240 V
Input Impedance >300 kΩ
Common Mode Rejection 150 dB Min.
Normal Mode Rejection 100 dB
Temperature Output Consistency Yes
Stable Temperature Output in the Field Yes
Open Wire Detection Yes
Virtual Channel to Channel Isolation +/-400 V
Digital Output
Channels 6 3
Type Isolated Open Collector
Sink/Source (NPN/PNP) Sink
Max. Load Current 700 mA/Channel 650 mA/Channel
Load Voltage 5 VDC ~ 50 V
Overvoltage Protection 60 V
Overload Protection 1.4 A
Short-circuit Protection Yes
Power-on Value Yes, Programmable
Safe Value Yes, Programmable
+/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA
(Requires Optional External 125 Ω Resistor)
rms
DC
DC
DC
DIN43710
)
Wire Connections
Voltage Input (Default)
Thermocouple Input (Default)
Current Input
Digital Output
Open Collector (Sink)
ON State
Readback as 1
Note: When connecting to a current source, an optional external 125 Ω resistor is required.
OFF State
Readback as 0
ICP DAS CO., LTD Website: http://www.icpdas.com Vol.
2021.01