ICP TSTAT0406, TSTAT0407 Installation Instructions & User Manual

Page 1
TSTAT0406 & TSTAT0407
997-060180-5
Installation Instructions / User’s Manual
TSTAT0406 and TSTAT0407 4 HEAT – 2 COOL – DUAL FUEL
TSTAT0406 & TSTAT0407 - 4 WIRE CAPABLE THERMOSTAT (NAXA00101DB Daughter Board sold separately)
LEFT OR PREVIOUS
SCREEN BUTTON
SELECT BUTTON
DOWN BUTTON
Apply logo label here
THERMOSTAT BUTTON OPERATION
UP BUTTON
RIGHT BUTTON
Menu Driven Display
NOTE: You must go through the Model Configuration menus first. If you do not configure your thermostat and go straight to the different modes you will get a “Configuration Error” code flashing at the top of the screen. To void error, run through the Configuration Mode Menus. To Enter Configuration Menu set mode to OFF, then push the up and down buttons simultaneously for 5 seconds.
International Comfort Products, LLC Page 1 48201530101 Sep 2008
Page 2
TSTAT0406 & TSTAT0407
TSTAT0406 AND TSTAT0407 MENU MAP
INSTALLER
SETTINGS
MAIN SCREEN
MODEL
CONFIGURATION HEAT/COOL SINGLE STAGE ELECTRIC
MULTI STAGE ELECTRIC
HEAT PUMP SINGLE STAGE ELECTRIC
MULTI STAGE ELECTRIC
ACCESSORIES AIR FILTER CUMULATIVE RUN TIME HOURS
HUMIDIFER CUMULATIVE RUN TIME HOURS
UV LAMP CUMULATIVE RUN TIME HOURS
ELEC. AIR CLEANER CUMULATIVE RUN TIME HOURS
INPUT DEALER INFO BRAND NAME
FAN WITH HEAT
OPTION
HUMIDITY OPTION
(HUMIDITY SETTINGS) HUMIDIFY ONLY
RESTORE DEFAULTS
OFFSETS TEMPERATURE OFFSETS TEMPERATURE OFFSET
CYCLES PER HOUR
PROGRAM SETTINGS SMART RECOVER
SERVICE
INFORMATION FAULT STATUS
DOWN STAGING
TEST MODE
COOL TO DEHUMIDIFY
RH (RELATIVE
HUMIDITY)
TEMP
MODE (OPERATING
MODE)
FAN
MENU (MAIN MENU) SET DATE AND TIME AUTO DAYLIGHT SAVING
FURNACE MODEL
NUMBER
HP MODEL NUMBER
CONTRACTOR NAME
CONTRACTOR PHONE
SMART HEAT STAGING
ELECTRIC/FUNRACE
FAULT CODE DEFINITION FLASH CODE 1-9
CLEAR FAULT HISTOR
DISPLAY DEALER INFO
SETTINGS (SETTING
SECURITY LOCKOUT TEMP ADJUST ONL
SAVE YOUR DEALER IS
DEHUMIDIFY ONL
AUTO
NONE
HUMIDITY OFFSET
ANTICIPATOR
EVENTS PER DAY
COOLING LOCKOUT
LOCKOUT
BALANCE POINT
HOLD (HOLD MENU) VACATION HOLD
PROGRAM MENU
MODE (OPERATING
FAN
MODE)
DISPLAY HUMIDIT
MENU) SCREEN SETTINGS FAHRENHEIT OR CELSIUS
Y
Y
Y
CALENDER TIME MONTHS
CALENDER TIME MONTHS
CALENDER TIME MONTHS
CALENDER TIME MONTHS
REMOTE INDOOR
OFFSET
OUTDOOR OFFSET
Y
SET DATE AND TIME
PERMANENT HOLD
PROGRAMMING
SCREEN
AUTO CHANGEOVER AUTO CHANGEOVER TIME
INTERMITTENT FAN INTERMITTEN FAN OFF TIME
TOTAL KEYPAD
LOCKOUT
MONTH/DAY/YEAR/HOUR/MINUTE
AUTO OR MANUAL CHANGE
Y
DUAL FUEL
DUAL FUEL
DAY/TIME
12 OF 24 HOUR CLOCK
LANGUAGE CONTRAST
BACKLIGHT ON TIME
GAS
GAS
International Comfort Products, LLC Page 2 48201530101 Sep 2008
Page 3
TSTAT0406 & TSTAT0407
Heat Cool / Heat Pump / Dual Fuel Communicating Thermostat
Installation and Start-up Instructions
INSTALLER SETTINGS
INSTALLER SETTINGS
INSTALLER SETTINGS
MODEL CONFIGURATION
MODEL CONFIGURATION ACCESSORIES INPUT DEALER INFO FAN WITH HEAT OPTION HUMIDITY OPTION RESTORE DEFAULTS OFFSETS CYCLES PER HOUR PROGRAM SETTINGS SERVICE INFORMATION DOWNSTAGING TEST MODE COOL TO DEHUMIDIFY
SELECT OPTION ∇? ? PREVIOUS
HUMIDITY OPTION – In thermostats with an internal humidity sensor (TSTAT0407) this determines if humidification or dehumidification will be energized. (Not shown on systems without humidity sensor) RESTORE DEFAULTS – This will restore all factory defaults. OFFSETS – Allows setting of permanent offsets to the temperatures and humidity to compensate for room differences or measurement differences. CYCLES PER HOUR – limits the cycling of the system to a set maximum per hour to reduce short cycling and extend system life. PROGRAM SETTINGS – Sets custom operation of the programming feature.
DOWN STAGING – You can turn down staging on or off. Default is on.
TEST MODE – Allows forced operation of all the different heating and cooling modes of the thermostat based on
The model configuration selected. Also shortens or eliminates the short cycle timer.
MODEL CONFIGURATION
MODEL CONFIGURATION
HEAT / COOL
HEAT PUMP
HEAT PUMP
SELECT OPTION ∇∆ PREVIOUS
MODEL CONFIGURATION
SINGLE STAGE
MULTI STAGE
MULTISTAGE
SELECT OPTION ∇∆ PREVIOUS
International Comfort Products, LLC Page 3 48201530101 Sep 2008
To enter the INSTALLER SETTINGS screen, the thermostat MUST be in the OFF mode and at the MAIN SCREEN press and hold the UP and DOWN buttons at the same time for 5 seconds. This will bring up the INSTALLER SETTINGS screen. The installer settings are options that are specific to a particular installation and should only be adjusted by qualified service personnel.
The INSTALLER SETTINGS options are:
MODEL CONFIGURATION – Defines what type of system the thermostat is controlling. ACCESSORIES – What else is attached to the system and sets service alerts. INPUT DEALER INFO – Allows service personnel to enter their name, phone number, and model information for display in service situations. FAN WITH HEAT OPTION – In a gas furnace application, this option turns the G output on when the heat is on
or off. G is default to ON when electric heat is selected.
SERVICE INFORMATION – This menu can bring up current faults along with last three faults of the Comfort Alert diagnostic module. It also has a list of fault code definitions and a method of clearing the faults out of the thermostat memory.
(Refer to down staging section for details)
Staging Properties: Thermostat models TSTAT0406 & TSTAT0407 use advanced logic to control a two-stage
heating or cooling system for better home comfort and higher efficiency. The thermostat continuously monitors set point, room temperature, anticipator setting, and temperature rate-of-change. Considering all the conditions, the thermostat decides which stage (high or low) the system should be running for better home comfort and higher efficiency. It is possible that the thermostat will keep the system running for longer periods of time in low stage. This is normal, as the thermostat works to achieve higher efficiency and better home comfort. The advanced logic operates in all modes and controls the system for ramp up (offlow stagehigh stage) and ramp down (high stagelow stageoff). There are NO differentials (dead bands) to set. Simply enter your desired room temperature and the thermostat will hold the room temperature to within ¼ ºF from setpoint.
COOL TO DEHUMIDIFY – Uses the HVAC equipment in cooling to dehumidify the conditioned space. This
feature is used when the system does not have variable speed capabilities.
Highlighting MODEL CONFIGURATION, in the INSTALLER SETTINGS screen, and pressing SELECT button will bring up the first MODEL CONFIGURATION screen.
The first option asks if the system is a HEAT PUMP or a HEAT/COOL system. Highlighting the proper configuration and pressing SELECT sets up the system and brings up the next configuration screen.
Highlighting the proper setting for single stage systems or multi stage systems and pressing the SELECT button sets the system for the proper operation.
If the system is configured for HEAT/ COOL operation and single or multi stage the next menu, ELECTRIC or GAS, is where you will choose your source of heat. By pressing the SELECT button you will return the display to the INSTALLER SETTINGS screen.
NOTE: If you have selected furnace and you wish to have G energized along with W you must turn the Fan
with Heat option to on.
If the system is configured for HEAT PUMP operation and single or multi stage the next menu, ELECTRIC or DUAL FUEL, is where you will choose your source of heat. For HEAT PUMP systems, the ELECTRIC OR DUAL FUEL configuration screen allows setting for gas or electric furnaces. If the auxiliary heat system is
Page 4
TSTAT0406 & TSTAT0407
MODEL CONFIGURATION
ELECTRIC
DUAL FUEL
MULTI FUEL
SELECT OPTION ∇∆ PREVIOUS
gas or oil, highlight the DUAL FUEL option. For electric add-on heat, highlight ELECTRIC. Pressing the SELECT button finishes the system configuration and returns the display to the INSTALLER SETTINGS screen.
NOTE: The configuration steps must be done at the initial installation of the thermostat or
CONFIGURATION ERROR will appear on the top line of the MAIN SCREEN.
NOTE: YOU MUST HAVE AN OUTDOOR SENSOR FOR A DUAL FUEL SYSTEM TO OPERATE
CORRECTLY.
ACCESSORIES
ACCESSORIES
AIR FILTER
AIR FILTER
HUMIDIFIER UV LAMP AIR CLEANER
Highlighting the ACCESSORIES option in the INSTALLER SETTINGS screen and pressing SELECT will bring up the ACCESSORIES screen. This allows identification of add on accessories and sets a service schedule for them.
Highlighting an accessory and pressing SELECT will bring up the NOTIFICATION METHOD screen.
SELECT OPTION ∇∆ PREVIOUS
AIR FILTER CHANGE
CUMULATIVE RUN TIME
CUMULATIVE RUN TIME
CALENDAR TIME
This screen allows selection of notification by elapsed time (Calendar) or by hours actually run (CUMULATIVE RUN TIME)
Highlighting CUMULATIVE RUN TIME and pressing the SELECT button will bring up the RUN HOURS SCREEN.
SELECT OPTION ∇∆ PREVIOUS
AIR FILTER CHA NGE
CUMULATIVE RUN TIME
1000
HOURS
CHANGE SETTING ∇∆ PREVIOUS
AIR FILTER CHANGE
CALENDAR TIME
12 MONTHS
CHANGE SETTING ∇∆ PREVIOUS
Thi t ti i id d i t d fid ti lt UTEl t i C t l I d
Thi t ti i id d i t d fi d ti lt UT El t i C t l I d
The thermostat will keep track of the hours the system is actually running and compare that number to the numbers of hours set in the CUMULATIVE RUN HOURS screen. When the hours are met, the thermostat will display a message on the top line of the MAIN screen. In the case of the AIR FILTER, the message will say CHANGE AIR FILTER. (See MAIN SCREEN _ TOP LINE for other messages)
Use the UP and DOWN buttons to set the hours from OFF to the maximum time allowed. (See defaults table for values)
Press the SELECT button to activate and save the settings. The thermostat will automatically return the display to the ACCESSORIES screen.
Highlighting the CALENDER TIME option and pressing the SELECT brings up the CALENDER TIME screen.
Use the UP and DOWN buttons to change the Calendar time before an alert is set. The time can be set from OFF to the maximum time for the particular accessory. When the desired time is displayed, press the SELECT button to activate and save the setting. The thermostat will automatically return the display to the ACCESSORY screen.
INPUT DEALER INFO
INPUT DEALER INFO
BRAND NAME
BRAND NAME FURNACE MODEL NUMBER HP MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE SERIAL NUMBER SAVE
SELECT OPTION ∇∆ PREVIOUS
International Comfort Products, LLC Page 4 48201530101 Sep 2008
DEALER INFO IS:
BRAND NAME:
XXXXXXXXXXXXXXXXXXXXX
FURNACE MODEL NUMBER:
XXXXXXXXXXXXXXXXXXXXX
HP MODEL NUMBER:
XXXXXXXXXXXXXXXXXXXXX
CONTRACTOR NAME:
XXXXXXXXXXXXXXXXXXXXX 260-555-5555
SERIAL NUMBER:
XXXXXXXXXXXXXXXXXXXXX
PREVIOUS
Highlighting INPUT DEALER INFO and pressing SELECT brings up the DEALER INFORMATION screen. The options are: BRAND NAME FURNACE MODEL NUMBER HEAT PUMP MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE SERIAL NUMBER
SAVE
Page 5
TSTAT0406 & TSTAT0407
DEALER INFO
MODEL NUMBER
USE ∇∆ TO SCROLL THRU CHARACTERS
A
A
_____________________________
CHANGE LETTER ∇∆ PREVIOUS
Highlighting the type of information to enter and pressing SELECT button brings up the DATA ENTRY
screen for that option. Use the UP and DOWN buttons to scroll through the letters and numbers and use the RIGHT button to move to the next space. When all desired information is entered, press the SELECT button to save and return to the DEALER INFORMATION screen. When all desired dealer information has been entered, highlight the SAVE option and press the SELECT button.
The screen will display all of the entered information. If changes are needed, pressing the LEFT button will return the display to the DEALER INFORMATION SCREEN and corrections can be made. Use the RIGHT button to move across the line without changing the previous information. If changes are not necessary, press the SELECT button when the information is displayed and the display will return to the INSTALLER SETTINGS screen.
FAN WITH HEAT OPTION
FAN ON WITH HEAT OPTION
ON
OFF
SELECT OPTION ∇∆ PREVIOUS
HUMIDITY OPTION (HUMIDITY SETTINGS) TSTAT0407 Model Only
SCREEN SETTINGS
HUMIDIFY ONLY
HUMIDIFY ONLY DEHUMIDIFY ONLY AUTO NONE
SELECT OPTION ∇∆ PREVIOUS
Highlighting the FAN WITH HEAT OPTION in the INSTALLER SETTINGS screen and pressing the SELECT button will bring up the FAN WITH HEAT screen. Highlighting the ON option and pressing the SELECT button will activate this option. When FAN WITH HEAT is active, the thermostat will turn on the fan output (G) whenever there is a call for heat. Without this option active, there is no call for FAN (G) when heat is on and the thermostat is configured for Gas heat. There is always a FAN (G) output when there is a Y output in Heat Pump applications and when the system is configured for electric heat.
Highlighting the HUMIDITY OPTION in the INSTALLER SETTINGS screen and pressing the SELECT button will bring up the HUMIDITY SETTINGS screen. The humidity options are: HUMIDIFY ONLY – Used when only a humidifier is attached to the system DEHUMIDIFY ONLY – Used when only a dehumidifier is attached to the system or the system has self dehumidification capability. AUTO – Allows for H output to be active for humidification in heating and dehumidification in cooling. The humidify set point will only be displayed in heating mode and the dehumidify set point will only be displayed in cooling mode. NONE – Used when no humidifier or dehumidifier is attached.
The settings for operation of the attached equipment are accessed from the MAIN screen by highlighting the RH option and pressing the SELECT button. To have the humidity displayed on the main screen select MENU/DISPLAY HUMIDITY from the main screen.
RESTORE DEFAULTS
RESTORE DEFAULTS
YES
NO
SELECT OPTION ∇∆
PREVIOUS
Highlighting The RESTORE DEFAULTS option in the INSTALLER SETTINGS screen and pressing the SELECT button will bring up the RESTORE DEFAULTS screen. By using the UP and DOWN buttons to highlight the YES option and pressing the SELECT button, all settings are returned to factory default condition.
NOTE: The configuration settings – HEAT COOL/HEAT PUMP, SINGLE/MULTI, GAS/ELECTRIC are NOT
reset by this command. The thermostat keeps the last valid settings. If these need to be changed, it must be done through the CONFIGURATION screen.
OFFSETS
OFFSETS
Highlighting the OFFSETS option in the INSTALLER SETTINGS screen and pressing the SELECT button will bring up the OFFSETS SCREEN. Offsets are used when the temperature on the thermostat is not
TEMPERATURE OFFSETS
TEMPERATURE OFFSET HUMIDITY OFFSET ANTICIPATOR
representative of the room temperature the system is controlling. This may be due to many factors including position of the thermostat, room air flow, sunlight on the thermostat and others. The OFFSET options are: TEMPERATURE OFFSETS – This can apply an offset of +- 5 degrees to change the temperature reading from the internal temperature sensor, the external temperature sensor, and the outdoor temperature sensor.
SELECT OPTION ∇∆ PREVIOUS
HUMIDITY OFFSET – This can apply an offset of +- 5% to the relative humidity read from the internal sensor ANTICIPATOR – This can be set from 0 to 4 and adjusts the sensed temperature with running time to help prevent overshoot in temperature regulation.
International Comfort Products, LLC Page 5 48201530101 Sep 2008
Page 6
TSTAT0406 & TSTAT0407
TEMPERATURE OFFSETS
TEMPERATURE OFFSETS
TEMPERATURE OFFSET
TEMPERATURE OFFSET REMOTE INDOOR OFFSET OUTDOOR OFFSET
TEMPERATURE OFFSET
Highlighting the TEMPERATURE OFFSETS and pressing SELECT will bring up the TEMPERATURE OFFSET screen. Selecting which offset to adjust and pressing SELECT will bring up the appropriate screen for the adjustment. Pressing the UP and DOWN buttons will change the offset. Pressing the SELECT button applies the offset to the temperature selected.
SELECT OPTION ∇∆ PREVIOUS
CHANGE SETTING ∇∆ PREVIOUS
HUMIDITY OFFSETS – Model TSTAT0407 Only
HUMIDITY OFFSET
%
0
CHANGE SETTING ∇∆ PREVIOUS
ANTICIPATOR
SET ANTICIPATOR
2
CHANGE SETTING ∇∆ PREVIOUS
CYCLES PER HOUR
CYCLES PER HOUR
MAXIMUM ALLOWED
4
CHANGE SETTING ∇∆ PREVIOUS
PROGRAM SETTINGS
PROGRAM SETTINGS
SMART RECOVERY EVENTS PER DAY
EVENTS PER DAY
SMART HEAT STAGING COOLING LOCKOUT ELECTRIC HEAT LOCKOUT BALANCE POINT
SELECT OPTION ∇∆ PREVIOUS
Highlighting the HUMIDITY OFFSET option and pressing SELECT will bring up the HUMIDITY OFFSET
screen. Pressing the UP and DOWN buttons will change the humidity value displayed and used in
thermostats equipped with an internal humidity sensor. Pressing the SELECT button will apply the offset to
the humidity.
Highlighting the ANTICIPATOR and pressing the SELECT button in the OFFSETS screen will bring up the
SET ANTICIPATOR screen. The anticipator can be adjusted from 1 to 9. The 9 setting adjusts the most.
This adjustment is applied is systems where the room temperature overshoots the set temperature at turn
off of the system. The UP and DOWN buttons will adjust the ANTICIPATOR and the SELECT button will
apply the setting.
Highlighting the CYCLES PER HOUR option and pressing the SELECT button will bring up the CYCLES
PER HOUR screen.
Pressing the UP and DOWN buttons can adjust the CYCLES PER HOUR to either 4 or 6. If set to 4 the
thermostat will not allow a cycle to start until 15 minutes have passed from the start of the last cycle.
Setting to 6 will make the system wait 10 minutes before starting the next cycle. The time is measured
from start of a cycle to the start of the next cycle, and not the off time between cycles.
Highlighting the PROGRAM SETTINGS option in the SETTINGS screen and pressing SELECT will bring
up the PROGRAM SETTINGS screen.
The PROGRAM SETTINGS options are:
SMART RECOVERY – The thermostat looks ahead to the next programmed time and temperature and
adjusts its operation to reach the desired temperature at the programmed time. The normal operation is to
change the set point at the set time and let the system adjust the temperature starting at the set event time.
EVENTS PER DAY – Sets the number of programmed events per day to either 2 or 4.
NOTE: OUTDOOR SENSOR REQUIRED FOR NEXT THREE SETTINGS
COOLING LOCKOUT – Does not allow cooling when the outside temperature is below a specified
temperature
ELECTRIC HEAT LOCKOUT/FURNACE LOCKOUT when configured for MULTI FUEL – Does not allow electric heat on a heat pump system or furnace to come on when the outdoor temperature is above a
specified temperature.
International Comfort Products, LLC Page 6 48201530101 Sep 2008
Page 7
TSTAT0406 & TSTAT0407
HEAT PUMP LOCKOUT – Does not allow the heat pump to operate when the outdoor temperature is below a specified temperature.
SMART RECOVERY
SMART RECOVERY
ON
ON
OFF
SELECT OPTION ∇∆ PREVIOUS
Highlighting the SMART RECOVERY option and pressing SELECT will bring up the SMART RECOVERY screen. Highlighting ON or OFF and pressing the SELECT button will turn smart recovery on or off and return the display to the PROGRAM SETTINGS screen. When SMART RECOVERY is ON, the thermostat tries to adjust the set temperature in advance of a programmed event to get the temperature adjusted to the set point at the time of the event. For example, if the set temperature is set for 65 degrees at 3PM and the next programmed event sets the temperature to 70 degrees at 5PM, the thermostat will start the system before 5PM to achieve 70 degrees at 5PM. The thermostat assumes a change rate of 6 degrees per hour so it would start at about 4:10 PM and slowly raise the set temperature to 70 at 5PM.
EVENTS PER DAY
EVENTS PER DAY
4 - RESIDENTIAL
2 – RESIDENTIAL
2 - BUSINESS
SELECT OPTION ∇∆ PREVIOUS
Highlighting the EVENTS PER DAY option and pressing SELECT will bring up the EVENTS PER DAY screen. Pressing the UP or DOWN buttons will set the events per day to 2 or 4 and business or residential. This selection determines how many programmed events are available each day.
The Residential events are WAKE, LEAVE, RETURN, SLEEP for 4 events or WAKE and SLEEP for 2 events. The Business events are named ACTIVE and IDLE.
COOLING LOCK OUT
COOLING LOCKOUT
NO COOLING BELOW
55°
CHANGE SETTING ∇∆ PREVIOUS
(OUTDOOR SENSOR REQUIRED)
Highlighting the COOLING LOCKOUT option in the PROGRAM SETTINGS screen and pressing the SELECT button will bring up the COOLING LOCKOUT SCREEN. This setting can be set from NONE to 55 degrees. When there is an outdoor thermistor attached and the outdoor temperature is below the set Cooling Lockout point, the cooling will not operate. Pressing the UP and DOWN buttons will change the setting and pressing the SELECT button will apply the setting.
ELECTRIC HEAT /FURNACE LOCKOUT (OUTDOOR SENSOR REQUIRED)
ELECTRIC HEAT LOCKOUT
NO EHEAT ABOVE
55°
CHANGE SETTING ∇∆ PREVIOUS
BALANCE POINT (OUTDOOR SENSOR REQUIRED) USED IN DUAL FUEL MODE
BALANCE POINT
NO HEAT PUMP BELOW
35°
Highlighting the ELECTRIC HEAT LOCKOUT (FURNACE LOCKOUT if configured as GAS or DUAL FUEL) option and pressing the SELECT button will bring up the ELECTRIC HEAT/FURNACE LOCKOUT screen. In a heat pump system with an outdoor thermistor, this setting allows the thermostat to lockout the electric heat when the outdoor temperature is above the Lockout set temperature. If your system is configured as a furnace, it will lockout the furnace when the outdoor temperature is above the lockout set temperature. Pressing the UP and DOWN buttons can change the setting temperature from NONE to 60 degrees. Pressing the SELECT button will apply the setting and return the display to the PROGRAM SETTINGS screen.
Highlighting the BALANCE POINT option and pressing the SELECT button will bring up the BALANCE
POINT screen. In a heat pump system with an outdoor thermistor, this setting allows the thermostat to
lockout the heat pump when the outdoor temperature is below the Lock Out set temperature.
Pressing the UP and DOWN buttons can change the setting temperature from NONE to 55 degrees.
Pressing the SELECT button will apply the setting and return the display to the PROGRAM SETTINGS
screen.
CHANGE SETTING ∇∆ PREVIOUS
International Comfort Products, LLC Page 7 48201530101 Sep 2008
Page 8
TSTAT0406 & TSTAT0407
SERVICE INFORMATION
SERVICE INFORMATION
FAULT STATUS
FAULT STATUS FAULT CODE DEFINITION CLEAR FAULT HISTORY
SELECT OPTION ∇∆ PREVIOUS
Highlighting the SERVICE INFORMATION option and pressing the SELECT button brings up the SERVICE INFORMATION screen. Pressing the UP or DOWN button will alternate between FAULT STATUS, FAULT CODE DEFINITION and CLEAR FAULT HISTORY. Selecting FAULT STATUS allows the FAULT STATUS screen to be selected. Selecting CLEAR FAULT HISTORY allows the CLEAR FAULT HISTORY screen to be selected. Pressing the SELECT button when the desired option is highlighted enables that option.
FAULT STATUS
FAULT STATUS
ACTIVE FAULT:
1 FLASH-LONG RUN TIME
LAST 3 FAULTS:
3 FLASH-SHORT CYCLING 5 FLASH-OPEN HI V CKT 9 FLASH-LOW VOLTAGE
Highlighting the FAULT STATUS option and pressing the SELECT button brings up the FAULT STATUS
screen. The ACTIVE FAULT indicates the active fault (if any) that is currently being transmitted from the “L”
output from the Comfort Alert Module. The LAST 3 FAULTS indicates the last 3 faults that were stored in
memory and transmitted from the Comfort Alert module from the most recent to the latest.
? PREVIOUS
FAULT CODE DESCRIPTION
FAULT CODE DEFINITION
FLASH CODE 1
FLASH CODE 1 FLASH CODE 2 FLASH CODE 3 FLASH CODE 4 FLASH CODE 5 FLASH CODE 6 FLASH CODE 7 FLASH CODE 8 FLASH CODE 9
SELECT OPTION ∇∆
PREVIOUS
Highlighting the FAULT CODE DEFINITION option and pressing the SELECT button brings up the FAULT CODE DEFINITION screen. Pressing the UP or DOWN button will alternate between FLASH CODE 1 THRU 9. Pressing the SELECT button when the desired selection is highlighted activates that option. Selecting one of the FLASH CODE options and pushing ENTER button will display the definition for the selected FLASH CODE.
CLEAR FAULT HISTORY
CLEAR FAULT HISTORY
YES
NO
SELECT OPTION ∇∆
PREVIOUS
Highlighting the CLEAR FAULT HISTORY option and pressing the SELECT button brings up the CLEAR
FAULT HISTORY screen.
Pressing the UP or DOWN button will alternate between NO & YES. Selecting NO will not change any of
the current adjustable settings and will return to the previous menu. Selecting YES will erase the Fault
Code History from the thermostat’s memory. Pressing the SELECT button when the desired option is
highlighted activates that option.
SERVICE NEEDED SCREEN
SERVICE NEEDED
CALL:
XXXXXXXXXXXXXXX 260-555-5555
BRAND:
XXXXXXXXXXXXXXX
MODEL NUMBER:
123ABC456DEF
SERIAL NUMBER:
123ABC456D
FAULT:
5 FLASH – OPEN HI V CKT
PREVIOUS
International Comfort Products, LLC Page 8 48201530101 Sep 2008
Anytime there is an active fault on the Comfort Alert module and the “L” input is wired to the TSTAT0406, TSTAT0407 thermostats or NAXA00101DB Daughter Board, the thermostat display will display the SERVICE NEEDED screen with the corresponding Comfort Alert Fault. The CONTRACTOR NAME, CONTRACTOR PHONE NUMBER, MODEL NUMBER and SERIAL NUMBER of the outdoor unit will be displayed also if the information has been programmed into the thermostat at the INPUT DEALER INFO screen in the INSTALLER SETUP menu. To exit the SERVICE NEEDED screen while there is an active fault, push the PREVIOUS button. Pushing the PREVIOUS button resets the active fault counter within the thermostat. If the fault is still active and the fault is validated after the proper recognition timing, the fault will again be displayed in the SERVICE NEEDED screen.
Page 9
TSTAT0406 & TSTAT0407
DOWN STAGING
DOWN STAGING
ON
ON
OFF
Highlighting the DOWN STAGING option and pressing the SELECT button brings up the DOWN STAGING screen. Pressing the UP or DOWN button will alternate between ON & OFF. Selecting ON will allow the thermostat to down stage to a lower heating or cooling stage as the ambient temperature gets closer to the temperature setpoint. Selecting OFF forces the thermostat to satisfy the call for heat or cool on the highest active stage without down staging. Pressing the SELECT button when the desired option is highlighted
activates that option.
SELECT OPTION ∇∆
PREVIOUS
TEST MODE
TEST MODE SCREEN
HEAT PUMP MULTI
OFF
OFF
1ST STAGE COOL 2ND STAGE COOL
1ST STAGE HEAT 2ND STAGE HEAT 3RD STAGE HEAT 4TH STAGE HEAT EMERGENCY HEAT
SELECT OPTION ∇∆ PREVIOUS
TEST MODE SCREEN
1ST STAGE COOL
W1 OFF W2 OFF
Y1 ON Y2 OFF GON O/B ON
MIN OFF TIMER = 0 TESTING TIMER = 28 MIN
CANCEL
Highlighting the TEST MODE option and pressing the SELECT button brings up the TEST MODE screen. Pressing the UP or DOWN button will alternate between OFF and a list of all the heating and cooling stages available in the model configuration you have programmed into the thermostat. Pressing the SELECT button when the desired option is highlighted activates that option. Selecting the OFF option will not change any settings and will return to the previous screen. Selecting one of the heating or cooling stages options will go to the associated screen and show the list of thermostat inputs and display their OFF or ON status as well as the cooling or heating stage selected at the top of the screen. The minimum off timer is set to zero and the testing timer is set to 30 minutes. The screen will flash red then blue throughout the testing process until the testing timer is satisfied or the center CANCEL button is pushed.
COOL TO DEHUMIDIFY
COOL TO DEHUMIDIFY
YES
YES
NO
CHANGE MODE
PREVIOUS
Highlighting the COOL TO HUMIDIFY option and pressing the SELECT button brings up the COOL TO DEHUMIDIFY screen. Pressing the UP or DOWN button will alternate between YES & NO. Selecting YES will allow the HVAC equipment in cooling to dehumidify the conditioned space. This feature is used when the system does not have variable speed capabilities. This feature energizes the cooling outputs (Y1, G & O) and the H output whenever the need for dehumidification is needed. This feature is only active when there is no active call for heating or cooling. Selecting NO does not allow this feature to be active at any
time. Pressing the SELECT button when the desired option is highlighted activates that option.
COMFORT ALERT MODULE FAULT CODES
Status LED Status LED Description Status LED Troubleshooting Information
Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal
Yellow “ALERT” Flash Code 1
Yellow “ALERT” Flash Code 2
Y is present, but the compressor is not running.
Long Run Time Compressor is running extremely long run cycles
System Pressure Trip
Discharge or suction pressure out of limits or compressor overloaded
1. Compressor protector is open
Check for high head pressure
Check compressor supply voltage
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open.
4. Broken wire or connector is not making contact
5. Low Pressure switch open if present in system
6. Compressor contactor has failed open.
1. Low refrigerant charge
2. Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or block age
Check evaporator blower wiring and connec tors
Check indoor blower control board
Check thermostat wiring for open circuit
3. Evaporator coil is frozen
Check for low suction pressure
Check for excessively low thermostat s etting
Check evaporator airflow (coil block ages or return air filter)
Check ductwork or registers for block age
4. Faulty metering device
Check TXV bulb installation (size, locatio n and contact)
Check if TXV/fixed orifice is stuck closed or defective
5. Condenser coil is dirty
6. Liquid line restriction (filter drier block ed if present in system)
7. Thermostat is malfunctioning
Check thermostat sub-base or wiring for short cir cuit
Check thermostat installation (location, level)
8. Comfort Alert Module failure
1. High head pressure
Check high pressure switch if present in s ystem
Check if system is overcharged with ref rigerant
Check for non-condensable in system
2. Condenser coil poor air circulation (dirty, block ed, damaged)
3. Condenser fan is not running
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
4. Return air duct has substantial leakage
5. If low pressure switch present in system, check Flash Code
6. 1 information
Status LED Status LED
Yellow “ALERT” Flash Code 3
Yellow “ALERT” Flash Code 4
Yellow “ALERT” Flash Code 5
Yellow “ALERT” Flash Code 6
Yellow “ALERT” Flash Code 7
Yellow “ALERT” Flash Code 8
Yellow “ALERT” Flash Code 9
Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LED’s flashing at the same time means control circuit voltage is too low for operation.
Description Short Cycling
Compressor is running only briefly
Locked Rotor
Open Circuit
Open Start Circuit
Open Run Circuit
Current only in start circuit
Welded Contactor
Low Voltage
Control circuit < 17 VAC
Status LED Troubleshooting Information
1. Thermostat demand signal intermittent
2. Time delay relay or control board defective
3. If high pressure switch present, go to Flash Code 2 inf ormation
4. If low pressure switch present, go to Flash Code 1 inf ormation
1. Run Capacitor has failed
2. Lo w line voltage (contact utility if voltage disconnect is lo w)
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Measure compressor oil level
1. Outdoor unit power disconnected
2. Compressor circuit breaker or fuse(s) open
3. Compressor contactor has failed open.
Check compressor contactor wiring and connectors
Check for compressor contactor failure (bur ned, pitted or open)
Check wiring and connection between suppl y and compressor
Check for low pilot voltage at compr essor contactor coil
4. High pressure switch is open and requires m anual reset
5. Open circuit in compressor supply wiring or connection s
6. Unusually long compressor protector reset tim e due to extreme ambient temperature
7. Compressor windings are damaged
Check compressor motor winding resistance
1. Run capacitor has failed
2. Open circuit in compressor start winding or connect ions
Check wiring and connections= between suppl y and the compressor “S” terminal
3. Compressor start winding is damaged
Check compressor motor winding resistance
1. Open circuit in compressor run wiring or connections
Check wiring and connectors between suppl y and the compressor “R” terminal
2. Compressor run winding is damaged
Check compressor motor winding resistance
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
1. Control circuit transformer is overloaded
2. Lo w line voltage (contact utility if voltage at disconnect is low)
Check wiring connections
International Comfort Products, LLC Page 9 48201530101 Sep 2008
Page 10
TSTAT0406 & TSTAT0407
MAIN SCREEN
MAIN SCREEN
The Thermostat operation runs from the main screen. With the exception of the SERVICE NEEDED
8/08/05 8:45 AM
OUTDOOR FAN AUTO
93° HEATING
73° HEAT
SETPOINT HEAT 62 COOL 85
TEMP
RH MODE FAN MENU
TOP LINE
TIME and DATE – Normal operation CONFIGURATION ERROR – The thermostat was not correctly set up when installed. HOLD UNTIL (DATE and TIME) – Thermostat is in a temporary or Vacation Hold PERMANENT HOLD – Thermostat is in a permanent hold condition. CHANGE AIR FILTER – Maintenance time for air filter CHANGE UV LAMP – Maintenance time for UV Lamp SERVICE TIME – Maintenance time for system SERVICE HUMIDIFIER – Maintenance time for humidifier . NOTE: these service times are set in the INSTALLER SCREENS SMART RECOVERY – The system is starting early to achieve temperature at the programmed time. INTERMITTENT FAN – The fan is running its cycle set by the intermittent fan option. COMMUNICATION ERROR – Only used in systems with the NAXA00101DB daughter board. LOCKED – The thermostat is LOCKED. You will need to enter the unlock code. DEFROST ERROR –If unit is in defrost 15 minutes after initiation, the thermostat will flash the SERVICE NEEDED screen and display the EXCESS DEFROST TIME as the fault. The thermostat will only use Auxiliary heat outputs during this lockout.
BOTTOM LINE contains a group of selectable menus.
RH (RELATIVE HUMIDITY) – Model TSTAT0407 Only
NOTE: All errors and reminders shown in the top line are alternately flashed at 1 second intervals with the date and time.
RH (where used) displays the relative humidity and allows selection of humidity operation points. TEMP sets a temporary hold. This will change the set point until the next programmed temperature change point. This can change to CANCEL HOLD when a hold is active, RESET ALARM when an alarm or fault is active, and CANCEL ERROR when a DEFROST ERROR is present. MODE allows you to select which operating mode to use. HEAT, COOL, EHEAT, AUTO, or OFF. FAN allows selection of fan operation. AUTO, ON, or PROGRAMMED. MENU takes you to the MAIN MENU of options.
HUMIDITY
48%
HUMIDITY
HUMIDIFY SETTING 30
HUMIDIFY SETTING 30
SELECT OPTION ∇∆
PREVIOUS
SCREEN, the display will revert to the Main Screen in 3 minutes if no buttons are pressed. The Main Screen displays the actual Temperature, the current MODE (HEAT, EHEAT, COOL, AUTO, OFF), and the temperature set points (Unless the MODE is set to OFF). If there is an Outdoor thermistor connected, the outdoor temperature is displayed. If the thermostat has Humidity sensing capability, the humidity may be displayed. HEATING will be displayed as a flashing icon under the FAN mode display on the main screen whenever there is an active heating thermostat call. COOLING will be displayed as a flashing icon under the FAN mode display on the main screen whenever there is an active cooling thermostat call. The top line of the MAIN SCREEN will normally display the time and date, but if exceptional conditions exist, the top line is used to display the condition. For example, if there is a HOLD
set, the indication HOLD UNTIL (TIME DATE) or PERMANENT HOLD will be flashed on the top line. If there are alerts from the alarm settings for filter or other maintenance, those are displayed on the top line. The bottom line is a menu group. These are selectable by using the Right and Left buttons to move the cursor and pressing the center SELECT button.
SET HUMIDITY
40%
CHANGE SETTING ∇∆ PREVIOUS
Selecting RH and pressing the SELECT button will bring up the HUMIDITY screen on thermostats equipped with a humidity sensor. If the thermostat does not have a humidity sensor, this position will allow display of dealer information. The HUMIDIFY or DEHUMIDIFY settings can be changed by using the SELECT Button to choose the HUMIDIFY SETTING or DEHUMIDIFY SETTING box. NOTE: In order to be able to select a Humidify or Dehumidify setting, the HUMIDITY OPTION must be set for HUMIDIFY ONLY, DEHUMIDIFY ONLY or AUTO in the HUMIDITY SETTINGS screen in the INSTALLER SETTINGS menu. Use the UP and DOWN buttons to change the HUMIDIFY or DEHUMIDIFY setpoints within the preset ranges. When the desired setting is reached, press the SELECT button. The H output on the thermostat will activate in the humidification mode when the sensed ambient humidity is below the setpoint selected and there is an active call for heating. The H output on the thermostat will activate in the dehumidification mode when the sensed ambient humidity is above the setpoint selected and there is an active call for cooling. HUMIDIFY ONLY option displays only HUMIDIFY SETTING DEHUMIDIFY ONLY option displays only DEHUMIDIFY SETTING AUTO option displays both HUMIDIFY and DEHUMIDY SETTINGS
Note: Please note wiring diagrams for the humidifier and dehumidifier
options to ensure proper system operation.
International Comfort Products, LLC Page 10 48201530101 Sep 2008
Page 11
TSTAT0406 & TSTAT0407
TEMP
HOLD THIS
TEMPERATURE
UNTIL 10:30 P.M.
HEAT
COOL
62° 85°
CHANGE SET TEMP ∇∆ PREVIOUS
MODE (OPERATING MODE)
OPERATING MODE MENU
OFF
AUTO
COOL HEAT EMERGENCY HEAT
CHANGE MODE ∇∆ PREVIOUS
Selecting TEMP and pressing the SELECT button will bring up the HOLD THIS TEMPERATURE screen. If the mode is set for OFF, the temperature will be the last mode set. Shown is the AUTO mode.
NOTE: Pressing the UP or DOWN button from the MAIN screen when in any mode but OFF will bring up this screen.
Use the UP and DOWN buttons to change the set temperature for HEAT and COOL. When the desired temperature is reached, press the SELECT button. The COOL option will be highlighted if in HEAT and the mode is set to AUTO or the selection will be saved and the thermostat will enter a HOLD condition. The new settings will be used until the next programmed time is reached or the CANCEL HOLD is selected on the main screen. The next programmed time is shown on the screen. The next programmed time is also
displayed in a flashing message on the TOP LINE of the main screen.
Highlighting the MODE option and pressing the SELECT button will bring up the Operating Mode screen. Use the UP and DOWN button to highlight the desired operation mode and press the SELECT button to activate the desired operating mode. NOTE: the EMERGENCY HEAT mode is only available when the thermostat is configured for HEAT PUMP. The CONFIGURATION screen is in the INSTALLER SETTINGS screen. The AUTO setting allows the setting of a HEAT and COOL temperature and the thermostat will set the appropriate mode for maintaining the desired temperature.
FAN
FAN MENU
AUTO
ON
PROGRAMMED FAN
SELECT OPTION ∇∆ PREVIOUS
MENU (MAIN MENU)
MAIN MENU
SET DATE AND TIME
HOLD PROGRAM FAN MODE DISPLAY HUMIDITY DISPLAY DEALER INFO SETTINGS SECURITY LOCKOUT
PREVIOUS
SET DATE AND TIME
SET DATE AND TIME
AUTO DAYLIGHT SAVING
SET DATE AND TIME
SELECT OPTION ∇∆ PREVIOUS
International Comfort Products, LLC Page 11 48201530101 Sep 2008
Highlighting the FAN and pressing the SELECT button will bring up the FAN MODE screen. The options are:
AUTO – The thermostat will decide when the fan should be on based on the operation of the heat and cool outputs. ON – The fan is on continuously PROGRAMMED FAN – the fan will either be ON or AUTO based on the setting in the Program Screen.
Highlighting the MENU and pressing the SELECT button will bring up the MAIN MENU screen. Highlighting one of the options by using the UP and DOWN buttons will bring up the appropriate screen for that option. Pressing the LEFT button will take you back to the Main screen.
NOTE: Products without Humidity sensors will not show DISPLAY HUMIDITY.
yg g
AUTO DAYLIGHT SAVING
ON
OFF
SELECT OPTION ∇∆ PREVIOUS
Highlighting the SET DATE AND TIME and pressing the SELECT button will bring up the SET DATE AND TIME SCREENS. The first screen gives an option of setting the AUTO DAYLIGHT SAVING time selection or the SET DATE AND TIME option.
Highlighting the AUTO DAYLIGHT SAVING selection and pressing the SELECT button will bring up the screen for selecting the AUTO DAYLIGHT SAVINGS TIME option.
Highlighting the OFF and pressing the SELECT button will turn OFF the
automatic adjustment for daylight savings time. Highlighting ON and pressing the SELECT button will turn on the automatic adjustment for daylight savings time.
Page 12
TSTAT0406 & TSTAT0407
SET DATE AND TIME
08
SET DAY
CHANGE SETTING ∇∆ PREVIOUS
SET DATE AND TIME
08
SET MONTH
CHANGE SETTING ∇∆ PREVIOUS
SET DATE AND TIME
05
SET YEAR
CHANGE SETTING ∇∆ PREVIOUS
SET DATE AND TIME
10
AM
SET HOUR
CHANGE SETTING ∇∆ PREVIOUS
SET DATE AND TIME
21
SET MINUTES
CHANGE SETTING ∇∆ PREVIOUS
Highlighting the SET DATE AND TIME and pressing the SELECT button will bring up the set date screens then progress through the set time screens. Using the UP and DOWN arrows will change the Month, Day, Year, Hour, and Minutes. Pressing the SELECT button when the desired setting is displayed will step on to the next setting. Pressing the LEFT button will go back to the last screen viewed.
Once the minutes are set and the SELECT button is pressed, the new time and date is accepted and the display returns to the MAIN
MENU.
HOLD MENU
HOLD MENU
VACATION
PERMANENT
Highlighting the HOLD and pressing the SELECT button will bring up the HOLD screens. The initial hold screen asks if the hold will be a permanent hold or a Vacation hold. A permanent hold will keep the hold setting until the hold is canceled by highlighting the CANCEL HOLD on the MAIN screen and pressing the SELECT button.
SELECT OPTION ∇∆
PREVIOUS
VACATION HOLD
VACATION HOLD
SET HOLD TEMPERATURE
HEAT
COOL
62°
CHANGE SETTING ∇∆
PREVIOUS
A vacation hold will ask for a time and date to release the hold automatically. Use Hold the UP and DOWN buttons to change the temperature setting in HEAT or COOL as
85°
VACATION HOLD
HOLD UNTIL
5:00 P.M.
8/08/05
CHANGE SETTING ∇∆ PREVIOUS
VACATION HOLD
HOLD UNTIL
8/08/05
5:00 PM
CHANGE SETTING ∇∆
PREVIOUS
appropriate and press the SELECT button to set the desired set temperature. Pressing the SELECT button will move the screen automatically to the next setting. Pressing the LEFT button will return to the last screen.
When the Temperature setting is complete, the next screen will be the TIME and DATE screen. Use the UP and DOWN buttons to select the desired date the press the SELECT button. The time set will be next. Use the UP and DOWN buttons to then select the desired time for the normal program to resume and press the SELECT button. The display will return to the MAIN MENU screen
PERMANENT HOLD
PROGRAM MENU
PERMANENT HOLD
SET HOLD TEMPERATURE
HEAT
62°
CHANGE SETTING ∇∆ PREVIOUS
PROGRAM MENU
COPY
TUESDAY
THURSDAY
SATURDAY
EVERY DAY
WEEKENDS
SELECT OPTION ∇∆ PREVIOUS
COOL
85°
MONDAY
WEDNESDAY
FRIDAY
SUNDAY
WEEKDAYS
Highlighting the PERMANENT HOLD and pressing the SELECT button will bring up the PERMENANT HOLD screen. Use the UP and DOWN buttons to set the desired temperature and press the SELECT button. The display will return to the MAIN MENU screen. A Permanent hold can be reset by changing the operating mode or by highlighting the CANCEL HOLD on the MAIN screen and pressing the SELECT button.
Highlighting the PROGRAM selection in the MAIN MENU and pressing the select button will bring up the PROGRAM MENU.
This menu allows the thermostat to change the set temperature depending on the day and time. The days of the week can be set independently, the weekdays can all be set together, the weekends can be set together or all the days can be set the same.
International Comfort Products, LLC Page 12 48201530101 Sep 2008
Page 13
TSTAT0406 & TSTAT0407
PROGRAMMING SCREEN
EVERY DAY
WAKE HEAT COOL FAN
LEAVE
RETURN
SLEEP
SAVE
PREVIOUS
70 78 AUTO
6:00A
8:00A 62 85 AUTO
5:00P 70 78 AUTO
10:00P 62 82 AUTO
To program a day, highlight the day to program and press SELECT. The display will go to the PROGRAMMING SCREEN. The programming screen will either have 4 events or 2 events to program depending on the EVENTS PER DAY setting in the SETTINGS menu. Use the UP and DOWN buttons to select an event to program and then use the RIGHT and LEFT buttons to navigate the time and temperature. To change the event time, highlight the time and use the UP and DOWN buttons to change the value. Go to the next value to change by pressing the SELECT or the RIGHT button. Go back to the last item by pressing the LEFT button. When the desired values are set, highlight the SAVE and press the SELECT button. If you wish to copy this program to another day or to all days, highlight the COPY and press SELECT button. You will be prompted to select the day to copy from and copy to. Press the SELECT button to copy or the LEFT button to go back.
DISPLAY HUMIDITY – TSTAT0407 Model Only
HUMIDITY
48%
HUMIDITY
HUMIDIFY SETTING 30
HUMIDIFY SETTING 30
Highlighting the DISPLAY HUMIDITY option and highlighting YES and pressing the SELECT button will allow the humidity to be displayed on the MAIN SCREEN.
SELECT OPTION ∇∆
PREVIOUS
DISPLAY DEALER INFO
BRAND NAME:
XXXXXXXXXXXXXXXXXXXXX
FURNACE MODEL NUMBER:
XXXXXXXXXXXXXXXXXXXXX
HP MODEL NUMBER:
XXXXXXXXXXXXXXXXXXXXX
CONTRACTOR NAME:
XXXXXXXXXXXXXXXXXXXXX 260-555-5555
SERIAL NUMBER:
XXXXXXXXXXXXXXXXXXXXX
PREVIOUS SAVE
Highlighting the DISPLAY DEALER INFO option and pressing the SELECT button will bring up the YOUR DEALER IS screen. This is an information only screen and no options are available at this screen.
Note: Information needs to be manually input into the INPUT DEALER INPUT screen in the INSTALLER SETTINGS screen before the data can be displayed on this screen.
SETTINGS (SETTINGS MENU)
SETTINGS MENU
SCREEN SETTINGS
AUTO CHANGEOVER
INTERMITTENT FAN
SELECT OPTION ∇∆ PREVIOUS
SCREEN SETTINGS
SCREEN SETTINGS
FAHRENHEIT OR CELSIUS
12 or 24 HOUR CLOCK
12 or 24 HOUR CLOCK LANGUAGE CONTRAST BACKLIGHT ON TIME
SELECT OPTION ∇∆ PREVIOUS
Highlighting the SETTINGS option on the MAIN MENU and pressing the SELECT button will bring up the SETTINGS MENU. The options available on the SETTINGS MENU are: SCREEN SETTINGS – these allow customizing the look of your screen. AUTO CHANGE OVER – Allows the use of the AUTO mode selection or disables this function. INTERMITTANT FAN – Runs the fan independently when the system has not run for a period of time to help equalize temperatures and mix the air.
Highlighting the SCREEN SETTINGS and pressing the SELECT button will bring up the SCREEN SETTINGS screen. The SCREEN SETTINGS options are: FAHRENHEIT OR CELSIUS – displays the temperature in F or C. 12 OR 24 HOUR CLOCK – displays the time in AM/PM or 24 hour style LANGUAGE – Only English is available at this time. CONTRAST – adjusts the darkness of the screen and characters BACKLIGHT ON TIME – sets the time the backlight stays on after the last button push.
International Comfort Products, LLC Page 13 48201530101 Sep 2008
Page 14
TSTAT0406 & TSTAT0407
FAHRENHEIT OR CELSIUS
TEMPERATURE SCALE
FAHRENHEIT
CELSIUS
Highlighting the FAHRENHEIT OR CELSIUS option and pressing the SELECT button will bring up the FAHRENHEIT OR CELSIUS screen. Use the UP and DOWN buttons to select the option desired and press the SELECT button. The display will convert to the selected temperature scale and return to the SETTINGS MENU.
SELECT OPTION ∇∆
PREVIOUS
12 OR 24 HOUR CLOCK
12 OR 24 HOUR CLOCK
12 HOUR
24 HOUR
SELECT OPTION ∇∆ PREVIOUS
Highlighting the 12 OR 24 HOUR CLOCK option and pressing SELECT will bring up the 12 OR 24 HOUR CLOCK screen.
This option will display the time in 12 hour format (5:22 PM) or in 24 hour format (17:22)
Use the UP and DOWN buttons to select the desired display method and press the SELECT button to enable. The display will return to the SETTINGS menu.
LANGUAGE
At this time ENGLISH is the only option available.
CONTRAST
CONTRAST
ADJUST FROM 1 TO 15 1 IS LOW – 15 IS HIGH
10
CHANGE SETTING ∇∆ PREVIOUS
Highlighting the CONTRAST option and pressing the SELECT button will bring up the CONTRAST screen. The contrast can be changed in real time by pressing the UP and DOWN buttons. When the desired contrast is achieved, press the SELECT button and the display will return to the SETTINGS menu.
BACKLIGHT ON TIME
BACKLIGHT ON TIME
WITH NO BUTTON PUSH
30
SECONDS
CHANGE SETTING ∇∆ PREVIOUS
Highlighting the BACKLIGHT ON TIME option and pressing the SELECT button will bring up the BACKLIGHT ON TIME screen. Use the UP and DOWN buttons to select the desired time for the backlight to stay on after the last button was pressed. It is usually not desirable to leave the backlight on continuously because the light may generate heat that could interfere with the room temperature measurement. When the desired on time is set, Press the SELECT button and return to the SETTINGS screen. (30 – 120 seconds)
To exit this or any other screen, press the LEFT button to return to the previous screen
International Comfort Products, LLC Page 14 48201530101 Sep 2008
Page 15
TSTAT0406 & TSTAT0407
AUTO CHANGEOVER
AUTO CHANGEOVER
AUTO CHANGEOVER TIME
AUTO CHANGOVER TIME
AUTO OR MANUAL CHANGE
SELECT OPTION ∇∆ PREVIOUS
Highlighting the AUTO CHANGEOVER option and pressing the SELECT button will bring up the AUTO CHANGEOVER screen. Auto changeover allows the thermostat to determine if Heat or Cool should be active. The AUTO OR MANUAL option determines if the AUTO mode is available. The AUTO CHANGEOVER TIME option sets the minimum off time necessary before switching modes.
WARNING: The COOLING LOCKOUT feature in conjunction with an outdoor sensor should be used, or a low ambient kit to protect the compressor when operating in coo l ing in cold weather.
AUTO CHANGEOVER TIME
AUTO CHANGEOVER TIME
30
MINUTES
Highlighting the AUTO CHANGEOVER TIME and pressing the SELECT button brings up the AUTO CHANGEOVER TIME screen. This screen sets the minimum time the system must be idle before the automatic change of mode is allowed. For example, if the auto changeover time is set to 30 minutes and the system was cooling and the room temperature drops below the heat set point, the cooling must be idle for 30 minutes before the heating mode takes over. The settings can be from 5 to 120 minutes in 15 minute increments.
CHANGE SETTING ∇∆ PREVIOUS
AUTO OR MANUAL CHANGE
AUTO OR MANUAL CHANGE
AUTO
AUTO
MANUAL
SELECT OPTION ∇∆ PREVIOUS
Highlighting the AUTO OR MANUAL option and pressing the SELECT button brings up the AUTO OR MANUAL CHANGE screen. Pressing the UP or DOWN button will alternate between AUTO and MANUAL. Selecting AUTO allows the AUTO mode to be selected. Selecting MANUAL removes the AUTO mode from the MODE screen and requires manual selection of HEAT or COOL modes. Pressing the SELECT button when the desired option is highlighted enables that option.
INTERMITTENT FAN NO HEAT OR COOL CALL FAN ON TIME
INTERMITTENT FAN
NO HEAT OR COOL CALL
FAN ON TIME
10
MINUTES
CHANGE SETTING ∇∆
PREVIOUS
INTERMITTENT FAN NO HEAT OR COOL CALL FAN OFF TIME
INTERMITTENT FAN
NO HEAT OR COOL CALL
FAN OFF TIME
10
MINUTES
CHANGE SETTING ∇∆
PREVIOUS
Highlighting the INTERMITTENT FAN option and pressing the SELECT button will bring up the INTERMITTENT FAN screen. Setting the intermittent fan option will run the fan for up to 20 minutes on and up to 40 minutes off if there has been no heat or cool call for 60 minutes. The fan run time is set first. Using the UP and DOWN buttons can select a fan run time from OFF (No intermittent fan operation) to 20 minutes.
Pressing the SELECT button will bring up the next setting, the off time. This is the time the fan must be off before the intermittent fan ON time can begin. If there is no heat or cool call and the fan is not turned on manually or by the programmed setting, the fan will turn on and run for the minutes set in the FAN ON TIME screen. Pressing the UP and DOWN button can set an OFF TIME from 5 to 40 minutes. Pressing the SELECT button will enable the intermittent fan option and return the display to the PROGRAM SETTINGS screen.
International Comfort Products, LLC Page 15 48201530101 Sep 2008
Page 16
TSTAT0406 & TSTAT0407
SECURITY LOCK OUT
To lockout the thermostat totally, highlight TOTAL KEYPAD LOCKOUT and press the SELECT button. To allow temporary override of the programmed temperatures or a change of set temperature in
The ENTER PIN NUMBER screen will appear.
SECURITY LOCKOUT
TEMP ADJUST ONLY
TOTAL KEYPAD LOCKOUT
SELECT OPTION ∇∆
PREVIOUS
SECURITY LOCKOUT
ENTER PIN NUMBER
0 0 0 0
CHANGE NUMBER ∇∆ ⊲ PREVIOUS
OPTION
Set Temperature
Displa y F or
Auto Daylight Savings Ti me
12 or 24 Hour Cl oc
Allow AUTO MODE
Temporary HOLD
Vacation Hol d
Permanent HOLD
Operating Mode
EVENTS PER DAY
TEMPERATURE OFFSET
REMOTE TEMPERATURE OFFSET
OUTDOOR TEMPERATURE OFFSET
HUMIDITY OFFSET
NO COOLIN G BELOW OUTDOOR TEMPER ATURE
NO ELECTRIC HEAT ABOVE OUTDOOR
ANTICI PATOR
TEMPERATURE
SMART RECOVERY
FAN OPERATI NG MODE
BACKLIGHT ON TI ME
CYCLES PER HOU
AUTO CHANGEOVER TIM
HUMIDITY SET POINT
DEHUMIDI FY SET POI NT
HUMIDITY OPTIONS
SMART HEAT STAGE TIME
SMART STAGING
INTERMITT ENT FAN ON TIME
INTERMITTENT FAN OFF TIM
LOCK SCREEN
AIR FILTER ALARM
AIR FI LTER ALARM MONTHS
AIR FILTER ALARM HOUR
HUMIDIFIER ALARM
HUMIDIFI ER ALARM MONTHS
HUMIDIFI ER ALARM HOURS
UV LAMP ALAR
UV LAMP ALARM MONTH
UV LAMP ALARM HOURS
SERVICE AIR CLEANER ALARM
SERVICE AIR CLEANER ALARM MONTHS
SERVICE AIR CLEANER ALARM HOURS
HEAT PUMP
BALANCE POINT
DEALER NAM
DEALER PHON
MODEL NUMBE
BRAND NAM
DOWN STAGI NG ON ON or OFF
COOL TO DEHUMI DIF
C
k
R
E
E
S
M
S
CONTRAST
E
E
R
E
Y YES YES o r NO
Highlighting the SECURITY LOCKOUT option from the MAIN MENU and pressing the SELECT button will bring up the SECURITY LOCKOUT screen. Activating the security lock out and setting a 4 digit PIN will prevent unauthorized changes to the thermostat. The lockout can be total, no functions are allowed without entering the PIN or partial that allows setting of a temporary hold to override the set temperature.
nonprogrammable systems, highlight the TEMP ADJUST ONLY and press the SELECT button.
Use the UP and DOWN buttons to change the highlighted PIN digit until the desired number is displayed. Press the SELECT button and the display will highlight the next digit. Be sure to choose a PIN that you will remember. When the last digit is selected, the screen will return to the MAIN SCREEN and attempts to change settings will flash the message LOCKED and bring up the UNLOCK SCREEN. Enter the PIN into the unlock screen to unlock and allow changes to the thermostat. Once the thermostat is unlocked, it is necessary to reset the PIN number to relock the thermostat.
NOTE: A PIN number of 9999 will always unlock the thermostat.
FACTORY DEFAULTS
DEFA U LT SE TTIN
30 SEC 15 TO ON
15 min. 5 TO 120
30 min OFF to 120 min.
MONTHS MONTHS OR HOURS
MONTHS MONTHS OR HOURS
MONTHS MONTHS OR HOURS
MONTHS MONTHS OR HOURS
G RANGE
70 55 - 95
FF or C
ON ON or OFF
12 12 or 24
ON ON or OFF OFF ON or OFF OFF ON or OFF OFF ON or OFF OFF OFF, HEAT, COOL, EHEAT, AUTO
42 OR 4 0-5 TO +5 0-5 TO +5 0-5 TO +5 0-10 TO +10% 31 TO 9
NONE OFF- 45 - 55
NONE NONE - 5 - 60
OFF ON - OFF
AUTO AUTO - ON - PROGRAMMED
44 OR 6
40 10 - 50% 60 40 - 90%
NONE HUMIDIFY, DEHUMIDIFY, AUTO, NONE
ON ON - OFF OFF OFF TO 20
40 5 TO 40
OFF
6 OFF TO 48 months
1000 OFF to 3600
OFF OFF TO 48 MONTHS
0FF OFF TO 3600 hours
OFF OFF TO 48 months OFF OFF TO 3600
OFF OFF TO 48 months OFF OFF TO 3600 hours
OFF OFF - 5 TO 55
4 1 to 10 Blank Up to 20 charact ers Blank 10 numbers Blank Up to 20 charact ers Blank Up to 20 charact ers
OFF, ALL, AL LOW TEMPERATURE CHANGE
Default Set Back Program
ALL DAYS WAKE HEAT COOL FAN
6:00AM 70 78 AUTO
LEAVE
8:00 AM 62 85 AUTO
RETURN
5:00 PM 70 78 AUTO
SLEEP
10:00 PM 62 82 AUTO
International Comfort Products, LLC Page 16 48201530101 Sep 2008
Page 17
TSTAT0406 & TSTAT0407
OUTDOOR / INDOOR SENSOR INFORMATION
Refer to the Outdoor Sensor literature for details. The literature is included within the sensor packet with the thermostat.
NOTE: The outdoor can be used as an indoor sensor and connected to the ID and GND terminals on the back of the thermostat. When an indoor sensor is used, it overrides the thermostat’s onboard sensor.
TEMP
(Fº)
40 344711 11.21 306069 383353 3.74 3.00 31 247768 10.83 220935 274601 3.61 3.00 22 180147 10.44 161340 198955 3.48 3.00 13 132410 10.06 119063 145757 3.36 3.00
4 98324 6.50 91933 104716 3.25 2.00
5 73724 6.30 69079 78368 3.15 2.00 14 55787 6.10 52384 59190 3.05 2.00 23 42583 5.92 40062 45104 2.96 2.00 32 32773 2.85 31839 33707 2.85 1.00 41 25456 2.76 24753 26158 2.76 1.00 50 19932 2.68 19397 20466 2.68 1.00 59 15725 2.59 15318 16133 2.59 1.00 68 12497 2.51 12183 12811 2.51 1.00 77 10000 2.44 9756 10244 2.44 1.00 86 8055 2.37 8764 8246 2.37 1.00 95 6528 2.30 6378 6679 2.30 1.00
104 5323 4.48 5085 5562 2.24 2.00 113 4365 4.34 4176 4554 2.17 2.00 122 3599 4.22 3447 3751 2.11 2.00 131 2983 6.16 2800 3167 2.05 3.00 140 2486 5.99 2337 2635 2.00 3.00 149 2082 5.83 1961 2204 1.94 3.00 158 1753 5.67 1653 1852 1.89 3.00 167 1482 7.36 1373 1591 1.84 4.00 176 1258 7.17 1168 1349 1.79 4.00 185 1073 8.73 979.4 1167 1.75 5.00 194 918.9 8.51 840.7 997.1 1.70 5.00 203 789.9 9.96 711.3 868.6 1.66 6.00 212 681.6 9.68 615.6 747.6 1.61 6.00
Rnominal
()
RES. TOL
±%
Rmin. () Rmax. () TEMP. COEF.
(%/*F)
TEMP. ACCY.
(±*F)
International Comfort Products, LLC Page 17 48201530101 Sep 2008
Page 18
TSTAT0406 & TSTAT0407
NAXA00101DB DAUGHTER BOARD
The NAXA00101DB daughter board control allows for using 4 existing thermostat wires in an existing, finished home to communicate with the TSTAT0406 & TSTAT0407 thermostats. The daughter board translates the communicated heating and cooling needs and sends the normal discrete thermostat outputs to the indoor and outdoor equipment as needed. The NAXA00101DB Daughter Board must be used in conjunction with the TSTAT406 or TSTAT0407 Communicating Thermostat for proper operation. The daughter board provides a two-wire RS485 ModBus communication link and 24VAC to the communicating thermostat via a 4 wire connection scheme, “L” input from the Comfort Alert Module, a sensor input for the remote outdoor sensor, seven thermostat 24VAC outputs (W,G,Y,O,W2,Y2,H) and status & communication LED’s.
NAXA00101 Daughter Board Kit includes the following:
NAXA00101DB Daughter Board
4 - # 6 Mounting Screws
“L” Input Pigtail Wire Harness & wire nut
Remote Outdoor Sensor Pigtail Wire Harness & wire nuts
Installation Instructions
LOD
NAXA00101DB 1164-402 0735
Y2 W2 H - Y G W O
Daughter Board Terminals & Connections
See wiring diagrams for proper wiring and installation.
The following connections are provided in the P2 terminal block: (Power and Communication Connections to Communicating Thermostat)
P2 - Pin 1 "R" 24VAC hot power connection for communicating thermostat P2 - Pin 2 "GND" Ground connection for communicating thermostat P2 - Pin 3 “DX+” DX+ connection to the A+ Terminal on the communicating thermostat P2 – Pin 4 “DX-” DX- connection to the B- Terminal on the communicating thermostat
The following connections are provided in the P3 terminal block: (Outputs to the HVAC Equipment)
P3 – Pin 1 “O” 24 VAC thermostat output P3 – Pin 2 “W” 24 VAC thermostat output P3 – Pin 3 “G” 24 VAC thermostat output P3 – Pin 4 “Y” 24 VAC thermostat output P3 – Pin 5 “Not Used” 24 VAC thermostat output
The following connections are provided in the P4 terminal block: (Outputs to the HVAC Equipment)
P4 – Pin 1 “H” 24 VAC thermostat output P4 – Pin 2 “W2” 24 VAC thermostat output P4 – Pin 3 “Y2” 24 VAC thermostat output P4 – Pin 4 “R” 24 VAC system power input P4 – Pin 5 “C” 24 VAC system common input
The following connections are provided in the P5 Connector: (Optional Location for the Outdoor Sensor Hook-up)
P5 – Pin 1 “OD” Ground for Remote Outdoor Temperature Sensor P5 – Pin 2 “OD” Remote Outdoor Temperature Sensor input P5 – Pin 3 “Not used” P5 – Pin 4 “Not used”
The following connections are provided in the P8 Connector: (Optional Connection for the Comfort Alert ALARM Output)
P8 – Pin 1 “Not Used” ----- No Connect---­P8 – Pin 2 “Not Used” - - - No connect - - ­P8 – Pin 3 “L” “L” fault input from Comfort Alert Module
International Comfort Products, LLC Page 18 48201530101 Sep 2008
Page 19
TSTAT0406 & TSTAT0407
Status LED Operation
The LED labeled LED5 is a status LED that will provide a “heart beat” blink of this LED to indicate that the NAXA00101DB communicating daughter board control is powered and working properly.
Communication LED Operation
The LED labeled LED3 will be illuminated for 100mS each time a successful communications packet is received from the TSTAT0406 or TSTAT0407 communicating thermostat.
Thermostat Call Output LED’s Operation There is an LED Output for each thermostat output from the daughter board. The corresponding LED will illuminate any time
the associated thermostat output is active.
“L” Input from Comfort Alert Module to Daughter Board
The Comfort Alert Module will transmit the active fault code. The Comfort Alert or thermostat does not have any effect on operation of the equipment during a Comfort Alert fault. The Comfort Alert fault output can be wired directly to the daughter board or communicating thermostat. When the Comfort Alert Module is wired to the “L” input of the daughter board, it will recognize the fault output after it has been active for 10 seconds. After the daughter board has recognized the active fault from the Comfort Alert Module, the daughter board will forward the fault information to the communicating thermostats via the communication wires. The communicating thermostat will then display the fault code as defined.
GENERIC AC TO FANCOIL WIRING (REFER TO UNITS I/O MANUAL FOR SPECIFICS)
REQUIRE
1 STAGE AC WITH 1 STAGE FANCOIL
THERMOSTAT FANCOIL AC THERMOSTAT FANCOIL AC THERMOSTAT FANCOIL AC
CCCCCCCC
W2 W2 W2 W2 W2
---
RR RR RR
W1 W W1W1 W1W1
HHHH
OPTIONAL
1 STAGE AC WITH VARIABLE SPEED
FANCOIL + 2 STAGE ELECTRIC HEAT
2 STAGE AC WITH VARIABLE SPEED
FANCOIL + 2 STAGE ELECTRIC HEAT
▬▬▬ R
H
C
O/B O/B O O/B O
Y2 Y2 Y1 Y2 Y/Y2 Y2 Y1 Y Y Y1 Y/Y2 Y Y1 Y1 Y1
GG GG GG
LLLLLL
---
A+ A+ A+
B- B- B-
GND GND GND
OD OD OD
ID ID ID
GND GND GND
OUTDOOR
SENSOR
OUTDOOR
SENSOR
OUTDOOR
GENERIC HP TO FANCOIL WIRING (REFER TO UNITS I/O MANUAL FOR SPECIFICS)
NOTES:
1 STAGE HP WITH 1 STAGE FANCOIL + 1
THERMOSTAT FANCOIL HP THERMOSTAT FANCOIL HP THERMOSTAT FANCOIL HP
REQUIRE
H ON THERMOSTAT - CAN BE PROGRAMMED FOR HUM OR DEHUM FUNCTION. DEHUM MUST BE SELECTED WHEN CONNECTED TO DEHUM ON VARIABLE SPEED FANCOIL.
STAGE ELECTRIC HEAT
CCCCCCCC
W2 W2 W2 W2 W2
---
RRRRRRRR
W1 WW2W1 W1W2W1 W1
HHHH
O/B O O/B O O O/B O O
Y2 Y2 Y1 Y2 Y/Y2 Y2 Y1 Y Y Y1 Y/Y2 Y Y1 Y1 Y
GG GG GG
LLLLLL
---
A+ A+ A+
B- B- B-
GND GND GND
OD OD OD
ID ID ID
GND GND GND
OUTDOOR
NOTE: “L” wire can be terminated at either the thermostat OR the daughter board.
SENSOR
OPTIONAL
1 STAGE HP WITH VARIABLE SPEED FANCOIL +2 STAGE ELECTRIC HEAT
OUTDOOR
SENSOR
2 STAGE HP WITH VARIABLE SPEED
FANCOIL + 2 STAGE ELECTRIC HEAT
OUTDOOR
International Comfort Products, LLC Page 19 48201530101 Sep 2008
SENSOR
C
▬▬▬ R
W2
H
SENSOR
Page 20
TSTAT0406 & TSTAT0407
NOTES: 24 VAC HUM - GOES TO HUMIDIFIER, ENERGIZES ON A CALL FOR W
REQUIRED
1 STAGE AC WITH 1 STAGE FURNACE
GENERIC AC TO FURNACE WIRING (REFER TO UNITS I/O MANUAL FOR SPECIFICS
OPTIONAL
1 STAGE AC WITH VARIABLE SPEED FURNACE
2 STAGE AC WITH 2 STAGE VARIABLE SPEED
FURNACE
THERMOSTAT FURNACE AC THERMOSTAT FURNACE
CCCCCCCC
W2 W2 W2 W2 W2
---
RR RR RR
W1 W W1W1 W1W1
H H DEHUM H DEHUM
O/B O/B O O/B O
Y2 Y2 Y1 Y2 Y/Y2 Y2 Y1 Y Y Y1 Y/Y2 Y Y1 Y1 Y1
GG GG GG
LLLLLL
---
A+ A+ A+
B- B- B-
GND GND GND
OD OD OD
ID ID ID
GND GND GND
24VAC HUM 24 VAC HUM 24 VAC HUM
OUTDOOR
SENSOR
*8MPV* "C" SERIES OR NEW ER *8MPV* "C" SERIES OR NEW ER *9MPV* "D" SERIES OR NEW ER *9MPV* "D" SERIES OR NEW ER
OUTDOOR
SENSOR
AC THERMOSTAT FURNACE AC
▬▬▬ R
OUTDOOR
SENSOR
GENERIC HP TO FURNACE WIRING (REFER TO UNITS I/O MANUAL FOR SPECIFICS
REQUIRED
NOTES:
1 STAGE HP WITH 1 STAGE FURNACE 1 STAGE HP WITH VARIABLE SPEED FURNACE
THERMOSTAT FURNACE HP THERMOSTAT FURNACE HP THERMOSTAT FURNACE HP
CCCCCCCC
W2 W2 W2 W2 W2
---
RRRRRRRR
W1 WW2W1W1W2W1W1
H H DEHUM H DEHUM
O/B O O/B O O O/B O O
Y2 Y2 Y1 Y2 Y/Y2 Y2 Y1 Y Y Y1 Y/Y2 Y Y1 Y1 Y
GG GG GG
LLLLLL
---
A+ A+ A+
B- B- B-
GND GND GND
OD OD OD
ID ID ID
GND GND GND
24 VAC HUM - GOES TO HUMIDIFIER, ENERGIES ON A CALL FOR W H - CAN BE PROGRAMMED FOR HUM OR DEHUM FUNCTION. DEHUM MUST BE SELECTED W HEN CONNECTED TO DEHUM ON VARIABLE SPEED FURNACE.
24VAC HUM 24 VAC HUM 24 VAC HUM
OUTDOOR
SENSOR
OPTIONAL
2 STAGE HP WITH 2 STAGE VARIABLE SPEED
OUTDOOR
SENSOR
*8MPV* "C" SERIES OR NEW ER *8MPV* "C" SERIES OR NEW ER *9MPV* "D" SERIES OR NEW ER *9MPV* "D" SERIES OR NEW ER
FURNACE
▬▬▬ R
OUTDOOR
SENSOR
= VARIABLE SPEED (DEHUM) = REQUIRED
C
C
W2
AC WITH FANCOIL / PSC FURNACE + HUMIDIFIER HP WITH FANCOIL + HUMIDIFIER
VARIABLE SPEED
FANCOIL/SPP
THERMOSTAT
ONLY
THERMOSTAT
VARIABLE SPEED
FANCOIL ONLY
AC WITH VARIABLE SPEED FURNACE + HUMIDIFIER HP WITH VARIABLE SPEED FURNACE + HUMIDIFIER
THERMOSTAT
FURNACE
THERMOSTAT
H HC CC
C C 24 VAC HUM O
W1 O H DEHUM H DEHUM
H H
N.O. RELAY
HUMIDIFIE
M
115v
N.C. RELAY
N.C. RELAY
HUMIDIFIER
M
115v
SPDT RELAY
HUMIDIFIE
115v
SPDT RELAY
M
HUMIDIFIE
M
115v
NOTE: A separate 115v supply should be used. NOTE: A separate 115v supply should be used. NOTE: A separate 115v supply should be used. NOTE: A separate 115v supply should be used.
NOTE: When using a humidifier on a HP co nnect to hot wat er. NOTE: When using a humidifier on a HP co nn ect to hot water.
International Comfort Products, LLC Page 20 48201530101 Sep 2008