These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and
NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manuals that may
apply to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE - Used to highlight suggestions which
will result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Inspect New Unit ............................... 2
Safety Considerations ........................... 2
Location ....................................... 2
Clearances ................................. 2 - 3
Unit Support ................................... 4
Refrigeration System ........................ 5 - 9
Electrical Wiring ............................ 9 - 10
Defrost System ............................... 11
Start-up Procedure ............................ 11
Refrigerant Charge ........................ 12 - 13
Sequence of Operation ......................... 14
Troubleshooting ............................... 14
Maintenance .................................. 14
Comfort Alert TM Diagnostics Codes .............. 15
R-410A Quick Reference Guide ................. 16
DEATH, PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning
could result in equipment malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified per-
sons could result in equipment malfunction, prop-
erty damage, personal injury and/or death.
The information contained in this manual is in-
tended for use by a qualified service technician fa-
miliar with safety procedures and equipped with
the proper tools and test instruments.
Installation must conform with local building
codes and with the National Electrical Code
NFPA70 current edition or Canadian Electrical
Code Part 1 CSA C.22.1.
428 01 5102 00 Aug 2008
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden company immediately and file a concealed damage
damage. If damage is found, notify the transportation claim.
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the
dealer/distributor for information and assistance. The
qualified installer must use factory authorized kits and
accessories when modifying this product. Refer to the
individual instructions packaged with the kit or accessory
when installing.
The weight of the product requires careful and proper
handling procedures when lifting or moving to avoid
personal injury. Use care to avoid contact with sharp or
pointed edges.
Follow all safety codes. Wear safety glasses, protective
clothing, and work gloves. Use a heat sinking material -
such as a wet rag - during brazing operations. Keep a fire
extinguisher available. Consult local codes and the
National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or
maintenance can void the warranty.
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis-
connect device could result in personal injury or
death.
Before installing, modifying or servicing system,
turn OFF the main (remote) electrical disconnect
device. There may be more than one disconnect
device. Lock out and tag switch with a suitable
warning label.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper-
ty damage
R-410A systems operate at higher pressures than
R-22 systems. When working with R-410A sys-
tems, use only service equipment and replace-
ment components specifically rated or approved
for R-410A service.
LOCATION
Check local codes for regulations concerning zoning,
noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or
bedroom windows. Noise may carry into the openings
and disturb people inside.
Locate unit in a well drained area, or support unit high
enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust
fumes will be discharged onto unit (as from dryer vents).
CLEARANCES
Nominal minimum clearances are 48 inches (1.2m)
above unit for discharge air and 18 inches (457mm) on
each side of the coil for intake air. Clearance on any one
side of the coil (normally between unit and structure) may
be reduced to 6 inches (152mm). Nominal minimum
clearances are based on a solid parallel object such as a
wall or roof overhang.
The clearance may be reduced for a single object with
small surface area, such as the end of a wall, outside
corner of a wall, fence section, post, etc. As a general
rule, the minimum clearance from the unit should equal
the width of the object. For example, a 6 inch (152mm)
fence post should be a minimum of 6 inches (152mm)
from the unit.
Locate unit away from recessed or confined areas where
recirculation of discharge air may occur (refer to
CLEARANCES section of this document).
Roof-top installation is acceptable providing the roof will
support the unit and provisions are made for water
drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require
wind baffles. Consult the manufacturer for additional
information.
Do not install unit under roof overhangs unless gutters are
present. A minimum vertical clearance of 48 inches
(1.2m) is required to the overhang.
Inside corner locations on single story structures require
evaluation. Large overhanging soffits may cause air
recirculation in a corner area even though recommended
minimum clearances are maintained. As a guide, locate
the unit far enough out so that half of the discharge grille is
out from under the soffit.
When placing two or more units side-by-side, provide a
minimum of 18 inches (457mm) between units.
Provide minimum service clearance of 24 inches
(610mm) from control box corner and side service panel.
Refer to Figure 1.
2 428 01 5102 00
Figure1 _ Clearances (various examples)
liiii !!i,!i
,,
(152mm)
24"
(610mm)
Service
18"
(457mm)
18"
(457mm)
18"
(457mm)
24" i
(610mm)
Service _;
8"
152ram)
18"
(457mm)
24"
(610mm) I
Service L_"
(6lOre.m) i
,,
(152mm)
(102mm)
24" i
4"
f
18"
(152mm)
(102mm)
wide fence
(610mm)
Service
24" Jr
,,
(152mm)
24"
(610mm)
18"
(457mm)
Service
6"
,,
(152mm)
Post
(610mm)
Service
f
24" __
18"
(457mm)
18"
(457mm)
18"
(457mm)
(457mm)
I 18"
428 01 5102 O0 3
UNIT SUPPORT
NOTE: Unit must be level + 2 degrees {% inch rise or fall
per foot of run (10mm rise or fall per 305 mm of run) } or
compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by
beams, platform, or a pad. Platform or pad can be of open or
solid construction but should be of permanent materials
such as concrete, bricks, blocks, steel, or pressure- treated
timbers approved for ground contact. Soil conditions must
be considered so that the platform or pad does not shift or
settle and leave the unit partially supported. Minimum pad
dimensions are shown in Figure 2.
If beams or an open platform are used for support, it is
recommended that the soil be treated or area be graveled
to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is
recommended that supports not be in contact with the
building structure. However, slabs on grade constructions
with an extended pad are normally acceptable.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Top surface of platform must be above estimated snow-
fall level to prevent snow blocking coil and to allow water
melt to drain from unit.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood
frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level.
If installation is on afiat roof, locate unit minimum 6 inches
(152mm) above roof level.
Place the unit over one or more load bearing walls. If there
are several units, mount them on platforms that are
self-supporting and span several load bearing walls. These
suggestions are to minimize noise and vibration
transmission through the structure. If the structure is a home
or apartment, avoid locating the unit over bedrooms or study.
NOTE: When unit is to be installed on a bonded
guaranteed roof, a release must be obtained from the
building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in
place, remove the knockouts in the base pan and install
tie down bolts through the holes (refer to Figure 2).
Contact local distributor for hurricane hold-down details and
the RE. (Professional Engineer) certification, when required.
I
Figure 2 J Tie Down Knockouts
%" (10rnrn) dia. Tie Down Knockouts [ View From Top
In Base Pan (2 places)
Base
Pan
Depth
o o
A
Base Pan Width
Inches (mm)
Base Pan
Width x Depth
23 x 23
(584 x 584)
25%6 x 25%6
(652 x 652)
31YBx 31Y8
(791 x 791)
3415_6x 3415_6
(887 x 887)
Tie Down
Knockouts
A B C
73_ 47_6 18
(197) (113) (457)
9_6 47_6 21ΒΌ
(230) (113) (540)
9_e 6Y2 24%
(230) (165) (625)
9_e 6Y2 287_6
(230) (165) (722)
Minimum
MountingPad
Dimensions
23 x 23
(584 x 584)
26 x 26
(660 x 660)
31Y2x 31Y2
(800 x 800)
35 x 35
(889 x 889)
PROPERTY DAMAGE HAZARD
Failuretofollow thiscautionmayresultinpropertydamage.
Inadequate unit support may cause excessive vibration,
noise, and/or stress on the refrigerant lines, leading to re-
frigerant line failure.
4 428 01 5102 00
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in
place, especially the indoor coil.
R-410A outdoor units can only be used with R-410A
specific indoor coils. If there is a refrigerant mis-match,
consult the indoor coil manufacturer to determine if a
refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. If any other
type of metering device is installed on the indoor coil,
consult the indoor coil manufacturer to determine ifa TXV
conversion kit is available.
When installing a TXV on an indoor coil, follow the
instructions provided with the new TXV.
A typical TXV installation is shown in Figure 3.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
Indoor coil and outdoor unit must be listed as a
certified combination (match) in the ARI Unitary
Directory of Certified Products.
Indoor coil must have R-410A specific, TXV refrig-
erant metering device.
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure
maximum efficiency and proper oil circulation.
Refer to Product Specifications and Long Line
Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet
(61m).
NOTE: A crankcase heater must be used when the
refrigerant line length exceeds 80 feet (24.4m).
If outdoor unit is more than 10 feet (3m) higher than the
indoor coil, refer to the Long Line Applications Guideline
for instructions.
NOTE: When the outdoor unit is higher than the indoor
coil, the vertical separation must not exceed 100 feet
(30m).
NOTE: When the outdoor unit is lower than the indoor
coil, the vertical separation must not exceed 50 feet
(15.2m).
If it is necessary to add refrigerant line in the field, use
dehydrated or dry, sealed, deoxidized, copper
refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing
until connections are ready to be made.
Be extra careful when bending refrigeration tubing.
Tubing can "kink" easily, and if this occurs, the entire
length of tubing must be replaced.
Figure 3 _ Typical TXV Installation
EQUALIZER
TUBE
SENSING SUCTION
BULB TUBE
LIQUID
TUBE
TXV
SENSING BULB
STRAP
(EITHE_
PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in
personal injury and/or death.
Relieve pressure and recover all refrigerant before
servicing existing equipment, and before final unit
disposal. Use all service ports and open all flow-
control devices, including solenoid valves.
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp-
er product operation.
Do not leave system open to atmosphere any lon-
ger than absolutely required for installation. Inter-
nal system components - especially refrigerant
oils - are extremely susceptible to moisture con-
tamination. Keep ends of tubing sealed during
installation until the last possible moment.
8 O'CLOCK
428 01 5102 00 5
4 O'CLOCK