ICP PGN324, PGN330, PGN342, PGN348, PGN360 Installation Instructions Manual

...
Installation Instructions
PGN3 Series
Single Phase
PACKAGED GAS / ELECTRIC UNITS
Page
SAFE INSTALLATION REQUIREMENTS 2........
INTRODUCTION 3.............................
RECEIVING AND INSTALLATION 3...............
Check Equipment 3.............................
Provide Unit Support 3..........................
Field Fabricate Ductwork 3.......................
Dimensions 4 -- 5...............................
Provide Clearances 6...........................
Rig and Place Unit 6............................
Connect Condensate Drain 8.....................
Install Flue Hood 8..............................
Install Gas Piping 8.............................
Install Duct Connections 10......................
Install Electrical Connections 1 1..................
PRE--START--UP 12............................
START--UP 13..................................
Check for Refrigerant Leaks 13...................
Start--Up Heating & Make Adjustments 13..........
Start--Up Cooling & Make Adjustments 17..........
MAINTENANCE 19.............................
Air Filter 20....................................
Indoor Blower and Motor 20......................
Flue Gas Passageways 20.......................
Induced Draft (Combustion Air) Blower 20..........
Limit Switch 20.................................
Burner Ignition 21...............................
Main Burners 21................................
Outdoor & Indoor Coil, & Condensate Drain Pan 21.
Outdoor Fan 22.................................
Electrical Controls and Wiring 22..................
Indoor Airflow 22................................
Metering Devices--Fixed Orifice 22................
TROUBLESHOOTING 26--28....................
START--UP CHECKLIST 29......................
Printed in U.S.A.
International Comfort Products, LLC Lewisburg, TN. 37091
462 01 1901 01 01--28--08
SAFE INSTALLATION REQUIREMENTS
FIGURE 1
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, ontags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, fire, or an explosion which could result in personal injury or unit damage. Consult a qualified installer, service agency, or gas supplier for information or assistance. The qualified installer or agency must use only factory--authorized kits or accessories when modifying this product.
PGN3 GAS / ELECTRIC UNIT
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Before performing service or maintenance operations on unit, turn off gas supply to unit.Then turn off unitmain power switch and install lockout tag.
Recognize safety information. This is the safety--alert symbol . When you see this symbol in instructions or
!
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in serious injury or death. WARNING signifies a hazard which could result in serious injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
Failure to carefully read and follow all instructions in this manual could result in furnace malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code NFPA 54--2006/ANSI Z223.1--2006 and the National Electrical Code NFPA70--2005 or in Canada the National Standard CAN/CGA B149--1 and CSA C.22.1 -- Canadian Electrical Code Part 1.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
SAFETY CONSIDERATIONS
Use only with type of gas approved for this unit. Refer to unit rating plate.
Install this unit only in a location and position as specified in this manual.
Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections.
Always install unit to operate within the unit’s intended temperature--rise r ange with a duct system, which has an external static pressure within the allowable range. Refer to unit rating plate for the allowable external static pres­sures.
2
All connecting ductwork to the unit (supply and return) must be sealed to the unit casing as specified in section 7.
Do NOT use this furnace as a construction heater.
Check to see that filters are installed correctly and are the
proper type an size.
NOTE: It is the personal responsibility and obligation of the customer to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances.
!
UNIT SAFETY Failure to follow this caution may reduce unit reliability.
It is recommended that a qualified service technician check the heat exchanger integrity every two (2) years, after the first four (4) years of operation.
CAUTION
INTRODUCTION
The PGN3 unit is a fully self--contained, combination Category I gas heating/electric cooling unit designed for outdoor installation (See Fig 3 and 4 for unit dimensions). All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory--shipped with all downflow duct openings covered.
Units may be installed either on a rooftop or at ground level. Models with a ”1” in the twelfth position of the model number
are dedicated Low NOx units designed for California installations. The emissions of these models do not exceed 40 nanograms of nitrogen oxide emissions per joule of heat output as shipped from the factory, and must be installed in California Air Quality Management Districts or any other regions in North America where a Low NOx rule exists.
RECEIVING AND INSTALLATION
Step 1—Check Equipment
IDENTIFY UNIT The unit model number and serial number are stamped on the unit information plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directlyto transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
Step 2—Provide Unit Support
For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate if required.
ROOFCURB
Install accessory roof curb in accordance with instructions shipped with curb. Install insulation,cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORT ANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance.
Curb should be level to within 1/4 in. (6mm) This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102mm) thick with 2 in. (51mm) above grade (See Fig. 2). The slab should extend approximately 2 in. beyond the casing on a ll 4 sides of the unit. Do not secure the unit to the slab except when required by local codes.
FIGURE 2
2"
EVAP. COIL COND. COIL
Slab Mounting Details
OPTIONAL
RETURN
AIR
OPENING
OPTIONAL
SUPPLY
AIR
OPENING
ADDITIONAL GROUND LEVEL PLATFORM REQUIREMENTS
The unit MUST be situated to provide safe access for servicing. The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure--treated timbers approved for ground contact. Soil conditions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Position platform separate from building foundation. Install in well--drained area, with top surface of platform above grade level. Platform must be high enough to allow for proper condensate trap installation and drainage.
Step 3—Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return isused on a vertical unit,the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return--air static shall not exceed --.25 in. wc.
3
*
FIGURE 3
PGN324--36 DIMENSIONS
REQUIRED CLEARANCE TO COMBUSTIBLE MATL (
R
efe
r t
o
M
aximu
m
O
perating
C
learance
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT.............................................................................0.50 [12.7]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE.36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
LEGEND
CG - Center of Gravity COND - Condensor EVAP - Evaporator NEC - National Electrical Code REQ’D - Required
NOTE: Dimensions are in in. [mm]
.
s
)
INCHES [mm]
INCHES [mm]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8]
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
INCHES [mm]
UNIT
ELECTRICAL
CHARACTERISTICS
PGN324 208/230--1--60 343 156 37 [940] 20.0 [508] 17.0 [432] 17.6 [447] PGN330 208/230--1--60 355 161 39 [991] 20.0 [508] 19.3 [490] 13.0 [330] PGN336 208/230--1--60 360 163 41 [1042] 21.0 [533] 21.0 [533] 16.6 [422]
4
UNIT WEIGHT
lb kg X Y Z
UNIT HEIGHT IN. [MM]
“A”
CENTER OF GRAVITY
IN. [MM]
FIGURE 4
PGN342--60 DIMENSIONS
REQUIRED CLEARANCE TO COMBUSTIBLE MATL
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT.............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
.
INCHES [mm]
INCHES [mm]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
LEGEND CG - Center of Gravity COND - Condensor EVAP - Evaporator NEC - National Electrical Code REQ’D - Required
NOTE: Dimensions are in in. [mm]
INCHES [mm]
UNIT
ELECTRICAL
CHARACTERISTICS
PGN342 208/230--1--60 450 204.1 40.98 [1041] 21.0 [533] 21.0 [533] 17.1 [434] PGN348 208/230--1--60 480 217.7 46.98 [1193] 21.0 [533] 20.0 [508] 17.4 [442] PGN360 208/230--1--60 484 219.5 46.98 [1193] 21.0 [533] 20.0 [508] 17.6 [447]
UNIT WEIGHT
lb kg X Y
UNIT HEIGHT IN. [MM]
“A”
CENTER OF GRAVITY
IN. [MM]
Z
5
Table 1—Filter Data-- PGN324--60
UNIT SIZE 024040 024060 030040 030060 036060 036090 042060 042090 RETURN--AIR FILTERS (in.)†
Throwaway
UNIT SIZE 048090 048115 048130 060090 060115 060130 RETURN--AIR FILTERS (in.)†
Throwaway
{ Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling
airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high--capacity type. Air filter pressure drop for non--standard filters must not exceed 0.08 in. wc.
Step 4—Provide Clearances
The required minimum operating and service clearances are shown in Fig. 3 and 4. Adequate combustion, ventilation and condenser air must be provided in accordance with section 9.3, Air for Combustion and Ventilation, of the National Fuel Gas Code ANSI (American National Standards Institute) Z223.1 or applicable provisions of local building code. In Canada, follow sections 8.2, 8.3, or 8.4 or Can/CGA (Canadian Gas Association) B149 Installation Codes or applicable provisions of local building code.
IMPORT ANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.
The condenser fan pulls air through the condenser coil and discharges it through the top grille. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48--in (1219mm). above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48--in (1219mm).
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab--mounted units should be at least 4 in. (102mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.
Step 5—Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).
Only trained, qualified crane operators and ground support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
20x24x1 20x24x1 20x24x1 20x24x1 20x24x1 20x24x1 24x36x1 24x36x1
24x36x1 24x36x1 24x36x1 24x36x1 24x36x1 24x36x1
INSPECTION The lifting/rigging bracket is engineered and designed to
be installed only on Small Packaged Products. This bracket is to be used to rig/lift a Small Packaged Product onto roofs or other elevated structures.
Prior to initial use, and at monthly intervals, all rigging
brackets and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded.
!
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Never stand beneath rigged units or lift over people.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
Rigging brackets for one unit use only. When removing a unit at the end of its useful life, use a new set of brackets.
USE OF RIGGING BRACKET
NOTE: Rigging brackets are factory installed on 3--phase units only. Single--Phase units require accessory kit NPLIFTBK003A10.
Field Installation of Rigging Bracket (if not already installed)
1. Remove unit from shipping carton. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.
2. Remove 4 screws in unit corner posts.
3. Attach each of the 4 metal rigging brackets under the panel rain lip (See Fig. 5). Use the screws removed in step 2 above to secure the brackets to the unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
Rigging bracket MUST be under the rain lip to provide adequate lifting.
WARNING
WARNING
WARNING
6
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
Do not strip screws when re--securing the unit. If a screw is stripped, replace the stripped one with a larger diameter screw (included). When straps are taut, the clevis should be a minimum of 36 in. (914mm) above the unit top cover.
WARNING
Rigging/Lifting of Unit
1. Bend top of brackets down approximately 30 degrees from the corner posts.
2. Attach straps of equal length to the rigging brackets at opposite ends of the unit. Be sure straps are rated to hold the weight of the unit (See Fig. 5).
3. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.
4. After unit is securely in place detach rigging straps. Remove corner posts screws, and rigging brackets then reinstall screws.
After the unit is placed on the roof curb or mounting pad, remove the top crating.
FIGURE 5
1
y
4
CORNER WEIGHTS (SMALL CABINET) CORNER WEIGHTS (LARGE CABINET)
PGN324
Unit
Total Weight 343 156 Corner Weight 1 69 31 Corner Weight 2 53 24 Corner Weight 3 83 38 Corner Weight 4 138 63
Rigging Weight 353 160
Shipping Weight 383 173
lb kg
Unit Corner Weight (lbs) and Rigging
2
x
PGN330 PGN336
lb kg lb kg
355 161 360 163
75 34 74 34 56 25 55 25
81 37 86 39 143 65 145 66 365 166 370 168 395 179 400 181
3
Rigging Brackets are factory installed on 3--- phase units only. Single ---phase units require accessory kit NPLIFTBK003A10
PGN342 PGN348 PGN360
Unit
Total Weight 450 204 480 218 484 220 Corner Weight 1 90 41 97 44 98 45 Corner Weight 2 72 33 74 34 75 34 Corner Weight 3 110 50 116 53 118 54 Corner Weight 4 176 81 193 88 193 88
Rigging Weight 465 211 495 225 499 226
Shipping Weight 510 231 540 245 544 247
lb kg lb kg lb kg
7
Step 6—Connect Condensate Drain
NOTE: When installing condensate drain connection be
sure to comply with local codes and restrictions.
The PGN3 disposes of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side. See Fig. 3 & 4 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field--supplied 2--in. (51mm) condensate trap at the end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (24mm) lower than the drain--pan condensate connection to prevent the pan from overflowing (See Fig. 6). Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
Connect a drain tube using a minimum of 3/4--in. PVC or 3/4--in. copper pipe (all field--supplied) at the outlet end of the 2--in. (51mm) trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1--in (25mm). for every 10 ft (3048mm) of horizontal run. Be sure to check the drain tube for leaks.
FIGURE 6
1" min.
Condensate Drain
TRAP OUTLET
2" min.
Step 7—Install Flue Hood
The flue assembly is secured and shipped in the return air duct. Remove duct cover to locate the assembly (See Fig. 8 and 9).
NOTE: Dedicated low NOx models MUST be installed in California Air Quality Management Districts where a Low NOx rule exists.
These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory.
NOTE: Low NOx requirements apply only to natural gas installations.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicted in this section of the unit installation instructions.
WARNING
Install the flue hood as follows:
8
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or NFPA (National Fire Protection Association) latest revision. Refer to Provincial and local plumbing or wastewater codes and other applicable local codes.
2. Remove flue hood from shipping location (inside the return section of the blower compartment--see Fig. 8 &
9). Remove the return duct cover to locate the flue hood. Place flue hood assembly over flue panel. Orient screw holes in flue hood with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw on the right side and the left side of the hood.
Step 8—Install Gas Piping
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/2--in. FPT gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to Table 2 and the NFGC for gas pipe sizing. Do not use cast--iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wc maximum pressure drop. Never use pipe smaller than the 1/2--in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wc or greater than 13 in. wc while the unit is operating. For propane applications, the gas pressure must not be less than 7.0 in. wc or greater than 13 in. wc at the unit connection.
A 1/8--in. NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the gas valve.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to theNFGC ANSI Z223.1--2005 NFPA latest edition (in Canada, CAN/CGA B149.1).
NOTE:In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. (6mm) for every 15 ft (4572mm) of length to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers,etc. Use aminimum of one hanger every 6 ft. (1829mm) For pipe sizes larger than 1/2 in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections.
Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. Never use Teflon tape.
FIGURE 7
Sediment Trap
IN
4. Install sediment trap in riser leading to heating section (See Fig. 7). This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft (1829mm) of heating section.
6. Install ground--joint union close to heating section between unit manual shutoff and external manual main shut--off valve.
OUT
TEE
NIPPLE
CAP
7. Pressure test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit.
8. Check for gas leaks at the field--installed and factory--installed gas lines after all piping connections have been completed. Use soap--and--water solution (or method specifiedby local codes and/orregulations).
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolatedfrom the gas piping system by closing the external main manual shutoff valve and slightly opening the ground--joint union.
Table 1
NOMINAL
IRON PIPE
SIZE (IN.)
1/2 .622 175 120 97 82 73 66 61 57 53 50 44 40 3/4 .824 360 250 200 170 151 138 125 11 8 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 1--1/4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280 1--1/2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5--in. wc (based on a 0.60 specific gravity gas). Refer to Table, National Fire Protection Association NFPA 54.
{ This length includes an ordinary number of fittings.
INTERNAL
DIAMETER
(IN.)
10 20 30 40 50 60 70 80 90 100 125 150 175 200
PIPING SIZES
LENGTH OF PIPE (FT)†
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
--Connect gas pipe to unit using a backup wrench to avoid damaging gas controls.
--Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
--Use proper length of pipe to avoid stress on gas control manifold.
--If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum of 2 in. (51mm) outside furnace casing.
--If codes allow a flexible connector , always use a new connector. do not use a connector which has previously serviced another gas appliance.
WARNING
9
Loading...
+ 20 hidden pages