ICP PGF060K140A, PGF048K120A, PGF042K100A, PGF036K100A, PGF036K060A Owner’s Manual

...
Installation Instructions
PGF, PGC, PGS, GPFM, GPCM, GPSM
!
COMBINATION UNITS
GAS HEAT / ELECTRIC COOL
11/2 to 5 TON
Printed in U.S.A.
462 01 1003 01 1-6-04
Danger,Warning and Caution
The signal words DANGER, WARNING and CAUTION are
used to identify levels of hazard seriousness. The signal
word DANGER is only used on product labels to signify an
immediate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout
this manual and other manuals that may apply to the
product.
Signal Words
DANGER - Immediate hazards which WILL result in
severe personal injury or death. WARNING - Hazards or unsafe practices which COULD
result in severe personal injury or death. CAUTION - Hazards or unsafe practices which COULD
result in minor personal injury or product or property
damage. Signal Words in Manuals
The signal word WARNING is used throughout this manual
in the following manner:
Danger Label
White lettering on a black background except the word
DANGER which is white with a red background,
Warning Label White lettering on a black background except the word
WARNING which is black with an orange background,
Caution Label White lettering on a black background except the word
CAUTION which is black with a yellow background,
The signal word CAUTION is used throughout this manual
in the following manner:
CAUTION
Product Labeling
Signal words are used in combination with colors and/or pictures on product labels. Following are examples of
product labels with explanations of the colors used.
J2J 462 01 1003 01
[IJ_lli I]I LV4:1l [.,-'][I]l [.,-_
1-1/2 TO 3-1/2 TON
BASE RAIL
BASE PAN - CHASSIS
L_-k
©
[ 4 TO 5 TON
I/lliI "A"
ALL DIMENSIONS IN INCHES
Connections Detail
BASE RAIL
AS /
ONNECTtON (
1/2 \
<F-1-3/4" VOLTAGE _
12-1/4 --
191 SUPPLY _
I
M
2-3/16
UNITSIZE A B C
1-112TO3-1/2 Ton 29-1/2 47-1/2 47-1/2
4 TO5 Ton* 37-1/2 47-1/2 51-1/2 ** Measured from inside to inside on base rails.
46 - 1/8"*
Condensate Drain
19
12-1/4
RETURN
2-3/16
3-3/4
D E F G H I J K L M
3 9-1/2 12 14 12 14 4-1/2 16 42-3/4 1-9/16
7-1/2 5-1/2 19 12 12 19 4-1/2 22 46-1/4 5-3/16
ELECTRICAL POWER
CONDUIT
N 46-1/2 49-3/4
46201100301 131
3. SAFE INSTALLATION REQUIREMENTS
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with
local building codes or, in the absence of local codes, with the ANSI Z223.1 and the National Electrical Code NFPA70-1990 or
in Canada the National Standard CAN/CGA B149-1 and CSA C.22.1 - Canadian Electrical Code Part 1.
The information contained in this manual is intended for use by a qualified service technician familiar with safety proce-
dures and equipped with the proper tools and test instru- ments.
Failure to carefully read and follow all instructions in this
manual can result in furnace malfunction, property damage, personal injury and/or death.
Do NOT use this furnace as a construction heater.
Use only the Type of gas approved for this furnace (See Rating Plate).
Do NOT use open flame to test for gas leak.
Seal supply and return air ducts.
Check to see that filters are installed correctly and are
the proper type an size.
NOTE: It is the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.
CAUTION
It is recommended that a qualified service technician
check the heat exchanger integrity every two (2) years, after the first four (4) years of operation.
4. LOCATING THE UNIT
NOTE: Units with available filter racks ( 3-1/2 to 5 ton), need
a 26" minimum clearance at side of unit for removal of filters. See chart below if unit is going to be placed near
combustible construction or materials. While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation around
the unit for proper operation in the cooling mode. Whenever
possible, it is desirable to allow additional clearance, especially around the condenser inlet and discharge
openings.
Do NOT install the unit in a location that will permit
discharged air from the condenser to recirculate to the condenser inlet.
CAUTION
Do NOT operate unit in a corrosive atmosphere con- taining chlorine, fluorine, or any other corrosive chemicals.
Minimum Clearances to Combustible Construction
Furnace Plenum .................................... 2"
Duct Side ................. 2" (6" on large chassis models)
Condenser Inlet ................................... 30"
Blower Service (Side) .............................. 30"
Control Service Side
(Front Combustion Air Inlet) ............. 30"
Clearance between 3 Ft. Overhang
and Top of Unit ........................ 30"
Combustible Base
(Wood or Class A, B or C
roof covering material) .................... 0"
FIGURE i Minimum Clearances(BChassisandshown)ACcessPanels
Blower Compartment Panel
Large Chassis
ACCESS PANELS
See FIGURE 1 for a general view of unit and location of
access panels.
Carbon monoxide poisoning hazard.
Keep blower door closed.
Failure to keep blower door closed can result in bodily injury
and/or death.
CLEARANCES
Internal Filter Access from Burner Compartment Side
26" (Large Chassis Units)
INSTALLATION
Burner Compartment
NOTICE
80-00-01
Panel
The location MUST allow for minimum clearances and should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. The
combustion air inlet openings MUST not be obstructed (see
FIGURE 1). In addition, local codes MUST be observed.
141 462 01 1003 01
Unit will NOT operate properly unless it is installed lev- el front to rear and side to side. The slope MUST NOT be
greater than 1/8"per foot (10mm per meter). For side to side leveling, the drain side MUST always be lower.
80 _
Ground Level Installation
Ground level platform requirements:
- The unit MUST be situated to provide safe access for servicing.
Platform may be made of either concrete or pressure treated wood and MUST be level and strong enough to support unit weight.
Position platform separate from building foundation.
Install in well-drained area, with top surface of platform above grade level.
Platform must be high enough to allow for proper con- densate trap installation and drainage. See FIGURE 3
and associated text for more information about conden- sate drainage.
Rooftop Installation
Rooftop platform requirements:
- The unit MUST be situated to provide safe access for servicing.
- The existing roof structure MUST be adequate to sup- port the weight of the unit or the roof MUST be
reinforced. Check the weight of the unit in relation to the roof struc-
ture and local building codes or ordinances and reinforce roof structure if necessary. See the last page of this manual for unit weights.
- Support for the unit MUST be level and strong enough to carry unit weight. The support may consist of a plat- form or a combination of platform and roof beams or
curb.
- See Hoisting section for hoisting instructions.
HOISTING NOTE: All access panels MUST be secured in place before
hoisting.
The unit should be hoisted with two lifting slings. Attach the slings to rigging shackles that have been hooked through
holes in the base rail.
Two spreader bars MUST be placed on top of the unit to
protect the unit from damage from the pressure exerted by
the slings. Make sure that all equipment is adequate to
handle the weight of the unit and that the slings will not allow
the unit to shift.
Refer to FIGURE 17 on the back cover of this manual for illustrated rigging instructions and weight chart.
DOWNFLOW CONVERSION
NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The center rail is attached to the base rail with screws.
These units are adaptable to downflow use. To convert to downflow use, follow these steps:
1. Remove the blockoff plates found in the return air compartment and the supply air compartment.
NOTE: Blockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant plate into dimples, then put plate into position and fasten
with screw.
2. Install the removed plates on the horizontal return and supply air openings.
3. Install roof curb on the building. Be sure to follow all di- rections included with curb and all applicable building codes in your installation.
Heating Vent Assembly
Refer to FIGURE 2 and assemble as shown.
FIGURE 2 Heating Vent Assembly
Atta(_t?with 2 screws
Heen_ingi__ _
CAUTION
DO NOT OPERATE THE UNIT WITHOUT THE VENT AS- SEMBLY INSTALLED
Condensate Drain
The condensate drain outlet is a 3/4" (19.1 mm) female PVC connection located at the bottom on the left hand side (see
FIGURE 3).
The circulating blower creates a negative pressure on the condensate drain line that can prevent the condensate from
draining properly. To combat this negative pressure, a field supplied condensate trap that will allow a standing column
of water of at least 2" (50.8mm) MUST be installed. Top of outlet from trap MUST be at least 1" (25.4mm) below top of
outlet from unit. Install the trap as near to the unit as
possible for proper drainage,
A3/4" (19.1mm) drain line MUST be installed if required by
local codes or if location of unit requires it. Run the drain line
to an open drain or other suitable disposal point.
Flue Pipe
3 | Condensateora ninformation*
$
3/4" (19,1mm)
Female PVC
Fitting X
(25.4mm)
80-31-32
(
2" (50.8mm)
3/4" (19.1mm) Drain Line
* Condensate trap MUST be installed.
462 01 1003 01 151
5. PRE-EXISTING COMMON VENT CHECK
If the installation of the combination unit involves removing
an existing furnace from a common vent with other appliances, the existing venting system will probably be too
large for the remaining appliances and they will not vent
properly. The existing venting system MUST be checked by a qualified technician to ensure it is properly sized and vents properly.
6. GAS SUPPLY AND PIPING
NOTE: Because there are many types of liquified petroleum
(LP) gases, the term LP as used in this manual refers to
propane gas. If you intend to use any type of LP gas, proper
precautions MUST be used in the handling, piping, and use of such gas. NOTE: In Canada, installations MUST be
performed by licensed LP installers. The UL/CSA Rating Plate located on the side panel on the
unit contains the model number, type of gas and gas input
rating, and other important information.
Fire and/or explosion hazard.
Make certain the unit is equippedto operate onthe type of gas
available. Models designated as natural gas are to be usedwith
naturalgas only.Modelsdesignated for use with liquefiedpetro- leum (LP) gas are shipped with orifices sized for commercially
pure propanegas. They MUST not beusedwith butane or a mix-
ture of butane and propane unless properly sized orifices are
installed by a licensed LP installer. Failure to follow this warning can result in property damage,
_ersonal injury,and/or death.
GAS PIPING
The gas supply line MUST be of adequate size to handle the
Btu/hr requirements and length of the run for the unit being
installed. Determine the minimum pipe size for natural gas from the table in FIGURE 4 or FIGURE 5. Base the length of the run from the gas meter or source to the unit.
Gas Pipe Size
Btu ratings of all other gas appliances MUST be considered for sizing of main gas line. Check gas line to installation for
compliance with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1 or in
Canada the National Standard CAN/CGA B149-1 or current editions.
FIGURE 4
Pipe Length Btu/hr (in thousands)
(Includes
Fittings) 3/4" 1" 11/4" 11/2" 2"
20' 190 350 730 1,100 2,100
40' 130 245 500 760 1,450
60 ' 105 195 400 610 1,150
Pipe Length Btu/hr (in thousands)
(Includes
Fittings) 1/2" 3/4" 1" 11/4"
20' 189 393 732 1,496
40' 129 267 504 1,039
60' 103 217 409 834
Gas Pipe Size, Length and Btu/hr Capacity for Schedule 40 Iron Pipe (English)
NATURAL GAS
LP GAS
11/2"
2,299 1,559 1,275
FIGURE 5
Pipe Length
(Includes
Fittings)
6.1m
12.2m 38 425
18.3m 31 337
Pipe Length kW**
(Includes
Fittings) 1/2" 3/4" 1 " 11/4 " 11/2"
6.1m 55 115 215 438 674
12.2m 38 78 148 305 457
18.3m 30 64 120 244 374 **kW (Kilowatts) is the metric equivalent of Btu/hr.
Gas Pipe Size, Length and Btu/hr Capacity for Schedule 40 Iron Pipe (English)
NATURAL GAS
kW**
3/4" 2"
56 615
1" 11/4" 11/2"
103 214 322
72 147 223 57 117 179
LP GAS
PIPING AT UNIT Connections
NOTE: The rules listed apply to natural and LP gas pipe installations.
1. If installation is for LP gas, have LP gas installer use TWO-STAGE REGULATION and make all connec-
tions from storage tank to unit.
2. Use black iron or steel pipe and fittings or other pipe ap- proved by local code.
3. If copper tubing is used, it MUST comply with limitation set in Fuel Gas Code.
NOTE: If a gas connector is used, it MUST be acceptable to local authority. Connector MUST NOT be used inside the
furnace or be secured or supported by the furnace or ductwork.
Fire and/or explosion hazard.
Gas connector MUST be properly installed and can NOT be used inside the furnace.
Failure to do so can result in property damage, bodily injury or death.
4. Use pipe joint compound on external (male) threads ONLY. Joint compound MUST be resistant to any chemical action of LP gases (NO TAG). Do NOT put pipe compound on last 2 threads of pipe.
5. Use ground joint unions and install a drip leg no less than 3 inches (76 mm) long to trap dirt and moisture be- fore it can enter gas valve.
CAUTION
Overtightening assembly may cause damage to the
gas valve and/or wiring and may misalign the burners,
6. Use a wrench on gas valve when making connections to prevent gas valve from turning. Do NOT use a pipe wrench on the gas valve body.
7. Provide a 1/8 inch (3mm) National Pipe Thread (NPT) plug for test gauge connection immediately upstream of the gas supply connection to the furnace ifnone is sup- plied with the gas valve of unit.
462 01 1003 01
Loading...
+ 12 hidden pages