Installation Instructions
PDX4 Series
PACKAGED DUAL FUEL UNITS
TABLEOFCONTENTS
UNITDIMENSIONS ...................................... 2 - 4
SAFEINSTALLATIONREQUIREMENTS ......................... 5
LOCATINGTHE UNIT ....................................... 6
CLEARANCES ............................................ 6
INSTALLATION............................................ 6
GROUNDLEVELINSTALLATION .............................. 7
HOISTING................................................ 7
DOWNFLOWCONVERSION .................................. 7
HEATINGVENTASSEMBLY.................................. 7
CONDENSATEDRAIN....................................... 8
PRE-EXISTINGCOMMONVENTCHECK......................... 8
GASSUPPLYAND PIPING ................................... 8
ORIFICES............................................... 9
ELECTRICALWIRtNG.................................. 11
DUCTWORK ......................................... 13
FILTERS ............................................ 14
AIRFLOWADJUSTMENT ............................... 15
START-UPPROCEDURES .............................. 16
GAS PRESSURES .................................... 16
GAS HEATINGSTART-UPPROCEDURES .................. 17
OPERATION......................................... 18
MAINTENANCE ...................................... 20
INSPECTIONANDCLEANING............................ 21
COMPONENTLOCATION............................... 22
RIGGING ........................................... 23
WIRINGDIAGRAMS ................................ 24- 25
CQUS
LISTED
Printed in U.S.A.
Code: PDX4
InternationalComfortProducts,LLC
Lewisburg,TN. 37091
518 01 1801 00 12-08-06
1. Unit Dimensions "B" CHASSIS UNIT DIMENSIONS
COMBINATION GAS/
ELECTRIC UNITS
"B" Chassis z A
DIM.
A
32-1/2 826 _ _ _ _,_,_-_"_._"_.
B
47-3/8I 1203 _ _ f(_d((_'_%_ _
C
47-3/8 I 1203 J J _ _N_.._.___._/ _. "_
D
3-1/8 I 79 _" _ _"___ _ ./i"
E
11-1/8 283 _ _
F
G
H
I
J
K
L
M
N
P
Q
R
S
12 I 308 _
14-1/4 I 363 L_ _
14-1/4 I 363 _ _
12 I 308 "_ _ _ 'w'
4 102 "1''j
3,4 I19 28
4-1/4I lO8 [ _ _ _ "E'_
4-3/8 111 .._ _ __ ....._-_ < .
14-1/2 I 368 _ ["1 _"""_/_ ...../ f "_
12-1/4 I 311 y/ _, _ )-d .... ,._ |,L--4 _ ,_
12-1/8 308 j / _ "D" _ "H" _"-_/
14-1/4 363 / / *" _ _"
12-1/4 I 318 _" / _. I _>_. _
Units in "B" Chassis Configuration
PDX424 - 30
I "F"
f 1-3/8" _ _NDUIT k _ _ _ S_'_-_
A ,. I '2"3'1123]16,PIP E
ROOF CURB Unit Base shown separately to
for units in illustrate bottom of duct openings,
"B" Chassis
(473/8 x 473/8) Units in "B" Chassis Configuration_
DIM.
,NC,E_ M......... 8 PDX424 - 30 _ _.
A
42-3/4 1086 .,._v
B
39-3/4 1010 J_ _
C
D
E
F
G
H
K*
18 457 _ _ _
18 457 _ j
3-3/4 98 _ _ _.....-_
42-3/4 1086 _ J _ _._
39-3/4 1010 _ _ J_ _ _.
18 457 __ _<'_ _- _- _ /'-_l
_ ..... __ _ _._ _,,B:_ A
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions).
2-3/8"
3i (75) 1-3/8"
25-1/16"
COMBINATION GAS/
ELECTRIC UNITS
"C" Chassis
(473/8 x 73)
DIN INCHE8 _41LLOMEYER8
A 36 914
B 47-3/8 1203
C 73 1354
D 4-5/8 117
E 15 361
F 12 307
G 18-3/4 476
H 18-3/4 476
I 12 306
J 4 102
K 1 &1-1/4 25&31
L 4-1/4 108
M 5-1/4 133
N 12-1/4 311
P 19 483
Q 15 381
R 19 483
S 12-1/4 318
T 16-7/8 429
ROOF CURB
for
"C" Chassis
(473/8 x 73)
IM INCHES MgLLIM_T_RS
A 67-3/4 1721
B 64-3/4 1645
C 23 584
D 23 584
E 2-1/2 64
F 42-3/4 1086
G 39-3/4 1010
H 23 584
I 12 305
J 12 305
K* 14 356
"C" CHASSIS UNIT DIMENSIONS
ECTRICAL POWER
CONDUIT ('l(" DIM.)
W VOLTAGE
1/2" (12.7) CONDUIT
GAS CONNECTION
1/2" (12.7) PIPE
(97.1)
3-13/16"
,,p,,
Unit Base shown separately to
illustrate bottom of duct openings,
Units in "C" Chassis Configuration
PDX436-42
"F'L
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions),
13
3" (75)
l 1-3/8"
31-1/16"
(789 4)
"C+" CHASSIS UNIT DIMENSIONS
ECTRICAL POWER
CONDUIT ('K" DIM.)
W VOLTAGE
_/2" (12.7) CONDUIT
GAS CONNECTION
1/2" (12.7) PIPE
"C"
1 (2_79,7) 3-13/16"
COMBINATION GAS/
ELECTRIC UNITS
"C" Chassis
(473/8 x 73)
DIM
INOHE8 MILL_MEYER8
A
B
C
D
E
F
G
H
I
J
K
L
M
N
P
Q
R
S
T
42 1067
47-3/8 1203
73 1354
4-5/8 117
15 361
12 307
18-3/4 476
18-3/4 476
12 306
4 102
1 &1-1/4 25&31
4-1/4 108
5-1/4 133
12-1/4 311
19 483
15 381
19 483
12-1/4 318
16-7/8 429
ROOF CURB
for
"C" Chassis
(473/8 x 73)
IM INCHES MOLLIM_T_RS
A 67-3/4 1721
B 64-3/4 1645
C 23 584
D 23 584
E 2-1/2 64
F 42-3/4 1086
G 39-3/4 1010
H 23 584
I 12 305
J 12 305
K* 14 356
(97.1)
,,p,,
Unit Base shown separately to
illustrate bottom of duct openings,
Units in "C" Chassis Configuration
PDX448-60
141
"F'L
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions),
2. SAFE INSTALLATION REQUIREMENTS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
components. Only trained and qualified personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters. All other operations
should be performed by trained service personnel. When
working on air-conditioning equipment, observe
precautions inthe literature, tags, and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing operations.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISON HAZARD
Improper installation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide
poisoning, fire, or an explosion which could result in
personal injury or unit damage. Consult a qualified
installer, service agency, or gas supplier for information
or assistance. The qualified installer or agency must use
only factory-authorized kits or accessories when
modifying this product.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISON HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Before performing service or maintenance operations
on unit, turn off gas supply to unit. Then turn off unit main
power switch and install lockout tag.
Recogniz_ safety information. This is the safety-alert
symbol/.rk. When you see this symbol in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in serious injury or death.
WARNING signifies a hazard which could result in serious
injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
These instructions cover minimum requirements and
conform to existing national standards and safety codes. In
some instances, these instructions exceed certain local
codes and ordinances, especially those that may not have
kept up with changing residential construction practices.
We require these instructions as a minimum for a safe
installation.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON
MONOXIDE POISON HAZARD
Failure to carefully readand follow all instructions in this
manual could result in furnace malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes or, in the absence of
local codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 and the National Electrical
Code NFPA70-2005 or in Canada the National Standard
CAN/CGA B149-1 and CSA C.22.1 - Canadian Electrical
Code Part 1.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
orocedures and equipped with the proper tools and test
instruments.
SAFETY CONSIDERATIONS
• Use only with type of gas approved for this unit. Refer to
unit rating plate.
• Install this unit only in a location and position as specified
in section 3 of this manual.
• Never test for gas leaks with an open flame. Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in
section 5.
•Always install unit to operate within the unit's intended
temperature-rise range with a duct system, which has an
external static pressure within the allowable range, as
specified in section 9. Refer to unit rating plate for the al-
lowable external static pressures.
•All connecting ductwork to the unit (supply and return)
must be sealed to the unit casing as specified in section 7.
• Do NOT use this furnace as a construction heater.
•Check to see that filters are installed correctly and are the
proper type an size.
NOTE: Itis the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.
UNIT SAFETY
Failureto follow this caution may reduceunit reliability.
It is recommended that a qualified service technician
check the heat exchanger integrity everytwo (2)years,
after the first four (4) years of operation.
INTRODUCTION
The PDX4 unit is a fully self-contained, combination
Category Igas heating/electric heat pump unit designed for
outdoor installation (See pages 2 to 4 for unit dimensions).
All unit sizes have return and discharge openings for both
horizontal and downflow configurations, and are
factory-shipped with all downflow duct openings covered.
Unitsmaybeinstalledeitherona rooftop,cementslab,or
directlyonthegroundiflocalcodespermit.
Modelswitha'l" inthetwelfthpositionofthemodelnumber
are dedicatedLowNOxunitsdesignedfor California
installations.Theemissionsofthesemodelsdonotexceed
40nanogramsofnitrogenoxideemissionsperjouleofheat
outputasshippedfromthefactory,andmustbeinstalledin
CaliforniaAirQualityManagementDistrictsor anyother
regionsinNorthAmericawherea LowNOxruleexists.
3. LOCATING THE UNIT
ACCESS PANELS
See Figure 1 for a general view of unit and location of
access panels.
CARBON MONOXIDE POISONING HAZARD.
Failure to follow this warning could result in personal
injury and/or death.
Keep blower door closed.
CLEARANCES
The location MUST allow for minimum clearances and
should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. The
combustion air inlet openings MUST not be obstructed (see
Figure 1). In addition, local codes MUST be observed.
NOTE: Units with available filter racks (3-1/2 to 5ton), need
a 26" minimum clearance at side of unit for removal of
filters. See chart below if unit is going to be placed near
combustible construction or materials.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation around
the unit for proper operation inthe cooling mode. Whenever
possible, it is desirable to allow additional clearance,
especially around the condenser inlet and discharge
openings.
Do NOT install the unit in a location that will permit
discharged air from the condenser to recirculate to the
condenser inlet.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shorten life
of unit components.
Do NOT operate unit in a corrosive atmosphere
containing chlorine, fluorine, or any other corrosive
chemicals.
Minimum Clearances to Combustible Construction
Furnace Plenum ..................................... 2"
Duct Side ........................................... 2"
Condenser Inlet .................................... 30"
Blower Service (Side) ............................... 30"
Control Service Side
(Front Combustion Air Inlet) .............. 30"
Clearance between 3 Ft. Overhang
and Top of Unit ......................... 30"
Combustible Base
(Wood or Class A, B or C
roof covering material) ..................... 0"
FIGURE 1
I Minimum Clearances and Access Panels
B Chassis Shown)
\
80-00-01
Internat Filter Access
from Burner Compartment Side
26" (C Chassis Units)
INSTALLATION
NOTICE
Unit will NOT operate properly unless it is installed
level front to rear and side to side. The slope MUST NOT
be greater than 1/8"per foot (10mm per meter). For side
to side leveling, the drain side MUST always be lower.
Ground Level Installation
Ground level platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- Platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough to
support unit weight.
- Position platform separate from building foundation.
- Install in well-drained area, with top surface of platform
above grade level.
- Platform must be high enough to allow for proper
condensate trap installation and drainage. See
FIGURE 4 and associated text for more information
about condensate drainage.
Rooftop Installation
Rooftop platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- The existing roof structure MUST be adequate to
support the weight of the unit or the roof MUST be
reinforced.
Check the weight of the unit in relation to the roof
structure and local building codes or ordinances and
reinforce roof structure if necessary. See the last page
of this manual for unit weights.
- Support for the unit MUST be level and strong enough
to carry unit weight. The support may consist of a
platform or acombination of platform and roof beams or
curb.
- See Hoisting section for hoisting instructions.
HOISTING
Burner Compartment
Panel
161
NOTE: All access panels MUST be secured inplace before
hoisting.
The unit should be hoisted with two lifting slings. Attach the
slings to rigging shackles that have been hooked through
holes in the base rail,
Two spreader bars MUST be placed on top of the unit to
protect the unit from damage from the pressure exerted by
the slings. Make sure that all equipment is adequate to
handle the weight ofthe unit and that the slings will not allow
the unit to shift,
Refer to Figure 20 on the back cover of this manual for
illustrated rigging instructions and weight chart,
DOWNFLOW CONVERSION
NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The
center rail is attached to the base rail with screws.
These units are adaptable to downflow use, To convert to
downflow use, follow these steps:
1, Remove the blockoff plates found in the return air
compartment and the supply air compartment.
NOTE: Blockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant
plate into dimples, then put plate into position and fasten
with screw,
I FIGURE 2 I Heating vent Assembly I
Screwsfor
"B" Chassis
(473/8 x 473/8)
/
FIGURE 3 1 Heating Vent Assembly
Flue Support
(Shipped mounted to unit
Flue Cover
Condensate Drain
The condensate drain outlet is a 3/4" (19.1mm) female PVC
connection located atthe bottom of the unit tothe right of the
filter access panel (see FIGURE 4).
The circulating blower creates a negative pressure on the
condensate drain line that can prevent the condensate from
draining properly. To combat this negative pressure, afield
supplied condensate trap that will allow a standing column
of water of at least 2" (50.8mm) MUST be installed. Top of
outlet from trap MUST be at least 1" (25.4mm) below top of
outlet from unit. Install the trap as near to the unit as
possible for proper drainage,
A 3/4" (19.1 mm) drain line MUST be installed if required by
local codes or if location of unit requires it. Run the drain line
to an open drain or other suitable disposal point,
2. Install the removed plates on the horizontal return and
supply air openings.
3, Install roof curb on the building. Be sure to follow all
directions included with curb and all applicable building
codes in your installation. See page 2 or 3 for
appropriate roof curb to use.
Heating Vent Assembly
The flue cover is packed with installation screws in the
return air compartment, Refer to FIGURE 3 and assemble
as shown,
FIGURE 4
3/4" (19.1mm)
Threaded Female
* Condensate trap MUST be installed.
/ Condensate Drain Information*
25-1/2 ("B" Chassis)
32-1/4 ("C" Chassis)
(25.4mm)
2" (50.8mm)
171
4. PRE-EXISTING COMMON VENT CHECK
If the installation of this new combination gas heat/electric
cool unit involves removing an existing gas-fired furnace
from a common vent system with other gas-fired
appliances (gas-fired hot water heater, etc.), the existing
vent system must be checked and inspected by a qualified
technician. The qualified technician can determine if the
existing vent system will properly vent the flue products of
the remaining gas-fired appliances. In many cases, the
existing vent system may be oversized for the remaining
appliances.
5. GAS SUPPLY AND PIPING
NOTE: Because there are many types of liquified petroleum
(propane (LP)) gases, the term propane (LP) as used inthis
manual refers to propane gas. Ifyou intend to use any type
of propane (LP) gas, proper precautions MUST be used in
the handling, piping, and use of such gas. NOTE: In
Canada, installations MUST be performed by licensed
propane (LP) installers.
The UL rating plate located on the side panel on the unit
contains the model number, type of gas, gas input rating,
and other important information.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Makecertainthe unitisequippedtooperateonthetype of
gasavailable.Models designatedasnatural gas areto be
used with natural gas only. Models designated for use
with liquefied petroleum (propane (LP)) gas are shipped
with orifices sized for commercially pure propane gas.
They MUST not be used with butane or a mixture of
butane and propane unless properly sized orifices are
installed by a licensed propane (LP) installer.
GAS PIPING
The gas supply line MUST be of adequate size to handle the
Btu!hr requirements and length of the run for the unit being
installed. Determine the minimum pipe size for natural gas
from the table in FIGURE 5 or FIGURE 6. Base the length
of the run from the gas meter or source to the unit.
Gas Pipe Size
Btu ratings of all other gas appliances MUST beconsidered
for sizing of main gas line. Check gas line to installation for
compliance with local codes or, in the absence of local
codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 or in Canada the National
Standard CAN/CGA B149-1 or current editions.
FIGURE 5 for Schedule 40 Iron Pipe tEn_llish/
Pipe Length Btu/hr (in thousands)
(includes
Fittings) 3/4" 1 " 11/4" 11/2" 2"
20' 190 350 730 1,100 2,100
40' 130 245 500 760 1,450
60' 105 195 400 610 1,150
Pipe Length Btu/hr (in thousands)
(includes
Fittings) 1/2" 3/4" 1" 11/4" 11/2"
20' 189 393 732 1,496 2,299
40' 129 267 504 1,039 1,559
60' 103 217 409 834 1,275
FIGURE 6 for Schedule 40 Iron Pipe (English)
Pipe Length kW**
(includes
Fittinqs) 3/4" 1 " 11/4" 11/2" 2"
6.1m 56 103 214 322 615
12.2m 38 72 147 223 425
18.3m 31 57 117 179 337
Pipe Length kW**
(includes
Fittings) 1/2" 3/4" 1" 11/4" 11/2"
6.1m 55 115 215 438 674
12.2m 38 78 148 305 457
18.3m 30 64 120 244 374
I Gas Pipe Size, Length and Btu/hr Capacity
NATURAL GAS
propane (LP) GAS
I Gas Pipe Size, Length and Btu/hr Capacity
NATURAL GAS
Propane (LP) GAS
**kW (Kilowatts) is the metric equivalent of Btu/hr.
PIPING AT UNIT
Connections
In the state of Massachusetts:
- This product must be installed by a licensed Plumber or
Gas Fitter.
- When flexible connections are used, the maximum
length shall not exceed 36 inches.
- When lever type gas shutoffs are used they shall be
T-handle type.
- The use of copper tubing for gas piping is not approved
by the state of Massachusetts.
NOTE: The rules listed apply to natural and propane (LP)
gas pipe installations.
1. Ifinstallation is for propane (LP) gas, have propane gas
installer use TWO-STAGE REGULATION and make
all connections from storage tank to unit.
2. Use black iron or steel pipe and fittings or other pipe
approved by local code.
3. tf copper tubing is used, it MUST comply with limitation
set in Fuel Gas Code.
NOTE: If a flexible gas connector is used, it MUST be
acceptable to local authority. Connector MUST NOT be
used inside the furnace or be secured or supported by the
furnace or ductwork. Do not use a connector which has
181