ICP PDX324040K00A1, PDX324040K01A1, PDX330060K00A1, PDX330060K01A1, PDX336080K00A1 Installation Guide

...
Installation Instructions
PDX3 Series
PACKAGED DUAL FUEL UNITS
TABLEOFCONTENTS
UNITDIMENSIONS ...................................... 2 - 3 BALANCEPOINTTEMPERATURES ....................... 10
SAFEINSTALLATIONREQUIREMENTS ......................... 4
LOCATINGTHE UNIT ....................................... 5
CLEARANCES ............................................ 5
INSTALLATION............................................ 5
GROUNDLEVELINSTALLATION .............................. 5
HOISTING................................................ 6
DOWNFLOWCONVERSION .................................. 6
HEATINGVENTASSEMBLY.................................. 6
CONDENSATEDRAIN....................................... 7
PRE-EXISTINGCOMMONVENTCHECK......................... 7
GASSUPPLYAND PIPING ................................... 7
ORIFICES............................................... 8
ELECTRICALWIRING...................................... 10 WIRINGDIAGRAMS ................................ 22- 23
DUCTWORK......................................... 11
FILTERS ............................................ 12
AIRFLOWADJUSTMENT ............................... 13
START-UPPROCEDURES .............................. 14
GAS PRESSURES .................................... 14
GAS HEATINGSTART-UPPROCEDURES .................. 15
OPERATION......................................... 16
MAINTENANCE ...................................... 17
INSPECTIONANDCLEANING............................ 19
COMPONENTLOCATION............................... 20
RIGGING ........................................... 21
CQUS
Printed in U.S.A.
Code: PDX3
InternationalComfortProducts,LLC Lewisburg,TN. 37091
518 01 1601 00 2-22-06
1. Unit Dimensions "B" CHASSIS UNIT DIMENSIONS
COMBINATION GAS/
ELECTRIC UNITS PDX324 - 36
"B" Chassis
DIM=
(473/8 x 473/8) "0" _ "B"
INCHES MILLOMETERS
A
B
47-3/8 1203
C
47-3/8 1203
D
3-1/8 79
32-1/2 826
E
11-1/8 283
F
G
H I
J
K
L
M N
P
Q
R
S
12 306
14-1/4 383 _ _
14-1/4 363 _ _
12 308 "4 _ _1 'w'
4 102 "1''/
314_I19_28 f_ _ _I" J'"_
4-1/4 lO8 [ o \ _ _ ;'E'_
I1_% 1_1 .t 7. __ ....._ <. _.
12-1/4 311 y/_ _..J _/ j'G_._ T _ '_ 12-1/8 308 / / _ 'U'_'" _ "H" -">,/ /
14-1/4 363 / / _ _ ' _ 12-1/4 318 i_--_ ._--'/_
2-1/2" I
1-1/2" "d"
Units in "B" Chassis Configuration
/
(53975) __ '_L"_ _ _ //_¢ \
.-li8 _ _._ / _'__ _ /_ ..X._/_-- \
(282.575) (101.6) _
ROOF CURB Unit Base shown separately to
for units in illustrate bottom of duct openings,
"B" Chassis
(473/8 x 473/8) Units in "B" Chassis Configuration_
DIM.
INCHES " ......... 8 PDX324 - 36 _ _
A
42-3/4 1086 /'_ _x
B
39-3/4 1010 _ _
C D E F G H K*
18 457 // _ _._.
18 457 _ _
3-3/4 95 _/ / _/._..._
42-3/4 1086 _ _ /_ _._
121
"F'_ 8o:_o:12
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions),
"C" CHASSIS UNIT DIMENSIONS
COMBINATION GAS/
ELECTRIC UNITS
"C" Chassis
(473/8 x 73)
DIM INCHES MILLOMETERS
A 36 914
B 47-3/8 1203
C 73 1354
D 4-5/8 117 E 15 361
F 12 307
G 18-3/4 476
H 18-3/4 476 I 12 306
J 4 102
K 1 &1-1/4 25&31 L 4-1/4 108 M 5-1/4 133 N 12-1/4 311
P 19 483
Q 15 381
R 19 483
S 12-1/4 318 T 16-7/8 429
ROOF CURB
for
"C" Chassis
(473/8 x 73)
_IM INCHES MgLLIM_T_RS
A 67-3/4 1721
B 64-3/4 1645
C 23 584
D 23 584 E 2-1/2 64 F 42-3/4 1086
G 39-3/4 1010
H 23 584 I 12 305
J 12 305
K* 14 356
CONDUIT ('K" DIM.)
1/2"
CAL POWER
VOLTAGE
_/2" (12.7) CONDUIT
GAS CONNECTION
1/2" (12,7) PIPE
,,p,,
Unit Base shown separately to
illustrate bottom of duct openings,
Units in "C" Chassis Configuration PDX342-60
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions),
131
2. SAFE INSTALLATION REQUIREMENTS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical
components. Only trained and qualified personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions inthe literature, tags, and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing operations.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISON HAZARD
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide
poisoning, fire, or an explosion which could result in personal injury or unit damage. Consult a qualified
installer, service agency, or gas supplier for information
or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when
modifying this product.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISON HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Before performing service or maintenance operations on unit, turn off gas supply to unit. Then turn off unit main power switch and install lockout tag.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
Failure to carefully readand follow all instructions inthis manual could result in furnace malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of
local codes, with the National Fuel Gas Code NFPA 54-2005/ANSI Z223.1-2005 and the National Electrical
Code NFPA70-2005 or in Canada the National Standard CAN/CGA B149-1 and CSA C.22.1 - Canadian Electrical
Code Part 1. The information contained in this manual is intended for
use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test
instruments.
SAFETY CONSIDERATIONS
Use only with type of gas approved for this unit. Refer to unit rating plate.
Install this unit only in a location and position as specified in section 3 of this manual.
Never test for gas leaks with an open flame. Use a com- mercially available soap solution made specifically for the
detection of leaks to check all connections.
Always install unit to operate within the unit's intended temperature-rise range with a duct system, which has an external static pressure within the allowable range, as specified in section 9. Refer to unit rating plate for the al- lowable external static pressures.
All connecting ductwork to the unit (supply and return) must be sealed to the unit casing.
Do NOT use this furnace as a construction heater.
Check to see that filters are installed correctly and are the proper type an size.
NOTE: Itis the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.
Recogniz_ safety information. This is the safety-alert
symbol/.rX. When you see this symbol in instructions or
manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in serious injury or death.
WARNING signifies a hazard which could result in serious
injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local
codes and ordinances, especially those that may not have
kept up with changing residential construction practices.
We require these instructions as a minimum for a safe
installation.
141
INTRODUCTION
The PDX3 unit is a fully self-contained, combination
Category Igas heating / electric heat pump unit designed for outdoor installation (See pages 2 and 3 for unit dimensions). All unit sizes have return and discharge openings for both horizontal and downflow configurations,
and are factory-shipped with all downflow duct openings covered.
Units may be installed either on a rooftop, cement slab, or directly on the ground if local codes permit.
Models with a"l" inthe twelfth position ofthe model number are dedicated Low NOx units designed for California
installations. The emissions ofthese models do not exceed 40 nanograms of nitrogen oxide emissions per joule of heat
output as shipped from the factory, and must be installed in
California Air Quality Management Districts or any other
regions in North America where a Low NOx rule exists.
3. LOCATING THE UNIT
ACCESS PANELS
See Figure 1 for a general view of unit and location of
access panels.
CLEARANCES
The location MUST allow for minimum clearances and should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. The
combustion air inlet openings MUST not be obstructed (see
Figure 1). In addition, local codes MUST be observed. NOTE: Units with available filter racks (3-1/2 to 5ton), need
a 26" minimum clearance at side of unit for removal of filters. See chart below if unit is going to be placed near
combustible construction or materials. While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation around
the unit for proper operation inthe cooling mode. Whenever
possible, it is desirable to allow additional clearance, especially around the condenser inlet and discharge
openings.
Do NOT install the unit in a location that will permit
discharged air from the condenser to recirculate to the condenser inlet.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shorten life of unit components.
Do NOT operate unit in a corrosive atmosphere containing chlorine, fluorine, or any other corrosive
chemicals.
Minimum Clearances to Combustible Construction
Furnace Plenum ..................................... 2"
Duct Side ........................................... 2"
Condenser Inlet .................................... 30"
Blower Service (Side) ............................... 30"
Control Service Side
(Front Combustion Air Inlet) .............. 30"
Clearance between 3 Ft. Overhang
and Top of Unit ......................... 30"
Combustible Base
(Wood or Class A, B or C
roof covering material) ..................... 0"
FIGURE i Minimum Clearances and AccessPanels(BChassis Shown)
I Blower Compartment Panel
B Chassis - 2" C Chassis - 6"
Internat Filter Access from Burner Compartment Side
26" (C Chassis Units)
Burner Compartment
Panel
INSTALLATION
NOTICE
Unit will NOT operate properly unless it is installed
level front to rear and side to side. The slope MUST NOT
be greater than 1/8" per foot (10mm per meter). For side to side leveling, the drain side MUST always be lower.
Ground Level Installation
Ground level platform requirements:
- The unit MUST be situated to provide safe access for servicing.
- Platform may be made of either concrete or pressure treated wood and MUST be level and strong enough to support unit weight.
- Position platform separate from building foundation.
- Install in well-drained area, with top surface of platform above grade level.
- Platform must be high enough to allow for proper condensate trap installation and drainage. See
FIGURE 4 and associated text for more information
about condensate drainage.
151
Rooftop Installation
Rooftop platform requirements:
- The unit MUST be situated to provide safe access for servicing.
- The existing roof structure MUST be adequate to support the weight of the unit or the roof MUST be
reinforced. Check the weight of the unit in relation to the roof
structure and local building codes or ordinances and reinforce roof structure if necessary. See the last page of this manual for unit weights.
- Support for the unit MUST be level and strong enough to carry unit weight. The support may consist of a platform or acombination of platform and roof beams or
curb.
- See Hoisting section for hoisting instructions,
HOISTING NOTE: All access panels MUST be secured in place before
hoisting.
The unit should be hoisted with two lifting slings. Attach the slings to rigging shackles that have been hooked through
holes in the base rail,
Two spreader bars MUST be placed on top of the unit to
protect the unit from damage from the pressure exerted by
the slings. Make sure that all equipment is adequate to
handle the weight ofthe unit and that the slings will not allow
the unit to shift.
Refer to FIGURE 10 on the back cover of this manual for illustrated rigging instructions and weight chart,
DOWNFLOW CONVERSION NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The center rail is attached to the base rail with screws.
These units are adaptable to downflow use, To convert to downflow use, follow these steps:
1. Remove the blockoff plates found in the return air compartment and the supply air compartment.
NOTE: Blockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant plate into dimples, then put plate into position and fasten
with screw.
I FIGURE2 1 Heating Vent Assembly
Screws for Screw for
"B" Chassis "C" Chassis
(473/8 x 473/8) (473/8 x 73)
2. Install the removed plates on the horizontal return and supply air openings.
3, Install roof curb on the building. Be sure to follow all
directions included with curb and all applicable building codes in your installation. See page 2 or 3 for appropriate roof curb to use.
Heating Vent Assembly
The flue cover is packed with installation screws in the
return air compartment, Refer to FIGURE 3 and assemble
as shown,
FIGURE 3 1 Heating Vent Assembly
Flue Support
(Shipped mounted to unit
Flue Cover
UNIT DAMAGE
Failure to follow this caution may result in unit damage.
Do not operate the unit without the vent assembly installed.
I
161
Condensate Drain
The condensate drain outlet is a 3/4" (19.1 mm) female PVC connection located atthe bottom ofthe unit tothe right ofthe
filter access panel (see FIGURE 4). The circulating blower creates a negative pressure on the
condensate drain line that can prevent the condensate from draining properly. To combat this negative pressure, a field supplied condensate trap that will allow a standing column
of water of at least 2" (50.8mm) MUST be installed. Top of outlet from trap MUST be at least 1" (25.4mm) below top of
outlet from unit. Install the trap as near to the unit as
possible for proper drainage.
A 3/4" (19.1mm) drain line MUST be installed if required by
local codes or if location of unit requires it. Run the drain line
to an open drain or other suitable disposal point.
FIGURE 4 Condensate Drain Information*
3/4" (19,1mm) Threaded Female
PVC Fitting
b
25-1/2 ("B" Chassis) 32-1/4 ("C" Chassis)
1 "
(25.4mm)
/
2" (5O.8mm)
80-30-27
* Condensate trap MUST be installed,
4. PRE-EXISTING COMMON VENT CHECK
If the installation of this new combination gas heat/electric cool unit involves removing an existing gas-fired furnace from a common vent system with other gas-fired
appliances (gas-fired hot water heater, etc.), the existing vent system must be checked and inspected by a qualified technician. The qualified technician can determine if the
existing vent system will properly vent the flue products of the remaining gas-fired appliances. In many cases, the
existing vent system may be oversized for the remaining appliances.
5. GAS SUPPLY AND PIPING
NOTE: Because there are many types of liquified petroleum (LP) gases, the term LP as used in this manual refers to
propane gas. Ifyou intend to use any type of LP gas, proper
precautions MUST be used in the handling, piping, and use
of such gas. NOTE: In Canada, installations MUST be
performed by licensed LP installers.
The UL rating plate located on the side panel on the unit contains the model number, type of gas, gas input rating,
and other important information.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Makecertainthe unitisequipped tooperate onthe type of gasavailable.Models designatedasnatural gas areto be used with natural gas only. Models designated for use
with liquefied petroleum (LP) gas are shipped with
orifices sized for commercially pure propane gas. They MUSTnot beusedwith butane or amixtureofbutane and
propane unless properly sized orifices are installed by a licensed LPinstaller.
GAS PIPING
The gas supply line MUST be of adequate size to handle the
Btu/hr requirements and length of the run for the unit being
installed. Determine the minimum pipe size for natural gas from the table in FIGURE 5 or FIGURE 6. Base the length of the run from the gas meter or source to the unit.
Gas Pipe Size
Btu ratings of all other gas appliances MUST be considered for sizing of main gas line. Check gas line to installation for
compliance with local codes or, in the absence of local codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 or in Canada the National
Standard CAN/CGA B149-1 or current editions.
FIGURE 5
Pipe Length Btu/hr (in thousands)
(includes
Fittings) 3/4" 1" 11/4" 11/2" 2"
20' 190 350 730 1,100 2,100 40' 130 245 500 760 1,450 60' 105 195 400 610 1,150
Pipe Length Btu/hr (in thousands)
(includes
Fittings) 1/2" 3/4" 1" 11/4"
20' 189 393 732 1,496 40' 129 267 504 1,039
60' 103 217 409 834
Gas Pipe Size, Length and Btu/hr Capacity for Schedule 40 Iron Pipe/English/
NATURAL GAS
LP GAS
11/2" 2,299 1,559 1,275
171
Loading...
+ 16 hidden pages