ICP PAPA48GA1, PAPA42GA1, PAPA42GA, PAPA36GA1, PAPA36GA Owner’s Manual

...
Installation Instructions
I DIRECT DRIVE BLOWER
Three Phase
PA55/PAPA SERI ES
SINGLEPACKAGEAIRCONDITIONERS
ELECTRICHEAT(OPTIONAL)c
ELECTRIC / @
TABLEOFCONTENTS
Danger, Warning and Caution ................................... 2
Clearances ................................................... 2
Dimensions ................................................... 2
Minimum Clearances to ComLJstibte Construction 3
Installation ................................................... 3
Installing Duct Collars .. 3
_'ondensate Drain ,1
Ground Connections ........................................... 4
Line Voltage Wiring ............................................ 4
Unit Disconnect ............................................... 4
Converting 230M tJnils to 208V ................................... 4
Low Voltage Wiring ........................................... 4
Thermostat Connections ........................................ 5
Field Installed Equipment ........................................ 5
General Information .......................................... 6
Adjustinc Thermostat Anticipator ....... 6
Limit Controls ....... 6
Operation ........ 6
Install Heater ................................................. 6
Heater Wiring ................................................. 6
Grounding ..................... 6
Installing Wrong 6
Unit Disconnect Breaker ......................................... 8
Rain Shield Installation ........................................ 8
6. Air Distribution System .............................. 8
Ductwork .................................................... 8
DuctworkInsulation.. ..... 8
DactwerkConnections........ 8
Filters ........................................................ 8
7. Start-up Procedul'es ................................ 9
Final Electrical Check ........................................... 9
Circulating Air Blower ......................................... 9
DeterminingEower Speed ......... g
BDeedTai3s.................. 9
Cooling and AuxiliaryElectric StripHeat ............................ 9
CheckBefore Starting .......................................... 9
CirculatingAir Blower ......... 10
Cooling ..................................... 10
Auxiliary _ea[mg......................... 10
Temperature Rise Check ..... i,,. ................................ 10
SequenceofOperation , .................................... 10
CoolingMode:Energizan RGY'_) De_ene_gized(NA ............... 10
8. Operation ............................................ 11
ScrollAnti-Cycle Timer {Wh_reApplicai:31e}......................... 11
Turning The UnitOff ............................................... 11
ThermostatFanSwitch Operation...,, ........................... 11
AdjustingRoomTemperatures .... .., ........................... 11
13, Maintenance ...................................... 11
MonthlyMaintenanceandInspection Checks ....................... 11
Air Fitters . 11
Cooling Season Checks (Monthly} ................................ 11
CondenserCo ..... 11
CondensateDrain... 11
AnnualMaintenanceand inspection .............................. 1t
CondenserFan Motor 11 CircaiatingAir Blower 12
Printed in U.S.A. 426 O11OO5 CO
1o/15/Ol
1. Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DAN-
GER is only used on product labels to signify an immediate haz- ard. The signal words WARNING and CAUTION will be used on
product labels and throughout this manual and other manuals that may apply to the product.
2. Safe Installation Requirements
Installation or repairs made by unqualified persons can result
in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the
National Electrical Code NFPA70-1990 or current edition.
The information contained in this manual is intended for use by a qualified service technician familiar with safety proce-
dures and equipped with the proper tools and test instru- ments.
Failure to carefully read and follow all instructions in this
manual can result in unit malfunction, property damage, per- sonal injury and/or death.
Seal supply and return air ducts.
Check to see that filters are installed correctly and are the proper type and size.
NOTE: It is the personal responsibility and obligation of the cus-
tomer to contact aqualified installer to ensure that the installation
is adequate and conforms to governing codes and ordinances.
CAUTION
Do NOT operate unit in a corrosive atmosphere containing chlorine, fluorine, or any other corrosive chemicals.
3. Locating & Installing The Unit
The unit is designed for outdoor installation only. Place the unit on a platform at ground level. The unit may be installed on a concrete
slab of 48" (1219mm) x 48" (1219mm) dimensions. Cement blocks on a 3" sand footing will also work. The slab or blocks
SHOULD NOT be in contact with any part of the structure. Check local codes covering zoning, noise, platforms, etc..
If practical avoid locating next to fresh air intakes, vent or bed-
room windows. Noise may carry into the openings and disturb people inside.
Avoid installations under roof overhangs without guttering. Water draining from the roof onto the unit could produce excessive
noise, and may cause ice to build up on coil or fan.
Placement of the unit should be in a well drained area or the unit
MUST be supported high enough so runoff will not enter the unit.
Do not locate unit where heat, lint or exhaust fumes wil! be dis-
charged on unit (as from dryer vents.)
Clearances
Minimum clearances, as specified in FIGURE 1, MUST be main- tained from adjacent structures to provide adequate air circula-
tion and room for service personnel. While minimum clearances are acceptable for safety reasons,
they may not allow adequate air circulation around the unit for proper operation. Whenever possible, it is desirable to allow addi-
tional clearance, especially around the condenser inlet and dis- charge openings.
Do NOT install the unit in a recessed or confined area that will per-
mit discharged air from the condenser to recirculate to the con- denser inlet.
Dimensions
NOTE: DUCT COLLARS ATTACHED TO SUPPLY AND RETURN MUST BE REVERSED AT INSTALLATION. SEE INSTRUCTIONS ON PAGE 3.
ALL DIMENSIONS IN INCHES ROUND SHAPED FLANGE WILL
T
IIIl_ll_1_LI1_1_l]_l_ll_m I_1_11m]11_1111_111 WILL
IlllHlllliltllliHla#ltlillllti/i_ll_Jlltll_iltlialtlla RETURN DUCT DIA HOLE**
26.5
_llllllllllll[llllll_ftlllllt_illlllJlllltlllit#lll_ll_
PRpEoSSUsRE_/_ 263/4 _ 1
<_ 61 \
* ELECTRICAL ACCESS FOR LINE VOLTAGE POWER SUPPLY-ONE FOR UNIT, ONE FOR HEATER ** FOR LOW VOLTAGE WIRING
COIL
ACCESS
PANEL
CONDENSATE DRAIN 41
CONECTION
ROUND FLANGE r /
ACCOMMODATE14D,A
10
2 426 01 1005 00
ACCOMMODATE 12" DtA. SUPPLY DUCT
3/4
Minimum Clearances to Combustible Construction ......
SERVICE ACCESS CLEARANCES
Blower Access Pane! Side ................... 30" (762mm)
Electrical Access Panel Side ................. 30" (762mm)
OPERATIONAL CLEARANCES Combustible Base
(Wood or Class A, B or C
roof covering material) .................... 0"
Supply and Return Air Ducts ........................... 0"
Duct Connection Side
....................................... 0 _
Clearance between Overhang
and Top of Unit ............... 48" (1219mm)
Clearance around Condenser Coil area to wall or shrubs . 10"
FIGURE i Minimum Clearances and Access Panels
Overhang
Evaporator 48" Minimum Overhang Clearance
Access Panel
Installing Duct Collars
J
lO"around
f condenser
coilarea
Duct collars are supplied with the unit and are attached to the sup-
ply and return openings with the flanges to the inside and must be reversed before unit's installation.
1. Remove the screws from the collars and reverse them so the flange is to the outside.
6 _
,,_ Cover Plate
Blower/Electrical
Access Panel
Installation
CAUTION
The unit must be installed as level as possible, with a maxi- mam slope no greater than 1/8" per foot (lOmm per meter).
For side to side leveling, the condensate drain side of the
unit MUST always be lower to provide proper drainage.
The unit MUST be situated in such a way as to provide safe access for servicing.
The platform may be made of either concrete or pressure treated wood and MUST be level and strong enough to
support the unit's weight.
2. Make sure when pushing the collars into place that the "V" flange of the collars seats into the supply and return holes
securely.
3. Re-install screw in each collar so it goes through both of the
holes in the collar end. It does not matter how the ends of
the collar overlap in order to accomplish this.
FIGURE 3 I Duct Collar Installation
Position platform separate from the building's foundation.
Install in a well-drained area, with the top surface of the platform high enough above grade level to allow installa-
tion of a condensate drain trap. See FIGURE 4
3
426 01 1005 O0
Condensate Drain
The condensate drain outlet is a 3/4" (19.1 mm) threaded female
PVC connection located at the bottom of the unit to the left of the
evaporator access panel. The circulating blower and the condenser fan create a negative
pressure on the condensate drain line that will prevent the con- densate from draining properly without a trap. To combat this neg- ative pressure, a field supplied condensate trap that will allow a
standing column of water of at least 2" (50.8mm) MUST be
installed. The outlet of the trap must be at least 1" below the unit
drain connection. Install the trap as near to the unit as possible
for proper drainage.
A 3/4" (19.1 mm) drain line MUST be installed if required by local codes or iflocation of unit requires it. Run the drain line to an open
drain or other suitable disposal point.
4. Electrical Wiring
Electrical shock hazard.
Disconnect power at fuse box or service panel before
making any electrical connections.
Unit MUST be grounded to electrical service panel. Failure to follow this warning can result in property
damage, personal injury, and/or death.
FIGURE 4 J Condensate Drain Information*
3/4" (19.1mm) Threaded Female
PVC Fitting
(25.4mm)
33/4 t_ .
(82.5mm)
trical control plate. Check all screw terminals to ensure they are tight.
NOTE: If an Electric Heat Accessory is installed, refer to the Elec- tric Heat Accessory section of this manual to determine line volt-
age connections. The Electric Heat Accessory mounts inside the unit in the heater box. Field supplied line voltage wires for the
Electric Heat Accessory (separate from the field supplied line voltage wires to the unit) connect to the appropriate circuit break- er (if used) in the Electric Heat Accessory.
2" (50.8mm)
* Condensate trap MUST be installed.
3/4" (19.1mm)
Drain Line
Unit Disconnect
NOTE: All electrical work MUST conform with the requirements of local codes and ordinances and in the United States with National
Electrical Code ANSI/NFPA 70-1990 (or current edition). Provide
line voltage power supply from a separate fused circuit with a dis- connect switch (when required) located within sight of the unit. Supply voltage, amperage, fuse and disconnect switch sizes
MUST conform with local codes and ordinances. Wiring MUST be protected from possible mechanical damage
and MUST NOT interfere with removal of access panels, filters,
etc.
All exposed line voltage connections MUST be made through liq- uid tight conduit to prevent water from entering the unit through
the electrical access..
Ground Connections
A ground lug is installed on the control plate (or electric heat mounting plate) for the ground connection. Use a copper conduc-
tor of the appropriate size from the unit to a grounded connection
in the electrical service panel or to a properly driven and electrical-
ly grounded ground rod.
Line Voltage Wiring
Do NOT complete line voltage connections until unit is perma- nently grounded. All line voltage connections and the ground con-
nection MUST be made with copper wire. Connections for line voltage are made on the unit electrical con-
trol plate (see FIGURE 7). For access, remove the Blower/Elec- trical access panel.
Refer to applicable wiring diagram and FIGURE 6. Complete the
line service connections to the contactor 'L' terminals on the elec-
A Disconnect Switch Kit is available that installs inside the unit or a seperate circuit breaker may be installed to control the unit. Re-
fer to instructions following heater installation section.
Converting 230V Units to 208V
To convert 230V units to 208V:
1. Turn electric power OFE
2. Remove the blower/electrical access panel.
3. Locate the 24V control transformer.
4. Remove wire from the terminal labeled "240V" on the 24V control transformer and reconnect it to the 208V terminal of the 24V control transformer.
5. Replace the electrical/compressor access panel.
Low Voltage Wiring
For access, remove the electrical control/blower access panel. Refer to the connection wiring diagram for the applicable model
and to the instructions included with the thermostat.
Route low voltage wires through the port located on the rear panel
and up to the control box. NOTE: If an Electric Heat Accessory is installed, see the Electric
Heat Accessory Installation Section of this manual for low voltage
connections.
4 426 01 1005 00
Thermostat Connections
The location of the thermostat has an important effect on the op- eration ofthe unit. See the thermostat instructions for proper con-
nection. See FIGURE 5 for Low Voltage Wire Harness Connections
Field Installed Equipment
Wiring to be done in the field between the unit and other devices, or between separate devices which are field installed and located,
MUST NOT exceed the temperature limitations for type T wire and MUST be installed according to the manufacturer's instruc-
tions for the devices.
FIGURE 5 I HarnessElectr°niCconnectionTherm°statDiagramL°WVoltage Wi ring
Typical Thermostat Subbase
[c] [?] [R,] _ _,]
I I I I I I I I I I
_ _ _ _ (when used)
I I I I /
i i i i A
I I I I I
Corn Fan 24V Comp Elect. (when Cool Heat
used) Acces.
[Blue] [Green] [F_ed][Yellow] [White] _[
Unit Low Voltage Wiring Harness.
I
FIGURE 6 I Typical Connections at Unit
USE COPPER CONDUCTORS ONLY
2g8/23gV 60HZ 3PH
FIGURE 7 Control Box Configuration
Outdoor Fan f._ '_-_ t
copao,tor\ _0-:__"_
Bl°wer Relay °r Sequence L __2_"_///_
Transformer%___ ___/__/_
Anti-Cycle Time J_.X_ _ I_:_"_:;_ j_f /'_" Control Box
_owvo,twireEntrance_ _.__ __i_i
c;: o;en,
Volt Wire Entrance
Wire
5
426 01 1005 O0
Loading...
+ 9 hidden pages