ICP OWB, OWT User Manual

Oil-Fired Water Boilers
Boiler Manual
Contents Page
1 Prepare boiler location ........................................................2
2 Prepare boiler ..................................................................... 5
3 Connect breeching .............................................................6
4 Connect water piping ..........................................................7
5 Connect tankless heater piping.........................................10
6 Connect wiring..................................................................11
8 Start-up ............................................................................15
9 Checkout procedure .........................................................16
10 Appendix ..........................................................................17
11 Service and maintenance ................................................. 1 8
12 Replacement parts ........................................................... 22
13 Dimensions ......................................................................26
14 Ratings .............................................................................27
Hazard definitions
Hazards that will cause severe personal injury, death or substantial property damage.
Hazards that can cause severe personal injury, death or substantial property damage.
INSTALLER — Read all instructions before installing. Read page 2 first. Follow all instructions in proper order to prevent personal injury or death.
Consider piping and installation when determining boiler location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
This manual must only be used by a qualified heating installer/service technician. Boiler and burner must be installed and serviced only by a qualified heating installer/service technician. Failure to comply could result in se vere personal injury , death or substantial property damage.
When calling or writing about the boiler— Please have: • boiler model number from the boiler rating label and • CP number from the boiler jacket. You ma y list the CP number in the space provided on the “Installation and service certificate” found on page 16.
Hazards that will or can cause minor personal injury or property damage.
Special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage .
USER — Please read the following. Failure to comply could result in severe personal injury , death or substantial property damage.
This manual is for use only by your qualified heating installer/service technician.
Please see the Users Inf ormation Manual for your reference.
Have the boiler serviced by a qualified service technician, at least annually .
Part Number 672 01 1005 00
OWB & OWT
Oil-Fired Water Boilers – Boiler Manual
1 Prepare boiler locationRead this first!
Failure to adhere to the guidelines below can result in severe personal injury, death or substantial property damage.
When servicing boiler
1. To avoid electric shock, disconnect electrical supply before performing maintenance.
2. To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation
3. Do not bloc k flow of combustion or v entilation air to boiler.
4. Should overheating occur, do not turn off or disconnect electrical supply to circulator. Instead, shut off the oil supply at a location external to the appliance, if possible.
5. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any burner control that has been under water .
Boiler water
6. DO NOT use petroleum-based cleaning or sealing compounds in boiler system. Water seal deterioration will occur, causing leakage between boiler sections, circulator flanges, diaphragm tanks or other system components. This can result in substantial property damage.
7. DO NOT use "homemade cures" or "boiler patent medicines". Serious damage to boiler , personnel and/or property may result.
8. Continual fresh makeup water will reduce boiler life. Mineral buildup in sections reduces heat transfer , ov erheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water .
9. Do not add cold water to hot boiler. Thermal shock can cause sections to crack.
Glycol potential fire hazard
All glycol is flammable when exposed to high temperatures. If glycol is allowed to accumulate in or around the boiler or any other potential ignition source, a fire can dev elop. In order to prevent potential se vere personal injury , death or substantial property damage from fire and/or structural damage:
Never store glycol of any kind near the boiler or any potential ignition source.
Monitor and inspect the system and boiler regularly for leakage. Repair any leaks immediately to prevent possible accumulation of glycol.
Never use automotive antifreeze or ethylene glycol in the system. Using these glycols can lead to hazardous leakage of glycol in the boiler system.
Codes & checklist
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances.
NFP A-31, Installation of Oil-Burning Equipment.
Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1, when required.
National Electrical Code.
For Canada only: B149.1 or B149.2 Installation Code, CSA
C22.1 Canadian Electrical Code Part 1 and any local codes.
Certification
The OWB and OWT boilers, burners and controls met safe lighting and other performance criteria when boiler underwent tests specified in CSA B140.0 and B140.7.1.
Before locating the boiler:
Check for nearby connection to:
System water piping
V enting connections (page 6)
Combustion and ventilation air provisions (page 4)
Oil supply piping (page 14 and burner manual)
Electrical power
Check area around boiler. Remov e any combustible materials,
gasoline and other flammable liquids.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death or substantial property damage.
Boiler must be installed so that burner and control system
components are protected from dripping or spraying water or rain during operation or service.
If new boiler will replace existing boiler, chec k f or and correct
system problems, such as:
1. System leaks causing oxygen corrosion or section cracks
from hard water deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze (when required) in boiler water causing
system and boiler to freeze and leak.
2 Part Number 672 01 1005 00
OWB & OWT
Oil-Fired Water Boilers – Boiler Manual
1 Prepare boiler location
Clearances Flooring and foundation
Minimum clearance to combustible materials
1. Minimum clearances from vent pipe to combustible material (see
Figure 1, vent clearances indicated with *):
Type “L” double wall vent 6 inches minimum
Singlewall vent 18 inches minimum
Flue pipe clearances must take precedence over jacket clearances (listed below).
Service clearances
1. Recommended service clearances (see Figure 1):
Front and top 24 inches
Left side, back and right side 6 inches
Right side for burner door swing radius 12 inches
2. Special close clearances (alcove, closet, under counters, etc.) – see Appendix,” page 17.
Figure 1 Minimum clearances
Flooring
The OWB and OWT boilers are approved for installation on combustible flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even if foundation is used. Fire can result, causing se vere personal injury , death or substantial property damage.
Foundation
1. Provide a solid brick or minimum 2-inch thick concrete foundation pad if any of the following is true:
floor can become flooded.
the boiler mounting area is not level.
2. See T ab le 1 for minimum f oundation dimensions.
Table 1 Minimum foundation size
Boiler model number
OWB/OWT3 17 22 2 OWB/OWT4 17 22 2 OWB/OWT5 20 22 2 OWB/OWT6 23 22 2
Length
inches
Width inches
Minimum
height inches
Residential garage installations
T ake the f ollowing special precautions when installing the boiler in a residential garage. If the boiler is located in a residential garage:
Mount the boiler a minimum of 18 inches above the floor of the garage to ensure the burner and ignition devices will be no less than 18 inches above the floor .
Locate or protect the boiler so it cannot be damaged by a moving vehicle.
3Part Number 672 01 1005 00
OWB & OWT
Oil-Fired Water Boilers – Boiler Manual
1 Prepare boiler location continued
Air contaminationAir for combustion and ventilation
Adequate combustion and ventilation air:
Assures proper combustion.
Reduces risk of severe personal injury or death from
possible flue gas leakage and carbon monoxide emissions.
Do not install exhaust fan in boiler room.
Consider building construction
Older buildings with single-pane windows, minimal weather-stripping and no vapor barrier often provide enough natural infiltration and ventilation without dedicated openings.
New construction or remodeled buildings are most often built tighter . Windows and doors are weather-stripped, vapor barriers are used and openings in walls are caulked. As a result, such tight construction is unlikely to allow proper natural air infiltration and ventilation.
Follow state, provincial or local codes when sizing adequate combustion and ventilation air openings. In absence of codes, use the following guidelines when boiler is in a confined room (defined by NFPA 31 as less than 7200 cubic feet per 1 GPH input of all appliances in area. A room 8 ft. high x 30.0 ft. x 30.0 ft. is 7200 cu. ft.).
Provide two permanent openings:
One within 12 inches of ceiling, one within 12 inches of floor. Minimum height or length dimension of each rectangular opening should be at least 3 inches.
When inside air is used:
Each opening must freely connect with areas having adequate infiltration from outside. Each opening should be at least 140 sq. in. per 1 GPH input (1 sq. in. per 1000 Btu input) of all fuel-burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer and fireplace).
When outside air is used:
Connect each opening directly or by ducts to the outdoors or to crawl or attic space that freely connects with outdoors. Size per below:
Through outside wall or vertical ducts at least 35 sq. in. per 1 GPH input (1 sq. in. per 4000 Btu input) of all fuel burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer and fireplace).
Through horizontal ducts at least 70 sq. in. per 1 GPH boiler input (1 sq. in. per 2000 Btu input) of all fuel-burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer and fireplace).
Where ducts are used, they should have same cross-sectional area as free area of openings to which they connect. Compensate for louver, grille or screen blockage when calculating free air openings. Refer to their manufacturer’s instructions for details. If unknown, use:
Wood louvers , which provide 20-25% free air.
Metal louvers or grilles, which provide 60-75% free air .
Lock louvers in open position or interlock with equipment to prove open before boiler operation.
Please review the following information on potential combustion air contamination problems.
See Tab le 2 for products and areas which may cause contaminated combustion air .
T o prev ent potential of severe personal injury or death, check for products or areas listed below before installing boiler. If any of these contaminants are found:
remove contaminants permanently .
OR
isolate boiler and provide outside combustion air. See national, provincial or local codes for further information.
Table 2 Corrosive contaminants and likely locations
Products to avoid
Spray cans containing chloro/fluorocarbons Permanent wave solutions Chlorinated waxes/cleaners Chlorine-based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning solvents found in
household laundry rooms Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Remodeling areas Garages with workshops
4 Part Number 672 01 1005 00
2 Prepare boiler
OWB & OWT
Oil-Fired Water Boilers – Boiler Manual
Place boiler
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 21 of this manual. F ailure to comply could result in severe personal injury .
1. Remov e circulator carton strapped to pallet. Circulator will be damaged if not removed before boiler
is lifted from pallet.
2. Remove boiler from pallet. Do not drop boiler or bump jacket or burner on floor
or pallet. Damage to boiler or burner can result. Smaller sized boilers may be top heavy . Use caution
when handling to avoid minor personal injury or property damage.
3. Check level. Shim legs if needed.
4. Open burner mounting door. V erify that chamber ceramic liner
is securely in place on target wall, chamber floor and burner door. V erify door seal is intact and in place. Close and securely bolt the door.
6. Visually check:
a. Flue collector hood seal. b . Burner mounting door seal.
Obtain gas-tight seal to prevent possible flue gas leakage and carbon monoxide emissions, which can lead to severe personal injury or death.
Hydrostatic pressure test
1. Install air vent in air vent tapping on top of boiler (see Figure 20, page 26, for location).
3. Plug supply and return tappings.
4. Drain valve is factory-installed.
5. Fill boiler. V ent all air. Pressure test boiler at 1 ½ times w orking pressure.
Do not leave boiler unattended. Cold water fill can expand and damage cast iron, resulting in severe personal injury, death or substantial property damage.
6. Verify that boiler maintains pressure for at least 10 minutes. Visually check for leaks if gauge pressure drops.
7. Drain boiler. Repair leaks if f ound.
Using petroleum-based compounds to repair leaks can damage system components, resulting in property damage.
8. Retest boiler after repairing leaks.
9. Remove air vent and plugs.
5Part Number 672 01 1005 00
OWB & OWT
Oil-Fired Water Boilers – Boiler Manual
3 Connect breeching
General venting requirements
Failure to follo w all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
Inspect existing chimney before installing boiler. Insufficient draft can cause flue gas leakage and carbon monoxide emissions. Failure to clean or replace perforated pipe or tile lining and/or patch mortar and joints can cause severe personal injury or death.
The OWB and OWT boilers are designed to operate with an over-fire draft of -0.01" to -0.02" w.c. Proper draft f or these oil boilers may be achieved using either a conventional chimney (natural draft) or a power vent (sidewall) system that has been properly designed for use with oil-fired equipment. Pow er vent manufacturers instructions must be f ollowed.
Use vent material approved by local codes for oil-fired burners. In their absence, refer to:
NFP A 31, Installation of Oil-Burning Equipment.
NFP A 211, Standard f or Chimneys, Fireplaces , Vents and
Solid Fuel Burning Appliances.
In Canada, refer to CSA B139, Installation Code for Oil-
Burning Equipment.
NFPA 211 requires chimney to be lined before connected
to boiler.
To prevent downdrafts, extend chimney at least 3 feet above highest point where it passes through roof and 2 feet higher than any portion of building within 10 feet. Increase chimney cross-sectional area and height at least 4% per 1,000 feet above sea level.
Provide minimum clearances from vent (flue) pipe to combustible material:
Type “L” double wall vent 6 inches minimum
Singlewall vent 18 inches minimum
Minimum chimney sizes should be used. See Table 3.
Oversized chimneys, outside masonry chimneys and/or derated inputs can result in condensation in chimney.
Connect breeching
Long horizontal breechings, excessive number of tees and elbows, or other obstructions restricting combustion gas flow can result in possibility of condensation, flue gas leakage and carbon monoxide emissions, which can lead to severe personal injury or death.
1. See Figure 2.
2. Connect full-sized breeching when possible. See Table 3.
3. Connection must be made above bottom of chimney to avoid blockage. Breeching must not enter chimney far enough to
Figure 2 Chimney and breeching connections
Table 3 Chimney and breeching minimum sizes
Boiler model number
OWB/OWT3 5" 8" x 8" 6" 15' OWB/OWT4 6" 8" x 8" 6" 15' OWB/OWT5 6" 8" x 8" 7" 15' OWB/OWT6 7" 8" x 8" 7" 15'
Notes:
1. Flue collar on boiler is7" diameter
2. 6 ¾"x6¾"insideliner
cause obstruction. Use thimble or slip joint where breeching enters chimney to allow removal for cleaning.
4. When burner and boiler are properly installed, draft overfire will be approximately -0.01" to -0.02" W .C . Install barometric control in breeching, per control manufacturer's instructions, when excess draft needs to be relieved or to comply with applicable codes and regulations. Use draft gauge to adjust proper opening.
5. An induced draft fan for the chimney may be necessary if:
Excessive resistance to flow of combustion gases can be
expected.
Cross-sectional area of chimney is smaller than minimum
recommended.
Chimney height is less than recommended.
Seal all vent joints. Interlock burner with fan operation.
Minimum
breeching
diameter
Note 1
Minimum I=B=R
chimney size
Rectangle
Note 2
Round
Minimum
chimney
height
6 Part Number 672 01 1005 00
OWB & OWT
4 Connect water piping
Oil-Fired Water Boilers – Boiler Manual
General
If installation is to comply with ASME or Canadian requirements, an additional high temperature limit is needed. Install control in supply piping between boiler and isolation valve. Set second control to minimum 20 °F above setpoint of first control. Maximum allowable setpoint is 240 °F. See page 11 for wiring.
A low water cutoff device is required when boiler is installed above radiation level or by cer tain state or local codes or insurance companies. Use low water cutoff designed for water installations. Electrode probe-type is recommended. Purchase and install in tee in supply piping above boiler .
Use backflow check valve in cold water supply if required by local codes.
Near -boiler piping
See Figure 3 (diaphragm-type or bladder-type expansion tank) or Figure 4 (closed-type expansion tank) on page 8, and Table 4, for near-boiler and single-zone systems designed for return water at least 130 °F. See Figure 6 or 7, page 9 for low return temperature applications.
See this page for multiple-zone piping. See page 8 for boilers used with refrigeration systems.
Relief valve
Install relief valve v ertically in ¾" tapping on rear of boiler using ¾" nipple and elbow supplied in bag with valve. See the tag attached to the relief valve f or manufacturer’s instructions.
To avoid water damage or scalding due to valve operation, discharge line must be connected to relief valve outlet and run to a safe place of disposal. T erminate the discharge line to eliminate possibility of severe burns should the valve discharge.
Discharge line must be as short as possible and be the same size as the valve discharge connection throughout its entire length.
Discharge line must pitch downward from the valve and terminate at least 6" above the floor drain where any discharge will be clearly visible.
The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
No shutoff valve shall be installed between the relief valve and boiler , or in the discharge line. Do not plug or place any obstruction in the discharge line.
Failure to comply with the above guidelines could result in failure of the relief valve to operate, resulting in possibility of severe personal injury, death or substantial property damage.
Test the operation of the valve after filling and pressurizing system by lifting the lever. Make sure the valve discharges freely. If the valve f ails to operate correctly , replace it with a new relief v alv e.
Near -boiler piping continued
Table 4 Water pipe size (based on 20 °F rise)
Boiler model number
OWB/OWT3 1 ¼" 1 ¼" OWB/OWT4 1 ¼" 1 ¼" OWB/OWT5 1 ½" 1 ½" OWB/OWT6 1 ½" 1 ½"
All piping sizes based on 20 °F temperaturerise through boiler.
Circulator
The circulator is shipped loose (wiring pre-attached to boiler) to allow you to locate it either in the return or supply piping, as desired. See page 8 for a typical installation. Pipe the expansion tank to the suction side of the circulator whenever possible. Install an air separator in the supply piping. Connect the expansion tank to the air separator only if the separator is on the suction side of the circulator. Always install the system fill connection at the same point as the expansion tank connection to the system. Figures 3 and 4, on page 8, show typical near-boiler piping connections.
Expansion tank
Diaphragm- or bladder-type expansion tank Figur e 3, page 8
1. Ensure expansion tank size will handle boiler and system water volume and temperature. T ank m ust be located in boiler return piping as close to boiler as possible, bef ore inlet side of circulator. See tank manufacturer’s instructions for details.
2. Install an automatic air vent as shown.
Closed-type expansion tank Figure 4, page 8
1. Ensure expansion tank size will handle boiler and system water volume and temperature. See tank manuf acturers instructions for details.
2. Connect tank to ½" NPT tapping located behind supply outlet, using ½" NPT piping. Pitch any horizontal piping up towards tank 1 inch per 5 feet of piping.
Undersized expansion tanks cause system water to be lost from relief valve and makeup water to be added through fill valve. Eventual section failure can result.
Water piping multiple zone systems
Install system piping using either circulator zoning or zone valve zoning. Install expansion tank on suction side of system pump. Always connect fill line only at the expansion tank never at another point in the system.
To
system
From
system
7Part Number 672 01 1005 00
OWB & OWT
Oil-Fired Water Boilers – Boiler Manual
4 Connect water piping continued
Figure 3 Diaphragm- or bladder-type expansion tank:
Piping to single-zone system using diaphragm-type or bladder-type expansion tank. See Table 4, page 7, for piping sizes.
Figure 4 Closed-type expansion tank: Piping to
single-zone system using closed-type expansion tank. See Table 4, page 7, for piping sizes.
Use Figure 3 or Figure 4 only for systems designed for return water at least 130 °F. For systems with low return water temperature possible, such as converted gravity systems and radiant heating systems, install by-pass piping (see page 9) to protect boiler against condensation. Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
If system includes radiant heating circuits, provide piping and controls to regulate the temperature supplying the radiant circuits. Failure to comply could result in substantial property damage.
Install boiler so that chilled medium is piped in parallel with heating boiler. Use appropriate valves to pre vent chilled medium from entering boiler. Consult I=B=R Installation and Piping Guides.
If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle. Circulation of cold water through the boiler could result in damage to the heat exchanger , causing possible severe personal injury, death or substantial property damage.
Water piping refrigeration systems
Prevent chilled water from entering boiler
Install boiler so that chilled medium is piped in parallel with the heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. See Figure 5 for typical installation of balancing valve and check valve.
Figure 5 Piping refrigeration systems
8 Part Number 672 01 1005 00
OWB & OWT
4 Connect water piping continued
Near -boiler piping continued
Oil-Fired Water Boilers – Boiler Manual
Figure 6 System bypass piping in boiler loop with
separate system circulator, using primary/ secondary piping.
Figure 7 Boiler bypass piping use only for high
water content systems DO NOT use for radiant panel systems.
System bypass method
1. Apply bypass piping of Figure 6 to high water content systems, radiant panel systems or any system that is likely to operate with low return water temperature for extended periods.
2. The bypass arrangement shown protects the boiler from damage caused by condensate corrosion due to low return water temperature and protects low temperature systems from too high a supply temperature.
3. Adjust the bypass valves as indicated below .
Adjust Bypass valves 1 and 2 as follows:
1. Start with valve 2 fully closed, valv e 1 fully open.
2. Slowly open valve 2 while closing valve 1. Adjust the valves until the boiler pressure/temperature gauge reads 160 °F or higher. As you open the valves, pause long enough to allow temperatures to level off. It takes a while for the boiler water temperature to rise as the flow changes.
3. Bypass valve 2 allows hot boiler outlet water to blend with colder return water, raising the supply temper ature to the boiler. Bypass valve 1 balances the pressure drop through valve 2.
4. The purpose of this piping is to raise the return water temperature to the boiler enough to prevent condensation of flue gases.
Install all components specified above and adjust valv es as described to prev ent low temper ature in the boiler . Fa ilure to prevent low water temperature in the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Boiler bypass method
1. Apply bypass piping of Figure 7 to high water content systems, such as converted gravity systems.
2. The bypass arrangement shown protects the boiler from damage caused by condensate corrosion due to low return water temperature. This method does not pro vide protection from high temperature water being supplied to the system.
3. DO NOT apply this piping to radiant panel systems.
4. Adjust the bypass valves as indicated below .
Adjust Bypass valves 1 and 2 as follows:
1. Start with valve 1 fully closed, valv e 2 fully open.
2. Slowly open valve 1 while closing valve 2. Adjust the valves until the boiler pressure/temperature gauge reads approximately 60 °F higher than the system temperature gauge. As you open the valves, pause long enough to allow temperatures to level off. It takes a while for the boiler water temperature to rise as the flow changes.
3. Bypass valve 1 controls system flow rate. Bypass valve 2 controls flow through the boiler.
4. The purpose of this piping is to cause a high enough temperature rise in the boiler that the average temperature will be warm enough to prevent condensation of flue gases.
9Part Number 672 01 1005 00
Loading...
+ 19 hidden pages