ICP OLR, OLR160B20B, OLR105A12B, OUF, OLF Installation Instructions And Homeowner's Manual

...
Page 1
Models:
OLR105A12B OLR160B20B OUF105A12B OUF160B18B
OLR
OLF
OUF
DNS-0562 Rev A
OLF105A12B NOLF105A12B NOUF105A12B NOUF160B18B
TABLE OF CONTENTS
Part 1, installation…………..…... Part 2, operation………………… Part 3, maintenance……………. Part 4, information…………….… Technical specifications………... Wiring diagram……………….…. Parts list……………………….….
Manufactured by:
ICP Corporation (Canada)
3400 Blvd Industriel Sherbrooke PQ Canada
19 23 26 27 34 35
3
OIL WARM AIR FURNACE
Save these instructions for future reference.
Printed in Canada
2000/11/23 X40030 Rev. i
445 01 4030 05
Page 2
PART 1
INSTALLATION
SAFETY CONSIDERATIONS
INSTALLATION OF OIL FIRED HEATING UNITS SHALL BE IN ACCORDANCE WITH THE REGULATION OF AUTHORITIES HAVING JURISDICTION AND THE CAN/CSA B139 OR USA/NFPA NO.31-1992 INSTALLATION CODE FOR OIL BURNING EQUIPMENT.
DO NOT OPERATE FURNACE IN A CORROSIVE ATMOSPHERE CONTAINING CHLORINE, FLUORINE OR ANY OTHER DAMAGING CHEMICALS.
DO NOT STORE OR USE GASOLINE, OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
1) SAFETY LABELLING AND SIGNAL WORDS
1.1) Danger, Warning and Caution:
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used in product labels to signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product.
CAUTION
2) SAFE INSTALLATION REQUIREMENTS
WARNINGWARNING
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with codes or, in the absence of local codes, with codes of the country having jurisdiction.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in furnace malfunction, property damage, personal injury and/or death.
1.2) Signal Words:
DANGER – Immediate hazards which WILL result in
death or serious injury.
WARNING – Hazards or unsafe practices which COULD result in death or injury.
CAUTION – Hazards or unsafe practices which COULD
result in personal injury or product or property damage.
1.3) Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNINGWARNING
The signal word CAUTION is used throughout this manual in the following manner:
NOTE: It is the personal responsibility and obligation of the customer to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances.
WARNINGWARNING
Fire hazard The furnace must be installed in a level
position, never where it will slope to the front.
If the furnace were installed in that position, oil could drain into the furnace vestibule and create a fire hazard, instead of draining properly into the combustion chamber.
3
Page 3
a. This furnace is NOT approved for installation in
mobile homes, trailers or recreation vehicles.
b. You must have a sufficient supply of fresh air for
combustion and ventilation to the area in which the furnace is located.
c. Do NOT use this furnace as a construction heater
or to heat a building that is under construction.
d. Use only the Type of fuel oil approved for this
furnace (see Rating Plate on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation.
e. Visually check all oil line joints for signs of wetness,
which would indicate a leak. f. Connect furnace to a side-wall terminal or chimney. g. The points in Part 2 “Operation” are vital to the
proper and safe operation of the heating system.
Take the time to be sure they are all done. h. Follow the rules of the NFPA Pamphlet No.31 (for
USA) and B-139 (for Canada) or local codes for
locating and installing the oil storage tank. i. Follow a regular service and maintenance schedule
for efficient and safe operation. j. Before servicing, allow furnace to cool. Always shut
off electricity and fuel to furnace when servicing.
This will prevent electrical shock or burns. k. Seal supply and return air ducts. l. The vent system MUST be checked to determine
that it is the correct type and size. m. Install correct filter type and size. n. Unit MUST be installed so electrical components
are protected from direct contact with water.
2.1) Safety Rules:
potentially dangerous fire or smoke, you should have fire and smoke detectors listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below).
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector.
CAUTION
Insure that the area around the combustion air intake terminal is free of snow, ice and debris.
CAUTION
The air pressure switch MUST be used when the furnace is vented by the side-wall.
CAUTION
Do not use any commercially available soot remover. This furnace has fiber type refractory combustion chamber. Normal servicing of this unit does not require cleanings of the combustion chamber. Use extreme care if for any reason you have to work in the area of the combustion chamber.
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
a. The U.S. Consumer Product Safety Commission
recommends that users of oil-burning appliances
install carbon monoxide detectors. There can be
various sources of carbon monoxide in a building or
dwelling. The sources could be gas-fired clothes
dryers, gas cooking stoves, water heaters,
furnaces, gas-fired fireplaces, wood fireplaces, and
several other items. Carbon monoxide can cause
serious bodily injury and/or death. Therefore, to
help alert people of potentially dangerous carbon
monoxide levels, you should have carbon monoxide
detectors listed by a nationally recognised agency
(e.g. Underwriters Laboratories or International
Approval Services) installed and maintained in the
building or dwelling (see Note). b. There can be numerous sources of fire or smoke in
a building or dwelling. Fire or smoke can cause
serious bodily injury, death, and/or property
damage. Therefore, in order to alert people of
2.2) Freezing Temperatures and Your Structure:
WARNINGWARNING
Freeze warning. Turn off water system. If your unit remains shut off during cold
weather the water pipes could freeze and burst, resulting in serious water damage.
Your unit is equipped with safety devices that may keep it from operating if sensors detect abnormal conditions such as clogged exhaust flues.
If the structure will be unattended during cold weather you should take these precautions.
4
Page 4
a. Turn off main water supply into the structure and
drain the water lines if possible. Open faucets in appropriate areas.
b. Have someone check the structure frequently
during cold weather to make sure it is warm enough to prevent pipes from freezing. Suggest they call a qualified service agency, if required.
3.1) Location:
Locate the furnace as closely as possible to the chimney or vent terminal, providing ample clearance to permit easy accessibility for cleaning the inside of the furnace, the removal of filters, blower, motors, controls and flue connections. The furnace may be installed on a combustible floor.
2.3) Installation regulation:
Installation MUST conform with local building codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No.70-1990 or current edition and Installation of Oil Equipment, NFPA No.31.
Do not install furnace directly on carpeting, tile or other combustible material.
The furnace must be installed level for safe quiet operation.
CAUTION
3) LOCATING THE FURNACE
Do NOT operate furnace in a corrosive atmosphere containing chlorine, fluorine or
CAUTION
Check carefully your furnace upon delivery for
any other damaging chemicals. Refer to Part 1, section 5.2.
any evidence of damage that may have occurred during shipping and handling. Any claims for damages or lost parts must be made with the Transport Company.
TABLE #1
Minimum Installation clearances from combustible materials (Chimney installation*)
LOCATION APPLICATION OLR160 - OUF160 –
NOUF160
Furnace 1” 1”
Sides Supply plenum, warm air duct
within 6 ft of furnace Back Furnace 18” 1” Top Furnace casing or plenum 2” 1” Bottom Furnace – combustible floor 0” 0” Front Furnace 24” 24” * See Part 1 section 4.3 for Direct Vent application clearance.
1” 1”
OLR105 –OLF105 – NOLF105 -
OUF105 – NOUF105
4) VENTING
4.1) General:
The furnaces can be vented in several ways:
Chimney Vented:
Using the Beckett AFG or Riello 40-F burner, the furnaces can be chimney vented with or without a barometric damper. The unit will be operated at a negative over fire draft and stack draft.
WARNINGWARNING
Poison carbon monoxide gas, fire and explosion hazard.
Read and follow all instructions in this section.
5
Page 5
Failure to properly vent this furnace can result in property damage, personal injury and/or death.
Additionally, the liner must be insulated according to the insulating procedure recommended by the manufacturer of the liner.
Side-wall Vented:
Using the Beckett AFII or Riello 40-BF burner with the integral pre and post purge controls, the system can be side-wall vented with the new DV-2000™ venting system for maximum efficiency, and without the use of a side-wall power ventor. The unit will be operated at a positive overfire draft and stack draft.
WARNINGWARNING
Poison carbon monoxide gas hazard Never co-vent the furnace with another
combustion appliance when side-wall venting.
To do so may result in asphyxiation and death to the occupants
4.2) Chimney installations:
The oil furnaces, when set up for chimney venting, are certified for use with L-vent, A-vent, tile-lined and metal­liner-tile-lined chimneys, and can be vented both with and without a barometric draft damper. However, the furnace has not been certified without the barometric damper when it is to be co-vented with another oil-fired appliance, such as a water heater.
When a damper is used, the basement air entering the damper reduces the possibility of vent condensation. However, if the barometric damper is not used, a chimney liner with insulation must be employed.
With a barometric damper:
WARNINGWARNING
Poison carbon monoxide gas hazard Never install a hand operated damper in
the vent pipe. However, any Underwriters Laboratories listed electrically operated automatic type vent damper may be installed if desired. Be sure to follow instructions provided with vent damper. Read and follow all instructions in this section.
Failure to properly vent this furnace or other appliances can result in property damage, personal injury and/or death.
Vent connectors:
For installations without barometric damper, the vent connector should be as short as possible and either be of double wall construction, or be of single wall construction insulated with 1” of insulation. It should rise a minimum of 1/4” per foot from the furnace to the chimney. Field fabricated connectors should be a minimum of 28 gauge. The joints must be mechanically secure and there must be no flue product leakage at the joints.
CAUTION
When the furnace (chimney installation) is co­vented with other combustion appliances such as a water heater, the allowable venting materials (i.e. L-Vent etc.) for use with those appliances should also be investigated.
The appliance may be installed in a chimney of the proper size and adequate chimney base temperature as specified in the Installation Code. The relevant excerpt from the code is found in this section - Use it as a guide when local or national codes do not exist.
Without a barometric damper:
Due to the lack of dilution air that would ordinarily be drawn into the barometric damper, the dew point of the flue gasses is raised. To offset the increased tendency for vent condensation, the chimney must be lined.
6
Flue pipe sizing:
The following table is an except from the installation code and indicates permitted flue sizes and minimum base temperatures for circular flues in chimney with thermal resistance less than R6 (6 ft2 hr •°F / Btu). Where a new appliance, burner, or chimney is installed, chimney vent sizes and maximum flue-gas temperatures (measured at the chimney connector with the barometric damper shut, after 5 minutes of operation) shall comply with the table #2.
Page 6
Notes: Thermal resistance values for typical chimneys are as follows:
R2 (2 ft2 hr •°F / Btu): clay-lined masonry, A-vent R3 (3 ft2 hr •°F / Btu): metal liner in clay-lined
Masonry
R6 (6 ft2 hr •°F / Btu): metal or clay-lined masonry
with R4.5 (4.5 ft2 hr •°F / Btu) insulation between liner and masonry (e.g. 2 in. of expanded mica or 1 3/8 in. of high density glass fibreboard.)
Applying the Table:
If a furnace with 0.60 USGPH nozzle is to be connected to a 20 ft. tall clay-lined masonry chimney, the thermal resistance of this chimney type is R2, which is less than R6. The actual firing rate at 156 psig is 1.25 x .60 = .75. Therefore this table shall apply as:
The minimum size permitted shall be 4 in. inside diameter.
The maximum size permitted shall be 5 in. inside diameter.
The minimum base temperature shall be about 320ºF.
TABLE # 2
Total input rating of all
connected appliances
kW kBtu/h USGPH Min. Max. 11 20 28 36
21 70 0.50 3 5 300 400 535 725 27 91 0.65 3 5 275 340 430 535 31 105 0.75 4 5 260 320 380 475 36 119 0.85 4 5 250 300 355 430 41 140 1.00 4 6 225 300 365 430 51 175 1.25 4 6 240 275 320 365
4.3) Side-wall venting, DV-2000™ Direct
Vent System:
The furnace can be side-wall vented without the use of a side-wall power ventor using the new DV-2000™ venting system with the high static pressure Beckett AFII and Riello 40-BF oil burners. Outdoor
combustion air must be directly connected to the burner of the DV-2000™ venting system will not function.
The notable characteristics of the DV-2000™ system are as follows:
Certified to use the following materials for ducting the intake air from the terminal to the burner; Schedule 40 PVC DWV, Schedule 40 ABS DWV, And ASTM 2729 Sewer Pipe.
One hole of minimal size (6”) is required to be cut in the side-wall, and the terminal is designed to fit through a minimum 2 X 8-joist space.
Flue inside diameter
(in)
Minimum base temperature (ºF)
for chimney height (ft) of :
Incorporates a vent blockage safety shutdown system. If the vent or intake opening ever becomes partially or fully blocked, the burner will shut down before a #1 smoke occurs.
The intake and vent circuits within the terminal can be accessed for cleaning.
There are 3 main components to the DV-2000™ system; the VTK vent terminal kit, the IFV insulated flexible venting material and the field-supplied 3” PVC or ABS intake piping.
Vent terminal kits – DV-2000™:
The certified standard vent terminal kit is Model No. VTK-1 or VTK-2, and is suitable for installation in walls up to 14” thick. An alternate kit, Model VTK-1-DW or VTK-2-DW is available to accommodate walls up to 25” thick. Both kits contain the following items to complete the hook-up to the venting and furnace:
The standard terminal is designed for a wall thickness up to 14”, and the deep wall terminal for wall thickness up to 25”.
1 Terminal 2 Sealing Clamps 1 Side-wall Venting Breech Plate 2 Sealing Strips 1 Inner Wall Plate 1 Pressure Control with Tubing 2 Insulated Quick-connect Terminals
7
Page 7
3 Stainless Steel Screws 6 Self tapping stainless steel screws
Insulated flexible venting - DV-2000™:
The certified venting materials come in 3 lengths, Model No. IFV3-15, IFV3-23 and IFV3-30 (or IFV4-15, IFV4-23 and IFV4-30 for 160 models) are corresponding to 15’, 23’ and 30’ continuous lengths of vent. The vent construction is coaxial and incorporates a stainless steel corrugated flexible liner surrounded by a thick insulation blanket and covered with an outer layer of flexible corrugated aluminium sleeve to protect the insulation. Splicing vent lengths together is prohibited. The maximum and minimum continuous vent lengths permitted for installation are:
5 feet minimum 30 feet maximum
WARNINGWARNING
Poison carbon monoxide gas hazard
c. within 6 feet of a window or door, or mechanical air
supply inlet to any building, including soffit openings;
d. above a gas meter/regulator assembly within 3 feet
of a vertical centerline of the regulator;
e. within 6 feet of any gas service regulator vent
outlet, or within 3 feet of an oil tank vent, or an oil fill
inlet; f. within less than 1 foot above ground level; g. 6 feet of any other combustion air inlet; h. within 6 feet of a property line; i. underneath a veranda, porch or deck; j. so that the flue gases are directed at combustible
material or any openings of surrounding buildings
that are within 6 feet; k. less than 3 feet from an inside corner of an L-
shaped structure; l. so that the bottom of the vent termination opening is
less than 1 foot above any surface that may support
ice, snow, or debris; m. so that the flue gases are directed toward
brickwork, siding or other construction, in such a
manner that may cause damage from heat or
condensation from flue gases.
Even though the flexible venting is insulated, it cannot be run through an unheated space.
To do so could cause residual condensation inside the stainless steel liner, which may eventually perforate the liner and allow vent gasses to enter the dwelling.
TABLE # 3
Side-wall venting clearances to combustibles
PORTION OF VENT CLEARANCES
Vent pipe, up to vent terminal* 3” Vent terminal ZERO
*Do not enclose venting
Installation considerations - DV-2000™:
Select a location for the vent terminal in accordance with all local and national codes. The following requirements shall be considered to be minimum requirements that can be overridden by stricter local and national codes.
The vent shall not terminate:
a. directly above a paved sidewalk or paved driveway
that is located between two buildings, and that serves both buildings;
b. less than 7 feet above any paved driveway;
CAUTION
Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances, even if all other code requirements as to construction and location have been complied with. The installer is ultimately responsible to do whatever is necessary to ensure that flue gasses do not enter the dwelling.
Installation of side-wall venting - DV-2000™:
WARNINGWARNING
Cuts and abrasion hazard. Always wear protective gloves and eye
protection when handling the vent material The process of cutting and fitting the flexible
venting material exposes the installer to sharp edges that could cause severe cuts to the skin.
8
Page 8
FIGURE # 1.1 FIGURE # 1.2
CUT OUTER SLEEVE BACK 5”
THREAD SPIN SLEEVE ONTO OUTER SLEEVE
FIGURE # 1.3 FIGURE # 1.4
THREAD SPIN SLEEVE BACK 10” CUT STAINLESS STEEL
CORE BACK BY 3”
FIGURE # 1.5 FIGURE # 1.6
INSERT STAINLESS STEEL CORE ONTO BREECH TUBE
DRIVE THREE STAINLESS STEEL SCREWS, STARTING NEAR TOP
9
Page 9
Connection to the furnace breech - DV-2000™:
1. Remove the standard breech plate by removing the brass nuts.
2. Determine which direction the venting will be routed from the furnace and then install the special side­wall venting breech plate provided in the VTK Series vent kit so that the breech plate test port will be accessible after vent installation. However, do not install the breech plate with the test port pointing downward. Tighten the brass nuts.
3. The flexible venting has 4 pieces of corrugated spin sleeving that has been temporarily screwed on over top of it. Remove the spin sleeving completely by unscrewing it in a counter-clockwise direction.
4. Using tin snips, cut the aluminium outer sleeve back by 5” for the IFV Series vent (see figure #1.1). Ensure the snips are well adjusted and sharp or the cut end of the venting will be too jagged to start the threads of the spin sleeve (see figure #1.1).
5. Prepare the furnace breech end of the insulated flex vent by first screwing the spin sleeve onto the corrugated aluminium jacket (see figure #1.2) until the trailing edge of the spin sleeve is about 12” from the end of the vent (see figure #1.3).
6. Pull the insulation back to expose the corrugated stainless steel core.
the seal strip around once, allow 1/2” overlap and tear off the residual length (see figure #1.7).
10. Break the residual length of seal strip in to 3 equal parts and stuff them onto the screw heads of the stainless steel self-drilling screws so that the screw heads are completely covered.
11. Two stainless steel band clamps are provided in the VTK Series kits. Position one stainless steel band clamp over the gum seal joint so that the edge of the clamp closest to the breech lines up with the edge of the gum seal that is closest to the breech. Ensure that the band will close with an action of one strip sliding over the other - not under the gearhead of the draw clamp (see figure #1.8). Tighten the band clamp with considerable torque to cause the gum seal be squeezed into all crevices and to ooze out of the end of the clamp closest to the breech (see figure #1.9). The gum will eventually become rubbery.
12. The seal is permanent and should never need to be disconnected as the breech plate can be removed for cleaning and inspection using the 4-bolt joint.
13. Tuck the vent insulation into the breech collar.
14. Screw the spin sleeve tightly into the breech collar for a finished appearance. Wrap the other end of the spin sleeve with aluminium tape to cover any metal burrs that may be present (see figure #1.10).
7. Cut the corrugated stainless steel core back by 3” for the IFV Series vent. You should now have about 3” of insulation hanging out past the stainless steel core (see figure #1.4).
8. Push the stainless steel core onto the breech pipe as far as it will go (see figure #1.5) and mechanically attach the vent to the breech using three of the #8 X 1/2” self-drilling screws provided with the VTK Series kit. The screws should be equally spaced around the circumference of the stainless steel core, starting with the first screw at top dead center. Start the drill point of the screws in the valleys of the corrugations at 3/8”-5/8” back from the end of the stainless steel core, so the screw heads can be properly sealed in the forthcoming operations (see figure #1.6).
9. With the stainless steel core now firmly attached to the breech, tear off one green gum-sealing strip from the backing strip. Wrap the seal strip around the joint, always keeping the centerline of the seal strip over the line where the corrugated stainless steel core makes the transition to the smooth outer surface of the breech pipe. In other words, the seal strip must be centered over the joint. After wrapping
15. Bend the venting into the desired radius coming off the breech.
Connection to the vent terminal - DV-2000™:
1. Prepare the terminal end of the insulated flex vent by first screwing the spin sleeve onto the corrugated aluminium jacket until the trailing edge of the spin sleeve is about 10” from the end of the vent.
2. Using sharp tin snips, cut the aluminium outer sleeve back by 5” for the IFV Series vent
3. Pull the insulation back to expose the corrugated stainless steel core.
4. Cut the corrugated stainless steel core back by 3” for the IFV Series vent. You should now have about 3” of insulation hanging out past the stainless steel core.
5. Push the stainless steel core onto the pipe on the back of the terminal as far as it will go and mechanically attach the vent to the terminal using three of the #8 X 1/2” self-drilling screws provided with the VTK Series kit. The screws should be
10
Page 10
FIGURE # 1.7 FIGURE # 1.8
APPLY THE SEALANT TO THE TUBE END
FIGURE # 1.9 FIGURE # 1.10
CORRECT BAND OVERLAP
SEALANT FLOWING OUT FROM UNDER
TWIST SPIN SLEEVE TIGHTLY INTO
BREECH COLLAR BAND CLAMP AT BREECH
SEALANT OUTFLOW
FIGURE # 1.11
SEALANT FLOWING OUT FROM UNDER BOND CLAMP AT TERMINAL
SEALANT OUT FLOW
11
Page 11
equally spaced around the circumference of the stainless steel core, starting with the first screw at top dead center. Start the drill point of the screws in the valleys of the corrugations at 3/8”-5/8” back from the end of the stainless steel core.
downward slope of the terminal, in the direction from the inside to the outside.
3. Remove the 2 screws fastening the end cone in place and remove the cone.
6. With the stainless steel core now firmly attached to the terminal, tear off the other green gum-sealing strip from the backing strip. Wrap the seal strip around the joint, always keeping the centerline of the seal strip over the line where the corrugated stainless steel core makes the transition to the smooth outer surface of the terminal pipe. After wrapping the seal strip around once, allow 1/2” overlap and tear off the residual length.
7. Break the residual length of seal strip in to 3 equal parts and stuff them onto the screw heads of the stainless steel self-drilling screws so that the screw heads are completely covered.
8. Position the other stainless steel band clamp over the gum seal joint so that the edge of the clamp closest to the terminal lines up with the edge of the gum seal that is closest to the terminal. Tighten the band clamp with considerable torque to cause the gum seal be squeezed into all crevices and to ooze out of the end of the clamp closest to the terminal (see figure #1.11).
9. The seal is permanent and should never need to be disconnected as the end of the terminal can be opened for cleaning and inspection by removing the screened end-cone assembly. Tuck the vent insulation into the recess in the terminal body.
10. Screw the spin sleeve tightly into the recess for a finished appearance. Wrap the other end of the spin sleeve with aluminium tape to cover any metal burrs that may be present (see figure #1.12).
11. Bend the venting into the desired radius coming off the terminal.
Installing terminal in the wall - DV-2000™:
1. Cut a 6” hole in the side-wall in accordance with the location considerations outlined in the previous section.
2. Fasten the wall plate to the inside-wall using 4 field­provided fasteners appropriate for the material behind the wall plate. Depending on the angle of access, the pressure control bracket may need to be removed to access the top right wall plate screw hole. For concrete and block, Tapcon™ screws or equivalent are recommended. Install the wall plate so that the top of the hole in the wall plate is positioned 1/8” lower than the top of the 6” hole in the wall. This will accommodate the proper
4. Remove the 2 screws fastening the stabiliser shroud in place and remove the stabiliser shroud.
5. Insert the main body of the terminal through the wall plate so that the end of the terminal extends about 2” past the outside wall.
6. Install the stabiliser shroud and replace the two mounting screws. (see figure #1.13).
7. For concrete and block wall installations in particular, If it appears that the flange on the back of the stabiliser shroud is not large enough to cover the irregularities in the hole, a field fabricated wall plate can be constructed out of 304, 316, or 316L stainless steel.
8. Silicone seal the circumference of the joint where the stabiliser shroud connects to the main body of the terminal.
9. Apply caulking to the back plate of the stabiliser shroud and push the terminal back firmly against the wall.
10. While pushing down gently on the top of the stabiliser shroud, install the 3 stainless steel 2” screws provided with the kit to secure the back of the shroud to the wall. Do not overtighten the screws or it will distort the stabiliser shroud. The screws will not be necessary in a concrete or block wall as the mortar can provide positive positioning.
11. Tighten the clamp on the wall plate to secure the terminal in position.
12. Apply more caulking all around the seam where the stabiliser shroud meets the wall. It is important to have a good seal to prevent water from entering the dwelling (see figure #1.14). A considerable amount of caulking may be necessary for irregular wall surfaces such as lapped siding.
13. Install the end cone and replace the two mounting screws.
14. Support the vent and intake air piping so that a 1/4” to 1/2” downward slope (toward the outside) results for proper drainage out the terminal body.
12
Page 12
FIGURE # 1.12
TWIST SPIN SLEEVE TIGHTLY INTO RECESS
VENT TERMINAL PRESSURE SWITCH. REFER TO WIRING DIAGRAM FOR ELECTRICAL CONNECTION.
FIGURE # 1.13 FIGURE # 1.14
INSTALL STABILIZER
CAULK TO SEAL STABILIZER SHROUD TO THE WALL
SHROUD
13
Page 13
Connection of combustion air piping to the terminal
- DV-2000™:
Refer to Part 1, section 5.3, Outdoor Combustion Air – Side-wall Venting, DV-2000™ for a complete description.
5) AIR FOR COMBUSTION
WARNING WARNING
Poison carbon monoxide gas hazard. Comply with NFPA standard for the
installation of Oil Burning Equipment and applicable provision of local building codes to provide combustion and ventilation air.
Failure to provide adequate combustion and ventilation air can result in personal injury and/or death.
The following areas or types of structures may contain or have exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion.
a. Commercial building. b. Building with indoor pools. c. Furnaces installed near chemical storage areas.
Exposure to these substances: a. Permanent wave solutions for hair.
b. Chlorinated waxes and cleaners. c. Chlorine based swimming pool chemicals. d. Water softening chemicals. e. De-icing salts or chemicals. f. Carbon tetrachloride. g. Halogen type refrigerants. h. Cleaning solvent (such as perchloroethylene). i. Printing inks, paint removers, varnishes, etc.. j. Hydrochloric acid. k. Solvent cements and glues. l. Antistatic fabric softeners for clothes dryers. m. Masonery acid washing materials.
5.3) Ducted outdoor combustion air:
5.1) General:
Oil furnaces must have an adequate supply of combustion air. It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace. However, home improvements such as new windows, doors, and weather stripping have dramatically reduced the volume of air leakage into the home.
Home air exhausters are common. Bath and kitchen fans, power vented clothes dryers, and water heaters all tend to create a negative pressure in the home. Should this occur, the chimney becomes less and less effective and can easily downdraft.
Heat recovery ventilation (HRV) systems are gaining in popularity. The HRVs are not designed to supply combustion air. If not properly balanced, a serious negative pressure condition could develop in the dwelling.
5.2) Contaminated Combustion Air :
Installation in certain areas or types of structures will increase the exposure to chemicals or Halogens which may harm the furnace. These instances will require that only outside air for combustion.
Three burners are set up to duct outside combustion air directly to the burner; the Beckett AFII and Riello 40-BF for side-wall venting using the new DV-2000™ venting system, and the Beckett AFG for use with conventional chimney venting. The Riello 40-F is not suitable for direct-connected outdoor air.
CAUTION
The use of ducted outside combustion air is mandatory for the DV-2000™ venting system. This system operates on a balanced flue principle and will not function properly if the combustion air piping is not attached and sealed at all connections between the vent terminal and burner inlet.
Outdoor combustion air kit – chimney venting:
The following kit has been certified for use on the appliance. The component kits contain an important safety feature, namely a vacuum relief valve, or VRV. During normal operation the burner aspirates outdoor air. If the intake terminal ever becomes partially blocked or fully blocked from ice or snow etc., the VRV will open to allow a proportion of air from the dwelling to enter the burner thus maintaining proper combustion. Once the blockage is removed, the VRV will close and the burner will draw all air from the outdoors again:
14
Page 14
CAS-2B Components (except air duct) for the Beckett AFG burner. The kit includes the intake terminal, vacuum relief valve (VRV) and special air boot connection with integral air adjustment means for the AFG burner. The CAS-2B can be used with 4” galvanised air duct or with 4” flexible aluminium air duct. It is recommended that the metallic air ducting material should be insulated from the air intake up to 5 feet from the burner to avoid condensation on the outside of the intake pipe.
CAD-1 Air duct kit consists of 25 feet of insulated UL/ULC Listed Class 1 air duct, and two 4” steel band clamps. The duct incorporates a corrugated flexible aluminium core, surrounded by fibreglass insulation
covered with a vinyl vapour barrier.
CAUTION
The CAS-2B does not turn the furnace installation into a direct vent system. Therefore the building structure must provide for adequate combustion air to be delivered at the vacuum relief valve. The burner will need to draw combustion air from the VRV’s surroundings if the intake ever becomes blocked. Therefore non-direct vent installation codes must be followed.
Comprehensive installation instructions are provided with the kit.
Outdoor combustion air – side-wall venting, DV­2000™:
The new DV-2000™ venting system is a sealed system and completely isolates the furnace from the interior of the building. The burner is totally unaffected by any pressure fluctuations within the building which makes it ideal for tight home constructions.
The DV-2000 ™ venting system requires additional parts, which are not included with the kit. These additional parts must be constructed of 3” Schedule 40 PVC, PVC-SWV, SDR-26,SDR-21, Septic Sewer Pipe, or ABS plastic pipe, fittings and sealant. Also, installation procedures, piping and fittings must conform to the following ANSI /ASTM standards:
Procedure for Cementing Joints ASTM D-2855
Additional parts required (not included in VTK kit):
a. 3” elbow fitting as required b. 3” plastic pipe c. 3” 90°elbow, female-female(for terminal) d. 3” female to 2” female reducer (Riello 40-BF burner
only)
e. 2” 90°elbow, street type, female-male (Riello 40-BF
burner only)
f. 3” female-female PVC or ABS coupling (not sewer
pipe) (Beckett AFII burner only)
g. transition bushings to go from PVC or ABS to
ASTM D2729 Septic Sewer Pipe (if applicable).
If PVC fittings are mixed with ABS fittings, use a solvent cement that is approved for bonding the two plastics.
Intake pipe length - DV-2000™:
The DV-2000 ™ venting system has been certified for 120 equivalent feet of 3” intake pipe. Count a 90°elbow as 10 equivalent feet and a 45°elbow as 5 equivalent
feet in the calculation. For Example: 1 5’ Length = 5 equivalent feet
2 10’ Lengths = 20 equivalent feet 3 90°elbows = 30 equivalent feet 2 45°elbows = 10 equivalent feet 1 90°elbow (terminal) = 10 equivalent feet 1 90°elbow (Riello Burner)= 10 equivalent feet
Total = 85 equivalent feet, which is less than 120 feet, which is acceptable.
Intake pipe installation - DV-2000™:
Obtain the necessary additional parts, to complete the installation, and start by piping at the burner. If the optional vestibule has been installed, remove the appropriate knockouts in the side panels of the vestibule. The lower 5” knockout in the right hand panel is used for the Beckett AFII burner. The higher 5” knockouts on the right and left-hand panels are for right or left connection to the Riello 40-BF burner.
Beckett AFII burner:
PVC ASTM D-1785 SDR26, SDR21 ASTM D-2241 Septic Sewer Pipe ASTM D-2729 PVC-DWV ASTM D-2665 PVC Primer and Solvent Cement ASTM D-2564 ABS Pipe and Fittings ASTM D-2235
Remove the burner intake cover by removing the 3 screws securing it in place. Discard the cover and screws. Apply silicone liberally around the end of a 3” coupling and fully insert the silicone end onto the burner opening. Fasten securely with 3 self-tapping sheet metal screws.
15
Page 15
Riello 40-BF burner:
7) BURNER INSTALLATION
Fully insert the female end of the 2” 90° street elbow into the combustion air fitting on top of the burner. Fasten securely with 3 self-tapping sheet metal screws. Cement the 2” end of the 3” female to 2” female reducer
onto the male end of the 2” 90° street elbow. If these parts are not easily obtained, use a 3” 90° street elbow with the male end fitted over the combustion air fitting. The fitting will have to be silicone sealed as the fit is a bit loose. Fasten securely with 3 self-tapping sheet metal screws.
Terminal connection:
Insert the 3” 90° female-female elbow onto the stainless steel air intake fitting located on the right side of the vent terminal (viewing from the rear). Fasten securely with 3 self-tapping sheet metal screws.
Intermediate piping:
Pipe as required between the terminal and the burner. Ensure that the 3” piping is routed and supported in accordance with local and national codes. Obey minimum furnace clearances to combustibles when routing any sections of 3” piping in the vicinity of the furnace. If Septic Sewer Pipe is to be used, install transition bushings at the 3” female ends of the fittings at the burner and at the terminal. Transition bushings are readily available and are required because 3” PVC and ABS pipes have a typical outside diameter of 3.5”, whereas Septic Sewer Pipe has a typical outside diameter of 3.25”.
6) OIL TANKS AND LINES
Check your local codes for the installation of the tank and accessories.
A manual shut-off valve and an oil filter shall follow sequence from tank to burner. Be sure that the oil line is clean before connecting to the burner. The oil line should be protected to eliminate any possible damage. Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel pump (more than 8’ lift use 2 stage pump and more than 16’ an auxiliary pump).
Mounting the burner:
a. The warm air furnace burner mounting plate has a
four bolts configuration.
b. Position the mounting gasket between the mounting
flange and the appliance burner mounting plate. Line up the holes in the mounting flange with the studs on the appliance mounting plate and securely
bolt in place.
After the burner is mounted:
a. Remove drawer assembly or air tube combination b. Install nozzle (see specifications) c. Confirm electrode settings d. Make the electrical connections e. Complete oil line connections
CAUTION
Do not turn on the burner until you have checked the polarity
Checking the polarity:
The oil burners used on the furnaces have solid state control systems which makes them sensitive to the proper connections of the hot and neutral power lines. The controls will be damaged if the two lines are reversed.
a. Set your voltmeter to line voltage. b. Place one prong on your grounded electric entry
box and one prong on the black wire.
c. Read the voltage. d. If the voltage is zero, check the white wire. If line
voltage shows. Reverse the 115-volt leads entering the furnace junction box.
FIGURE # 2
Follow the pump instructions to determine the size of tubing you need in relation of the lift, or the horizontal distance.
16
Page 16
Nozzles:
The burners are provided with the highest capacity USGPH nozzle installed. If another size nozzle, or replacement nozzle is required, use the nozzle spray angle, type and manufacturer recommended in Table #4.1 to 4.3. Note that all nozzle-marked sizes are based on a pump pressure of 100 psi.
NOTE: You may notice a slight odor the first time your furnace is operated. This will soon disappear. It is only the oil used on the parts during manufacturing.
8) INSTALLING ACCESSORIES
Always select nozzle sizes by working back from the actual desired flow rate at operating pressure, and not by the nozzle marking.
Air and turbulator settings:
Before starting the burner for the first time, adjust the air and turbulator settings to those listed in the Table #4.1 to #4.3. Once the burner becomes operational, final adjustment will be necessary.
Fuel supply system:
Fuel Specifications
NOTE: Use No.1 or No.2 Heating Oil (ASTM D396) or in Canada, use No.1 or No.2 Furnace Oil.
Before starting the burner be sure the fuel tank is adequately filled with clean oil.
WARNING WARNING
WARNING WARNING
Electrical shock hazard. Turn OFF electric power at fuse box or
service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
Failure to do so could result in property damage, bodily injury or death.
8.1) Electronic air cleaner:
Wire leads are provided to direct 115 volts @ 0.5 Amp maximum to an electronic air cleaner (EAC). Power will be available to the EAC at all times, so it must incorporate a flow proving switch if it is to be wired into the furnace control box. Most modern EACs have the required integral airflow-proving switch. Wire the electronic air cleaner as indicated in figure #6.
Fire and explosion hazard. Use only approved heating type oil in this
furnace. DO NOT USE waste oil, used motor oil, gasoline or kerosene.
Use of these will result in death, personal injury and/or property damage.
IMPORTANT
When using nozzle sizes of less than .75 USGPH, the Installation Code for oil burning equipment requires the installation of a 10 micron (or less) filter in the fuel oil line. ICP requires that this practice be followed in order to keep the lifetime heat exchanger warranty intact.
8.2) Humidifier:
Terminals are provided to direct 115 volts @ 1.0 Amp maximum to the transformer powering the humidifier. The humidifier will be energised anytime the blower is operating on the “Heating Speed”. Wire the 115-volt power as indicated in figure #6.
8.3) Air conditioning:
An air conditioning coil may be installed on the supply airside only. Also, notwithstanding the evaporator coil manufacturer’s instructions, a minimum of 6 inches clearance must be allowed between the bottom of the coil drain pan, and the top of the heat exchanger. Wire the thermostat and condensing unit contactor as indicated in figure #6.
17
Page 17
8.4) Ductwork and Filter:
Installation:
Design and install air distribution system to comply with Air Conditioning Contractors of America manuals or other approved methods that conform to local codes and good trade practices.
When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct outside furnace space.
Install air conditioning cooling coil (evaporator) on downstream side (in the supply air plenum) or furnace.
If separate evaporator and blower unit is used, install good sealing dampers for air flow control. Cold air from the evaporator coil going through the furnace could cause condensation and shorten furnace life.
WARNINGWARNING
Poison carbon monoxide gas hazard. Do NOT draw return air from inside a
closet or utility room. Return air duct MUST be sealed to furnace casing.
Failure to properly seal duct can result in death, personal injury and/or property damage.
WARNINGWARNING
Poison carbon monoxide gas hazard.
CAUTION
Dampers (purchased locally) MUST be automatic.
Install evaporator coil on the supply side of the furnace ducting.
Evaporator coil installed in return side ducting can cause condensation to form inside heat exchanger resulting in heat exchanger failure. This could result in death, personal injury and/or property damage.
18
Page 18
PART 2
OPERATION
1) MANUAL OPERATION SWITCHES
FIGURE # 3
Constant blower operation switch (low speed)
Main power ON­OFF switch
7. After fan-limit control heats up to the factory set point, the circulating air blower starts.
8. The circulating air blower, burner motor and ignition transformer remains on until the thermostat is satisfied. Also, the solenoid valve remains open.
9. Thermostat is satisfied.
10. SPDT relay contacts open, solenoid valve closes, burner fan motor post-purges the combustion chamber and vent for a pre-set time (30 sec. to 4 min.). The ignition transformer also continues to spark for this time period.
11. During the post-purge cycle, the fan-limit control cools down to the factory set point of 90 degrees Fahrenheit, and the circulating air blower turns off.
2.2) Sequence of operation - Riello 40-
BF, Side-wall Venting:
1. Normally open contact (W-R) on SPDT relay closed when thermostat calls for heat.
DNS-0574 Rev. B
2) SEQUENCE OF OPERATION
2.1) Sequence of operation - Beckett AFII, Side-wall venting:
1. For the Beckett AFII burner, the T-T terminal have
to be jumped on the primary control of the burner.
2. Normally open contact (W-R) on SPDT relay closed
when thermostat calls for heat.
3. Burner motor starts and spark is established. The
burner motor fan pre-purges the combustion chamber and vent for 15 or 20 seconds, establishing the combustion air pattern.
4. After prepurge period, solenoid valve opens
allowing oil to flow through nozzle.
5. The ignition transformer spark ignites oil spray.
6. Cad cell senses flame and burner continues to fire.
2. Burner motor starts. The burner motor fan pre­purges the combustion chamber and vents for 10 seconds, establishing the combustion air pattern. During this time the solenoid valve holding coil pressure will be approximately 100 psig.
3. After prepurge period, solenoid valve opens, allowing oil to flow through nozzle. At the same time, the burner motor’s ignition coil produces spark.
4. The ignition transformer spark ignites oil spray.
5. Cad cell senses flame and burner continues to fire. Ignition transformer ceases sparking.
6. After fan-limit control heats up to the factory set point, the circulating air blower starts.
7. The circulating air blower and burner motor remain on until the thermostat is satisfied. Also, the solenoid valve remains open.
8. Thermostat is satisfied.
9. Relay contacts open, solenoid valve closes, and then the burner fan motor post-purges the combustion chamber and vent for a pre-set time (5” breech model only) (0 min. to 6 min.).
19
Page 19
10. During the post-purge cycle, the fan-limit control BI­metal cools down to the factory set point of 90 degrees Fahrenheit, and the circulating air blower turns off.
2.4) Sequence of operation – internal furnace controls (All models) :
No call for heating or cooling:
NOTE: With burner relay contact open, the Riello 40-
BF will post-purge when 115 volt power is applied to the burner.
2.3) Sequence of operation - Beckett AFG and Riello 40-F, chimney:
1. For the AFG burner, the T-T terminal have to be
jumped on the primary control of the burner.
2. Normally open contact (W-R) on SPDT relay closed
when thermostat calls for heat.
3. AFG Burner: The motor starts and spark is
established. The pump pressure builds and the poppet valve opens admitting fuel to the nozzle. Pressure builds and poppet valve opens, allowing oil to flow through nozzle.
40F: Burner motor starts. The burner motor fan pre-purges the combustion chamber and vent for 10 seconds, establishing the combustion air pattern. During this time the solenoid valve holding coil pressure will be approximately 100 psig. Solenoid valve opens, allowing oil to flow through nozzle. At the same time, the burner motor’s ignition coil produces spark.
Power is available to the Electronic Air Cleaner (EAC) at all times. Power at L1 enters the common terminal of the single pole double throw (SPDT) relay, and then passes through the normally closed (NC) switch of the relay and continues to the normally closed (NC) switch of the fan control. This provides power to the constant blower operation speed tap on the blower motor if the constant (low speed) blower operation switch is selected to be close. The low speed motor tap would normally be chosen for constant blower operation.
Call for heat:
Power comes from L1 to the limit control and then leaves the limit control via the red wire to provide power to the burner. RH - W close in the thermostat completing a 24 volt circuit the SPDT relay coil. This relay energises and switches 115 volts power to operate the oil burner.
When the plenum temperature reaches the fan “On” setting, the normally open (NO) fan control contacts close and the normally closed (NC) contacts open. Power then flows to the heating speed tap selected on the blower motor, and to the HUM power lead to supply 115 volts to the humidifier transformer.
Call for cooling:
4. Spark ignites oil droplets.
5. Cad cell senses flame and burner continues to fire.
Ignition transformer ceases sparking (Riello R40-F).
6. After fan-limit control heats up to the factory set
point, the circulating air blower starts.
7. The circulating air blower and burner motor remain
on until the thermostat is satisfied (AFG). The ignition transformer continues to spark (AFG). The solenoid valve remains open (R40-F).
8. Thermostat is satisfied.
9. SPDT relay contacts open, solenoid valve closes
(R40-F), burner fan motor shuts down. The ignition transformer ceases sparking (AFG).
10. The fan-limit control BI-metal cools down to the
factory set point of 90 degrees Fahrenheit, and the circulating air blower turns off.
20
Rc - G close in the thermostat completing a 24-volt circuit to the SPDT relay coil. The NC contacts open interrupting power to the fan control. The NO contacts close and power flows to the cooling speed tap selected.
Rc - Y also close in the thermostat completing a 24-volt circuit to the outdoor condensing unit contactor coil. The contactor closes and switches power to the compressor and condenser fan in the condensing unit.
2.5) Sequence of operation - DV-2000™ Venting system:
Normal operation:
1. Before a call for heat the contacts of the pressure
switch are closed.
2. When the room thermostat calls for heat the
normally open contact W-R close and the burner blower starts and creates suction in the intake piping circuit and a pressure in the vent piping circuit.
Page 20
3. The differential pressure setpoint of the pressure switch is not exceeded and the thermostat circuit remains closed until the call for heat has ended.
Abnormal operation:
should flow absolutely free of white streaks or bubbles to indicate that no air is being drawn into the suction side of the oil piping and pump. Tighten the bleed screw and the burner will fire. Adjust the oil pressure as indicated in Table #4.1 to #4.3.
Start-up:
1. When the room thermostat calls for heat the normally open contact W-R close and the burner blower starts and creates suction in the intake piping circuit and a pressure in the vent piping circuit.
2. If there is a blockage in the intake or vent openings to cause a pressure differential beyond the set point of the pressure switch, then the thermostat circuit is opened and the burner will go into a 2 minute post­purge and then shut down.
3. After the post-purge, once the burner blower shuts down, the pressure switch contacts will re-close. If the call for heat remains, the burner will re-start. If the blockage still exists, the thermostat is again opened, and the burner post- purges again. The post-purge function thus becomes an inherent anti­short cycling device.
4. The unit will essentially go into a continuous re­cycling post-purge mode with no heat being supplied to the dwelling, which will prompt a call for service to the equipment.
IMPORTANT
The burner must be put in operation for at least 10 minutes before any test readings are taken. For new installations, set up the burner to the settings (see table #4.1 to 4.3), before firing. These are rough adjustments but they will ensure that the burner will start and run smoke-free in advance of the fine adjustments being made.
3.2) Restart if Burner Should Stop:
1. Set thermostat lower than the room temperature.
2. Press the reset button on the burner primary control (relay).
3. Set thermostat higher than the room temperature for 10 seconds and set lower than room temperature. This will start pre purge cycle. Repeat twice.
4. Set thermostat higher than the room temperature.
5. During the re-cycling post-purges, if the blockage of the terminal is removed, the burner will immediately fire up at the end of the current post purge cycle.
During operation:
If the terminal vent or intake openings become blocked to the point where the set point of the pressure switch is exceeded, during a firing cycle, the burner flame will shut down and the burner will go into the indefinite recycling post-purge mode as described above, until the blockage is removed.
3) CHECKS AND ADJUSTMENTS
3.1) General:
During initial start-up and subsequent yearly maintenance calls, the furnace must be thoroughly tested.
Open the oil bleed port screw and start the burner. Allow the oil to flush into a portable container for at least 10 seconds. Slowly close the bleed screw - the oil
5. If the burner motor does not start or ignition fails, turn off the disconnect switch and CALL YOUR SERVICEMAN
CAUTION
Do not attempt to start the burner when excess oil has accumulated, when the furnace is full of vapour, or when the combustion chamber is very hot. Always keep the supply valve shut off if the burner is shut down for an extended period of time.
3.3) Combustion chamber curing:
Some moisture and binders remain in the ceramic combustion chambers after fabrication. It is important to clear the chamber of these residues before testing. If you smoke test before curing, the instrument may become damaged. To cure the chamber, run the unit for 3 consecutive cycles, with 3 minutes of elapsed time in between each cycle. Each burn cycle should be 3
21
Page 21
minutes duration. The exhaust will have a pungent odor and produce a white cloud of steam.
3.4) Perform the smoke / CO2 test:
fan speed, investigate for ductwork restriction(s), dirty or improper air filter, or overfiring caused by excessive pump pressure, or inproper nozzle sizing.
1. For chimney installations, pierce a test hole in the smoke pipe near the furnace breech. For side-wall vented installations, remove the threaded cap from the extended test pipe that is welded into 4-bolt breech plate. Insert the smoke test instrument probe into the open hole.
2. Starting with a zero smoke reading, gradually reduce the burner air setting until just a trace (#1 on Bacharach Scale) of smoke results.
3. Take a CO2 sample at the same test location where the smoke sample was taken. Note the CO2 reading associated with the #1 smoke condition.
4. For chimney vented installations, adjust the burner air setting to obtain a CO2 reading 1% lower than the reading associated with the #1 smoke.
5. For side-wall vented installations, adjust the burner air setting to obtain a CO2 reading 1.5% lower than the reading associated with the #1 smoke.
1. This method of adjusting the CO2 will allow adequate excess air to ensure that the burner will burn clean for the entire heating season, and will ensure proper calibration of the DV-2000™ blocked intake/ vent safety shutdown system used in side­wall venting applications.
3.5) Perform the supply air temperature
rise test:
1. Operate the burner for at least 10 minutes.
2. Measure the temperature of the air in the return air plenum.
3.6) Fan limit adjustment:
FIGURE # 4
DNS-0355 Rev.B
1
Limit “FAN OFF”
2
Limit “FAN ON” Model : OLR160 Model : OUF105, OLF105, OLR105,
OUF160, NOUF105, NOLF105 & NOUF160
3
Limit “HI” Model: OLR160 Model: OUF105, OLF105, OLR105, NOUF105 & NOLF105 Model: OUF160 & NOUF160
900F
1100F 1300F
1700F 1800F
2200F
3. Measure the temperature of the air in the largest trunk coming off the supply air plenum, just “out of the line of sight” of the radiation coming off the heat exchanger; 12” away from the plenum on the main take-off usually satisfies this objective.
4. The temperature rise is calculated by subtracting the return air temperature from the supply air temperature.
5. If the temperature rise exceeds the temperature specified in table #4.1 to #4.3, change to the next higher blower speed tap until the temperature rise falls to at this temperature or below. If the excessive temperature rise cannot be reduced by increasing
22
3.7) Vent temperature test:
1. Place a thermometer in the test hole located in the breech pipe.
2. The vent temperature should be between 400 and 575°F. If not, check for improper air temperature
rise, pump pressure, nozzle size, or for a badly sooted heat exchanger.
Page 22
3.8) DV-2000™ Blocked intake / blocked vent test:
Test, and allow the 1.5% CO2 operating headroom required by the instructions.
For side-wall venting the furnace the DV-2000™ venting system incorporates a safety shutdown system that will shut the burner down before a #1 smoke occurs due to the presence of a blocked intake or blocked vent outlet. Test the system as follows:
1. Ensure that the furnace has been running for at
least 10 minutes.
2. Gradually block the intake. The burner flame should
shut down before a #1 smoke reading occurs.
3. Gradually block the vent outlet. The burner flame
should shut down before a #1 smoke reading occurs.
4. If the burner does not shut down before a #1 smoke
occurs, ensure that the burner is set up according to Part 2, section 3.4. Perform the CO2/ Smoke
5. If the burner still does not shut down before a #1 smoke occurs, check for blockage of the pressure hose, or at the hose connection points.
IMPORTANT
The DV-2000™ safety shutdown system will act to shut down the burner flame during a blocked intake or blocked vent condition if and only if the burner has been set up and calibrated in accordance with Part 2, section
3.4. Perform the CO2/ Smoke Test. For
instance, if the burner is adjusted and final-set to a #1 smoke condition during normal operation, the burner flame can’t possibly shut down before a #1 smoke occurs during a blockage condition.
MAINTENANCE
1) GENERAL
Preventive Maintenance: “Preventive maintenance” is the best way to avoid
unnecessary expense and inconvenience. Have your heating system and burner inspected at regular intervals by a qualified service man.
After inspection, a complete combustion test must be performed after each annual service of the unit to maintain optimum performance and reliability.
WARNINGWARNING
Electrical shock hazard. Turn OFF power to furnace before any
disassembly or servicing. Failure to do so can result in property
damage, bodily injury and/or death.
PART 3
Do not tamper with the unit or controls. Call your service technician.
Before calling for service, check the following.
a. Check oil tank gauge and check if the oil tank valve
in oil is open.
b. Check fuse or circuit breaker. c. Check if shut-off switch is “ON”. d. Reset thermostat above room temperature. e. If ignition does not occur turn off the disconnect
switch and call your qualified service technician.
When ordering replacement parts, specify the complete furnace model number.
1.1) Heat exchanger:
The entire heat exchanger should be inspected annually for soot accumulation. If the burner is operating normally there should very little soot accumulation. If the heat exchanger requires scale removal, use a wire brush first to loosen the scale and then vacuum the soot and scale that has fallen into the secondary heat exchanger (radiator) section. You will
23
Page 23
find that a 36” long flexible hose attachment will be helpful to reach into the back of the radiator; a piece of 1/2” flexible gas connector, or a piece of 1/2” liquid-tight vinyl jacket metallic electrical conduit works well as a makeshift device.
Cleaning the heat exchanger:
Remove the 4-bolt flange from the front of the furnace to reveal the clean-out port and check for soot deposits. If there is very little soot in the radiator section visible from the clean-out port, you will not need to clean it. However, if you notice scaling in the radiator, you should remove the scale.
The wrap-around radiator can now be cleaned entirely from the front inspection port. Also the new furnace has external clean-out ports so the soot does not fall into the fan compartment during the cleaning operation.
Flooding of the fire pot:
Flooding can occur when the oil primary control has been reset a number of times in a no-heat situation. Each time oil is fired into the pot and does not ignite, it is absorbed in the pot. Even if the burner is removed and the pot is felt for wetness, it is difficult to assess the degree of oil absorption by the pot.
There is only one way to properly service a flooded fire pot, and that is to change it.
CAUTION
If you observe the red warning light on the burner, push once ONLY to try and restart. If the burner will not start, phone your authorised service agent. Do not press the button again.
IMPORTANT
Do not vacuum the ceramic chambers—they are easily damaged.
Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil, or if the burner has been operating in a severely fouled condition.
1.2) Refractory fire pot:
Remove the burner and check the fire pot.
IMPORTANT
Use extreme care if cleaning of the pot is required. After firing, the pot becomes very fragile. Do not use any commercially available soot remover. This furnace has a fiber type refractory combustion chamber. Normal servicing of this unit does not require cleaning of the combustion chamber.
Self-aligning firepot:
a. The appliance primary heat exchanger is comprised
of an upper and lower half. The lower half is essentially a “can” that houses a self-aligning firepot. the firepot will fit into the bottom half in one orientation only.
b. A slot in the front of the firepot acts as a track that
captures a burner tube sleeve that extends into the bottom heat exchanger half. This provides automatic rotational alignment, vertical alignment.
c. Five tabs around the bottom and four tabs around
the top provide automatic centering of the firepot.
Removing the firepot:
The firepot is seldom replaced, but when it must be replaced one must simply :
1. Remove the burner.
2. Remove the burner limit control.
3. Remove the breech plate.
4. Remove the front panel.
5. Remove the brass nuts on the stainless steel heat exchanger studs.
If the pot is damaged, it must be replaced. A damaged pot could lead to premature heat exchanger failure. Cracking of the fire pot is normal, however, replace the pot if the cracks have propagated more than 2/3 the way through the wall thickness. The average wall thickness of the firepot is 3/4”.
24
6. Pry the bottom heat exchanger halves apart using the designated prying tabs.
7. Remove the bottom heat exchanger half from the furnace cavity through the front of the furnace.
8. Pull the firepot up and out of the bottom heat exchanger half.
Page 24
9. Pull the old sealing gasket down off the flange of the upper heat exchanger half.
10. Scrape off any residual gasket material off the heat exchanger mating flanges.
Replacing the firepot:
1. Align the slot in the front face of the firepot with the burner tube sleeve and gently lower the firepot into the bottom heat exchanger half.
2. Holding the firepot near the perimeter, gently push the firepot all the way into the bottom heat exchanger half until it seats.
3. Completely wet the gasket with water using a spray pump bottle, position the tabs over the studs, and push the gasket upward against the sealing flange of the upper heat exchanger half.
4. Install the brass nuts on the studs by engaging only 2 or 3 threads.
be removed to check the retention head and to check for proper “Z” dimension with the Beckett “T” gauge supplied with every burner. Check for any sign of oil boiling out of the nozzle and caulking - the solenoid valve could be leaking (if applicable).
1.4) Nozzle:
Replace the nozzle with the one specified in table #4.1 to #4.3.
1.5) Oil filter:
Tank filter:
The tank filter should be replaced as required.
Secondary filter:
The 10 micron (or less) filter cartridges should be replaced annually.
5. Position the bottom heat exchanger half underneath the upper heat exchanger half and rotate the bottom half so that the slots in the bolting tabs engage the stainless steel studs. There is no further need to hold onto the bottom half as it will now be suspended on the stud nuts.
6. Push upward on the can and thread the nuts finger­tight as far as possible.
7. Intermittently tighten the stud nuts with a wrench in a sequence that will pull the heat exchanger halves together evenly. Tighten all nuts to 90 inch-lbs Torque once and then alternately re-tighten all nuts again to 100 inch-lbs THE RE-TIGHTENING
SEQUENCE IS ABSOLUTELY NECESSARY TO ENSURE A TIGHT JOINT.
8. Tighten the nuts until further torquing meets with much resistance. The heavy spring action of the bolting tabs keeps a constant tension on the joint.
9. Re-assemble the front panel, breech plate, limit control and burner in opposite sequence to their removal.
1.6) Air filters:
Air filters are the disposable types. The disposable filters should be replaced on at least an annual basis. Dusty conditions, presence of animal hair etc. may demand much more frequent filter changes. Dirty filters will impact furnace efficiency and increase oil consumption.
1.7) Motor lubrication:
Do not lubricate the oil burner motor or the direct drive blower motor as they are permanently lubricated.
1.8) CAS-2B combustion air kit (chimney venting):
If used, check the CAS-2B combustion air kit for proper operation. Check to see that the inlet screen is not plugged. Block the air inlet completely and ensure that a zero smoke reading results. If a zero smoke reading is not obtained, set up the burner as indicated in Part 2, section 3.
10. Follow the instructions for starting the burner for the first time to cure the firepot and perform combustion checks.
1.3) Drawer assembly:
Remove the drawer assembly. Clean all foreign matter from the retention head and electrodes. If a Beckett AFG burner has been installed, the burner will have to
Gradually block off the intake. The CO2 should increase by a maximum of 0.5 percentage points at the fully blocked condition. If not, check that the VRV gate is pivoting freely and that the pivot rod is in a horizontal position. Also, check that the counterweight has been properly adjusted in accordance with the CAS-2B installation instructions.
25
Page 25
PART 4
INFORMATION
Model : Serial number: Date of installation of the furnace : Service telephones - day : Night : Dealer’s name and address :
RESULT OF START-UP TEST
Nozzle: Pressure : lbpsi Burner adjustments : Primary air
Fine air
Draw Assembly CO2 : % Smoke scale : (Bacharach) Gross stack temperature: Ambiant temperature: Chimney draft: " C.E. Overfire draft : " C.E.
Test made by :
0
F
0
F
26
Page 26
TABLE # 4.1
Technical specifications
Model : OLR
RATING AND PERFORMANCE
Firing rate .50 .63 .75 .72 0.85 0.97 1.14 Pump pressure (PSIG) 100 156 156 145 130 130 130 Input (BTU/h) 70 000 88 200 105 000 100 800 119 000 135 800 159 600 Heating capacity, chimney installation (BTU/h) 59 200 73 000 87 800 98 000 110 000 127 000 Heating capacity, side-wall installation (BTU/h) 59 400 73 200 88 200 84 200 98 000 110 000 127 000 Minimum - maximum temperature rise Stack draft, (Chimney), (Side-wall) Overfire pressure (chimney), (Side-wall)
BECKETT BURNER, CHIMNEY INSTALLATION
Low firing rate baffle Yes Yes Yes Yes Yes Yes Static disc, model 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 Nozzle (Delavan) 0.50 - 70A 0.50 - 70A 0.60 - 70B 0.75 - 70B 0.85 - 70B 1.00 - 70B Combustion air adjustment (shutter / band) 4.5 / 0 8 / 0 7.5 / 0 5 / 0 6.5 / 0 10 / 0
RIELLO BURNER, CHIMNEY INSTALLATION
Nozzle (Delavan) 0.50 - 60A 0.60 - 60A 0.75 - 70B 0.85 - 70B 1.00 - 70B Combustion air adjustment (turbulator / damper) 0 / 3 0 / 4 1 / 2 1 / 2.5 1 / 3
RIELLO BURNER, CHIMNEY INSTALLATION
Nozzle (Delavan) 0.50 - 60A 0.60 - 60A N /A N /A N /A Combustion air adjustment (turbulator / damper) 0 / 3 0 / 4 N /A N /A N /A
BECKETT BURNER, SIDE-WALL INSTALLATION
Nozzle (Delavan) 0.50 - 60W 0.50 - 60W 0.60 - 60W 0.75 - 70B 0.85 - 70B 1.00 - 70B Combustion air adjustment (screw / dial) or (dial only) 3 / 1.5 3 / 3 3 / 4.5 2.75 4.25 6.75
RIELLO BURNER, SIDE-WALL INSTALLATION
Nozzle (Delavan) 0.50 - 60W 0.60 - 60W 0.75 - 70B 0.85 - 70B 1.00 - 70B Combustion air adjustment (turbulator / damper) 0 / 6 0 / 7.5 1 / 3 1 / 4 2 / 4.5
ELECTRICAL SYSTEM
Volts - Hertz - Phase Operating voltage range Rated voltage Amp Minimum ampacity for wiring sizing Max. fuse size (Amps) Control transformer Ext. control power available, cooling and accessories
BLOWER DATA
Blower speed at 0.5" W.C. static pressure MED-LO MED-HI HIGH HIGH MED-LO MED-HI HIGH Blower speed at 0.25" W.C. static pressure LOW MED-HI MED-HI MED-HI MED-LO MED-HI MED-HI Maximum cooling, speed LOW MED-LO MED-HI HIGH MED-LO MED-HI HIGH Maximum cooling, tons @ 0.5" W.C. 1.5 2 2.5 3 3.5 4 5 Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size (1) 20 X 20
(-0,035 to -0,06) (+0,04 to +0,16)
(0,00 to +0,035) (+0,10 to +0,25) (-0.00 to +0.04) (+0.10 to +0.25)
AFG-F0 (tube insersion 5 1/8")
40-F3 (tube insersion 5 3/16")
R35.3 (tube insersion 5 3/16")
AFII-85 (tube insersion 4 15/16")
40-BF3 (tube insersion 5 3/16")
OLR105A12B OLR160B20B
52 - 75 Degr. F
(-0.035 to -0.06) (+0.04 to +0.22)
AFG-F3 (tube insersion 6 5/8")
40-F5 (tube insersion 6 5/8")
AFII-150 (tube insersion 6 5/8")
40-BF5 (tube insersion 6 5/8")
115-60-1 104 - 132
12,2
13.7 15
40 Va 30 Va
1/3 HP / 4 speeds
10 X 10
50 - 80 Degr.F
115-60-1
104 - 132
15.7
18.1
40 Va
30Va
3/4 HP / 4 speeds
12 X 10
(2) 16 X 24
20
TABLE # 5.1
Air delevery - CFM with air filter
OLR105A12B OLR160B20B
EXTERNAL STATIC PRESSURE WITH AIR FILTER EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED 0.25 0.5 0.25 0.5
LOW 850 700 1100 1020
MED-LO 940 750 1360 1350
MED-HI 1090 1000 1625 1540
HIGH 1390 1300 2100 1850
27
Page 27
TABLE # 4.2
Technical specifications
Model : OUF / NOUF
RATING AND PERFORMANCE
Firing rate .50 .63 .75 .72 .85 .97 1.14 Pump pressure (PSIG) 100 156 156 145 130 130 130 Input (BTU/h) 70 000 88 200 105 000 100 800 119 000 135 800 159 600 Heating capacity, chimney installation (BTU/h) 58 900 73 500 86 100 98 000 110 000 127 000 Heating capacity, side-wall installation (BTU/h) 59 800 74 600 87 800 83 900 97 000 110 000 127 000 Minimum - maximum temperature rise Stack draft, (Chimney), (Side-wall) Overfire pressure (chimney), (Side-wall)
BECKETT BURNER, CHIMNEY INSTALLATION
Low firing rate baffle Yes Yes Yes Yes Yes Yes Static disc, model 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 Nozzle (Delavan) 0.50 - 70A 0.50 - 70A 0.60 - 70B 0.75 - 70B 0.85 - 70B 1.00 - 70B Combustion air adjustment (shutter / band) 4.5 / 0 8 / 0 7.5 / 0 5 / 0 6,5 / 0 10 / 0
RIELLO BURNER, CHIMNEY INSTALLATION
Nozzle (Delavan) 0.50 - 60A 0.60 - 60A 0.75 - 70B 0.85 - 70B 1.00 - 70B Combustion air adjustment (turbulator / damper) 0 / 3 0 / 4 0 / 2.5 0 / 2.8 0 / 3.9
BECKETT BURNER, SIDE-WALL INSTALLATION
Nozzle (Delavan) 0.50 - 60W 0.50 - 60W 0.60 - 60W 0,75 - 70B 0,85 - 70B 1,00 - 70B Combustion air adjustment (screw / dial) or (dial only) 3 / 1.5 3 / 3 3 / 4.5 2,75 4,25 6,0
RIELLO BURNER, SIDE-WALL INSTALLATION
Nozzle (Delavan) 0.50 - 60W 0.60 - 60W 0,75 - 70B 0,85 - 70B 1,00 - 70B Combustion air adjustment (turbulator / damper) 0 / 6 0 / 7.5 0 / 3,75 0 / 4 0 / 4,875
ELECTRICAL SYSTEM
Volts - Hertz - Phase Operating voltage range 104 - 132 Rated voltage Amp Minimum ampacity for wiring sizing Max. fuse size (Amps) Control transformer Ext. control power available, cooling and accessories
BLOWER DATA
Blower speed at 0.5" W.C. static pressure LOW LOW MED-HI MED-HI MED-LO MED-HI HIGH Blower speed at 0.25" W.C. static pressure LOW LOW MED-LO MED-LO MED-LO MED-LO MED-HI Maximum cooling, speed LOW MED-LO MED-HI HIGH MED-LO MED-HI HIGH Maximum cooling, tons @ 5" W.C. 2 2.5 2.5 3 3.5 4 5 Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size
OUF105A12B / NOUF105A12B OUF160B18B / NOUF160B18B
52 - 75 Degr. F
(-0,035 to -0,06) (+0,04 to +0,16) (-0,035 to -0,6) (+0,04 to +0,18)
(0,00 to +0,035) (+0,10 to +0,25) (0,00 to +0,04) (+0,10 to +0,25)
AFG-F0 (tube insersion 5 1/8")
40-F3 (tube insersion 5 3/16")
AFII-85 (tube insersion 4 15/16")
40-BF3 (tube insersion 5 3/16")
115-60-1
104 - 132
15.4
17.7 20
40 Va 30 Va
1/2 HP / 4 speeds
10 X 10
(1) 20 X 20
AFG-F3 (tube insersion 6 5/8")
40-F5 (tube insersion 6 5/8")
AFII-150 (tube insersion 6 5/8")
40 - BF5 (tube insersion 6 5/8")
50 - 80 Degr. F
115-60-1
16.9
19.5 20
40 Va 30 Va
0.85 HP / 4 speeds 12 X 10
(1) 24 X 24
TABLE #5.2
Air delevery - CFM with air filter
OUF105A12B / NOUF105A12B OUF160B18B / NOUF160B18B
EXTERNAL STATIC PRESSURE WITH AIR FILTER EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED 0.25 0.5 0.25 0.5
LOW 960 920 1080 990
MED-LO 1100 1000 1350 1310
MED-HI 1300 1150 1605 1510
28
Page 28
TABLE # 4.3
AFII-85 (tube insersion 4 15/16")
Technical specifications
Model : OLF / NOLF
RATING AND PERFORMANCE
Firing rate .50 .63 .75 .72 Pump pressure (PSIG) 100 156 156 145 Input (BTU/h) 70 000 88 200 105 000 100 800 Heating capacity, chimney installation (BTU/h) 59 200 73 000 87 800 Heating capacity, side-wall installation (BTU/h) 59 400 73 200 88 200 84 200 Minimum - maximum temperature rise Stack draft, (Chimney), (Side-wall) Overfire pressure (chimney), (Side-wall)
BECKETT BURNER, CHIMNEY INSTALLATION
Low firing rate baffle Yes Yes No Static disc, model 2 3/4 #3383 2 3/4 #3383 2 3/4 #3383 Nozzle (Delavan) 0.50 - 70A 0.50 - 70A 0.60 - 70B Combustion air adjustment (shutter / band) 4.5 / 0 8 / 0 7.5 / 0
RIELLO BURNER, CHIMNEY INSTALLATION
Nozzle (Delavan) 0.50 - 60A 0.60 - 60A Combustion air adjustment (turbulator / damper) 0 / 3 0 / 4
BECKETT BURNER, SIDE-WALL INSTALLATION
Nozzle (Delavan) 0.50 - 60W 0.50 - 60W 0.60 - 60W Combustion air adjustment (screw / dial) 3 / 1.5 3 / 3 3 / 4.5
RIELLO BURNER, SIDE-WALL INSTALLATION
Nozzle (Delavan) 0.50 - 60W 0.60 - 60W Combustion air adjustment (turbulator / damper) 0 / 6 0 / 7.5
ELECTRICAL SYSTEM
Volts - Hertz - Phase Operating voltage range Rated voltage Amp Minimum ampacity for wiring sizing Max. fuse size (Amps) Control transformer Ext. control power available, cooling and accessories
BLOWER DATA
Blower speed at 0.5" W.C. static pressure LOW MED-HI HIGH HIGH Blower speed at 0.25" W.C. static pressure LOW MED-HI HIGH HIGH Maximum cooling, speed LOW MED-LO MED-HI HIGH Maximum cooling, tons @ 5" W.C. 1.5 2 2.5 3 Motor (HP) / number of speeds Blower wheel size (in.) 10 X 10
OLF105A12B / NOLF105A12B
52 - 75 Degr. F
(-0,035 to -0,06) (+0,04 to +0,16)
(0,00 to +0,035) (+0,10 to +0,25)
AFG-F0 (tube insersion 5 1/8")
40-F3 (tube insersion 5 3/16")
40-BF3 (tube insersion 5 3/16")
115-60-1
104 - 132
12,2
13.7 15
40 Va 30 Va
1/3 HP / 4 speeds
SPEED 0.25 0.5
LOW 840 770
MED-LO 960 800
MED-HI 1050 980
HIGH 1300 1200
TABLE # 5.3
Air delevery - CFM with air filter
OLF105A12B / NOLF105A12B
EXTERNAL STATIC PRESSURE WITH AIR FILTER
29
Page 29
FIGURE # 5.1
Model: OLR105A12B
DNS-0571 Rev. B
FIGURE # 5.2
Model: OLR160B20B
DNS-0573 Rev. B
30
Page 30
FIGURE # 5.3
Model: OUF105A12B
DNS-0568 Rev. C
FIGURE # 5.4
Model: OUF160B18
DNS-0572 Rev. C
31
Page 31
FIGURE # 5.5
Model : OLF105A12B
DNS-0570 Rev. B
FIGURE # 5.6
Model: NOUF105A12B
DNS-0674 Rev. C
32
Page 32
FIGURE # 5.7
Model: NOUF160B18B
DNS-0675 Rev. D
FIGURE # 5.8
Model: NOLF105A12B
DNS-0676 Rev. C
33
Page 33
FIGURE # 6
Wiring diagram, OLR105A12B, OLR160B20B, OUF105A12B, NOUF105A12B, OUF160B18B,
NOUF160B18B, OLF105A12B & NOLF105A12B
DNS-0447 Rev. I
34
Page 34
PARTS LIST
ITEM
DESCRIPTION
MANUFAC.
ITEM
DESCRIPTION
MANUFAC.
Model : OLR105A12B Serial # > 264 000
DNS-0564 Rev. D
1 Complet heat exchanger B30756-02 2 Top heat exchanger B30465-02 3 Combustion chamber B30414 4 Gasket, heat exchanger B30517 5 Bottom heat exchanger B30757 6 Hexagonal flange nut 3/8-16NC brass F07O001 7 Gasket panel, peep hole B30753 8 Division panel B30488
9 Plenum divider B30478 10 Floor B30472 11 Left side panel ass'y B30509-02 12 Left side panel insulation B30493-04 13 Top rear panel B30511 14 Blower door ass'y B30512 15 Air filter drawer B30507 16 Right side panel ass'y B30509-01 17 Right side panel insulation B30493-03 18 Right filter support B30479-01 19 Left filter support B30479-02 20 Gasket, extruded 1/2" X 1/8" x 25' J06L001 21 Front panel ass'y B30768-01 22 Front panel insulation B30762 23 Washer 3/8" AA zinc F06F005 24 Hexagonal nut 3/8-16NC brass F07F024 25 Washer, peep hole B30752 26 Hexagonal flange nut 3/8-16NC brass F07O001
27A 5" breech plate B30459 27B 3" breech plate B30515
28 Gasket, breech plate B30415-02 29 Electrical box cover (without cosmetic) B40085 30 Electrical box B30514 31 Rocker switch SPST L07F003
32 Fan limit control R02I005 33 Transformer 120/24 VAC / 40 VA K03040 34 Relay SPDT 24VAC L01H009 35 Terminal strip, 6 positions L05F011 36 Blower weel 10 X 10 Z01L002 37 Capacitor holder B01024 38 5 MF capacitor L01I001 39 Blower electrical kit B30057 40 Screw cable tie F11F007 41 Blower support bracket B30473 42 1/3 HP direct drive motor B01890-01
43 Motor mount ass'y B01888 44A Blower 10 X 10 Z01I004 44B Blower ass'y B01405-03
45 Rubber grommet #19 Z01F006
46 Sealing strip B01291-01
47 Strip B30188-02
48 Gasket, access cover B30415-01
49 Flange plate B30487
50 Hexagonal flange nut 3/8-16NC brass F07O001
51 Access cover B30486
52 Rocker switch SPST L07F016
53 Terminal strip, 6 positions A00336
54 Floor baffle B30480
55 Gasket, access cover B30415-02
56 Gasket, burner B30534
57 Gasket, access cover B30415-02
58 Gasket, sealing plate B30533 59A Peep hole kit K30011 59B Overfire pressure test kit K30012
60 Gasket, glass B30055
61 Glass, neoceram B30041-01
35
Page 35
PARTS LIST
ITEM
DESCRIPTION
MANUFAC.
ITEM
DESCRIPTION
MANUFAC.
Model : OLR160B20B Serial # > 264 000
DNS-0567 Rev. D
1 Complet heat exchanger B30786-02 2 Top heat exchanger B30596 3 Combustion chamber B30584 4 Hexagonal flange nut 3/8-16NC brass F07O001 5 Gasket, panel, peep hole B30753 6 Bottom heat exchanger B30787 7 Gasket, heat exchanger B30532 8 Gasket, heat exchanger B30534
9 Gasket, heat exchanger B30415-02 10 Front baffle B30665 11 Rear baffle B30664 12 Division panel B30666 13 Plenum divider B30669 14 Floor baffle B30481 15 Floor B30663 16 Left side panel ass'y B30680-02 17 Left side panel insulation B30686-02 18 Left bottom filter support B30668-02 19 Left top filter support B30667 20 Strip B10256-99 21 Sealing strip B01291-02 22 Blower door ass'y B30683 23 Air filter drawer B30678 24 Top rear panel B30682 25 Gasket, breech plate B30589-01
26A 5" breech plate B30646 26B 4" breech plate B30647
27 Hexagonal flange nut 3/8-16NC brass F07O001 28 Gasket, extruded 1/2" X 1/8" x 25' J06L001 29 Right side panel ass'y B30680-01 30 Right side panel insulation B30686-01 31 Right bottom filter support B30668-01 32 Right top filter support B30667
33 Front panel ass'y B30782-01 34 Front panel insulation B30780 35 Washer, peep hole B30752 36 Washer 3/8" AA zinc F06F005 37 Hexagonal nut 3/8-16NC brass F07F024 38 Flange plate B30676 39 Hexagonal flange nut 3/8-16NC brass F07O001 40 Access cover B30486 41 Electrical box cover (without cosmetic) B40085 42 Terminal strip, 6 positions L05F011 43 Rocker switch SPST L07F016 44 Rocker switch SPST L07F003 45 Electrical box B30514 46 Fan limit control R02I005 47 Transformer 120/24 VAC / 40 VA K03040 48 Terminal strip, 6 positions A00336 49 Relay SPDT 24VAC L01H009 50 Rubber grommet #19 Z01F006 51 Blower support bracket B01756 52 Blower electrical kit B30530-01 53 Strain release bushing SR-9P-2 L04I010 54 Capacitor holder B01024 55 15 MF capacitor L01I005
56 Blower weel 12 X 10 Z01L003 57A Blower 12 X 10 Z01I008 57B Blower ass'y B01406-05
58 Motor mount ass'y B01889
59 3/4 HP direct drive motor L06I004 60A Peep hole kit K30011 60B Overfire pressure test kit K30012
61 Gasket, glass B30055
62 Gasket, neoceram B30041-01
36
Page 36
PARTS LIST
Model : OUF105A12B Serial # > 264 000
DNS-0563 Rev. D
ITEM DESCRIPTION MANUFAC.
1 Complet heat exchanger B30756-01 2 Top heat exchanger B30465-01 3 Gasket, heat exchanger B30517 4 Combustion chamber B30414 5 Bottom heat exchanger B30757 6 Hexagonal flange nut 3/8-16NC brass F07O001 7 Gasket panel, peep hole B30753 8 Division panel B30431
9 Floor B30430 10 Baffle B30426 11 Rear panel ass'y B30457 12 Rear panel insulation B30419 13 Right side panel ass'y B30458-01 14 Right side panel insulation B30418 15 Front panel ass'y B30760-01 16 Front panel insulation B30761 17 Blower door ass'y B30455 18 Door handle Z99F050 19 Left side panel ass'y B30458-02 20 Left side panel insulation B30418
21A 5" breech plate B30459 21B 3" breech plate B30515
22 Gasket, breech plate B30415-02 23 Hexagonal flange nut 3/8-16NC brass F07O001 24 Hexagonal nut 3/8-16NC brass F07F024 25 Washer 3/8" AA zinc F06F005
ITEM DESCRIPTION MANUFAC.
26 Terminal strip, 6 positions L05F011 27 Electrical box cover (without cosmetic) B40085 28 Relay SPDT 24VAC L01H009 29 Transformer 120/24 VAC / 40 VA K03040 30 Fan limit control R02I005 31 Rocker switch SPST L07F003 32 Electrical box B30514 33 Blower side rails B30433 34 Blower weel 10 X 10 Z01L002 35 1/2 HP direct drive motor L06H004 36 Blower electrical kit B30096 37 Capacitor holder B01024 38 7.5 MF capacitor L01I002 39 Motor mount ass'y B01888
40 Sealing strip B01291-01 41A Blower 10 X 10 Z01I004 41B Blower ass'y B01405-02
42 Blower slide support B30513
43 Washer, peep hole B30752
44 Rocker switch SPST L07F016
45 Terminal strip, 6 positions A00336
46 Gasket, burner B30534 47A Peep hole kit K30011 47B Overfire pressure test kit K30012
48 Gasket, glass B30055
49 Glas, neoceram B30041-01
37
Page 37
PARTS LIST
Model : OUF160B18B Serial # > 264 000
DNS-0566 Rev. D
ITEM DESCRIPTION MANUFAC.
1 Complet heat exchanger B30786-01 2 Top heat exchanger B30597 3 Combustion chamber B30584 4 Hexagonal flange nut 3/8-16NC brass F07O001 5 Gasket, heat exchanger B30532 6 Bottom heat exchanger B30787 7 Rear baffle B30619 8 Front baffle B30618
9 Top baffle B30639 10 Division panel B30627 11 Blower slide support B30625 12 Floor B30628 13 Left side panel ass'y B30653-02 14 Left side panel insulation B30658 15 Rear panel ass'y B30652 16 Rear panel insulation B30659 17 Hexagonal flange nut 3/8-16NC brass F07O001 18 Breech plate B30487 19 Gasket, access cover B30415-01 20 Gasket, access cover B30415-02 21 Right side panel ass'y B30653-01 22 Right side panel insulation B30658 23 Gasket panel, peep hole B30753 24 Gasket, burner B30534 25 Gasket, breech plate B30589-01 26 Front panel ass'y B30781-01 27 Front panel insulation B30779 28 Blower door ass'y B30651 29 Door handle Z99F050 30 Washer 3/8" AA zinc F06F005
ITEM DESCRIPTION MANUFAC.
31 Hexagonal nut 3/8-16NC brass F07F024 32A 5" breech plate B30646 32B 4" breech plate B30647
33 Hexagonal flange nut 3/8-16NC brass F07O001
34 Electrical box B30514
35 Relay SPDT 24VAC L01H009
36 Transformer 120/24 VAC / 40 VA K03040
37 Fan limit control R02I005
38 Rocker switch SPST L07F003
39 Electrical box cover (without cosmetic) B40085
40 Washer, peep hole B30752
41 .85 HP direct drive motor L06K001
42 Motor mount ass'y B01889
43 Terminal strip, 6 positions L05F011
44 Blower electrical kit B30530
45 Blower wheel 12 X 10 Z01L003
46 Sealing strip B01291-01
47 Blower side rails B30626 48A Blower 12 X 10 Z01I008 48B Blower ass'y B02167-01
49 Capacitor holder B01024
50 10 MF capacitor L01I003
51 Rocker switch SPST L07F016
52 Terminal strip, 6 positions A00336
53 Gasket, sealing plate B30533 54A Peep hole kit K30011 54B Overfire pressure test kit K30012
55 Gasket, glass B30055
56 Glass, neoceram B30041-01
38
Page 38
PARTS LIST
ITEM
DESCRIPTION
MANUFAC.
Model : OLF105A12B Serial # > 264 000
DNS-0565 Rev. D
ITEM DESCRIPTION MANUFAC.
1 Complet heat exchanger B30756-01 2 Top heat exchanger B30465-01 3 Combustion chamber B30414 4 Gasket, heat exchanger B30517 5 Bottom heat exchanger B30757 6 Hexagonal flange nut 3/8-16NC brass F07O001 7 Gasket panel, peep hole B30753 8 Division panel B30477
9 Plenum divider B30478 10 Floor B30472 11 Left side panel ass'y B30504-02 12 Left side panel insulation B30493-02 13 Top rear panel B30506 14 Blower door ass'y B30512 15 Air filter drawer B30507 16 Right side panel ass'y B30504-01 17 Right side panel insulation B30493-01 18 Right filter support B30479-01 19 Left filter support B30479-02 20 Gasket, extruded 1/2" X 1/8" X 25' B30483 21 Front panel ass'y B30767-01 22 Front panel insulation B30761 23 Washer 3/8" AA zinc F06F005 24 Hexagonal nut 3/8-16NC brass F07F024 25 Washer, peep hole B30752 26 Hexagonal flange nut 3/8-16NC brass F07O001
27A 5" breech plate B30459
27B 3" breech plate B30515
28 Gasket, breech plate B30415-02 29 Electrical box cover (without cosmetic) B40085
30 Electrical box B30514 31 Rocker switch SPST L07F003 32 Fan limit control R02I005 33 Transformer 120/24 VAC / 40 VA K03040 34 Relay SPDT 24VAC L01H009 35 Terminal strip, 6 positions L05F011 36 Blower weel 10 X 10 Z01L002 37 Capacitor holder B01024 38 5 MF capacitor L01I001 39 Blower electrical kit B30057 40 Screw cable tie F11F007 41 Blower support bracket B30473 42 1/3 HP direct drive motor B01890-01
43 Motor mount ass'y B01888 44A Blower 10 X 10 Z01I004 44B Blower ass'y B01405-03
45 Rubber grommet #19 Z01F006
46 Sealing strip B01291-01
47 Strip B30188-02
48 Rocker switch SPST L07F016
49 Terminal strip, 6 positions A00336
50 Gasket, breech plate B30415-02
51 Gasket, burner B30534
52 Rear baffle B30490
53 Front baffle B30480 54A Peep hole kit K30011 54B Overfire pressure test kit K30012
55 Gasket, glass B30055
56 Glass, neoceram B30041-01
39
Page 39
PARTS LIST
ITEM
DESCRIPTION
MANUFAC.
ITEM
DESCRIPTION
MANUFAC.
Model : NOUF105A12B Serial # > 264 000
DNS-0681 Rev. B
1 Complet heat exchanger B30756-01 2 Top heat exchanger B30465-01 3 Gasket, heat exchanger B30517 4 Combustion chamber B30414 5 Bottom heat exchanger B30757 6 Hexagonal flange nut 3/8-16NC brass F07O001 7 Gasket panel, peep hole B30753 8 Division panel B30431
9 Floor B30430 10 Baffle B30426 11 Rear panel ass'y B30457 12 Rear panel insulation B30419 13 Right side panel ass'y B30458-01 14 Right side panel insulation B30418 15 Front panel ass'y B30760-01 16 Front panel insulation B30761 17 Blower door ass'y B30455 18 Door handle Z99F050 19 Left side panel ass'y B30458-02 20 Left side panel insulation B30418
21A 5" breech plate B30459 21B 3" breech plate B30515
22 Gasket, breech plate B30415-02 23 Hexagonal flange nut 3/8-16NC brass F07O001 24 Hexagonal nut 3/8-16NC brass F07F024 25 Washer 3/8" AA zinc F06F005 26 Terminal strip, 6 positions L05F011 27 Electrical box cover (without cosmetic) B40085 28 Relay SPDT 24VAC L01H009
29 Transformer 120/24 VAC / 40 VA K03040 30 Fan limit control R02I005 31 Rocker switch SPST L07F003 32 Electrical box B30514 33 Blower side rails B30433 34 Blower weel 10 X 10 Z01L002 35 1/2 HP direct drive motor L06H004 36 Blower electrical kit B30096 37 Capacitor holder B01024 38 7.5 MF capacitor L01I002 39 Motor mount ass'y B01888
40 Sealing strip B01291-01 41A Blower 10 X 10 Z01I004 41B Blower ass'y B01405-02
42 Blower slide support B30513
43 Washer, peep hole B30752
44 Rocker switch SPST L07F016
45 Terminal strip, 6 positions A00336
46 Gasket, burner B30534
47 Front door, vestibule B40293
48 Right panel, vestibule B30725
49 Left panel, vestibule B30726
50 Top panel, vestibule B30723
51 Bottom panel, vestibule B30724
52 Draft regulator Z06F001 53A Peep hole kit K30011 53B Overfire pressure test kit K30012
54 Gasket, glass B30055
55 Glass, neoceram B30041-01
40
Page 40
PARTS LIST
ITEM
DESCRIPTION
MANUFAC.
Model : NOUF160B18B Serial # > 264 000
DNS-0680 Rev. B
ITEM DESCRIPTION MANUFAC.
1 Complet heat exchanger B30786-01 2 Top heat exchanger B30597 3 Combustion chamber B30584 4 Hexagonal flange nut 3/8-16NC brass F07O001 5 Gasket, heat exchanger B30532 6 Bottom heat exchanger B30787 7 Gasket panel, peep hole B30619 8 Front baffle B30618
9 Top baffle B30639 10 Division panel B30627 11 Blower slide support B30625 12 Floor B30628 13 Left side panel ass'y B30653-02 14 Left side panel insulation B30658 15 Rear panel ass'y B30652 16 Rear panel insulation B30659 17 Hexagonal flange nut 3/8-16NC brass F07O001 18 Breech plate B30487 19 Gasket, access cover B30415-01 20 Gasket, access cover B30415-02 21 Right side panel ass'y B30653-01 22 Right side panel insulation B30658 23 Gasket panel, peep hole B30753 24 Gasket, burner B30534 25 Gasket, breech plate B30589-01 26 Front panel ass'y B30781-01 27 Front panel insulation B30779 28 Blower door ass'y B30651 29 Door handle Z99F050 30 Washer 3/8" AA zinc F06F005 31 Hexagonal nut 3/8-16NC brass F07F024
32A 5" breech plate B30646 32B 4" breech plate B30647
33 Hexagonal flange nut 3/8-16NC brass F07O001 34 Electrical box B30514 35 Relay SPDT 24VAC L01H009 36 Transformer 120/24 VAC / 40 VA K03040 37 Fan limit control R02I005 38 Rocker switch SPST L07F003 39 Electrical box cover (without cosmetic) B40085 40 Washer, peep hole B30752 41 .85 HP direct drive motor L06K001 42 Motor mount ass'y B01889 43 Terminal strip, 6 positions L05F011 44 Blower electrical kit B30530 45 Blower wheel 12 X 10 Z01L003 46 Sealing strip B01291-01
47 Blower side rails B30626 48A Blower 12 X 10 Z01I008 48B Blower ass'y B02167-01
49 Capacitor holder B01024
50 10 MF capacitor L01I003
51 Rocker switch SPST L07F016
52 Terminal strip, 6 positions A00336
53 Gasket, sealing plate B30533
54 Front door, vestibule B40295
55 Right panel, vestibule B30632
56 Left panel, vestibule B30633
57 Top panel, vestibule B30732
58 Bottom panel, vestibule B30728
59 Draft regulator Z06F001 60A Peep hole kit K30011 60B Overfire pressure test kit K30012
61 Gasket, glass B30055
62 Glass, neoceram B30041-01
41
Page 41
PARTS LIST
ITEM
DESCRIPTION
MANUFAC.
ITEM
DESCRIPTION
MANUFAC.
Model : NOLF105A12B Serial # > 264 000
DNS-0679 Rev. B
1 Complet heat exchanger B30756-01 2 Top heat exchanger B30465-01 3 Combustion chamber B30414 4 Gasket, heat exchanger B30517 5 Bottom heat exchanger B30757 6 Hexagonal flange nut 3/8-16NC brass F07O001 7 Gasket panel, peep hole B30753 8 Division panel B30477
9 Plenum divider B30478 10 Floor B30472 11 Left side panel ass'y B30504-02 12 Left side panel insulation B30493-02 13 Top rear panel B30506 14 Blower door ass'y B30512 15 Air filter drawer B30507 16 Right side panel ass'y B30504-01 17 Right side panel insulation B30493-01 18 Right filter support B30479-01 19 Left filter support B30479-02 20 Gasket, extruded 1/2" X 1/8" X 25' B30483 21 Front panel ass'y B30767-01 22 Front panel insulation B30761 23 Washer 3/8" AA zinc F06F005 24 Hexagonal nut 3/8-16NC brass F07F024 25 Washer, peep hole B30752 26 Hexagonal flange nut 3/8-16NC brass F07O001
27A 5" breech plate B30459 27B 3" breech plate B30515
28 Gasket, breech plate B30415-02 29 Electrical box cover (without cosmetic) B40085 30 Electrical box B30514 31 Rocker switch SPST L07F003 32 Fan limit control R02I005
33 Transformer 120/24 VAC / 40 VA K03040 34 Relay SPDT 24VAC L01H009 35 Terminal strip, 6 positions L05F011 36 Blower weel 10 X 10 Z01L002 37 Capacitor holder B01024 38 5 MF capacitor L01I001 39 Blower electrical kit B30057 40 Screw cable tie F11F007 41 Blower support bracket B30473 42 1/3 HP direct drive motor B01890-01
43 Motor mount ass'y B01888 44A Blower 10 X 10 Z01I004 44B Blower ass'y B01405-03
45 Rubber grommet #19 Z01F006
46 Sealing strip B01291-01
47 Strip B30188-02
48 Rocker switch SPST L07F016
49 Terminal strip, 6 positions A00336
50 Gasket, breech plate B30415-02
51 Gasket, burner B30534
52 Rear baffle B30490
53 Front baffle B30480
54 Front door, vestibule B40292
55 Right panel, vestibule B30729
56 Left panel, vestibule B30730
57 Top panel, vestibule B30723
58 Bottom panel, vestibule B30724
59 Draft regulator Z06F001 60A Peep hole kit K30011 60B Overfire pressure test kit K30012
61 Gasket, glass B30055
62 Glass, neoceram B30041-01
42
Loading...