ICP OMF112K14A, OMV112K14A Installation Instructions And Homeowner's Manual

OMF112K14A OMV112K14A
DNS-1225A
US C
MULTIPOSITION
OIL FIRED FURNACE
INSTALLER / SERVICE TECHNICIAN: USE THE INFORMATION IN THIS MANUAL FOR THE
INSTALLATION / SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE.
HOMEOWNER: PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR
FUTURE REFERENCE.
Printed on 100% recycled paper 2009-12-07 X40165 Rev. B
Attention: Do not tamper with the unit or its
controls. Call a qualified service technician.
Manufactured by: UTC Canada Corporation
ICP Division
445 014101 00
445 01 4101 00
TABLE OF CONTENTS
1 SAFETY REGULATIONS ..................................................................................3
1.1 SAFETY LABELING AND WARNING SIGNS .............................................................................................3
1.2 IMPORTANT INFORMATION.....................................................................................................................3
1.3 DETECTION SYSTEMS.............................................................................................................................3
1.4 DANGER OF FREEZING............................................................................................................................3
2 INSTALLATION ................................................................................................. 4
2.1 POSITIONING THE FURNACE ..................................................................................................................4
2.2 CONFIGURATIONS (FIGURES 1 & 2) ..........................................................................................................4
2.3 ELECTRICAL SYSTEM (FIGURES 3 & 4).....................................................................................................5
2.4 INSTALLATION OF THE THERMOSTAT ...................................................................................................5
2.5 INSTALLATION OF THE BURNER.............................................................................................................6
2.6 VENTING ...................................................................................................................................................6
2.7 BLOCKED VENT SHUT-OFF DEVICE (BVSO) FOR CHIMNEY VENTING.................................................7
2.8 COMBUSTION AIR SUPPLY AND VENTILATION......................................................................................7
2.9 OIL TANK...................................................................................................................................................8
2.10 DUCTING...................................................................................................................................................8
2.11 SUPPLY AIR ADJUSTMENTS (4 SPEED MOTORS).................................................................................8
2.12 SUPPLY AIR ADJUSTMENTS (ECM VARIABLE SPEED MOTORS).........................................................9
2.13 INSTALLATION OF ACCESSORIES..........................................................................................................9
3 OPERATION .................................................................................................... 10
3.1 START-UP................................................................................................................................................10
3.2 OPERATING SEQUENCE OIL HEATING MODE .....................................................................................10
3.3 CHECKS AND ADJUSTMENTS...............................................................................................................10
4 MAINTENANCE...............................................................................................12
4.1 CLEANING THE HEAT EXCHANGER......................................................................................................12
4.2 CLEANING THE BLOCKED VENT SHUT-OFF DEVICE (BVSO)..............................................................12
4.4 REPLACING THE NOZZLE......................................................................................................................12
4.5 REPLACING THE OIL FILTER .................................................................................................................12
4.6 REPLACING THE AIR FILTER.................................................................................................................12
5 FURNACE INFORMATION.............................................................................. 13
TABLE 1 - TECHNICAL SPECIFICATIONS................................................................................................................. 14
TABLE 2 - AIR FLOW, UNITS WITH ½ HP ECM MOTEUR ......................................................................................... 15
TABLE 3 - AIR FLOW, UNITS WITH ½ HP PSC MOTEUR.......................................................................................... 16
TABLE 4 - MINIMUM CLEARANCES FROM COMBUSTIBLE MATÉRIAL................................................................... 16
FIGURE 5 - DIMENSIONS..............................................................................................................................................17
FIGURE 6 - WIRING DIAGRAM, DD, 4 SPEED PSC MOTOR....................................................................................... 18
FIGURE 7 - WIRING DIAGRAM, DD, VARIABLE SPEED ECM MOTEUR.................................................................... 19
EXPLODED VIEWS OF COMPONENTS AND PARTS LISTS................................................................................20 to 23
TABLES AND FIGURES
2
445 01 4101 00
1 SAFETY REGULATIONS
1.1 SAFETY LABELING AND
WARNING SIGNS
The words DANGER, WARNING AND CAUTION are used to identify the levels of seriousness of certain hazards. It is important that you understand their meaning. You will notice these words in the manual as follows:
DANGER
Immediate hazards that WILL result in death, serious bodily injury and/or property damage.
WARNING
Hazards or unsafe practices that CAN result in death, bodily injury and/or property damage.
CAUTION
Hazards or unsafe practices that CAN result in bodily injury and/or property damage.
1.2 IMPORTANT INFORMATION
WARNING
Non-observance of the safety regulations outlined in this manual will potentially lead to consequences resulting in death, serious bodily injury and/or property damage.
a) It is the homeowner’s responsibility to engage a
qualified technician for the installation and subsequent servicing of this furnace;
b) Do not use this furnace if any part of it w as under
water. Call a qualified service technician immediately to assess the damage and to replace all critical parts that were in contact with water;
c) Do not store gasoline or any other flammable
substances, such as paper, carton, etc. near the furnace;
d) This furnace is designed for use with #1 or #2
heating oil only. The use of gasoline, motor oil or any other oil containing gasoline is prohibited;
e) Never block or otherwise obstruct the filter and/or
return air openings;
f) Ask the technician installing your furnace to show
and explain to you the following items: i) The main disconnect switch; ii) The shut-off valve on the oil tank;
iii) The oil filter and how to change it (once a
year);
iv) The air filter and how to change it (check
monthly and clean or replace if necessary.)
g) Before calling for service, be sure to have the
information page of your manual close by in order to be able to provide the contractor with the required information, such as the model and serial numbers of the furnace.
WARNING
Installations and repairs performed by unqualified persons can result in hazards to them and to others. Installations must conform to local codes or, in the absence of same, to codes of the country having jurisdiction.
The information contained in this manual is intended for use by a qualified technician, familiar with safety procedures and who is equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in death, bodily injury and/or property damage.
1.3 DETECTION SYSTEMS
It is recommended that carbon monoxide detectors be installed wherever oil or gas fired heaters are used. Carbon monoxide can cause bodily harm or death. For this reason, agency approved carbon monoxide detectors should be installed in your residence and properly maintained to warn of dangerously high carbon monoxide levels.
There are several sources of possible smoke and flames in a residence. Smoke and flames can cause bodily harm or death. For this reason, agency approved smoke detectors should be installed in your residence and properly maintained, to warn early on, of a potentially dangerous fire. Also, the house should be equipped with approved and properly maintained fire extinguishers.
Your unit is equipped with safety devices that can prevent it from functioning when anomalies are detected such as a blocked venting system.
1.4 DANGER OF FREEZING
If your furnace is shut down during the cold weather season, water pipes may freeze, burst and cause serious water damage. Turn off the water supply and bleed the pipes.
If the heater is left unattended during the cold weather season, take the following precautions:
a. Close the main water valve in the house and purge
the pipes if possible. Open all the faucets in the house;
b. Ask someone to frequently check the house during
the cold weather season to make sure that there is sufficient heat to prevent the pipes from freezing. Tell this person to call an emergency number if required.
CAUTION
3
445 01 4101 00
2 INSTALLATION
This furnace is a true multi-position unit, in that it will function in an upflow, downflow or horizontal configuration to the left or the right. Only a few modifications are required during installation to change from one position to another. The unit is shipped in the upflow configuration and instructions as to how to change to the other positions are included in this manual.
The unit is shipped with a burner and its controls. It requires a 115VAC power supply to the control panel and thermostat hook-up as shown on the wiring diagram, one or more oil line connections, suitable ductwork and connection to a properly sized vent.
All local and national code requirements governing the installation of oil burning equipment, wiring and the flue connection MUST be followed. Some of the codes that may apply are:
CSA B139: Installation code for oil burning
equipment.
ANSI/NFPA 31: Installation of oil burning equipment. ANSI/NFPA 90B: Warm air heating and air conditioning
systems.
ANSI/NFPA 211: Chimneys, Fireplaces, Vents and solid
fuel burning appliances.
ANSI/NFPA 70: National Electrical Code. CSA C22.1 or CSA C22.10:
Canadian Electrical Code.
Only the latest issues of these codes may be used.
2.1 POSITIONING THE FURNACE
WARNING
Fire and explosion hazard. The furnace must be installed in a level position, never
where it will slope toward the front. Do not store or use gasoline or any other flammable
substances near the furnace. Non-observance of these instructions will potentially
result in death, bodily injury and/or property damage.
CAUTION
This furnace is not watertight and is not designed for outdoor installation. It must be installed in such a manner as to protect its electrical components from water. Outdoor installation will lead to a hazardous electrical condition and to premature failure of the equipment.
The minimum clearances from combustible material for each of the positions are specified in Table 4.
If the furnace is installed in a basement or on a dirt floor, in a crawl space for example, it is recommended to install the unit on a cement base 2.5 cm to 5.0 cm (1" to 2") thick.
DNS-1227A
The unit must be installed in an area where the ambient and return air temperatures are above 15°C (60°F). In addition, the furnace should be installed as closely as possible to the vent, so that the connections are direct and kept to a minimum. The heater should also be located close to the centre of the air distribution system.
2.1.1
Installation in an enclosure
The unit can be installed in an enclosure such as a closet. However, 2 ventilation openings are required for combustion air. The openings should be located in front of the furnace approximately 15 cm (6") above the floor and 15 cm (6") below the ceiling. Figure 1 indicates the minimum dimensions required and the location of the openings.
Figure 1
Location and dimensions of
ventilation air openings in a closet door
2.2 CONFIGURATIONS
2.2.1 Upflow Installation
The return air opening may be located on either side of the furnace. Care should be taken not to damage the wires inside, while cutting the opening. Install the filter rack supplied with the unit according to the instructions provided with it. It is also recommended to install the blower door before handling or moving the unit. Refer to Figure 2 for additional details.
Figure 2
Burner position
Filter 20X24
Combustible or non­combustible floor
4
445 01 4101 00
2.2.2 Downflow Installation
When the furnace is installed in the downflow position on a combustible floor, the clearances from combustibles must be adhered to. The downflow base DFB-103 or KLASB0901DET can be used to ensure these clearances. Refer to Figure 3 and the installation instructions provided with the base.
The burner must always be installed in the same manner, regardless of the discharge position of the furnace. Refer to Figure 3 for additional details.
Figure 3
2.2.3 Horizontal Installation
When the furnace is installed in the horizontal position, either suspended or on a combustible floor with a choice of right or left discharge, the clearances from combustible material must be adhered to. If the unit is installed on a combustible floor, the horizontal floor base HFB-101 or KLASB0701DET can be used to ensure these clearances. Refer to the instructions supplied with the base.
The burner must always be installed in the same manner, regardless of the discharge position of the furnace. Refer to Figure 4 for additional details.
Burner position
Filter 20 x 24
Downflow base is required for combustible floor
DNS-1227A
Horizontal floor base required for combustible floor
Burner position
Filter 20 x 24
DNS-1227A
2.3 ELECTRICAL SYSTEM
CAUTION
The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm, if ever an electrical problem develops. A green ground screw is supplied with the control box for that purpose.
The appliance must be installed in accordance with the current ANSI/NFPA 70 National Electrical Code, CSA C22.1 Canadian Electrical Code Part 1 and/or local codes.
The control system depends on the correct polarity of the power supply. Connect “HOT” wire (H) and “NEUTRAL” wire (N) as shown in Figures 6 and 7, p. 18 and 19.
A separate line voltage supply should be used, with fused disconnect switch or circuit breaker, between the main power panel and the unit.
Only copper wire may be used for the 115V circuit on this unit. If wires need to be changed, the replacements must have the same temperature resistance as the originals.
2.4 INSTALLATION OF THE THERMOSTAT
A thermostat must be installed to control the temperature of the area to be heated. Follow the instructions supplied with the thermostat. Also refer to the wiring diagrams provided with the heating/air conditioning unit. The connections must be made as indicated on the following diagrams and the wiring diagrams, p. 18 and 19.
Thermostat Wiring
Heating and Air Conditioning
Figure 4
with 4-speed motor
5
445 01 4101 00
Thermostat Wiring
Heating and Air Conditioning
with ECM variable speed motor
Thermostat Wiring
Heating and Air Conditioning/Heat pump
with ECM variable speed motor
Note: On units with 2 stage cooling or heat pump, terminal Y1 must be used. When Y1 on the electronic control receives a 24 VAC signal, the air flow is reduced by 20%. Do not use terminal Y1 with a single stage cooling or heat pump.
2.5 INSTALLATION OF THE BURNER
Refer to the burner manufacturer’s instructions. Also, the burner must be installed always in the same way independently of the furnace orientation.
1. Position the mounting gasket between the mounting flange and the burner mounting plate. Align the holes in the burner mounting plate with the studs on the mounting flange and bolt securely in place.
2. Remove the burner drawer assembly or the air tube assembly;
3. Install the nozzle (refer to Technical Specifications, p.14);
4. Check the electrode settings;
5. Make the electrical connections;
6. Complete oil line connections.
2.5.1 Nozzles
The burner comes equipped with an appropriate nozzle. However, if another size or a replacement nozzle is required, use the manufacturer’s recommended spray angle and type a shown in Table 1 and based on a pump pressure of 100 psi.
Always select nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking.
2.5.2 Air and Turbulator Settings
Before starting the burner for the first time, adjust the air and turbulator settings to those listed in this manual. Once the burner becomes operational, final adjustments will be required. Refer to section 3 of this manual.
2.5.3 Post purge delay adjustment
The post purge delay on the oil-fired burners is factory set to zero second. This delay is applicable for all installations with chimney venting. For heating units installed with side wall venting and a burner equipped with this feature, the post purge delay must be set to 15 seconds. Refer to the burner control instruction manual and markings for proper adjustment of the post purge delay.
2.6 VENTING
WARNING
Poisonous carbon monoxide gas, fire and explosion hazard.
Read and follow all instructions in this section. Failure to properly vent this furnace can result in in death, bodily injury and/or property damage.
To ensure the safe and proper functioning of an oil furnace, it must always be connected to a flue with sufficient draft or to an approved side-wall venting system. In addition, it is strongly recommended to perform a complete inspection of all the existing venting systems.
WARNING
Poisonous carbon monoxide gas hazard. Never install a hand operated damper in the vent pipe.
However, any Underwriters Laboratories listed, electrically operated automatic type vent damper may be installed if desired. Be sure to follow the instructions provided with vent damper. Also, read and follow all instructions in this section of the manual.
Failure to properly vent this furnace or other appliances can result in death, bodily injury and/or property damage.
6
445 01 4101 00
2.6.1 Masonry chimney
This furnace can be vented into an existing masonry chimney. However, the unit must not be vented into a chimney into which a solid fuel burning furnace is already being vented.
Before venting this furnace into a chimney, its condition must be checked and repairs made, if necessary. Also, the chimney lining and dimensions must conform to local and national codes.
2.6.2 Factory Built Chimneys
Oil fired furnaces are approved for use with “L” type vents. The unit may also be used with an approved chimney of proper dimensions and temperature ratings as specified in the installation code. Refer to chimney manufacturer’s instructions for proper installation.
2.6.3 Draft Regulator
This unit may be installed with or without a draft regulator. However, it is recommended that a draft regulator be installed in cases where the draft is either high or variable due to external conditions. Follow the instructions provided with the regulator.
2.6.4 Side-wall Venting
The heating unit is approved for side-wall venting. This system is comprised of a model VTK-098 / KLAVT0101DET side-wall venter and a 4” insulated vent pipe, model IFV098 / KLAFVxx01DET. Refer to the installation instructions provided with the venting system.
2.7 BLOCKED VENT SHUT-OFF DEVICE (BVSO) FOR CHIMNEY VENTING
CAUTION
It is imperative that this device be installed by a qualified service technician.
A positive pressure venting system (Sealed Combustion System or Direct Vent) MUST NOT use the BVSO. Follow the instructions supplied with the venting system.
This device is designed to detect the insufficient evacuation of combustion gases in the event of a vent blockage. In such a case the thermal switch will shut down the oil burner. The device will then need to be re-armed MANUALLY.
Refer to the detailed instructions and wiring diagrams supplied with the BVSO for the installation and wiring procedures. The length of wires supplied with the unit is such that the safety device must be installed between the flue outlet of the appliance and the draft regulator, as indicated in the instructions.
It is also essential that the BVSO be maintained annually. For more details refer to the instructions supplied with the device itself, as well as Section 3. of this Manual.
2.7.1 BVSO Performance Test
The purpose of the following test is to check that the electrical outlet on the furnace, designated to the BVSO, is functional.
7
1. Start up the burner;
2. Remove the three-pole plug from the BVSO outlet on the furnace;
3. The burner must shut-off immediately, while the blower continues to run to the end of the cool-down cycle.
If the test is not in line with the above, call a QUALIFIED SERVICE TECHNICIAN.
2.8 COMBUSTION AIR SUPPLY
VENTILATION
AND
WARNING
Poisonous carbon monoxide gas hazard. Comply with NFPA 31 (U.S.) and CSA B139 (Canada)
standards for the installation of Oil Burning Equipment and applicable provisions of local building codes to provide combustion and ventilation air.
Failure to provide adequate combustion and ventilation air can result in death, bodily injury and/or property damage.
Oil furnaces must have an adequate supply of combustion air. It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace. However, home improvements such as new windows, doors, and weather stripping have drastically reduced the volume of air infiltration into the home.
Refer to oil furnace installation codes relative to combustion and ventilation air requirements. Consult Section 2.2 in this manual, specifically for units installed in an enclosed space.
Home air exhausters are common. Bathroom and kitchen fans, power vented clothes dryers and water heaters all tend to create a negative pressure condition in the home. Should this occur the chimney becomes less and less effective and can easily downdraft. In certain cases, mechanically supplied air, by way of a blower, interlocked with the unit, is necessary. It is the installer’s responsibility to check that.
2.8.1 Contaminated Combustion Air
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the furnace. These conditions will require that only outside air be used for combustion.
The following areas or types of structures may contain or be exposed to certain substances, potentially requiring outside air for combustion:
a. Commercial buildings; b. Buildings with indoor pools; c. Furnaces installed near chemical storage areas.
Exposure to the following substances: a. Permanent wave chemicals for hair; b. Chlorinated waxes and cleaners; c. Chlorine based swimming pool chemicals; d. Water softening chemicals; e. De-icing salts or chemicals; f. Carbon tetrachloride;
Loading...
+ 16 hidden pages