ICP FLO115DABR-C, MBO115DABR-D, MBOV115DABR-D, LBO125DABR13-D, OLF140C12C DN, OLR182A16C, LBO145DABR34-D Installation Instruction And Care Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
OIL FIRED FURNACE
445 01 4054 06
UPFLOW
Models :
FLO115DABR-C
LBO125DABR13-D
LBO145DABR34-D
MBO115DABR-D
D
N
S
-
0
6
6
5
R
é
v
.
A
D
N
S
-
0
5
7
5
R
é
v.
A
D
N
S
-
0
59
4
R
é
v
.
A
INSTALLER / SERVICE TECHNICIAN:
USE THE INFORMATION IN THIS MANUAL FOR THE
INSTALLATION AND SERVICING OF THE UNIT. KEEP THE
DOCUMENT NEAR THE FURNACE FOR FUTURE
REFERENCE.
HOMEOWNER
:
PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR
FUTURE REFERENCE.
MBOV115DABR-D
OLF140C12C
OLR182A16C
Caution: Do not tamper with
the unit or its controls.
INSTALLATION OF OIL FIRED HEATING UNITS
SHALL BE IN STRICT ACCORDANCE WITH THE
REGULATIONS OF THE AUTHORITIES HAVING
JURISDICTION. IN CANADA CSA B139 AND IN THE
UNITED STATES NFPA NO.31-1992 INSTALLATION
CODES FOR OIL BURNING EQUIPMENT APPLY.
DO NOT OPERATE FURNACE IN A CORROSIVE
ATMOSPHERE CONTAINING CHLORINE, FLUORINE
OR ANY OTHER DAMAGING CHEMICALS.
DO NOT STORE OR USE GASOLINE, OR OTHER
FLAMMABLE VAPOURS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
1.1) SAFETY LABELING AND WARNING SIGNS
DANGER, WARNING AND CAUTION
The words DANGER, WARNING and CAUTION are used to identify
the levels of seriousness of certain hazards. It is important that you
understand their meaning. You will notice these words in the manual
as follows:
DANGER
Immediate hazards that WILL result in death or
serious damage to body and/or property.
WARNING
Hazards or unsafe practices that CAN result in
death or damage to body and/or property.
CAUTION
Hazards or unsafe practices which CAN result in
damage to body and/or property.
1.2) SAFE INSTALLATION REQUIREMENTS
WARNING
Installation or repairs performed by unqualified
persons can result in hazards to them and others.
Installation MUST conform to local codes or, in the
absence of same, to codes of the country having
jurisdiction.
The information contained in this manual is
intended for use by a qualified service technician
familiar with safety procedures and equipped with
the proper tools and test instruments.
Failure to carefully read and follow all instructions
in this manual can result in death and/or personal
injury, property damage, furnace malfunction.
WARNING
Fire hazard
The furnace must be installed in a level position,
never where it will slope toward the front. If the
furnace is installed in the latter position, oil will
drain into the furnace vestibule and create a fire
hazard.
NOTE: It is the personal responsibility and obligation of the
homeowner to contact a qualified technician to ensure that the
installation conforms to applicable local and/or national codes and
ordinances.
a. This furnace is NOT approved for installation in mobile homes,
trailers or recreational vehicles;
b. Do NOT use this furnace as a construction heater or to heat a
building under construction;
c. There must be a sufficient supply of fresh air for combustion as
well as ventilation in the area where the furnace is located;
d. Use only the Type of fuel oil approved for this furnace (see
Rating Plate on unit). Overfiring will result in heat exchanger
failure and cause dangerous operating conditions;
e. Visually check all oil line joints for signs of wetness, which would
indicate a leak;
f. Connect furnace to the chimney;
g. The points in Part 2 “Operation” are vital to the proper and safe
operation of the heating system. Take the time to ensure that all
steps were followed;
h. Follow the regulations of the ANSI/NFPA No.31 (in the USA) and
CSA B-139 (in Canada) or local codes for placing and installing
the oil storage tank;
3
445 01 4054 06
i. Follow a regular service and maintenance schedule for the most
efficient and safe operation of the furnace.
j. Before servicing, allow furnace to cool. Always shut off electricity
and fuel to the furnace when servicing. This will prevent electrical
shock or burns;
k. Seal supply and return air ducts;
l. The vent system MUST be checked to determine that it is the
correct type and size;
m. Install correct filter type and size;
n. Unit MUST be installed so that electrical components are
protected from direct contact with water.
1.2.1) Safety Rules
Your unit is built to provide many years of safe and dependable
service, providing it is properly installed and maintained. However,
abuse and/or improper use can shorten the life of the unit and create
hazards for you, the owner.
a. The U.S. Consumer Product Safety Commission recommends
that users of oil or gas-burning appliances install carbon
monoxide detectors. Carbon monoxide can cause serious injury
and/or death. Therefore, to help alert people of potentially
dangerous carbon monoxide levels, you should have carbon
monoxide detectors, listed by a nationally recognized agency
(e.g. Underwriters Laboratories or International Approval
Services) and maintained in the building or dwelling (see Note
below).
b. There can be numerous sources of fire or smoke in a building or
dwelling. Fire or smoke can cause death, serious bodily injury
and/or property damage. Therefore, in order to alert people of
potentially dangerous fire or smoke, you should have fire and
smoke detectors installed (listed by Underwriters Laboratories)
and maintained in the building or dwelling (see Note below).
NOTE: The manufacturer of your furnace does not test any detectors
and makes no representations regarding any brand or type of
detector.
CAUTION
Ensure that the area around the combustion air intake
terminal is free of snow, ice and debris.
CAUTION
Do not use any commercially available soot remover.
This furnace has a fibre type refractory combustion
chamber. Normal servicing of this unit does not require
cleaning of the combustion chamber. Use extreme care
if for any reason you have to work in the area of the
combustion chamber.
1.2.2) Freezing temperatures and your building
WARNING
Freezing temperature warning.
Turn off water supply.
If your heater remains shut off during cold weather
the water pipes could freeze and burst, resulting in
serious water damage.
Your unit is equipped with safety devices that may keep it from
operating if sensors detect abnormal conditions such as clogged
exhaust flues.
If the structure is unattended during cold weather you should take the
following precautions:
a. Turn off main water supply into the structure and drain the water
lines if possible. Open faucets in appropriate areas;
b. Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes from
freezing. Contact a qualified service agency, if required.
1.2.3) Installation regulations
All local and national code requirements governing the installation of
oil burning equipment, wiring and flue connections MUST be followed.
Some of the codes that may be applicable are:
CSA B139 Installation code for oil burning equipment
NFPA 31 Installation of oil burning equipment
ANSI/NFPA 90B Warm air heating and air conditioning systems
ANSI/NFPA 70 National electrical code
CSA C22.2 Nr. 3 Canadian electrical code
Only the latest issues of the above codes should be used.
1.3) POSITIONING THE FURNACE
CAUTION
Carefully check your furnace upon delivery for any
evidence of damage that may have occurred during
shipping and handling. Any claims for damages or lost
parts must be made with the Transport Company.
This furnace is approved for reduced clearances to combustible
construction. Therefore, it may be installed in a closet or similar
enclosure. In any case, the unit must always be installed level.
In a basement, or when installed on the floor (as in a crawlspace), it is
recommended that the unit be installed on a concrete pad that is
2.54 cm to 5.08 cm (1" to 2") thick.
The unit must be installed in a location where the ambient and return
air temperatures are above 15°C (60°F).
4
1.3.1) Installation of the filter rack
445 01 4054 06
When you install your furnace, the filter rack opening can be installed
on either side (right or left) for air filter maintenance.
DNS-0678 Rev. B
The required minimum clearanc es for this furnace are specified
in Table 1.
The furnace should be positioned as closely as possible to the
chimney to keep vent connections short and direct. It should also be
as close as possible to the centre of the air distribution system.
FIGURE 1
CAUTION
Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging
chemicals. Refer to Part 1, section 5.2 (1.5.2).
WARNING
Electrical shock hazard.
This furnace is not watertight and is not designed
for outdoor installation. This furnace shall be
installed in such a manner as to protect the
electrical components from water.
Outdoor installation will lead to a hazardous
electricalcondition, premature furnace failure,
property damage, injury or death.
1.4) VENTING
WARNING
Poisonous carbon monoxide gas, fire and
explosion hazard.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in
property damage, injury or death.
CAUTION
When the furnace is chimney vented together with other
combustion appliances such as a water heater, the
allowable venting materials for use with those
appliances must be investigated (“L”-Vent, etc.).
These oil furnaces are certified for use with "L" vent, "A" vent, tile-lined
and metal-liner-tile-lined chimneys. The appliance may be connected
to a chimney of proper size and adequate chimney base temperature,
as specified in the Installation Code. The relevant excerpt from the
code is found in this section. Use it as a guide when local or national
codes do not exist.
Flue pipe sizing
The following table is an excerpt from the installation code that
indicates permitted flue sizes and minimum base temperatures for
circular flues in chimneys with a thermal resistance of less than R6
2
•hr •°F / Btu).
(6 ft
Where a new appliance, burner, or chimney is installed, chimney vent
sizes and maximum flue-gas temperatures shall comply with Table 2,
p. 6. Measurements must be taken at the chimney connector, after 5
minutes of operation with the barometric damper shut.
WARNING
Poisonous carbon monoxide gas hazard.
Never install a hand operated damper in the vent
pipe. However, any Underwriters Laboratories listed
electrically operated automatic type vent damper
may be installed if desired. Be sure to follow the
instructions provided with vent damper. Also, read
and follow all instructions in this section of the
manual.
Failure to properly vent this furnace or other
appliances can result in death or personal injury,
property damage.
Furnace 2.54 cm (1") 2.54 cm (1")
Supply plenum within 6 ft of furnace 2.54 cm (1") 2.54 cm (1")
Furnace or plenum 2.54 cm (1") 5.08 cm (2")
Horizontal warm air duct within 6 ft of furnace 2.54 cm (1") 5.08 cm (2")
Horizontally or below flue pipe 22.86 cm (9") 22.86 cm (9")
Vertically above flue pipe 22.86 cm (9") 22.86 cm (9")
TABLE 1
5
NOTE: Thermal resistance values for typical chimneys are as
445 01 4054 06
follows:
2
•hr •°F / Btu): Clay-lined masonry, "A" vent
R2 (2 ft
2
R3 (3 ft
•hr •°F / Btu): Metal liner in clay-lined masonry
R6 (6 ft2 •hr •°F / Btu): Metal or clay-lined masonry with R4.5
Applying Table 2
If a furnace with a 0.60 USGPH nozzle is to be connected to a 6.1 m
(20') tall clay-lined masonry chimney, the thermal resistance of this
chimney type is R2, therefore, inferior to R6. The actual firing rate at
156 psig is 1.25 x 0.60 = 0.75. Therefore this table shall apply as
follows:
The minimum permitted inside diameter shall be 4";
The maximum permitted inside diameter shall be 5";
The minimum base temperature shall be about 160°C (320°F).
The vent should not end:
a) Directly above a sidewalk or mutual driveway;
b) Less than 2.1 m (7') above a paved driveway;
c) Less than 1.8 m (6') from a door, window or opening that
supplies air to the building;
d) Above a gas meter or regulator or less than 0.9 m (3') from the
centre of the regulator;
e) Less than 1.8 m (6') from any gas regulator vent exits or less
than 0.9 m (3') from an oil tank vent or oil fill inlet;
f) Less than 0.3 m (1') above ground level or less than 1.8 m (6')
from a combustion air inlet;
g) Less than 1.8 m (6') from a property line;
h) Under a veranda, porch or patio;
i) With the combustion gas being directed toward combustible
material or openings of a nearby building less than 1.8 m (6')
away;
j) Less than 0.9 m (3') from the interior corner of an "L" shaped
structure;
k) With the opening of the vent located less than 0.3 m (1') from any
surface that supports ice, snow or debris.
Total input rating of all
connected appliances
kW BTU/h USGPH Min. Max. 11' 20' 28' 36'
21 70,000 0.50 7.62 cm (3") 12.70 cm (5") 149°C (300°F) 204°C (400°F) 279°C (535°F) 385°C (725°F)
27 91,000 0.65 7.62 cm (3") 12.70 cm (5") 135°C (275°F) 171°C (340°F) 221°C (430°F) 279°C (535°F)
31 105,000 0.75 10.16 cm (4") 12.70 cm (5") 127°C (260°F) 160°C (320°F) 193°C (380°F) 246°C (475°F)
36 119,000 0.85 10.16 cm (4") 12.70 cm (5") 121°C (250°F) 149°C (300°F) 179°C (355°F) 221°C (430°F)
41 140,000 1.00 10.16 cm (4") 15.24 cm (6") 107°C (225°F) 149°C (300°F) 185°C (365°F) 221°C (430°F)
51 175,000 1.25 10.16 cm (4") 15.24 cm (6") 116°C (240°F) 135°C (275°F) 160°C (320°F) 185°C (365°F)
2
•hr •°F / Btu) insulation between
(4.5 ft
liner and masonry (e.g. 2" of expanded
mica or 1 ⅜" of high density glass
fibreboard.)
Inside diameter of flue Minimum base temperature for chimney height
TABLE 2
1.5) AIR FOR COMBUSTION
WARNING
Poisonous carbon monoxide gas hazard.
Comply with ANSI/NFPA (in the U.S.A.) or CSA (in
Canada) standards for the installation of Oil
Burning Equipment and applicable provisions of
local building codes to provide combustion and
ventilation air.
Failure to provide adequate combustion and
ventilation air can result in death and/or personal
injury.
1.5.1) General
Oil furnaces must have an adequate supply of combustion air. It is
common practice to assume that older homes have sufficient
infiltration to accommodate the combustion air requirement for the
furnace. However, home improvements such as new windows,
and weather stripping have drastically reduced the volume of air
infiltration into the home.
Home air exhausters are common. Bathroom and kitchen fans, power
vented clothes dryers, and water heaters all tend to create negative
pressure in the home. Should this occur, the chimney becomes less
and less effective and can easily downdraft.
Heat Recovery Ventilation (HRV) systems are gaining in popularity.
HRVs are not designed to supply combustion air. If not properly
balanced, a serious negative pressure condition could develop in the
dwelling.
1.5.2) Contaminated Combustion Air
Installation in certain areas or types of structures will increase the
exposure to chemicals or halogens which may harm the furnace.
These instances will require that only outside air be used for
combustion.
The following areas or types of structures may contain or have
exposure to the substances listed below. The installation must be
carefully evaluated, as it may be necessary to provide outside air for
combustion.
a. Commercial buildings;
b. Buildings with indoor pools;
c. Furnaces installed near chemical storage areas.
doors,
6
Exposure to these substances:
445 01 4054 06
a. Permanent wave chemicals for hair;
b. Chlorinated waxes and cleaners;
c. Chlorine based swimming pool chemicals;
d. Water softening chemicals;
e. De-icing salts or chemicals;
f. Carbon tetrachloride;
g. Halogen type refrigerants;
h. Cleaning solvents (such as perchloroethylene);
i. Printing inks, paint removers, varnishes, etc.;
j. Hydrochloric acid;
k. Solvent based glue;
l. Antistatic fabric softeners for clothes dryers;
m. Acid based masonry cleaning materials.
1.5.3) Ducted outdoor combustion air
Outdoor combustion air kit – chimney venting
The following kits have been certified for use with the appliance. The
component kits contain an important safety feature, namely a Vacuum
Relief Valve or VRV. During normal operation the burner aspirates
outdoor air. If the intake terminal ever becomes partially or fully
blocked from ice or snow etc., the VRV will open to allow a proportion
of air from the dwelling to enter the burner, thus maintaining proper
combustion. Once the blockage is removed, the VRV will close and
the burner will draw all the air from the outside again:
CAS-2B
Components for the Beckett AFG burner (except air duct): The kit
includes the intake terminal, vacuum relief valve (VRV) and
boot connection with integral air adjustment means for the
burner. The CAS-2B can be used with a 10 cm (4") galvanized air duct
or a 10 cm (4") flexible aluminium air duct. It is recommended that the
metallic air ducting material be insulated from the air intake up to
1.5 m (5') from the burner to avoid condensation from forming on the
outside of the intake pipe.
CAD-1
Air duct kit consists of 7.6 m (25') of insulated UL/ULC Listed Class 1
air duct, and two 10 cm (4") steel band clamps. The duct incorporates
a corrugated flexible aluminium core, surrounded by fibreglass
insulation covered with a vinyl vapour barrier.
special air
AFG
CAUTION
The CAS-2B does not turn the furnace installation into a
direct vent system. Therefore the building structure
must provide for adequate combustion air to be
delivered to the Vacuum Relief Valve. The burner will
need to draw combustion air from the VRV’s
surroundings if the intake ever becomes blocked.
Therefore, non-direct vent installation codes must be
followed.
Comprehensive installation instructions are provided with the kits.
1.6) OIL TANKS AND LINES
Check your local codes for the installation of the tank and accessories.
A manual shut-off valve and an oil filter shall be installed in sequence
from tank to burner. Be sure that the oil line is clean before connecting
to the burner. The oil line should be protected to eliminate any
possible damage. Installations where the fuel oil tank is below the
burner level must employ a two pipe fuel supply system with an
appropriate fuel pump. A rise of more than 2.4 m (8') requires a 2
stage pump and more than 4.9 m (16') an auxiliary pump.
Follow the pump instructions to determine the size of tubing you need
in relation to the rise, or to the horizontal distance.
Inspect the entire oil distribution system for leaks at the beginning of
each annual heating season.
1.7) BURNER INSTALLATION
DNS-0830 REV. B
Installing the burner
a. Verify tube insertion dimensions in the Technical Specification
b. The warm air furnace burner mounting plate has a 4-bolt
c. Position the mounting gasket between the mounting flange and
After the burner is mounted
a. Remove drawer assembly;
b. Install nozzle (see specifications);
c. Check electrode settings;
d. Make the electrical connections;
e. Complete oil line connections.
Ceramic sleeve installa tion (R iello burn er only )
Tables 3.1 to 3.4, p. 15 to 18.
configuration;
the appliance burner mounting plate. Line up the holes in the
mounting flange with the studs on the appliance mounting plate
and securely bolt in place.
FIGURE 2
CAUTION
Do not turn on the burner until you have checked the
polarity.
7
Checking the polarity
445 01 4054 06
The oil burners used on the furnaces have solid state control systems
that make them sensitive to the proper connections of the hot and
neutral power lines. The controls will be damaged if the two lines are
reversed.
1. Set your voltmeter to line voltage;
2. Place one prong on your grounded electric entry box and one
prong on the black wire;
3. Read the voltage;
4. If the voltage is zero, check the white wire. If line voltage shows.
Reverse the 115-volt leads entering the furnace junction box;
5. If you do not have a voltmeter, use a pilot light.
DNS-0864 Rev. A
Checking the Nozzle
The burner is equipped with the appropriate nozzle. However, if
another size or a replacement nozzle is required, use the
manufacturer’s recommended spray angle and type as shown in
Tables 3.1 to 3.4, p. 15 to 18. Note that all nozzle sizes are based on
a pump pressure of 100 psi.
Always select nozzle sizes by working back from the desired flow rate
at operating pressure, and not the nozzle marking.
Checking air and turbulator settings
Before starting the burner for the first time, adjust the air and turbulator
settings to those listed in the Tables 3.1 to 3.4, p. 15 to 18. Once the
burner becomes operational, final adjustment will be necessary.
Checking the fuel supply system
Fuel Specifications
NOTE: Use No.1 or No. 2 Heating Oil (ASTM D396) or in Canada
use No.1 or No. 2 Furnace Oil.
Before starting the burner, be sure that the fuel tank is filled with clean
oil.
FIGURE 2.1
IMPORTANT
When using nozzle sizes of less than 0.75 USGPH, the
Installation Code for oil burning equipment requires the
installation of a 10 micron (or finer) filter in the fuel oil
line. ICP requires that this practice be followed in order
to keep the lifetime heat exchanger warranty intact.
WARNING
Fire and explosion hazard.
Use only approved heating type oil in this furnace.
DO NOT USE waste oil, used motor oil, gasoline or
kerosene.
Use of these will result in property damage injury or
death.
NOTE: You may notice a slight odour the first time your furnace is
operated. This will soon disappear. It is only the oil used on certain
parts during manufacturing.
1.8) BLOCKED VENT SHUT-OFF (BVSO)
For chimney venting
WARNING
It is imperative that this device be installed by a
qualified agency.
This device is designed to detect the insufficient evacuation of
combustion gases in the event of a vent blockage. In such a case the
thermal switch will shut down the oil burner.
to be restarted MANUALLY.
The device will then need
Refer to the wiring diagrams and the detailed instructions supplied
with the BVSO for the installation and wiring procedures. The length of
wires supplied with the unit is such that the safety device must be
installed between the flue outlet of the appliance and the draft
regulator, as indicated in the instructions.
It is further imperative that the BVSO be
more details refer to the instructions supplied with the device itself, as
well as Section 3 of this Manual.
maintained annually. For
CAUTION
A positive pressure venting system (Sealed Combustion
System or Direct Vent) MUST NOT use the BVSO. Follow the
instructions supplied with the venting system.
1.9) INSTALLING ACCESSORIES
WARNING
Electrical shock hazard.
Turn OFF electric power at fuse box or service
panel before making any electrical connections and
ensure a proper ground connection is made before
connecting line voltage.
Failure to do so could result in bodily injury or
death, property damage.
8
1.9.1) Air conditioning
445 01 4054 06
An air conditioning coil may be installed on the
Also, notwithstanding the evaporator coil manufacturer’s instructions,
a minimum clearance of 15 cm (6") must be allowed between the
bottom of the coil drain pan, and the top of the heat exchanger. Wire
the thermostat and condensing unit contactor as indicated in the wiring
diagram in Figure 5, p. 21.
supply air side only.
1.9.2) Ductwork and Filter
Installation
Design and install the air distribution system to comply with Air
Conditioning Contractors of America manuals or other approved
methods that conform to local codes and good trade practices.
When ducting supplies air to a space other than where the furnace is
located, the return-air ducts must be sealed and also be directed to
the space other than where the furnace is located.
Install the air conditioning cooling coil (evaporator) downstream from
the supply air plenum of the furnace. If a separate evaporator and
blower unit is used, install appropriate sealing dampers for air flow
control. Cold air from the evaporator coil going through the furnace
could cause condensation and shorten furnace life.
CAUTION
Dampers (purchased locally) MUST be automatic.
WARNING
Poisonous carbon monoxide gas hazard.
Do NOT draw return air from inside a closet or
utility room. Return air duct MUST be sealed to
furnace casing.
Failure to properly seal ducts can result in death,
personal injury and/or property damage.
WARNING
Poisonous carbon monoxide gas hazard.
Install evaporator coil on the supply side of the
furnace ducting.
Evaporator coil installed in return side ducting can
cause condensation to form inside heat exchanger
resulting in heat exchanger failure. This could result
in death, personal injury and/or property damage.
9
OPERATION
445 01 4054 06
2.1) SEQUENCE OF OPERATION
2.1.1) Sequence of operation
1. Normally open contact (T-T) on primary relay closed when
2.
3.
4. Spark ignites oil droplets;
5. Cad cell senses flame and burner continues to fire. Ignition
6. After Fan-Limit control heats up to the factory set point, the
7. The circulating air blower and burner motor remain on until the
9. The Fan-Limit control bi-metal cools down to the factory set point
2.2) CHECKS AND ADJUSTMENTS
2.2.1) General
After initial installation and subsequent yearly maintenance calls, the
furnace must be thoroughly tested.
The burner must be functioning for at least 10 minutes
before any test readings are taken. Adjustments are to
be made according to the Technical Specifications in
this manual.
Open the oil bleed port screw and start the burner. Allow the oil to
drain into a container for at least 10 seconds. Once the oil flows
absolutely free of white streaks or air bubbles to indicate that no air is
being drawn into the suction side of the oil piping and pump, slowly
close and tighten the bleed screw. The burner should now fire. Adjust
the oil pressure as indicated in the Technical Specification Tables 3.1
to 3.4, p. 15 to 18.
2.2.2) Restart after burner failure
1. Set thermostat lower than the room temperature;
2. Press the reset button on the burner primary control (relay);
3. Set thermostat higher than the room temperature;
4. If the burner motor does not start or ignition fails, turn off the
Beckett AFG, Riello 40-F and Aero F-FAC
thermostat calls for heat;
AFG and F-FAC burner: The motor starts and spark is
established. The pump pressure builds and the oil supply
mechanism opens, admitting fuel to the nozzle;
R40-F Burner: The burner motor starts. The burner motor fan
pre-purges the combustion chamber and vent for 10 seconds,
establishing the combustion air pattern. During this time the
solenoid valve holding coil pressure is approximately 100 psig.
The solenoid valve opens, allowing oil to flow through the nozzle.
At the same time, the burner motor ignition coil produces a spark;
transformer ceases sparking (Riello R40-F);
circulating air blower and electronic air cleaner start;
thermostat is satisfied. The ignition transformer continues to
spark (AFG). The solenoid valve remains open (R40-F);
burner fan motor shuts down. The ignition transformer ceases
sparking (AFG);
of 32°C (90°F), the circulating air blower and the electronic air
cleaner turn off.
IMPORTANT
disconnect switch and CALL A QUALIFIED SERVICE
TECHNICIAN.
PART 2
CAUTION
Do not attempt to start the burner when excess oil has
accumulated, when the furnace is full of vapour, or
when the combustion chamber is very hot.
2.2.3) BVSO Performance Test
The purpose of the following test is to check that the electrical outlet
on the furnace, designated to the BVSO, is functional.
1. Start up the burner;
2. Remove the three-pole plug from the BVSO outlet on the
furnace;
3. The burner must shut-off immediately, while the blower continues
to run to the end of the cool-down cycle.
If the test is not in line with the above,CALL A QUALIFIED SERVICE
TECHNICIAN.
2.2.4) Combustion chamber curing
Some moisture and binders remain in the ceramic combustion
chamber after manufacture. It is important to clear the chamber of this
residue before testing. If you smoke test before curing, the instrument
may become damaged. To cure the chamber, run the unit for 3
consecutive cycles, with 3 minutes of elapsed time in between each
cycle. Each burn cycle should least 3 minutes. The exhaust will have a
pungent odour and produce a white cloud of steam.
2.2.5) Smoke / CO2 test
1. Pierce a test hole in the smoke pipe near the furnace breech.
Insert the smoke test instrument probe into the open hole;
2. Starting with a zero smoke reading, gradually reduce the burner
air setting until just a trace of smoke results (#1 on Bacharach
Scale);
3. Take a CO
sample was taken. Note the CO
smoke condition;
4. Adjust the burner air setting to obtain a CO
than the reading associated with the #1 smoke;
5. This method of adjusting the CO
to ensure that the burner will burn clean for the entire heating
season.
sample at the same test location where the smoke
2
reading associated with the #1
2
reading 1% lower
2
will allow adequate excess air
2
2.2.6) Supply air temperature rise test
1. Operate the burner for at least 10 minutes;
2. Measure the air temperature in the return air plenum;
3. Measure the air temperature in the largest trunk coming off the
supply air plenum, just outside the range of radiant heat coming
off the heat exchanger; 0.3 m (12") from the plenum on the main
take-off usually sufficient;
4. The temperature rise is calculated by subtracting the return air
temperature from the supply air temperature;
5. If the temperature rise exceeds the temperature specified in
Tables 3.1 to 3.4, p. 15 to 18, change to the next higher blower
speed tap until the temperature rise falls to this temperature or
below. If the excessive temperature rise cannot be reduced by
increasing fan speed, investigate for ductwork restriction(s), dirty
or improper air filter, overfiring caused by excessive pump
pressure, or improper nozzle sizing.
10
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.