ICP OCF105A12C Installation Instructions And Service Manual

OIL FIRED FURNACE
445 01 4024 05
DOWNFLOW or HORIZONTAL
Model:
OCF105A12C
D
N
S
-
0
58
8
R
ev
.
B
INSTALLER / SERVICE TECHNICIAN: USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION / SERVICING OF THE UNIT AND KEEP THE DOCUMENT NEAR THE FURNACE FOR FUTURE REFERENCE.
HOMEOWNER: PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE.
Printed in Canada Printed on 100% recycled paper
Caution: Do not tamper with the unit or its controls. Call a qualified service technician.
Manufactured by: UTC Canada Corporation
ICP DIVISION
3400 Industrial Boulevard Sherbrooke, Quebec - Canada J1L 1V8
2008/12/02 X40084 Rev. K
PART 1
445 01 4024 05
INSTALLATION
SAFETY CONSIDERATIONS
INSTALLATION OF OIL FIRED HEATING UNITS SHALL BE IN STRICT ACCORDANCE WITH THE REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION. IN CANADA, CSA B139 AND IN THE UNITED STATES, NFPA NO.31-1992 INSTALLATION CODES FOR OIL BURNING EQUIPMENT APPLY.
DO NOT OPERATE FURNACE IN A CORROSIVE ATMOSPHERE CONTAINING CHLORINE, FLUORINE OR ANY OTHER DAMAGING CHEMICALS.
DO NOT STORE OR USE GASOLINE, OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
1.1) SAFETY LABELLING AND WARNING SIGNS
DANGER, WARNING AND CAUTION
The words DANGER, WARNING and CAUTION are used to identify the levels of seriousness of certain hazards. It is important that you understand their meaning. You will notice these words in the manual as follows:
DANGER
Immediate hazards which WILL result in death or serious injury.
WARNING
Hazards or unsafe practices which CAN result in death or injury.
CAUTION
Hazards or unsafe practices which CAN result in personal injury or product or property damage.
1.2) SAFE INSTALLATION REQUIREMENTS
WARNING
Installation or repairs performed by unqualified persons can result in hazards to them and others. Installation MUST conform to local codes or, in the absence of same, to codes of the country having jurisdiction.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in personal injury and/o r death, property damage, furnace malfunction.
WARNING
Fire hazard. The furnace must be installed in a level position;
never where it will slope toward the front. If the furnace is installed in that position, oil will
drain into the furnace vestibule and create a fire hazard, instead of being directed into the combustion chamber.
NOTE: It is the personal responsibility and obligation of the customer
to contact a qualified installer to ensure tha t the installation conforms to governing local and/or national codes and ordinances.
a. This furnace is NOT approved for installation in mobile homes,
trailers or recreational vehicles;
b. Do NOT use this furnace as a construction he ater or to heat a
building under construction;
c. There must be a sufficient suppl y of fresh air for combustion as
well as ventilation in the area where the furnace is located;
d. Use only the type of fuel oil approved for this furnace (see Rating
Plate on unit). Overfiring will result in heat exchanger failure and
cause dangerous operat ing con di tio ns; e. Visually check all oil line joints for signs of leakage; f. Connect furnace to a side-wall terminal or chimney; g. The points in Part 2 “Oper ation” are vital to the proper and safe
operation of the heating system. Tak e the time to ensure that all
steps were followed; h. Follow the regulations of the ANSI / NFPA No.31 (USA) and
B-139 (Canada) or local codes for placing and installing the oil
storage tank; i. Follow a regular service and maintenance schedule for efficient
and safe operation;
3
445 01 4024 05
j. Before servicing, allow furnace to cool down. Always shut off
electricity and fuel to furnace when servicing. This will prevent
electrical shock or burns; k. Seal supply and return air ducts; l. The vent s ystem MUST be checked to determine that it is the
correct type and size; m. Install correct filter ty pe and size; n. Unit MUST be installed so that electrical components are
protected from direct contact with water.
1.2.1) Safety Rules
Your unit is built to provide many years of safe and dependable service, provided it is properly installed and maintained. However, abuse and/or improper use can s horten the life of the unit and create hazards for you, the owner.
a. The U.S. Consumer Product Safety Commission recommends
that users of oil-burning appliances install carbon monoxide
detectors. There can be various sources of carbon monoxide in a
building or dwelling. The sources could be gas-fired clothes
dryers, gas cooking stoves, water heaters, furnaces, gas-fired
fireplaces, wood fireplaces, and several other items. Carbon
monoxide can cause serious bodily injury and/or death.
Therefore, to help alert people to pot entially dangerous carbon
monoxide levels, you should have carbon monoxide detectors
listed by a nationally recognised agency (ex. Underwriters
Laboratories or International Approval Services) installed and
maintained in the building or dwelling (see Note below). b. There can be numerous sources of fire or smoke in a buil ding or
dwelling. Fire or smoke can cause serious bodily injury, death,
and/or property damage. Therefore, in order to alert people to
potentially dangerous fire or smoke conditions, you should have
Underwriters Laboratories listed fire and smoke detectors
installed and maintained in the building or dwelling (see Note
below).
NOTE: The manufacturer of your furnace does not test detectors and makes no representations regarding any brand or type of detector.
CAUTION
Ensure that the area around the combustion air intake terminal is free of snow, ice and debris.
CAUTION
An air pressure switch MUST be used when the furnace is side-wall vented.
CAUTION
Do not use any commercially available soot remover. This furnace has a ceramic fibre type of combustion chamber. Normal servicing of this unit does not require the cleaning of same. Use extreme caution if for any reason you have to work in the area of the combustion chamber.
1.2.2) Freezing Temperatures and Your Structure
WARNING
Freezing temperature warning. Turn off water supply. If your heater remains shut off during cold weather,
the water pipes could freeze and burst, resulting in serious water damage.
Your unit is equipped with safety devices that may keep it from operating if sensors detect abnormal conditions such as clogged exhaust flues.
If the structure is unattended durin g cold weather you sh ould take the following precautions:
a. Tu rn off main water suppl y into the structure a nd drain the water
lines if possible. Open faucets in appropriate areas;
b. Have someone check the structure frequently during cold
weather to make sure it is warm enoug h to prevent pipes from freezing. Contact a qualified service agency, if required.
1.2.3) Installation regulations
All local and national code requirements governing the installation of oil burning equipment, wiring and flue connections MUST be follo wed. Some of the codes that may be applicable are:
CSA B139 INSTALLATION CODE FOR OIL
BURNING EQUIPMENT
NFPA 31 INSTALLATION OF OIL B URN ING
EQUIPMENT
ANSI/NFPA 90B WARM AIR HEATING AND AIR
CONDITIONING SYSTEMS ANSI/NFPA 70 NATIONAL ELECTRICAL CODE CSA C22.1 CANADIAN ELECTRICAL CO DE
Only the latest issues of the above codes should be used.
1.3) POSITIONING THE FURNACE
CAUTION
Carefully check your furnace upon delivery for any evidence of damage that may have occurred during shipping and handling. Any claims for damages or lost parts must be made with the Transport Company.
4
Minimum Installation clearances from combustible materials (Chimney installation*)
445 01 4024 05
LOCATION APPLICATION OCF105 AND ODH53
Sides Back Furnace 25.4 mm (1”)
Top Furnace casing or plenum 25.4 mm (1”) 0.6 m (24”) Bottom Furnace – combustible floor ** 0” ** Front Furnace 0.6 m (24”)
* See Part 1 Section 4.3 for Direct Vent application clearances. ** Combustible floor requires accessory bases CFB-1 or HFB-1.
Furnace 25.4 mm (1”) Supply plenum, warm air duct within 6 ft of furnace 25.4 mm (1”)
1.3.1) Location
Position the furnace as closely as possible to the chimney or vent terminal, providing ample clearance to permit easy accessibility for cleaning the inside of the furnace, the removal of filters, blower, motors, controls and flue connections.
This furnace is approved for reduced clearances to combustibles. Therefore, it may be installed in an alcove, closet, or crawl space. Clearances indicated on the rating plate must be respected.
In the downflow position, this furnace is approved for installation on combustible floors only when the accessory No C FB-1 "Combustible Floor Base" is used.
In the horizontal position (air left or right), this furnace is approved for installation on combustible floors only when the accessory No. HFB-1 "Horizontal Floor Base" is used.
In the horizontal position (air left or right), this furnace may be suspended using an angle iron frame with threaded rod hangers. Appropriate calculations, considering the weight of the furnace and the frame must be made.
However, do not install furnac e dir ectly on carp et o r othe r c ombus tibl e material, which can trap air under the floor.
The furnace must be installed level for safe and quiet operation.
CAUTION
Do NOT operate the furnace in a corrosive a tmosphere containing chlorine, fluorine or any other damaging chemicals. Refer to Part 1, section 5.2.
1.4) VENTING
1.4.1) General
The furnaces can be vented in several ways:
Chimney Vented
Using the Beckett AFG or Riello 40-F burner, the furnaces can be chimney vented with or without a barometric damper. The unit will operate at a negative overfire draft and flue dra ft.
TABLE 1
RECOMMENDED ACCESS
FOR SERVICE
WARNING
Poisonous carbon monoxide gas, fire and explosion hazard.
Read and follow all instructions in this section. Failure to properly vent this furnace can cause
bodily injury or death, property damage.
Side-wall Vented
Using the Beckett AFII or Riello 40-BF burner with the integral pre­and post-purge controls, the system can be side-wall vented with the new DV-2000™ venting system f or maximum efficiency and without the use of a side-wall power vent. The unit will operate at a positive overfire draft and flue draft.
WARNING
Poisonous carbon monoxide gas hazard. Never vent this furnace together with another
combustion appliance when side-wall venting. To do so may result in asphyxiation and death to
the occupants
1.4.2) Chimney installations
When set up for chimney venting, this furnace is certified for use with an L-vent, A-vent, tile-lined and metal-lin er-tile lined chimn ey, and can be vented both with and without a barometric draft damper. However, this furnace is not approved for use without a barometric damper if it is to be vented together with another oil-fired appli ance such as a water heater.
With barometric damper
This furnace may be vented into a chimney of suitable size and adequate chimney base temperatur e, as specified in the Installation Code. When a barometric damper is used, the ba sement air entering the damper reduces the possibility of vent condensation. The relevant excerpt from the code is found in this section and can be used as a guide where local or national codes do not exist. One option, to increase the chimney base temperature, is to use vent connection insulation.
5
Without barometric damper
445 01 4024 05
Due to the lack of dilution air that would ordinarily be drawn into the barometric damper, the dew point of the flue g ases is raise d. To offs et the increased tendency for vent condensation , the chimney must be lined. The liner must be insulated according to the insulating procedure recommended by the manuf acturer of the liner. Also, the vent connector should be as short as p ossible an d eithe r be of do uble wall construction or of single wall construction with 25.4 mm (1") of insulation.
WARNING
Poisonous carbon monoxide gas hazard. Never install a hand operated damper in the vent
pipe. However, any Underwriters Laboratories listed electrically operated automatic type vent damper may be installed if desired. Be sure to follow instructions provided with vent damper. Read and follow all instructions in this section.
Failure to properly vent this furnace or other appliances can result in personal injury and/or death, property damage.
CAUTION
When the furnace (chimney installation) is vented together with other combustion appliances such as a water heater, the allowable venting materials (L-Vent, etc.) for use with those appliances must be investigated.
Flue pipe sizing
The following table is an excerpt from the Installation Code and indicates the permitted flue sizes and minimum base temperat ures for circular flues in chimneys with thermal resistance of less than R6 (6 ft
hr •°F / Btu). Where a new appliance, burner, or chimney is installed, chimney vent sizes and maximum flue ga s te mp erat ur e s (me a sur ed at the chimney connector with the barometric damper shut, after 5 minutes of operation) shall comply with Table 2.
Note: Thermal resistance values for typical chimneys are as follows:
Total input rating of all
connected appliances
kW Btu/h USGPH Min. Max. 11' 20' 28' 36'
21 70,000 0.50 76.2 mm (3") 0.13 m (5") 149°C / 300°F 204°C / 400°F 279°C / 535°F 385°C / 725°F 27 91,000 0.65 76.2 mm (3") 0.13 m (5") 135°C / 275°F 171°C / 340°F 221°C / 430°F 279°C / 535°F 31 105,000 0.75 0.1 m (4") 0.13 m (5") 127°C / 260°F 160°C / 320°F 193°C / 380°F 246°C / 475°F 36 119,000 0.85 0.1 m (4") 0.13 m (5") 121°C / 250°F 149°C / 300°F 179°C / 355°F 221°C / 430°F 41 140,000 1.00 0.1 m (4") 0.15 m (6") 107°C / 225°F 149°C / 300°F 185°C / 365°F 221°C / 430°F 51 175,000 1.25 0.1 m (4") 0.15 m (6") 116°C / 240°F 135°C / 275°F 160°C / 320°F 185°C / 365°F
Flue inside diameter
2
TABLE 2
R2 (2 ft2 hr •°F / Btu): Clay-lined masonry, A-vent
2
hr •°F / Btu): Metal liner in clay-lined Masonry
R3 (3 ft
2
R6 (6 ft
hr •°F / Btu): Metal or clay-lined masonry with R4.5 (4.5
Applying Table 2
If a furnace with a 0.60 USGPH nozzle is to be connected to a 20 foot tall clay-lined masonry chimney, the thermal resistance of this type of chimney is R2, (which is less than R6). The actual firing rate at 156 psig is 1.25 x .60 = .75. Therefore this table shall apply as follows:
The minimum size permitted shall be 101.6 mm (4") inside diameter; The maximum size permitted shall be 127.0 mm (5") inside diameter; The minimum base temperatur e sha ll be abou t 160°C (320°F).
2
hr •°F / Btu) insulation between liner
ft and masonry (e.g. 2" of expanded mica or 1 3/8" of high density glass fibreboard.)
1.4.3) Side-wall venting - DV-2000™
Direct Vent System
The furnace can be side-wall vented without the use of a side-wall power vent, using the new DV-2 000™ venting system with the high static pressure Beckett AFII and Riello 40-BF oil burners. Outdoor
combustion air must be directly conn ected to the burner or the DV-2000™ venting system will not function.
The notable characteristics of the DV-2000™ system are as follows: a) Certi fied to use the following materials for d ucting the intake air
from the terminal to the burner: Schedule 40 PVC DWV, Schedule 40 ABS DWV, and ASTM 2729 sewer Pipe;
b) One hole of minimal size (152.4 mm
into the side-wall, and the terminal is designe d to fit through a minimum 2 X 8 joist space;
c)
Incorporates a vent blockage safety shutdown system. If the vent or intake opening ever becomes partially or fully blocked, the burner will shut down before a #1 smoke
d) The intake and vent circuits within the te rminal can be accessed
for cleaning.
There are 3 main components to the DV-2000™ system: the VTK vent terminal kit, the IFV insulated flexible venting material and the field-supplied 3 inch PVC or ABS intake piping.
Minimum base temperature
for chimney height of:
ø
/ 6"ø) is required to be cut
condition occurs;
6
DV-2000™ – Vent terminal kits
445 01 4024 05
The certified standard vent termi nal kit is Mod el No. VTK-1 for models ODH5-F and OCF105A12B and is suitable for installation in walls up to 0.3 m (14") thick. Both kits contain the following items to complete the hook-up to the venting and furnace:
Qty Description
1 Terminal 2 Sealing clamps 1 Side-wall venting breach plate 2 Sealing strips 1 Inner wall plate 1 Pressure control with tubing 2 Insulated quick-connect terminals 3 Stainless steel screws 6 Self tapping stainless steel screws
Insulated flexible venting - DV-2000™
The certified venting materials come in 3 l engths, Model No. IFV 3-15, IFV3-23 and IFV3-30 and correspond t o 4.6 m, 7.0 m, and 9 .1 m (15', 23' and 30') of continuous lengths of ve nt. The vent construction is coaxial and incorporates a stainless steel corrugated flexible liner surrounded by a thick blanket of insulation and covered with an o uter layer of flexible corrugated aluminium sle eve to protect the insulation . Splicing vent lengths together is prohibited. The minimum and maximum continuous vent lengths permitted for installation are:
1.5 m (5') minimum 9.1 m (30') maximum
WARNING
Poisonous carbon monoxide gas hazard Even though the flexible venting is insulated, it
must not be run through an unheated space. To do so can cause residual condensation inside
the stainless steel liner, which may eventually perforate the liner and allow vent gasses to enter the dwelling. This can result in death, personal injury and/or property damage.
Side-wall venting clearances to combustibles
PORTION OF VENT CLEARANCES
Vent pipe, up to vent terminal* 76.2 mm (3”) Vent terminal ZERO
*Do not enclose venting
Installation considerations - DV-2000
Select a location for the vent terminal i n accordance with all local and national codes. The following requ irements shall be considered to be minimum requirements that can be overridden by stricter local and national codes.
TABLE 3
TM
-
DNS-0623 Rev. A
The vent shall not terminate
a. Directly above a paved sidewalk or paved driveway that is
located between two buildings, and that serves both buildings; b. Less than 2.1 m (7') above any paved driveway; c. Within 1.8 m (6') (in Canada ) of a windo w or door, or mech anical
air supply inlet to any building, including soffit openings;* d. Within 1.8 m (6') (in Canada) from the soffit of the roof of the
structure;* e. Above a gas meter/regulator assembly within 0.9 m (3') of a
vertical centreline of the regulator; f. Within 1.8 m (6') of any gas service regulator vent outlet, or within
0.9 m (3') of an oil tank vent, or an oil fill inlet; g. Within less than 0.3 m (1') above grade level; h. Within 1.8 m (6') of any other combustion air inlet; i. Within 1.8 m (6') of a property line; j. Underneath a veranda, porch or deck; k. So that the flue gases are directed at combustible material or any
openings of surrounding buildings that are within 1.8 m (6');
l. Less than 0.9 m (3') from an inside corner of an L-shaped
structure;
m. So that the bottom of the vent termination opening is less than
0.3 m (1') above any surface that may support ice, snow, or
debris;
n. So t hat the flue gases are directed toward brickwork , siding or
other construction, in such a manner that may cause damage from heat or condensation from flue gases.
For installations in the U.S.A. refer to Sectio n 6.7.3.4 of t he NFPA
31.
FIGURE 1
CAUTION
Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances, even if all other code requirements as to construction and location have been complied with. The installer is ultimately responsible to do whatever is necessary to ensure that flue gasses do not enter the dwelling.
7
Side wall venting installation - DV-2000™
445 01 4024 05
WARNING
Cuts and abrasion hazard. Always wear protective gloves and eye protection
when handling the vent material. The process of cutting and fitting the flexible
venting material exposes the installer to sharp edges that could cause severe cuts to the skin.
Connection to the furnace breach - DV-2000™
1. Remove the standard breach plate by removin g the brass nu ts;
2. Determine which direction the venting will be routed from the furnace and then install the special side-wall venting breach plate provided in the VTK Series vent kit so that the breach plate test port will be accessible after vent installation. However, do not install the breach plate with the test port pointing downward. Tighten the brass nuts;
3. The flexible venting h as 4 pieces of corrugated spin sleeve that has been temporarily screwed on over top of it . Remove t he spin sleeve completely by unscrewing it in a counter-clockwise direction;
4. Using tin snips, cut t he aluminium outer sleeve back by 127.0 mm (5") on the IFV Series vent (see Figure 1.1). Ensure the snips are well adjusted and sharp or th e cut end of the venting will be too jagged to start the threads of the spin sleeve (see Figure 1.1);
5. Prepare the furnace breach end of the i nsulated fle x vent by first screwing the spin sleeve onto the corrugated aluminium jacke t (see Figure 1.2) until the trailing edge of the s pin sleeve is about
0.3 m (12") from the end of the vent (see Figure 1.3);
6. Pull the insulatio n back to expose the corrugated s tainless steel core;
7. Cut th e corrugated stainless steel core b ack by 76.2 mm (3") on the IFV Series vent. You should now have about 76 .2 mm (3") o f insulation hanging out past the stainless steel core (s ee Figure
1.4);
8. Push the stainless steel core ont o the b re ach pipe as far as it will go (see Figure 1.5) and mechanically attach the vent to the breach using three of the #8 X 1/2” self-drilling screws provided with the VTK Series kit. The screws should be equally space d around the circumference of the s tainl ess st eel c o r e, sta rtin g with the first screw at top dead centre. Start the drill point of the screws in the valleys of the corru gations at 9.5 mm –15.8 mm (3/8”-5/8”) back from the end of the s tainless steel core, so the screw heads can be properly sealed in the forthcoming operations (see Figure 1.6);
9. With the stainless steel core no w firmly attached to the breach, tear off one green gum-sealing str ip from the backing. Wrap the seal strip around the joint, always keeping the centreline of the seal strip over the line where the corrugate d stainless steel core makes the transition to the smooth oute r surface of the breach pipe. In other words, the seal strip must be ce nt re d over t he j oin t. After wrapping the seal strip around once, allow 12.7 mm (1/2”) overlap and tear off the residual length (see Figure 1.7);
10. Break the residual length of seal strip into 3 equal parts a nd stuf f them onto the screw heads of the stainless steel self-drilling screws so that the screw heads are completely covered;
11. Two stainless steel band clamps are provided in the VTK Series kits. Position one stainless steel band clamp over the gum seal joint so that the edge of the clamp closest to t he breach lines up with the edge of the gum seal that is closest to the breach. Ensure that the band will close with an action of one strip sliding over the other - not under the gear hea d of the draw clamp (see Figure 1.8). Tighten the band cla mp with considerable torque to cause the gum seal to be squeezed i nto all crevice s and to ooze out of the end of the clamp closest to the breach (see Figure 1.9). The gum will eventually become rubbery;
12. The seal is permanent and should never need to be disconnected as the breach plate can be r emoved for cleaning and inspection using the 4-bolt joint;
13. Tuck the vent insulation into the breach collar;
14. Screw the spin sleeve tightly into the breach c ollar for a finished appearance. Wrap the other end of the spin sleeve with aluminium tape to cover any metal burrs that may be present (see Figure 1.10);
15. Bend the venting into the desired radius coming off the breach.
Connection to the vent terminal - DV-2000™
1. Prepare the terminal end of the insulated flex vent by first screwing the spin sleeve onto the corrugated aluminium jacke t until the trailing edge of the spin sleeve is about 254.0 mm (10") from the end of the vent;
2. Using sharp tin snips, c ut the aluminium outer sleeve back by
127.0 mm (5") on the IFV Series vent;
3. Pull the insulatio n back to expose the corrugated s tainless steel core;
4. Cut th e corrugated stainless steel core b ack by 76.2 mm (3") on the IFV Series vent. You should now have about 76 .2 mm (3") o f insulation hanging out past the stainless st eel core ;
5. Push the stainless steel core onto the pipe on the back of the terminal as far as it will go and mechanically attach the vent to the terminal using three of the #8 X 1/2” self-drilling screws provided with the VTK Series kit. The screws sho uld be equally spaced around the circumference of the stainless steel core, starting with the first screw at top dead centre. Start the d rill point of the screws in the valleys of the corrugations at 9.5 mm-15.8 mm (3/8”-5/8”) back from the end of the stainless steel core;
6. With the s tainless steel core now firmly at tached to the terminal, tear off the other green gum-sealing strip from the backing. Wrap the seal strip around the joint, al ways keeping the centreline of the seal strip over the line whe re the corrugated stainless steel core makes the transition to the smooth outer surface of the terminal pipe. After wrapping the seal strip around once, allow
12.7 mm (1/2”) overlap and tear off the residual length;
7. Break the residual length of se al strip in to 3 e qual parts and s tuff them onto the screw heads of the stainless steel self-drilling screws so that the screw heads are completely covered;
8. Position the o ther stainless steel band clam p over the gum seal joint so that the edge of the clamp closest to the terminal lines up with the edge of the gum seal that is closest to the terminal. Tighten the band clamp with considerable t orque to cause the gum seal to be squeezed into all crevices and to ooze out of the end of the clamp closest to the terminal (see Figure 1.11);
9. The seal is permanent and should never need to be disconnected as the end of the terminal can be opened for cleaning and inspection by removing the screened end-cone assembly. Tuck the vent insulation into the recess in the terminal body;
10. Screw the spin sleeve tightly into the recess for a finished appearance. Wrap the other end of the spin sleeve with aluminium tape to cover any metal burrs that may be present (see Figure 1.12);
11. Bend the venting into the desired radius coming off the terminal.
8
THREAD SPIN SLEEVE ONTO OUTER SLEEVE
CUT OUTER SLEEVE
BACK 5”
THREAD SPIN SLEEVE BACK 10” CUT STAINLESS STEEL
CORE BACK BY 3”
9
FIGURE 1.3 FIGURE 1.4
FIGURE 1.1 FIGURE 1.2
FIGURE 1.5 FIGURE 1.6
INSERT STAINLESS STEEL CORE ONTO BREECH TUBE
DRIVE THREE STAINLESS STEEL SCREWS, STARTING NEAR TOP
445 01 4024 05
Loading...
+ 18 hidden pages