ICP C8MPT050B12A1, C8MPT075F14A1, C8MPT100F14A1, C8MPT100J20A1, C8MPT125J20A1 Installation Guide

...
INSTALLATION INSTRUCTIONS
For Natural Gas to Propane and High Altitude Conversion Kit No: 1011789
This kit is designed to convert the NTP6, TNE, NDP6, TDE, NTPM, TNK, NCPM, TCK, NTVM, VNK, *9MPV, *9MPT, *8MPV and *8MPT Series Furnaces equipped with Honeywell SV9540 Series gas valves and Honeywell Q3450 igniters from Natural Gas to Propane Gas.
* Denotes Brand (T, H or C)
This conversion kit shall be installed by aqualified service agency. Please read these instructions completely before attempting installation. Consult gas supplier and tables in National Fuel Gas
Code NFPA 54/ANSI Z223.1,1992 or latest edition. InCanada, the National Standard CAN/CGA B149-1 and B149-2.
Parts List
Description Part# Qty Burner Orifice #54 1011376 5
Pilot Orifice, LP (0.011) 1009136 1 Honeywell Cony. Kit #396021 1011828 1
Switch, Low Pressure 1008801 1 Fitting Asy. 1009775 1
Inlet Fitting 1147904 1 Wire Asy. 1009516 1
Label, Field Conversion 1009678 1 Label, LP Conversion 1011832 1 Label, Derate 2505235 1 Instructions 44106101507 1
Parts for High Altitude Conversion Burner Orifice #55 (2000' - 7000')
Burner Orifice #56 (7000' - 8000') Orifices required, but not included in kits.
1011354 as required 1011355 as required
This conversion kit shall be installed by a
qualified service technician in accordance with the Manufacturer's instructions and all applicable
codes and requirements of the authority having
jurisdiction. The qualified service agency
performing this work assumes responsibility for
the proper conversion of this furnace with this kit.
Failure to follow these instructions exactly can result in death, personal injury and/or property damage.
AVERTISSMENT
Cet ensemble de conversion ne doit etre installe
que par le representant d'un organisme qualifie et
conformement aux instructions du fabricant et tous les codes et exigences applicables de
I'autorite competente. L'organisme qualifie quieffectue les travaux est responsable de la
conversion correcte de ce generateur d'air chaud
I'aide de cet ensemble. Quiconque ne respecte pas a la lettre les instructions darts le present manuel risque de declencher un incendie ou une
explosion entrainant des dommages materiels,
des lesions corporelles ou la perte de vies humaines.
General Information
This kit is for conversion of furnaces equipped with Honeywell SV9540 Series 2-stage gas valves certified for use with Natural Gas (and so marked) to units functionally the same as the certified furnace for use with Propane Gas. Before the furnace can be operated with LP Gas, the LP low pressure must be installed (90+ models ONLY). A gas valve conversion kit must be installed and main burner orifices and pilot burner orifice must be replaced with orifices in this kit or with properly sized orifices for high altitude ordered separately.
The orifices provided in this kit are stamped to indicate the size (twist drill number) and are sized for commercially pure propane
gas ONLY. Do NOT use them with butane or a mixture of butane and propane gas, or at elevations above 2000'. The parts list
specifies the size orifices supplied in the kit. Compare the size marking on the orifices with the sizes as listed in the parts list. Make sure you have the correct main burner orifices.
Extreme care is used to assure that this kit contains the proper orifices. Oversized orifices could result in hazardous
conditions, especially if the venting is inadequate. For that reason, we recommend that the installer check the size of the
orifice with a new twist drill of the correct size. This procedure assures that the orifices provided are the correct size.
D Shut off gas supply to furnace at manual shut-off valve
before starting installation.
D Disconnect electric power supply to the furnace before
starting installation.
D Check for gas leaks after installation of kit and before
attempting to start furnace.
D Locate the LP Gas Conversion Label next to the furnace
rating plate.
D Fill out and attach the Field Conversion Label to the front
exterior of the furnace.
Gas Pressure
D Refer to the furnace rating plate for the approved gas input
ratings.
D Gas input to burners MUST NOT exceed the rated input
shown on rating plate.
D Do NOT allow minimum gas supply pressure to vary
downward. Doing so will decrease input to furnace. Refer to Table 1 for gas supply and manifold pressures.
441 06 1015 07 (10/2003)
Table 1 Gas Pressures
Gas Pressure
Type Recommended Max. Min. Hi Fire Lo Fire
Nat. 7" 14" 4.5" 3.5" 1.7"
LP 11" 14" 11" 10" 4.9"
With Propane gas, the rated input is obtained when the BTU content is 2,500 BTU per cubic foot and manifold pressure set at 10 inches W.C.
If Propane gas has a different BTU content, orifices MUST be changed by licensed Propane installer.
Measured input can NOT exceed rated input.
Combustion Air Box Cover MUST be removed when ad-
justing manifold pressure.
Any major change in gas flow requires changing burner orifice size.
Supply Pressure Manifold
(1.7kPa) (3.5kPa) (1.1kPa) (0.9kPa) (0.5kPa)
(2.7kPa) (3.5kPa) (2.7kPa) (2.5kPa) (1.3kPa)
Important Notes
Installation
Electric shock hazard/Fire and/or explosion hazard.
Disassembly
NTPM/TNK NCPM/TCK
NTVM/VNK
NTP6/TNE NDP6/TDE
Turn OFF gas supply at manual gas valve before turning OFF electric power supply and starting
installation. Turn OFF electric power supply at disconnect
switch or service panel before starting installation. Failure to follow this warning can result in death,
personal injury, property damage and/or equipment damage.
Disassembly
Refer to Figure 1 and the following steps.
1. After disconnecting power and gas supply to the furnace, remove the access door, exposing gas valve and burner compartment.
2. Disconnect gas line from gas valve so manifold assembly can be removed.
3. Remove screws securing burner compartment cover and remove cover. Use care to avoid damage to gasket. (if
used)
4. Disconnect wiring at gas valve. Be sure to note the proper location of any and all electrical wiring disconnected.
5. Remove the pilot supply line from the gas valve.
6. Remove the screws holding the manifold and gas valve to the manifold supports. Do Not discard any screws.
_" 25-22-36
*9MPT & *9MPV *8MPT & *8MPV
25-23-86
7.
Carefully remove the manifold assembly.
8.
NDP6/TDE & NTP6/TNE series furnaces ONLY. Remove the four (4) screws holding the manifold supports to the front
partition and remove the NOx inserts. Replace the screws that secure the NOx inserts and discard the NOx inserts.
(Figure 2) Note: Step 8 applies to exposed or enclosed burner models
with NOx inserts.
441 06 1015 07 2
High Altitude Installation
CarbonMonoxidehazard.
NOxinsertsfor usewith NaturalGasunits
ONLY.If LPGasisrequired,NOxinsertsmust beremoved.
Failureto followthis warningcan result in
property damage,personal injury and/or death.
Removing NOx inserts
NTP6/TNE & NDP6/TDE SERIES FURNACES
ONLY
These units may be installed at full input rating when installed at altitudes up to 2000'. The #54 burner orifices supplied in this kit are sized for commercially pure propane gas only, for use between
0-2000' elevation. Do not use them with butane or a mixture of butane and propane, or at elevations above 2000'.
When installed above 2000', the input MUST be derated by 4% for each 1000 feet above 2000'. Orifices for conversion at high
altitude (2000' - 8000') must be ordered from Service Parts. A #55 orifice is indicated for use between 2000' and 7000', and a #56
orifice is indicated for altitudes in the 7000' - 8000' range. Refer to the parts list provided to determine the proper orifice part number for ordering purposes.
iiiiiiiiiiiiiiiiiiiiiiiiiii!iiiii_ii_!il! !!i!ii!ii!i!_iliiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!i!i!i!iiChanging Orifices
(I J Measure from face of orifice
___ _ to the back side of the
_£-,,d manifold.
293+_11.!1mm
Changing Pilot Burner Orifice
Main Burner Orifices
Remove the Natural gas (brass) burner orifices from the
1. 2. Disconnect the pilot supply from pilot igniter. manifold assembly and replace them with the appropriate
Propane (silver) orifices furnished in the conversion kit. Tighten orifices so they are seated and gas tight (Figure 3).
2. 4. Reconnect pilot tubing securely to the pilot. Make sure orifice is installed straight so that it forms a right
angle (90 °) to the manifold bracket.
_i!_ l i l Pil°t Burner L°cati°n Dimensi°ns f°r Nzp61zNE' NDp61zDE' NzpMIzNK'
NCPM/TCK, NTVM/VNK, "*9MPT, *9MPV, "8MPT and *8MPV Series Furnaces
ONLY
\ /
_ _ _ 4.2"(107mm)
Burner Bracket Assembly _ Burner Support Bracke _ |
1. Remove two (2) screws securing pilot assembly to burner bracket.
3. Remove pilot orifice and replace with propane orifice (marked with a red dot) supplied in kit.
5. Verify proper relationship of pilot burner assembly per Figure 4.
DIMENSIONS
,,Art
(End of burner bracket
to edge of pilot bracket)
7.2" (126mm)
10.2" (126mm)
45°_1
Furnace Size
(Number of Burners)
2
3,4 5,6
Feamale Gas Lin_e_Nut
A _ (Do.... N"^ " _ ot Bend Pilot Bracket)
441 06 1015 07 3
a25-21-52c
Loading...
+ 4 hidden pages