ICP N9MP1, N9MP2, T9MPD, H9MPD, C9MPD Service Manual

MULTI POSITION
SINGLE STAGE
GAS FURNACES
N9MP1, N9MP2 & *9MPD
Manufactured by:
ã 2001 International Comfort Products Corporation (USA)
“A1 & A2”
Part Number
440 08 2001 02
4/2002
N9MP1 -- Indoor combustion air (1 pipe only)
N9MP2 -- Direct Vent ONLY (2 pipe only)
*9MPD -- Dual Certified Venting (1 or 2 pipes)
* Denotes Brand (T, C or H)
Single Stage Multi Position Furnace
Service Manual
TABLE OF CONTENTS
1. INTRODUCTION 2............................................................
2. UNIT IDENTIFICATION 2.....................................................
3. FURNACE THEORY OF OPERATION 3........................................
4. ELECTRICAL SUPPLY 4......................................................
5. INTERLOCK SWITCH 5......................................................
6. GAS SUPPLY 5..............................................................
7. BURNERS 7................................................................
8. L.P. PRESSURE SWITCH 7...................................................
9. HIGH ALTITUDE OPERATION 7...............................................
10. CHECKING TEMPERATURE RISE 8..........................................
11. ROOM THERMOSTATS 8....................................................
12. CONTROL WIRING 9.......................................................
13. TWINNING KITS 10..........................................................
14. LIMIT SWITCHES 10.........................................................
15. PRESSURE SWITCHES 12...................................................
16. VENT/COMBUSTION AIR PIPING 14..........................................
17. STANDARD VENT TERMINATION 14..........................................
18. CONCENTRIC VENT TERMINATION 16........................................
19. EXHAUST BLOWER 17......................................................
20. CONDENSATE DRAIN TRAP 17...............................................
21. HONEYWELL ST9160B FAN TIMER/FURNACE CONTROL 18....................
22. ST9160B TESTING SEQUENCE 19............................................
23. ST9160B -- UNIQUE CONTROL FUNCTIONS/RESPONSES 19...................
24. HONEYWELL SV9541M GAS VALVE/IGNITION SYSTEM 20.....................
25. HONEYWELL SV9541M SYSTEM OPERATION 20..............................
26. CHECKING FLAME CURRENT 21.............................................
27. CAPACITORS 22............................................................
28. BLOWER ASSEMBLY 22.....................................................
29. BLOWER ROTATION 23......................................................
30. HEAT EXCHANGER REMOVAL/REPLACEMENT 44.............................
SV9541M “SMART VALVE” -- Sequence of Operation 45.............................
SV9541M “SMART VALVE” -- Trouble shooting 47...................................
SV9541M “SMART VALVE” -- Electrical Variation 49.................................
WIRING DIAGRAM 50...........................................................
TECHNICAL SERVICE DATA (N9MP1 or 2) 52......................................
TECHNICAL SERVICE DATA (*9MPD/A1) 54......................................
TECHNICAL SERVICE DATA (*9MPD/A2) 55......................................
BLOWER PERFORMANCE DATA (N9MP1 or 2 & *9MPD) 56.........................
APPENDIX OF HELPFUL INFORMATION 57.......................................
Service
Manual
1. INTRODUCTION
This service manual is designed to be used in conjunction with the installation manual and/or technical support manual provided with each furnace.
These furnaces represent the very latest in high efficiency gas furnace technology. Consequently, they incorporate the use of certain controls that contain highly sophisticated elec­tronic components which are not user serviceable. there- fore, it is essential that only competent, qualified, service personnel attempt to install, service, or maintain this prod­uct.
This Service manual was written to assist the professional HVAC service technician to quickly and accurately diagnose and repair any malfunction of this product.
This service manual covers our new multi--position furnaces, both Direct Vent (2 pipe Only), Indoor combustion (1 pipe Only) and Dual Certified (1 or 2 pipe) models. The overall op­eration of all of these models is essentially the same.
This manual, therefore, will deal with all subjects in a general nature (I.E. all text will pertain to all models) unless that sub­ject is unique to a particular model or family, in which case it will be so indicated.
Single Stage Multi Position Furnace
!
The information contained in this manual is intended for use by a qualified service technician who is familiar with the safety procedures required in installation and repair and who is equipped with the proper tools and test instruments.
Installation or repairs made by the unqualified persons can result in hazards subjecting the unqualified person making suchrepairs to the risk of injury or electrical shock which can be serious, or even fatal not only to them, but also to persons being served by the equipment.
If you install or perform service on equipment, you must assume responsibility for any bodily injury or property damage which may result to you or others. We will not be responsible for any injury or property damage arising from improper installation, service and/or service procedures.
2. UNIT IDENTIFICATION
The unit’s rating plate contains important information for the service technician. It also lists the complete Model Manufac­turing and Serial Numbers.
These complete numbers are required to obtain correct re-
MODEL NUMBER IDENTIFICATION GUIDE
placement parts (example, in certain model families a unit having a MARKET REVISION of “C” is likely to be equipped with one or more different components.
* 9 MP D 075 B 12 A 1
Brand Identifier Engineering Rev.
T=Tempstar Denotes minor changes
C = Comfortmaker Marketing Digit
H=Heil Denotes minor change
A = Arcoaire
X = Evaluation Cooling Airflow
Brand Identifier 08 = 800 CFM
8 = Non--Condensing, 80+% Gas Furnace 12 = 1200 CFM
9 = Condensing, 90+% Gas Furnace 14 = 1400 CFM
Installation Configuration 16 = 1600 CFM
UP = Upflow DN = Downflow UH = Upflow/Horizontal 20 = 2000 CFM
HZ = Horizontal DH = Downflow/Horizontal
MP = Multiposition, Upflow/Downflow/Horizontal Cabinet Width
Major Design Feature B = 15.5² Wide
1 = One (Single) Pipe N = Single Stage F = 19.1² Wide
2=TwoPipe P=PVCVent J = 22.8² Wide
D = 1 or 2 Pipe T = Two Stage L = 24.5² Wide
L = Low NOx V = Variable Speed Input (Nominal MBTUH)
440 08 2001 02
2
Single Stage Multi Position Furnace
Service
Manual
Figure 1
Gas Valve/Ignition Module
Component Locations for Four Position Furnaces
Furnace Vent Pipe
Manual Gas Valve
Vent Drain Fitting
Diagnostic Light
Combustion Air
5
Blower
/8² OD Vent Pipe
Drain Hose
3
/4² OD Transition Box
Drain Hose
Door Interlock Switch
Fan/Delay Control
Vent Pipe Grommet
Rating Plate
Air Intake Pipe
(Dual Certified or Direct
Vent Model)
Primary Heat Exchanger
Secondary Heat Exchanger
Pressure Switch
Plastic Transition Box
Circulating Air Blower
dwg 25--23--29a
3. FURNACE THEORY OF OPERATION
The high efficiencies and lower profile (compared to previous series) of this furnace have been obtained using design tech­niques not typical of traditional furnace designs. A brief de­scription of these new design techniques and the purpose they serve follows.
1. Reducing the height of the furnace while maintaining the high efficiency of pervious models required main­taining the surface area of the heat exchanger and yet minimizing the overall size.
The design required to achieve these results is the “SER­PENTINE” design, wherein the flue gasses must follow a serpent shaped passage through the heat exchanger via convection.
This “Serpentine” path is resistive to normal convective flow, and requires that a partial vacuum be created at the outlet of the heat exchanger to maintain the flow of flue products through the heat exchanger.
2. The serpentine heat exchanger design does not lend itself well to the ribbon type, or slotted port type burner found in more traditional design furnaces for the follow­ing reasons:
A. The secondary combustion airflows at right angles
to the burner flame, making it likely to “pull” the flame off a ribbon or slotted port type burner.
B. The flame “height” of a ribbon or slotted port type
burner would make it difficult (if not impossible) to prevent impingement of the flame on the heat ex­changer surfaces whole maintaining the low profile heat exchanger.
For these reasons, an “INSHOT” type burner is used in this series. The inshot burner (also called a “jet” burner) fires a flame straight out its end. This burner is designed to fire into a tube style heat exchanger, making it an ideal application in the tube--like passages of the serpentine heat exchanger.
3. In order to extract the maximum amount of heat pos­sible from the flue gasses, a secondary heat exchang­er (condenser) is connected to the outlet of the primary heat exchanger. This condenser removes additional heat from the flue gasses, causing their temperature to drop below dew point. This results in the forming of condensation (water) which then must be routed to a drain.
4. The placement of the secondary heat exchanger at the outlet of the primary heat exchanger creates additional resistance to the flow of gasses.
5. To overcome the resistance to convective flow of the Primary and Secondary heat exchangers requires the use of an Induced Draft Combustion Blower Assembly.
3
440 08 2001 02
Service
Manual
Single Stage Multi Position Furnace
6. The Combustion Blower Assembly is mounted on the outlet side of the Secondary heat exchanger, This blower creates a partial vacuum (negative pressure) within the heat exchangers drawing the flue products out of the furnace.
4. ELECTRICAL SUPPLY
!
Electrical shock hazard.
Turn OFF electric power at fuse box or service panel before making any electrical connections and en­sure a proper ground connection is made before connecting line voltage.
Failure to do so can result in death, personal injury and/or property damage.
SUPPLY CIRCUIT
The furnace cannot be expected to operate correctly unless it is properly connected (wired) to an adequately sized (15 amp.) single branch circuit.
SUPPLY VOLTAGE
Supply voltage to the furnace should be a nominal 115 volts. It MUST be between 97 volts and 132 volts. Supply voltage to the furnace should be checked WITH THE FURNACE IN OPERATION. Voltage readings outside the specified range can be expected to cause operating problems. Their cause MUST be investigated and corrected.
ELECTRICAL GROUND
Grounding of the electrical supply to ALL FURNACES IS REQUIRED for safety reasons.
CHECKING GROUNDING AND POLARITY
7. A pressure switch (Air Proving Switch) is used as a safety device that prevents the ignition system from fir­ing the furnace until it senses that a proper draft has been established through the furnace.
Polarity may be verified as follows:
1. Turn the power supply “ON”.
2. Using a Vo lt m e t e r check for voltage between the Hot (Black) and Neutral (White) wire of supply circuit.
POLARITY
CORRECT POLARITY of the line voltage supply to all fur­naces is also required for safety reasons.
3. Reading should be Line (Supply) Voltage.
4. Check for Voltage between the Neutral (White) wire and Ground wire of the supply circuit.
5. Reading should be zero Volts. (if line voltage is read, polarity is reversed)
6. A zero Volt reading indicates there is no voltage poten­tial on Neutral wire.
7. Double check by checking for voltage between the Hot (Black) wire and Ground wire of the supply circuit.
8. Reading should be Line (supply) Vo lt a g e.(ifzero volts is read, there is no ground, or polarity is re­versed.)
Figure 2
NOTE: Junction Box can be mounted to either the
left or right side.
Electrical Connections
Grounding may be verified as follows:
1. Turn the power supply “OFF”.
2. Using an Ohmmeter check for continuity between the Neutral (white) wire and Ground wire (green) of the supply circuit.
3. With the Ohmmeter set on the R x 1 scale, the reading should be zero Ohms.
4. A zero Ohm reading indicates that the neutral is grounded back to the main panel.
5. An alternate check would be to check for continuity from the Neutral to a cold water pipe, (Pipe must be metal, and must have a continuous, uninterrupted con­nection to ground) or to a continuous, uninterrupted connection to ground) or to a driven ground rod.
6. Any readings other than zero Ohms would indicate a poor ground, or no ground.
440 08 2001 02
25--23--42
4
Single Stage Multi Position Furnace
5. INTERLOCK SWITCH
The blower compartment door of all models is equipped with an interlock switch. This switch is “Normally Open” (closes when the door is on the furnace) and interrupts furnace op­eration when the door is open. This interlock switch is a safe­ty device, and SHOULD NEVER BE BY--PASSED.
Since this is a single pole switch, (breaking only one side of the line) proper line voltage is essential to insure that furnace components are not “HOT” when switch is open. (See Checking Grounding and Polarity)
6. GAS SUPPLY
Typ ical Gas Valve HoneywellFigure 4
Pilot Pressure
Adjustment (Hid-
den)
On\Off Switch
Diagnostic Light
An adequately sized gas supply to the furnace is required for proper operation. Gas piping which is undersized will not provide sufficient capacity for proper operation. Piping should be sized in accordance with accepted industry stan­dards.
NATURAL GAS
OUTLET
Manifold Pressure
Adjustment
dwg 25--23--31a
INLET
Manual
10--12--96
Figure 3
Service
Typical Interlock Switch
the inlet pressure MUST be a minimum of 11² W.C. If this cannot be obtained, problems are indicated in either the reg­ulator or pipe sizing.
Table 1 Gas Pressures Below 2000¢¢¢¢
Gas
Type
Natural 7² 14² 4.5² 3.5²
· With Propane gas, the rated input is obtained when the
· If Propane gas has a different BTU content, orifices
· Measured input can NOT exceed rated input.
· Any majorchange in gas flow requires changing burner
Recommended Max. Min.
LP 11² 14² 11² 10²
BTU content is 2,500 BTU per cubic foot and manifold pressure set at 10²²²² W.C.
MUST be changed by licensed Propane installer.
orifice size.
Supply Pressure
Important Note:
Manifold
Pressure
CHECKING INPUT (FIRING) RATE
Once it has been determined that the gas supply is correct to the furnace, it is necessary to check the input (firing) rate, This can be done in two (2) ways. First by checking and ad­justing (as necessary) the manifold (Outlet) pressure. The second way is to “Clock” the gas meter.
Inlet (Supply) pressure to the furnace should be checked (at the gas valve) with ALL OTHER GAS FIRED APPLIANCES OPERATING. Inlet (Supply) pressure to the furnace under these conditions MUST be a minimum of 4.5² W.C. (Water Column). If the inlet pressure is less, it may be an indication of undersized piping or regulator problems.
L.P. GAS
Inlet (Supply) pressure to the furnace should be checked in the same manner as for Natural Gas, however with L.P. Gas,
!
Fire or explosion hazard.
Turn OFF gas at shut off before connecting manometer.
Failure to turn OFF gas at shut off before connecting manometer can result in death, personal injury and/or property damage.
5
440 08 2001 02
Service
H
Manual
Single Stage Multi Position Furnace
Figure 5
Pressure Connections
Typical "U" Tube
Manometer
MANIFOLD PRESSURE AND ORIFICE SIZE FOR HIGH ALTITUDE APPLICATIONS
Gas Pressure Testing Devices
3
2
1
0
1
2
3
0
INCHES OF WATER
510
MAGNEHELIC
MAX. PRESSURE 15 PSIG
15
1. Connect a manometer or Magnehelic gauge (0-- 12² W.C. range) to the pressure tap on the “OUTLET” side of the gas valve.
2. Turn gas “ON”, fire the furnace, and remove adjust­ment cover (screw--cap).
3. Turn adjustment screw clockwise (IN) to INCREASE pressure, and counterclockwise (OUT) to DECREASE pressure.
4. At altitudes BELOW 2,000¢¢¢¢ set manifold pressure to
3.5² W.C. for Natural Gas, and 10² W.C. for L.P. Gas.
5. For Natural Gas units ABOVE 2,000¢¢¢¢, set manifold pressure according to TABLE 2.
6. For L.P. Gas units ABOVE 2,000¢¢¢¢, insure that orifice size has been changed (per “National Fuel Gas Code”
-- Appendix “F”) if gas supply has not already been de-­rated for altitude by the gas supplier .
7. For ALL UNITS ABOVE 8,000¢, contact the factory for SPECIFIC de--rating information.
CHECKING MANIFOLD PRESSURE
Table 2 NATURAL GAS
eatValue
Btu/Cu.Ft.
800 3.5 3.5 3.5 3.5 3.5 3.5 3.5
850 3.5 3.5 3.5 3.5 3.5 3.5 3.5
900 3.5 3.5 3.5 3.5 3.5 3.5 3.4
950 3.5 3.5 3.5 3.5 3.3 3.2 3.1
1000 3.5 3.4 3.3 3.2 3.0 2.9 2.8
1050 3.2 3.1 3.0 2.9 2.7 2.6 2.5
1100 2.9 2.8 2.7 2.6 2.5 2.4 2.3
Orifice Size #42 #42 #42 #42 #42 #42 #42
0--1999 (²²²²××××wc)
2000--2999
(²²²²××××wc)
3000--3999
(²²²²××××wc)
“CLOCKING” GAS METER (NATURAL GAS)
1. Check with gas supplier to obtain ACTUAL BTU con­tent of gas.
2. Turn “OFF” gas supply to ALL other gas appliances.
3. Time how many seconds it takes the smallest (normal­ly 1 cfh) dial on the gas meter to make one complete revolution.
Elevation Above Sea Level
4000--4999
(²²²²××××wc)
5000--5999
(²²²²××××wc)
6000--6999
(²²²²××××wc)
4. Calculate input rate by using ACTUAL BTU content of gas in formula shown in example.
Example
Natural Gas
BTU Content
1,000 3,600 48 75,000
No. of Seconds
Per Hour
1,000 x 3,600 ¸ 48 = 75,000 BTUH
Time Per Cubic
Foot in Seconds
7000--7999
(²²²²××××wc)
BTU Per
Hour
440 08 2001 02
6
Single Stage Multi Position Furnace
7. BURNERS
Burners used in this series of furnace are of the “INSHOT” type. Their operation can be compared to that of a torch in that they produce a hard, sharp, somewhat noisy flame. Noise should not be an issue, however, because of the closed compartment design. In order to insure that the burn­ers are operating properly, and at their design noise level, proper adjustment of the gas (manifold) pressure is essen­tial. See page 6 for further information on manifold pressure adjustments.
The burners used in this series ARE NOT EQUIPPED WITH AIR SHUTTERS, as none are required. Proper operation (flame characteristics) is obtained by insuring that the orifice size, and manifold pressure are correct for the fuel being used and the altitude of the installation.
8. L.P. PRESSURE SWITCH
Models converted to operate on L.P. Gas will be installed with an L.P. Pressure Switch. If so equipped, the switch will be located in the gas supply line (in a “Tee” fitting), just ahead of the gas valve.
Figure 6
Figure 7
Service
Main Burner
Burner Face
Typical L.P . Pressure Switch
Manual
10--10--78
The purpose of this switch is to prevent furnace operating un­der low line (Supply) pressure conditions. Operating under low line pressure conditions, can create problems such as in­complete combustion, flashback, sooting, etc.
The switch is a “Normally Open” pressure operated switch that is wired in series with the furnace (vent) pressure switch. The L.P. Pressure Switch closes when line (Supply) pres­sure is 8.0² W.C. or higher. the L.P. Pressure Switch Opens
if line pressure falls below 6.0² power to the gas valve.
On some models, it is located (electrically) between the Fur­nace (vent) pressure switch and the gas Valve.
+
0.6² W.C. interrupting
9. HIGH ALTITUDE OPERATION
These furnaces are designed to operate in the majority of the country without modifications. At altitudes over 2,000¢ above sea level, however, certain measures need to be taken to in­sure continued, safe reliable operation. For example, units must be de--rated for altitude (by adjusting manifold pres­sure and/or changing orifice size) based upon the type of fuel (I.E. Natural Gas or L.P. gas), Btu content of the gas, and installed altitude.
ALL UNITS must have a high altitude pressure switch installed at altitudes above 4,000¢ above sea level.
When servicing a unit installed at altitudes above 2,000¢ in­sure that it has been properly modified to operate at that alti­tude. See the sections on Gas pressure (Page *), and pres­sure switches (Page **) to obtain specific information for you particular installation altitude.
7
440 08 2001 02
Service
Manual
10. CHECKING TEMPERATURE RISE
Single Stage Multi Position Furnace
Figure 8
Thermometer:
Return Air Temp.
Return
Air Flow
Checking Temperature Rise
Supply
Air Flow
Thermometer;
Supply Air Temp.
The furnace is designed to operate within a certain specified range of temperature rise.
Operating the furnace outside the specified range may result in lower efficiency and/or comfort levels, as well as prema­ture combustion component failures.
Simply stated, the temperature rise through the furnace is the difference in temperature between the return air, and the supply air.
NOTE: BEFORE CHECKING TEMPERATURE RISE BE CERTAIN THAT MANIFOLD PRESSURE IS PROPERLY ADJUSTED.
ALLOWABLE TEMPERATURE RISE ALL MODELS
Model
50 Mbtu 35°F--65°F
75, 100 & 125 Mbtu 40°F--70°F
Operate the furnace for 15 minutes before taking tempera­ture readings. Subtract the return air temperature from the supply air temperature. The result is the temperature rise. Compare with the allowable rise listed for the model (size) you are checking.
Temperature Rise can be checked by placing a thermometer in the return air duct within 6¢ of furnace. Place a second ther­mometer in the supply duct at lease two (2) ft. away from the furnace. (This will prevent any false readings caused by radi­ation from the furnace heat exchanger) Make sure that the FILTER IS CLEAN and that ALL REGISTERS AND/OR DAMPERS ARE OPEN.
If the rise is not within the specified range, it will be necessary to change the heating blower speed. If the rise is too high, it will be necessary to increase the blower speed. If the
rise is too low, it will be necessary to reduce the blower speed.
Example:
Supply T emp. 170 Return Temp. 70° Temperature Rise 100° =
Too High
Solution: Increase Blower Speed
Range
°
11. ROOM THERMOSTATS
Room thermostats are available from several different manufactures in a wide variety of styles. They range from the very simple and inexpensive Bi--metallic type to the complex. They are simply a switch (or series of switches) designed to turn equipment (or components) “ON” or “OFF” at the de­sired conditions.
An improperly operating, or poorly located room thermostat can be the source of perceived equipment problems. A care­ful check of the thermostat and wiring must be made then to insure that it is not the source of problems.
440 08 2001 02
8
Figure 9
THERMOSTAT
5 ft.
Thermostat Location
DRAFTS
SUN
SHIELD
LIGHT
Single Stage Multi Position Furnace
Service
Manual
LOCATION
The thermostat should not be mounted where it may be af­fected by drafts, discharge air from registers (hot or cold), or heat radiated from the sun of appliances. Never install in al­coves, bathrooms or bedrooms.
The thermostat should be located about 5 ft. above the floor in an area of average temperature, with good air circulation. Normally, an area in close proximity to the return air grille is the best choice.
Mercury bulb type thermostats MUST be level to control tem­perature accurately to the desired set--point. Electronic digi­tal type thermostats SHOULD be level for aesthetics.
HEAT ANTICIPATORS
Heat anticipators are small resistance heaters built into most electric--mechanical thermostats. Their purpose is to pre­vent wide swings in room temperature during furnace opera­tion.
In order to accomplish this, the heat output from the anticipa­tor must be the same regardless of the current flowing through it. Consequently, most thermostats have an adjust­ment to compensate for varying current draw in the thermo­stat circuit.
The proper setting of heat anticipators then is important to insure proper temperature control and customer satisfac­tion.
Figure 10
Measuring Current Draw
The best method to obtain the required setting for the heat anticipator, is to measure the actual current draw in the con­trol circuit (“W”) using a low range (0--2.0 Amps) Ammeter. (See Figure 10) After measuring the current draw, simply set the heat anticipator to match that value.
If a low range ammeter is not available, a “Clamp--on” type meter may be used as follows:
1. Wrap EXACTLY ten (10) turns of wire around the jaws of a clamp--on type ammeter.
2. Connect one end of the wire to the “W” terminal of the thermostat sub--base, and the other to the “R” termi­nal.
3. Turn power on, and wait approximately 1 minute, then read meter.
4. Divide meter reading by 10 to obtain correct anticipator setting.
If an ammeter is not available, a setting of 0.30 amps may be used for models equipped with the HONEYWELL SV9541M Gas Valve/Ignition Control. They should, howev­er, provide satisfactory operation in most cases.
Electronic thermostats do not use a resistance type anticipa­tor. These thermostats use a microprocessor (computer) that determines a cycle rate based on a program loaded into it at the factory.
These cycle rates are normally field adjustable for different types to equipment. The method of adjustment, however, varies from one thermostat manufacturer to another. Check with the thermostat manufacturer to find out the proper way of adjusting the cycle rate.
W
Amps
R
Subbase
Ammeter
12. CONTROL WIRING
Control wiring is an important part of the total equipment installation, since it provides the vital communications link between the thermostat, and the equipment malfunctions. Control wiring that is either too long, undersized, or improp­erly connected (be it simply loose, or on the wrong terminal) can in fact be the source of many equipment problems.
ALWAYS check to make sure that the control wiring is con­nected to the proper terminal(s) of the equipment and ther­mostat you are using. Remember, also, that the thermostat terminals are not always identified alike by different thermo­stat manufacturers. Connections MUST be clean and tight
to insure trouble--free operation.
For years, installers have run a wire from the “Y” terminal of the room thermostat and connected it directly to the contact on coil of a condensing unit. (not making any connection to the furnace with this wiring. Then, run the low voltage “Com­mon” wire from the condensing unit back to the “C” terminal of the furnace.
With the HONEYWELL ST9160B electronic Fan Timer/Fur­nace Control, the “Y” terminal of the furnace does in fact serve a particular purpose. Failure to connect it will result in certain improper operation as follows:
9
440 08 2001 02
Service
Manual
Single Stage Multi Position Furnace
The COOLING fan speed is energized via the “Y” terminal. Failure to connect the thermostat “Y” terminal to the “Y” ter­minal on the control will result in the failure to energize the
13. TWINNING KITS
Some installations may require a Heating capacity or Airflow capabilities greater than a single furnace of this series can provide.. When this is necessary, furnaces may be installed in a “Twinned” configuration.
The T winning Kit allows the two (2) furnaces to be controlled by the same room thermostat. When Twinned, the circulat­ing (conditioned air) blowers of BOTH furnaces will operate
14. LIMIT SWITCHES
Two (2) different kinds of limit switches are used on this se­ries of furnaces. They are the main limit and roll out limit switches. The main limit, and roll limit switches are used on all models.
NOTE: All limit switch es are safety devices and other than for testing purposes, should never be jumped out! Limit switches are “normally closed” electrical switches, de­signed to open when their predetermined “limit setting” has been reached.
It should also be remembered, that when a limit switch opens, it more than likely is not due to a bad switch! The cause of the opening limit must be found and corrected, be­fore the furnace can resume proper operation.
COOLING speed on a call for cooling from the thermostat. (The HEATING speed will be energized instead via the “G” terminal)
simultaneously.
Models equipped with a HONEYWELL ST9160B series Fan Timer/Furnace Control may be twinned using a model NAHA003WK01 twinning kit.
To assist troubleshooting efforts of “Twinned” installations, “TYPICAL” control wiring diagrams are provided on pages ** through **.
Maximum allowable outlet air temperature. While the main limit is open, combustion blower, and/or the circulating blow­er will be energized continuously. This control is an “Auto­matic” reset control, which will reset itself when the tempera­ture sensed drops to a safe level.
If furnace (burner) cycles on this limit switch, (I.E. switch opens and closes during furnace operation) it is more than likely due to a high temperature rise through the furnace. (See checking temperature on page 8 of this manual)
High temperature rise can be caused by either OVER FIRING (high manifold pressure. incorrect orifices, etc.) or LOW AIR FLOW (dirty filter, blower speed too low, excessive static in duct system, etc.)
!
Fire hazard.
Limit controls are factory preset and MUST NOT be adjusted. Use ONLY manufacturer’s authorized replacement parts.
Failure to do so can result in death, personal injury and/or property damage.
The specific functions of the two (2) limit switches used in this series of furnaces are as follows:
MAIN LIMIT SWITCH
A “Normally Closed” switch located on the front partition of the furnace. It monitors supply air temperature, and inter­rupts furnace (burner) operation when a supply air tempera­ture is sensed which would result in the furnace exceeding
Figure 11
Typical Limit Switch
440 08 2001 02
10
Single Stage Multi Position Furnace
Service
Manual
To verify this, the cut--out (opening) point of the switch should be checked (using a thermocouple type thermometer con­nected to the face of the switch) as follows:
1. Operate furnace for several minutes.
2. Block return air grille(s) to furnace.
3. Observe temperature at which switch opens (burner operation ceases).
4. Remove blockage from return grille(s).
5. Observe temperature at which switch closes (burner operation resumes).
6. Compare readings with the limit setting listed in the appropriate chart for the model you are servicing.
If switch is opening within the specified range, then it is sim­ply doing its job, and the cause of the over--temperature must be determined and corrected.
If, however , the switch is found to be opening prematurely, then it should be replaced. When replacing ANY limit switch, use ONLY a switch of EXACTLY the same temperature set­ting. Use of a different temperature limit switch can create a dangerous situation. Some of the main limit switches used in this series are SIMILAR IN APPEARANCE. DIFFERENT TEMPERATURE SETTINGS, HOWEVER, ARE USED for different models. Be certain you have the correct control for the model you are servicing.
ROLL OUT LIMIT
A “Normally Closed” switch (wired in series with the Main Limit switch) mounted on the burner box.
This switch may be of the manual type, depending upon the particular model and/or family. Different temperature (OPENING) settings are also used on different models. When replacing this switch, be absolutely certain the correct one is used.
The roll out switch monitors the temperature inside the burn­er box, and interrupts furnace (burner) operation when its temperature indicates flame roll out has occurred.
If the roll out switch has opened, the cause must be deter­mined. Some possible reasons for flame roll out include a re­stricted primary or secondary heat exchanger or over fired furnace.
MANUAL RESET SWITCH MODELS
Furnace models which are equipped with a Honeywell ST9160 Fan timer/furnace control use a manual reset roll out switch. Once the roll out switch has opened, burner opera­tion will be prevented until the roll out switch is “Manually Re­set” by pressing the red button located on the switch. While the roll out switch is open, (Depending upon the particular model) the combustion blower and/or circulating blower will be energized continuously.
AUXILIARY LIMIT SWITCHES
All models are equipped with one (1) additional (AUXILIARY) limit switch mounted on the blower deck. Its purpose is to monitor return air temperature, and interrupt burner opera­tion when a temperature is sensed which could result in the filter surface(s) exceeding allowable temperatures. Depend­ing upon the particular model, the combustion blower, and/or circulating blower may be energized continuously while the auxiliary limit switch remains open.
This control is an “Automatic” reset control which will reset itself when the temperature drops to a safe level. See the Tech. Service Data Sheet for the model you are servicing, to obtain its specific auxiliary limit switch setting.
Figure 12
Typical Roll Out Limit Switch
CAUTION
NEVER use an automatic reset roll out switch to replace a manual reset type roll out switch.
Doing so may cause potentially unsafe and/or intermit­tent operation.
11
440 08 2001 02
Service
²
W.C
1
8+0.1
0
W.C
Manual
15. PRESSURE SWITCHES
Single Stage Multi Position Furnace
Transition Pressure Switch
This switch is designed to monitor a blockage of the conden­sate drain line. It uses a single tap (port) “Normally Open” pressure switch (wired in series with the furnace air proving (pressure) switch. The switch “Closes” at a (negative) pres­sure setting for the switch associated with that particular model furnace (See unit specitications).
Under normal operating conditions, sufficient pressure is de­veloped by the exhaust (combustion) blower to close the switch, and permit the burner to operate. As the condensate drain begins to back--up, however, the pressure begins to re­duce. When the pressure drops sufficiently, burner operation will be prevented until the condition is corrected.
Blower Pressure Switch
An air proving switch (pressure switch) is used on all models to insure that a draft has been established through the heat exchanger before allowing burner operation.
To insure continued SAFE, RELIABLE, operation, NEVER SUBSTITUTE a pressure switch with one that is similar in appearance. ONLY FACTORY PROVIDED or AUTHORIZED SUBSTITUTES ARE ACCEPTABLE.
All models installed at altitudes of 4,000¢ above sea level or higher require replacing the standard pressure switch with a high altitude pressure switch. The different pressure switch settings allow continued SAFE, RELIABLE, high altitude operation.
Figure 13
Pressure Switches
Blower
Transition
HIGH ALTITUDE PRESSURE SWITCHES - ALL
MODELS
--1.40
Max.
Close
²
Open Part #
--
--1.
.
²
--
.
Model
Upflow
Downflow
CHECK CURRENT TECHNICAL SUPPORT MANUAL FOR PART NOS.
Under normal operating conditions, sufficient negative pres­sure will be created to close the pressure switch, and keep it closed to keep furnace operating. Under abnormal condi­tions, however, such as a restricted vent pipe, or a leak in one of the heat exchangers, sufficient negative pressure will not be created. This will result in the switch failing to close or fail­ing to remain closed during furnace operation.
When servicing a unit whose pressure switch will not close, or remain closed during operation, the operating pressure of that furnace should be checked and compared to approximate operating pressures listed in Tab le 3 and the switch setting(s) listed above for the model family you are servicing.
It is important to remember, that greater negative pressures are created by the furnace when “HOT” (I.E. upon initial start--up) than when “COLD” (I.E. after furnaces has been in operation for a few minutes). Because of this, furnace pres­sure should ONLY be checked when “HOT” to insure accu­rate readings.
Tab l e 3 lists approximate operating pressures for Direct Vent (I.E. Two Pipe) installations of models in this series. They were obtained in a test lab, under controlled conditions using two (2) specific vent lengths. They are included in this manual to provide you with a “Barometer” to gauge our pres­sures against. The pressures you obtain in the field will differ slightly from these figures based upon vent length, gas pres­sure, operating temperature, etc.
Major discrepancies in pressures, will normally cause problems with pressure switch operation. These Major dis­crepancies should be investigated as follows:
25--23--72
440 08 2001 02
12
Single Stage Multi Position Furnace
0Mb
M
b
100Mb
1
25M
b
Tab l e 3 APPROXIMATE OPERATING PRESSURES (²²²² OF W.C.)
Model Vent Length @Blower @ Transition
5
75
tu
tu
tu
tu
Short -- (5¢ No. Elbows) --1.80 --2.60
Long -- (40¢ +590° Elbows) --1.30 --2.30
Short -- (5¢ No. Elbows) --1.80 --2.60
Long -- (40¢ +590° Elbows) --1.30 --2.30
Short -- (5¢ No. Elbows) --1.80 --2.60
Long -- (40¢ +590° Elbows) --1.70 --2.50
Short -- (5¢ No. Elbows) --1.80 --2.60
Long -- (40¢ +590° Elbows) --1.70 --2.50
Service
Manual
Lower (Lesser) Negative Pressures
Lower than normal negative pressures measured at the Combustion Blower may be caused by:
1. Restriction on the Outlet side of the combustion blow­er. (I.E. Blocked Flue, Vent too long, Heat Exchanger leak, etc.)
2. Leak (lack of restriction) on the Inlet side of the com­bustion blower.
Figure 14
UPFLOW
*8²²²² Min. 20¢¢¢¢ Max. in same atmospheric zone
Vent Pipes MUST be
supported Horizontal-
ly and Vertically
Typical Vent/Combustion Air Piping Installation
Aluminum or non--rusting shield recommended.
(See Vent Termination Shielding for dimensions).
Inlet Pipe
(not used
on
Single Pipe
models)
DISCHARGE AIR
Coupling on ends of ex­haust pipe. Total pipe & coupling outside struc­ture = 8²²²²
*8²²²² Min. 20¢¢¢¢ Max. in same atmospheric zone
Higher (Greater) Negative Pressures
Higher than normal negative pressures measured at the Combustion Blower may be caused by:
1. Restriction on the Inlet side of the combustion blower. (I.E. Plugged Heat Exchanger, air inlet orifice too small)
DOWNFLOW
Inlet Pipe
(not used on
Single Pipe
models)
Vent Pipes MUST be supported Horizontally and Vertically
See Vent Termination Shielding in Vent Section.
*8²²²² Min. 20¢¢¢¢ Max. in same atmospheric zone
Coupling on inside and outside of wall to restrain vent pipe
8² Min.
*8²²²² Min. 20¢¢¢¢ Max. in same atmospheric zone
* Increase minimum from 8²
0 °°°° F).
² to 18²²²² for cold climates (sustained temperatures below
²²
25--23--33
13
* Increase minimum from 8²²²² to 18²²²² for cold climates (sustained temperatures
below 0°°°°F).
25--23--33a
440 08 2001 02
Service
Manual
16. VENT/COMBUSTION AIR PIPING
Single Stage Multi Position Furnace
Vent and combustion air piping are an extremely important part of the total furnace installation. Improperly installed or inadequately sized vent and/or combustion air piping can be the source of many perceived furnace problems.
For example, most problems associated with pressure switch operation can normally be traced to short comings in the vent and/or combustion air piping. Anytime these type problems arise, a thorough inspection of the vent and/or combustion air piping should be conducted.
ALL MODELS require a vent (exhaust) pipe to carry flue
17. STANDARD VENT TERMINATION Vent/Combustion Air Piping Charts
Dual Certified Models ONLY - Non- Direct Vent Installation
Single Piping Chart
Tab l e 4
50,000 & 75,000 Btuh Furnaces
40¢ & (5) 90° elbows with 2² PVC pipe or 70¢ & (5) 90° elbows with 3² PVC pipe or
70¢ & (5) 90° elbows with 3² PVC pipe
40¢ & (5) 90° elbows with 3² PVC pipe
Elbows are DWVLong Radius Type for 2² and 3² vents.
If more than five elbows are required,reduce the length of both the inlet and exhaust pipes 5¢ for each additional elbow used.
NOTE: It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters than shown.
All Series (Models) - Direct Vent Installation
Tab l e 5
50,000 & 75,000 Btuh Furnaces
40¢ & (5) 90° elbows with 2² PVC pipe or 70¢ & (5) 90° elbows with 3² PVC pipe or
70¢ & (5) 90° elbows with 3² PVC pipe
40¢ & (5) 90° elbows with 3² PVC pipe
Elbows are DWVLong Radius Type for 2² and 3
² ven ts.
Pipe Diameter Table
Single Piping ONLY
100,000 Btuh Furnace
125,000 Btuh Furnace
Dual Piping Chart
Pipe Diameter Table
Dual Piping ONLY
100,000 Btuh Furnace
125,000 Btuh Furnace
products to the outside of the structure.
Direct VENT (ONLY) models require a combustion air inlet to bring in all air for combustion from outside the struc­ture.
DUAL CERTIFIED models require a combustion air inlet pipe to bring in all air for combustion from outside the struc­ture only when installed as a Direct Vent Furnace (I.E. Two Pipe Installation)
Consult the appropriate Venting tables and/or piping chart for the model (series) you are servicing.
If more than five elbows are required,reduce the length of both the inlet and exhaust pipes 5¢ (1.5m) for each additional elbow used.
* Feet of pipe is whichever pipe run is the longest, eitherinlet or outlet side.
Figure 15
Inlet is optional on
Dual Certified models
A=12² Above roof or snow accumulation level
B=8² Min., 20¢ Maximum, except in areas with extreme cold
temperatures (sustained below 0°F), the 18² Min.
Figure 16
Inlet is optional on
Dual Certified models
Standard Termination Rooftop Termination
B
A
A
25--00--06
Sidewall Termination12² or More Above Snow Level or Grade Level
8²²²² *
MIN.
20
MAX
*18² Minimum for cold climates
(substained below 0° F)
25--00--05F
440 08 2001 02
14
Single Stage Multi Position Furnace
Service
Manual
Figure 17
12²²²² Min.
Grade or
Snow Level
Dimension “A” is touching or 2² maximum separation.
Figure 18
Combustion
Concentric Vent and Combustion-
Air Roof Termination
Exhaust
Combustion
Air
Concentric Vent and Combustion-­Air Sidewall Termination
Air
“A”
1²²²² Maximum
(TYP.)
Ven t
Figure 20
18²²²² Min. for Cold Climates
(Sustained Below 0°°°° F)
Exhaust
Figure 21
18²²²² Min. for Cold Climates
(Sustained Below 0°°°° F)
Sidewall Inlet Vent and Exhaust--Air Termination with Exterior Risers
8²²²²
Inlet
Min.
12²²²² Min.
Grade or
Snow Level
8²²²² Min.
20¢¢¢¢ Max.
“A”
“A”
Dimension “A” is touching or 2² maximum separation.
Rooftop Inlet Vent and Exhaust--Air Termination
Inlet
8²²²² Min.
20¢¢¢¢ Max.
Dimension “A” is touching or 2² maximum separation.
Figure 19
Inlet
12²²²² Min. Grade
or Snow Level
“A”
Ven t
Exhaust
25-- 22- -02d
Sidewall Inlet Vent and Exhaust--Air Termination
“A”
Ex-
haust
“A”
8²²²² Min.
20¢¢¢¢ Max.
18²²²² Min. for
Cold Climates
(Sustained Below 0°°°° F)
Dimension “A” is touching or 2² maximum separation.
8²²²²
Min.
12²²²² Min.
Grade or
Snow Level
Exhaust
25-- 22- -43
15
440 08 2001 02
Service
Manual
Single Stage Multi Position Furnace
Figure 22
FRONT VIEW
Recommended Alternate Installa­tion for Sustained Cold Weather (--0°°°° F & below)
OVERHANG
12²²²² MIN.
EXHAUST
90°°°°
INLET
12² MIN. Ground
Level
OR Snow Level
SIDE VIEW
12²
25--23--73
Same Joist
Space
18. CONCENTRIC VENT TERMINATION Vent/Combustion Air Piping Charts
Concentric Termination Kit NAHA001CV
Tab l e 6
NAHA002CV -- 35¢ & (4) 90° elbows with 2² PVC pipe NAHA001CV -- 65¢ & (4) 90° elbows with 3² PVC pipe
NAHA001CV -- 65¢ & (4) 90° elbows with 3² PVC pipe
NAHA001CV -- 35¢ & (4) 90° elbows with 3² PVC pipe
1. Do not include the field supplied 45° elbow in the total elbow count.
2. If more than four elbows are required, reduce the length of both the inlet and the exhaust pipes five feet for each additional elbow used.
3. Elbows are DWV long radius type for 2² and 3² vents.
& NAHA002VC Venting Table Dual Piping
ONLY
50,000 & 75,000 Btuh Furnaces
100,000 Btuh Furnace
125,000 Btuh Furnace
Figure 23
Roof Boot/
Flashing
(Field Supplied)
Concentric Vent Roof Installation
Vent
Combustion
Air
Vent
Maintain 12² min. clearance
above highest anticipated
snow level. Max. of 24² above
roof.
Support
(Field Supplied)
45° Elbow
(Field Supplied)
440 08 2001 02
Note:
Support must be field installed to secure termination kit to structure.
16
Combustion Air
25--22--02
Loading...
+ 42 hidden pages