ICP LBO125DABR13-B, MBO115DABR-B, LBO145DABR12-B, LBO145DABR34-B, MBOV115DABR-B Installation Instructions And Use & Care Manual

...
UPFLOW WARM AIR
FURNACE
Printed in Canada
Save these instructions for future reference.
Caution : Do not tamper with the unit or its controls. Call a qualified service technician.
Manufactured by:
International Comfort Products
3400 Blvd Industriel Sherbrooke PQ Canada
2001/08/10
X40054 Rev. H
Models:
FLO115DABR-A LBO125DABR13-B LBO145DABR12-B LBO145DABR34-B
MBO115DABR-B MBOV115DABR-B MBOV115DABRU-B MBOV115DBU-C
445 02 4054 01
OLF140C12A OLR182A16A
(Division of U.T.C. Canada)
PART 1
!
!
INSTALLATION
SAFETY CONSIDERATIONS
INSTALLATION OF OIL FIRED HEATING UNITS SHALL BE IN ACCORDANCE WITH THE REGULATION OF AUTHORITIES HAVING JURISDICTION, IN CANADA THE CSA B139 OR IN UNITED STATES THE NFPA NO.31-1992 INSTALLATION CODE FOR OIL BURNING EQUIPMENT.
DO NOT OPERATE FURNACE IN A CORROSIVE ATMOSPHERE CONTAINING CHLORINE, FLUORINE OR ANY OTHER DAMAGING CHEMICALS.
DO NOT STORE OR USE GASOLINE, OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
1) SAFETY LABELLING AND SIGNAL WORDS
1.1) Danger, Warning and Caution:
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used in product labels to signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product.
2) SAFE INSTALLATION REQUIREMENTS
WARNINGWARNING
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with codes or, in the absence of local codes, with codes of the country having jurisdiction.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in furnace malfunction, property damage, personal injury and/or death.
WARNINGWARNING
Fire hazard The furnace must be installed in a level position,
never where it will slope to the front.
1.2) Signal Words:
DANGER – Immediate hazards which WILL result in death or serious
injury. WARNING – Hazards or unsafe practices which COULD result in
death or injury. CAUTION – Hazards or unsafe practices which COULD result in
personal injury or product or property damage.
1.3) Signal Words in Manuals:
The signal word WARNING is used throughout this manual in the following manner:
WARNINGWARNING
The signal word CAUTION is used throughout this manual in the following manner:
CAUTION
If the furnace were installed in that position, oil could drain into the furnace vestibule and create a fire hazard, instead of draining properly into the combustion chamber.
NOTE: It is the personal responsibility and obligation of the customer
to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances.
a. This furnace is NOT approved for installation in mobile homes,
trailers or recreation vehicles.
b. You must have a sufficient supply of fresh air for combustion and
ventilation to the area in which the furnace is located.
c. Do NOT use this furnace as a construction heater or to heat a
building that is under construction.
d. Use only the Type of fuel oil approved for this furnace (see
Rating Plate on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation.
e. Visually check all oil line joints for signs of wetness, which would
indicate a leak. f. Connect furnace to the chimney. g. The points in Part 2 “Operation” are vital to the proper and safe
operation of the heating system. Take the time to be sure they
are all done. h. Follow the rules of the NFPA Pamphlet No.31 (for USA) and B-
139 (for Canada) or local codes for locating and installing the oil
storage tank. i. Follow a regular service and maintenance schedule for efficient
and safe operation.
3
j. Before servicing, allow furnace to cool. Always shut off electricity
and fuel to furnace when servicing. This will prevent electrical
shock or burns. k. Seal supply and return air ducts. l. The vent system MUST be checked to determine that it is the
correct type and size. m. Install correct filter type and size. n. Unit MUST be installed so electrical components are protected
from direct contact with water.
2.2) Freezing Temperature and Your Structure:
WARNINGWARNING
Freeze warning.
2.1) Safety Rules:
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
a. The U.S. Consumer Product Safety Commission recommends
that users of oil-burning appliances install carbon monoxide detectors. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas-fired fireplaces, wood fireplaces, and several other items. Carbon monoxide can cause serious bodily injury and/or death. Therefore, to help alert people of potentially dangerous carbon monoxide levels, you should have carbon monoxide detectors listed by a nationally recognised agency (e.g. Underwriters Laboratories or International Approval Services) installed and maintained in the building or dwelling (see Note).
b. There can be numerous sources of fire or smoke in a building or
dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have fire and smoke detectors listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below).
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector.
Turn off water system. If your unit remains shut off during cold weather the
water pipes could freeze and burst, resulting in serious water damage.
Your unit is equipped with safety devices that may keep it from operating if sensors detect abnormal conditions such as clogged exhaust flues.
If the structure will be unattended during cold weather you should take these precautions.
a. Turn off main water supply into the structure and drain the water
lines if possible. Open faucets in appropriate areas.
b. Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes from freezing. Suggest they call a qualified service agency, if required.
2.3) Installation regulation:
All local and national code requirements governing the installation of oil burning equipment, wiring and flue connections MUST be followed. Some of the codes that may be applicable are:
CSA B139 INSTALLATION CODE FOR OIL
BURNING EQUIPMENT
CAUTION
Insure that the area around the combustion air intake terminal is free of snow, ice and debris .
CAUTION
Do not use any commercially available soot remover. This furnace has fiber type refractory combustion chamber. Normal servicing of this unit does not require cleanings of the combustion chamber. Use extreme care if for any reason you have to work in the area of the combustion chamber.
4
ANSI/NFPA 31 INSTALLATION OF OIL BURNING
EQUIPMENT
ANSI/NFPA 90B WARM AIR HEATING AND AIR
CONDITIONING SYSTEMS ANSI/NFPA 70 NATIONAL ELECTRICAL CODE CSA C22.2 No3 CANADIAN ELECTRICAL CODE Only the latest issues of the above codes should be used.
3) LOCATING THE FURNACE
CAUTION
Check carefully your furnace upon delivery for any evidence of damage that may have occurred during shipping and handling. Any claims for damages or lost parts must be made with the Transport Company.
This furnace is approved for reduced clearances to combustible construction, therefore, it may be installed in a closet or similar enclosure and in any case, the unit should always be installed level.
In a basement, or when installed on the floor (as in a crawlspace), it is recommended that the unit be installed on a concrete pad that is 1” to 2” thick.
The required minimum clearances for this furnace are specified in table #1.
WARNINGWARNING
The furnace should be located as close as possible to the chimney to keep vent connections short and direct. The furnace should also be located as near as possible to the center of the air distribution system.
Electrical shock hazard. This furnace is not watertight and is not designed
for outdoor installation. This furnace shall be
CAUTION
Do NOT operate furnace in a corrosive atmosphere
installed in such a manner as to protect the electrical components from water.
containing chlorine, fluorine or any other damaging chemicals. Refer to Part 1, section 5.2.
Outdoor installation would lead to a hazardous electrical condition and to premature furnace failure, property damage, bodily injury or death.
Minimum clearances – combustion materials (in)
LOCATION APPLICATION In
Sides
Back Furnace 18”
Top
Bottom Furnace (combustible floor) 0”
Flue pipe
Front From burner 24”
Furnace 1” Supply plenum within 6 ft of furnace 1”
Furnace or plenum 1” Horizontal warm air duct within 6 ft of furnace 1”
Horizontally or below flue pipe 9” Vertically above flue pipe 9”
4) VENTING
TABLE #1
the chimney connector with the barometric damper shut, after 5 minutes of operation) shall comply with the table #2.
WARNINGWARNING
Poison carbon monoxide gas, fire and explosion hazard.
Read and follow all instructions in this section. Failure to properly vent this furnace can result in
property damage, personal injury and/or death.
CAUTION
When the furnace (chimney installation) is co-vented with other combustion appliances such as a water heater, the allowable venting materials (i.e. L-Vent etc.) for use with those appliances should also be investigated.
The oil furnaces are certified for use with L-vent, A-vent, tile-lined and metal-liner-tile-lined chimneys. The appliance may be installed in a chimney of the proper size and adequate chimney base temperature as specified in the Installation Code. The relevant excerpt from the code is found in this section - Use it as a guide when local or national codes do not exist.
Flue pipe sizing:
The following table is an except from the installation code and indicates permitted flue sizes and minimum base temperatures for circular flues in chimney with thermal resistance less than R6 (6 ft2 •hr
•°F / Btu). Where a new appliance, burner, or chimney is installed, chimney vent sizes and maximum flue-gas temperatures (measured at
WARNINGWARNING
Poison carbon monoxide gas hazard Never install a hand operated damper in the vent
pipe. However, any Underwriters Laboratories listed electrically operated automatic type vent damper may be installed if desired. Be sure to follow instructions provided with vent damper. Read and follow all instructions in this section.
Failure to properly vent this furnace or other appliances can result in property damage, personal injury and/or death.
NOTES: Thermal resistance values for typical chimneys are as
follows:
R2 (2 ft2 hr •°F / Btu): clay-lined masonry, A-vent R3 (3 ft2 hr •°F / Btu): metal liner in clay-lined
Masonry R6 (6 ft2 hr •°F / Btu): metal or clay-lined masonry
with R4.5 (4.5 ft2 hr •°F / Btu)
insulation between liner and
masonry (e.g. 2 in. of
expanded mica or 1 3/8 in. of
high density glass fibreboard.)
5
Applying the Table:
The minimum size permitted shall be 4 in. inside diameter.
If a furnace with 0.60 USGPH nozzle is to be connected to a 20 ft. tall clay-lined masonry chimney, the thermal resistance of this chimney type is R2, which is less than R6. The actual firing rate at 156 psig is
1.25 x .60 = .75. Therefore this table shall apply as:
TABLE # 2
Total input rating of all
connected appliances
kW kBtu/h USGPH Min. Max. 11 20 28 36
21 70 0.50 3 5 300 400 535 725 27 91 0.65 3 5 275 340 430 535 31 105 0.75 4 5 260 320 380 475 36 119 0.85 4 5 250 300 355 430 41 140 1.00 4 6 225 300 365 430 51 175 1.25 4 6 240 275 320 365
Flue inside diameter (in) Minimum base temperature (ºF)
5) AIR FOR COMBUSTION
WARNING WARNING
Poison carbon monoxide gas hazard. Comply with ANSI/NFPA (in U.S.) or CSA (in
Canada) standard for the installation of Oil Burning Equipment and applicable provision of local building codes to provide combustion and ventilation air.
Failure to provide adequate combustion and ventilation air can result in personal injury and/or death.
The maximum size permitted shall be 5 in. inside diameter. The minimum base temperature shall be about 320ºF.
for chimney height (ft) of :
evaluated carefully as it may be necessary to provide outside air for combustion.
a. Commercial building. b. Building with indoor pools. c. Furnaces installed near chemical storage areas.
Exposure to these substances: a. Permanent wave solutions for hair.
b. Chlorinated waxes and cleaners. c. Chlorine based swimming pool chemicals. d. Water softening chemicals. e. De-icing salts or chemicals. f. Carbon tetrachloride. g. Halogen type refrigerants. h. Cleaning solvent (such as perchloroethylene). i. Printing inks, paint removers, varnishes, etc.. j. Hydrochloric acid. k. Solvent cements and glues. l. Antistatic fabric softeners for clothes dryers. m. Masonery acid washing materials.
5.1) General:
Oil furnaces must have an adequate supply of combustion air. It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace. However, home improvements such as new windows, doors, and weather stripping have dramatically reduced the volume of air leakage into the home.
Home air exhausters are common. Bathroom and kitchen fans, power vented clothes dryers, and water heaters all tend to create a negative pressure in the home. Should this occur, the chimney become less and less effective and can easily downdraft.
5.3) Ducted outdoor combustion air:
Outdoor combustion air kit – chimney venting:
The following kit has been certified for use on the appliance. The component kits contain an important safety feature, namely a vacuum relief valve, or VRV. During normal operation the burner aspirates outdoor air. If the intake terminal ever becomes partially blocked or fully blocked from ice or snow etc., the VRV will open to allow a proportion of air from the dwelling to enter the burner thus maintaining proper combustion. Once the blockage is removed, the VRV will close and the burner will draw all air from the outdoors again:
Heat recovery ventilation (HRV) systems are gaining in popularity. The HRVs are not designed to supply combustion air. If not properly balanced, a serious negative pressure condition could develop in the dwelling.
5.2) Contaminated Combustion Air :
Installation in certain areas or types of structures will increase the exposure to chemicals or Halogens which may harm the furnace. These instances will require that only outside air for combustion.
The following areas or types of structures may contain or have exposure to the substances listed below. The installation must be
6
CAS-2B Components (except air duct) for the Beckett AFG burner. The kit includes the intake terminal, vacuum relief valve (VRV) and special air boot connection with integral air adjustment means for the AFG burner. The CAS-2B can be used with 4” galvanised air duct or with 4” flexible aluminium air duct. It is recommended that the metallic air ducting material should be insulated from the air intake up to 5 feet from the burner to avoid condensation on the outside of the intake pipe.
CAD-1 Air duct kit consists of 25 feet of insulated UL/ULC Listed Class 1 air duct, and two 4” steel band clamps. The duct incorporates a corrugated flexible aluminium core, surrounded by fibreglass insulation covered with a vinyl vapour barrier.
CAUTION
The CAS-2B does not turn the furnace installation into a direct vent system. Therefore the building structure must provide for adequate combustion air to be delivered at the vacuum relief valve. The burner will need to draw combustion air from the VRV’s surroundings if the intake ever becomes blocked. Therefore non-direct vent installation codes must be followed.
Comprehensive installation instructions are provided with the kit.
6) OIL TANKS AND LINES
FIGURE # 1
Check your local codes for the installation of the tank and accessories. A manual shut-off valve and an oil filter shall follow sequence from
tank to burner. Be sure that the oil line is clean before connecting to the burner. The oil line should be protected to eliminate any possible damage. Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel pump (more than 8’ lift use 2 stage pump and more than 16’ an auxiliary pump).
Follow the pump instructions to determine the size of tubing you need in relation of the lift, or the horizontal distance.
7) BURNER INSTALLATION
Mounting the burner:
a. The warm air furnace burner mounting plate has a four bolts
configuration.
b. Position the mounting gasket between the mounting flange and
the appliance burner mounting plate. Line up the holes in the mounting flange with the studs on the appliance mounting plate and securely bolt in place.
After the burner is mounted:
a. Remove drawer assembly or air tube combination b. Install nozzle (see specifications) c. Confirm electrode settings d. Make the electrical connections e. Complete oil line connections
CAUTION
Do not turn on the burner until you have checked the polarity
Nozzles:
The burners are provided with the highest capacity USGPH nozzle installed. If another size nozzle, or replacement nozzle is required, use the nozzle spray angle, type and manufacturer recommended in Table #3.1 to 3.5. Note that all nozzle-marked sizes are based on a pump pressure of 100 psi.
Always select nozzle sizes by working back from the actual desired flow rate at operating pressure, and not by the nozzle marking.
Air and turbulator settings:
Before starting the burner for the first time, adjust the air and turbulator settings to those listed in the Table #3.1 to #3.5. Once the burner becomes operational, final adjustment will be necessary.
Fuel supply system:
Fuel Specifications
NOTE: Use No.1 or No.2 Heating Oil (ASTM D396) or in Canada, use No.1 or No.2 Furnace Oil.
Before starting the burner be sure the fuel tank is adequately filled with clean oil.
IMPORTANT
When using nozzle sizes of less than .75 USGPH, the Installation Code for oil burning equipment requires the installation of a 10 micron (or less) filter in the fuel oil line. ICP requires that this practice be followed in order to keep the lifetime heat exchanger warranty intact.
Checking the polarity:
The oil burners used on the furnaces have solid state control systems which makes them sensitive to the proper connections of the hot and neutral power lines. The controls will be damaged if the two lines are reversed.
a. Set your voltmeter to line voltage. b. Place one prong on your grounded electric entry box and one
prong on the black wire. c. Read the voltage. d. If the voltage is zero, check the white wire. If line voltage shows.
Reverse the 115-volt leads entering the furnace junction box.
WARNING WARNING
Fire and explosion hazard. Use only approved heating type oil in this furnace.
DO NOT USE waste oil, used motor oil, gasoline or kerosene.
Use of these will result in death, personal injury and/or property damage.
7
NOTE: You may notice a slight odor the first time your furnace is
!
operated. This will soon disappear. It is only the oil used on the parts during manufacturing.
8) INSTALLING ACCESSORIES
WARNING WARNING
Electrical shock hazard.
8.4) Ductwork and Filter:
Installation:
Design and install air distribution system to comply with Air Conditioning Contractors of America manuals or other approved methods that conform to local codes and good trade practices.
When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct outside furnace space.
Install air conditioning cooling coil (evaporator) on downstream side (in the supply air plenum) or furnace.
Turn OFF electric power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
Failure to do so could result in property damage, bodily injury or death.
8.1) Electronic air cleaner (E.A.C.):
Wire leads are provided to direct 115 volts @ 0.5 Amp maximum to an electronic air cleaner (EAC). Power will be available to the E.A.C when E.A.C switch is on or during heating speed blower operation. Wire the electronic air cleaner as indicated in the wiring diagram (figures # 4.1, # 4.2 and # 4.3).
8.2) Humidifier:
Terminals are provided to direct 115 volts @ 1.0 Amp maximum to the transformer powering the humidifier. The humidifier will be energised anytime the blower is operating on the “Heating Speed”. Wire the 115-volts power as indicated in figures # 4.1, # 4.2 and # 4.3.
8.3) Air conditioning:
An air conditioning coil may be installed on the supply airside only. Also, notwithstanding the evaporator coil manufacturer’s instructions, a minimum of 6 inches clearance must be allowed between the bottom of the coil drain pan, and the top of the heat exchanger. Wire the thermostat and condensing unit contactor as indicated in the wiring diagram (figures # 4.1, # 4.2 and # 4.3).
If separate evaporator and blower unit is used, install good sealing dampers for air flow control. Cold air from the evaporator coil going through the furnace could cause condensation and shorten furnace life.
CAUTION
Dampers (purchased locally) MUST be automatic.
WARNINGWARNING
Poison carbon monoxide gas hazard. Do NOT draw return air from inside a closet or
utility room. Return air duct MUST be sealed to furnace casing.
Failure to properly seal duct can result in death, personal injury and/or property damage.
WARNINGWARNING
Poison carbon monoxide gas hazard. Install evaporator coil on the supply side of the
furnace ducting. Evaporator coil installed in return side ducting can
cause condensation to form inside heat exchanger resulting in heat exchanger failure. This could result in death, personal injury and/or property damage.
8
PART 2
OPERATION
1) SEQUENCE OF OPERATION
1.1) Sequence of operation - Beckett AFG, Riello
40-F and Aero F-FAC:
1. Normally open contact (T-T) on primary relay closed when
thermostat calls for heat.
2. AFG and F-FAC burner: The motor starts and spark is
established. The pump pressure builds and the poppet valve
opens admitting fuel to the nozzle. Pressure builds and poppet
valve opens, allowing oil to flow through nozzle.
40F: Burner motor starts. The burner motor fan pre-purges the
combustion chamber and vent for 10 seconds, establishing the
combustion air pattern. During this time the solenoid valve
holding coil pressure will be approximately 100 psig. Solenoid
valve opens, allowing oil to flow through nozzle. At the same
time, the burner motor’s ignition coil produces spark.
3. Spark ignites oil droplets.
4. Cad cell senses flame and burner continues to fire. Ignition
transformer ceases sparking (Riello R40-F).
5. After fan-limit control heats up to the factory set point, the
circulating air blower and electronic air cleaner starts.
6. The circulating air blower and burner motor remain on until the
thermostat is satisfied (AFG). The ignition transformer continues
to spark (AFG). The solenoid valve remains open (R40-F).
7. Thermostat is satisfied.
bleed screw - the oil should flow absolutely free of white streaks or bubbles to indicate that no air is being drawn into the suction side of the oil piping and pump. Tighten the bleed screw and the burner will fire. Adjust the oil pressure as indicated in Table # 3.1 to # 3.5.
2.2) Restart if Burner Should Stop:
1. Set thermostat lower than the room temperature.
2. Press the reset button on the burner primary control (relay).
3. Set thermostat higher than the room temperature.
4. If the burner motor does not start or ignition fails, turn off the disconnect switch and CALL YOUR SERVICEMAN
CAUTION
Do not attempt to start the burner when excess oil has accumulated, when the furnace is full of vapour, or when the combustion chamber is very hot.
2.3) Combustion chamber curing:
Some moisture and binders remain in the ceramic combustion chambers after fabrication. It is important to clear the chamber of these residues before testing. If you smoke test before curing, the instrument may become damaged. To cure the chamber, run the unit for 3 consecutive cycles, with 3 minutes of elapsed time in between each cycle. Each burn cycle should be 3 minutes duration. The exhaust will have a pungent odor and produce a white cloud of steam.
8. Primary relay contacts open, solenoid valve closes (R40-F), burner fan motor shuts down. The ignition transformer ceases sparking (AFG).
9. The fan-limit control BI-metal cools down to the factory set point of 90 degrees Fahrenheit, the circulating air blower and the electronic air cleaner turns off.
2) CHECKS AND ADJUSTMENTS
2.1) General:
During initial start-up and subsequent yearly maintenance calls, the furnace must be thoroughly tested.
IMPORTANT
The burner must be put in operation for at least 10 minutes before any test readings are taken. For new installations, set up the burner to the settings (see table # 3.1 to # 3.5), before firing. These are rough adjustments but they will ensure that the burner will start and run smoke-free in advance of the fine adjustments being made.
Open the oil bleed port screw and start the burner. Allow the oil to flush into a portable container for at least 10 seconds. Slowly close the
2.4) Perform the smoke / CO2 test:
1. Pierce a test hole in the smoke pipe near the furnace breech. Insert the smoke test instrument probe into the open hole.
2. Starting with a zero smoke reading, gradually reduce the burner air setting until just a trace (#1 on Bacharach Scale) of smoke results.
3. Take a CO2 sample at the same test location where the smoke sample was taken. Note the CO2 reading associated with the #1 smoke condition.
4. Adjust the burner air setting to obtain a CO2 reading 1% lower than the reading associated with the #1 smoke.
5. This method of adjusting the CO2 will allow adequate excess air to ensure that the burner will burn clean for the entire heating season.
2.5) Perform the supply air temperature rise test:
1. Operate the burner for at least 10 minutes.
2. Measure the temperature of the air in the return air plenum.
3. Measure the temperature of the air in the largest trunk coming off the supply air plenum, just “out of the line of sight” of the radiation coming off the heat exchanger; 12” away from the plenum on the main take-off usually satisfies this objective.
9
4. The temperature rise is calculated by subtracting the return air
!
temperature from the supply air temperature.
5. If the temperature rise exceeds the temperature specified in table # 3.1 to # 3.5, change to the next higher blower speed tap until the temperature rise falls to at this temperature or below. If the excessive temperature rise cannot be reduced by increasing fan speed, investigate for ductwork restriction(s), dirty or improper air filter, or overfiring caused by excessive pump pressure, or inproper nozzle sizing.
2.6) Vent temperature test:
1. Place a thermometer in the test hole located in the breech pipe.
2. The vent temperature should be between 400 and 575°F. If not, check for improper air temperature rise, pump pressure, nozzle size, or for a badly sooted heat exchanger.
2.7) Fan limit adjustment:
FIGURE # 2
DNS-0355 Rev.B
MBO, MBOV 1 Limit “FAN OFF” 900F 2 Limit “FAN ON” 1100F 3 Limit “HI” 2000F LBO & OLR 1 Limit “FAN OFF” 900F 2 Limit “FAN ON” 1200F 3 Limit “HI”
Model: LBO125 1900F Model: LBO145-12 1800F Models: LBO145-34 and OLR182 1900F
FLO & OLF 1 Limit “FAN OFF” 900F 2 Limit “FAN ON” 1100F 3 Limit “HI” 1500F
1) GENERAL
Preventive Maintenance: “Preventive maintenance” is the best way to avoid unnecessary
expense and inconvenience. Have your heating system and burner inspected at regular intervals by a qualified service man.
After inspection, a complete combustion test must be performed after each annual service of the unit to maintain optimum performance and reliability.
10
PART 3
MAINTENANCE
WARNINGWARNING
Electrical shock hazard. Turn OFF power to furnace before any disassembly
or servicing. Failure to do so can result in property damage,
bodily injury and/or death.
Do not tamper with the unit or controls. Call your service technician.
Before calling for service, check the following.
a. Check oil tank gauge and check if the oil tank valve in oil is open. b. Check fuse or circuit breaker. c. Check if shut-off switch is “ON”. d. Reset thermostat above room temperature. e. If ignition does not occur turn off the disconnect switch and call
your qualified service technician.
When ordering replacement parts, specify the complete furnace model number and serial number.
1.1) Heat exchanger cleaning:
If the pot is damaged, it must be replaced. A damaged pot could lead to premature heat exchanger failure. Cracking of the fire pot is normal, however, replace the pot if the cracks have propagated more than 2/3 the way through the wall thickness. The average wall thickness of the firepot is 3/4”.
Flooding of the fire pot:
Flooding can occur when the oil primary control has been reset a number of times in a no-heat situation. Each time oil is fired into the pot and does not ignite, it is absorbed in the pot. Even if the burner is removed and the pot is felt for wetness, it is difficult to assess the degree of oil absorption by the pot.
There is only one way to properly service a flooded fire pot, and that is to change it.
Ordinarily, it is not necessary to clean the heat exchanger or flue pipe every year, but it is advisable to have your oil burner serviceman check the unit before each heating season to determine whether cleaning or replacement of parts is necessary.
If cleaning is necessary, the following steps should be perfomed:
1. Turn “OFF” all utilities upstream of the furnace.
2. Disconnect the flue pipe.
3. Remove the flue collar panel located in the rear part of the warm air furnace.
4. Remove the radiator baffle.
5. Disconnect the oil line and remove the oil burner from the furnace.
6. Clean the secondary tubes, and the primary cylinder with stiff brush and vacuum cleaner.
7. Before reassemble, the heat exchanger and combustion chamber should be inspected to determine if replacement is required.
8. After cleaning, replace the radiator baffle, flue collar plate and oil burner.
9. Readjust burner for proper operation.
Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil, or if the burner has been operating in a severely fouled condition.
CAUTION
If you observe the red warning light on the burner, push once ONLY to try and restart. If the burner will not start, phone your authorised service agent. Do not press the button again.
1.3) Burner drawer assembly:
Remove the drawer assembly. Clean all foreign matter from the retention head and electrodes. If a Beckett AFG burner has been installed, the burner will have to be removed to check the retention head and to check for proper “Z” dimension with the Beckett “T” gauge supplied with every burner. Check for any sign of oil boiling out of the nozzle and caulking - the solenoid valve could be leaking (if applicable).
1.4) Nozzle:
Replace the nozzle with the one specified in table # 3.1 to # 3.5.
1.5) Oil filter:
Tank filter:
The tank filter should be replaced as required.
Secondary filter:
The 10 micron (or less) filter cartridges should be replaced annually.
1.6) Air filters:
1.2) Refractory fire pot:
Remove the burner and check the fire pot.
IMPORTANT
Use extreme care if cleaning of the pot is required. After firing, the pot becomes very fragile. Do not use any commercially available soot remover. This furnace has a fiber type refractory combustion chamber. Normal servicing of this unit does not require cleaning of the combustion chamber.
IMPORTANT
Do not vacuum the ceramic chambers—they are easily damaged.
Air filters are the disposable types. The disposable filters should be replaced on at least an annual basis. Dusty conditions, presence of animal hair etc. may demand much more frequent filter changes. Dirty filters will impact furnace efficiency and increase oil consumption.
1.7) Motor lubrication:
Do not lubricate the oil burner motor or the direct drive blower motor as they are permanently lubricated.
1.8) CAS-2B combustion air kit :
If used, check the CAS-2B combustion air kit for proper operation. Check to see that the inlet screen is not plugged. Block the air inlet completely and ensure that a zero smoke reading results. If a zero smoke reading is not obtained, set up the burner as indicated on table # 3.1 to # 3.5.
11
Gradually block off the intake. The CO2 should increase by a maximum of 0.5 percentage points at the fully blocked condition. If not, check that the VRV gate is pivoting freely and that the pivot rod is in a
INFORMATION
horizontal position. Also, check that the counterweight has been properly adjusted in accordance with the CAS-2B installation instructions.
PART 4
Model :
Date of installation of the furnace :
Service telephones - day :
Dealer’s name and address :
RESULT OF START-UP TEST
Nozzle:
Burner adjustments :
CO2 :
Gross stack temperature:
% Smoke scale : (Bacharach)
Primary air Fine air Draw Assembly
Serial number:
Night :
Pressure : lbpsi
0
F
Ambiant temperature:
Chimney draft:
Overfire draft :
Test made by :
12
0
F " C.E. " C.E.
13
TABLE # 3.1
Technical specifications, MBO115DABR-B, MBOV115DABR-B, MBOV115DABRU-B & MBOV115DBU-C
TABLE # 4.1
Air delevery - CFM air filter
Firing rate USGPH 0.65 0.75 0.85 0.90 Input (BTU/h) 91 000 105 000 119 000 126 000 Heating capacity (BTU/h) 74 000 85 000 97 000 103 000 Maximum heating temperature rise (degr.F)
BURNER BECKETT (3450 RPM)
Low firing rate baffle Static disc, model Nozzle - 100 PSIG pump pressure (Delavan) 0.65 - 70W 0.75 - 70W 0.85 - 70W Combustion air adjustment (band / shutter) 0 / 4 0 / 6 0 / 7
RIELLO BURNER; MODEL 40
Nozzle (Delavan) 0.50 - 60W 0.60 - 60W 0.75 - 60W Pump pressure (PSIG) 165 155 145 Combustion air adjustment (turbulator / damper) 0 / 2.25 1 / 2.75 2 / 3.75
AERO BURNER (1725 RPM)
Nozzle - 100 PSIG pump pressure (Delavan) 0.65 - 70W 0.75 - 70W 0.85 - 70W
Volts - Hertz - Phase Operating voltage range Rated current (Amp.) Minimum ampacity for wiring sizing Max. fuse size (Amps)
Blower speed at 0.4" W.C. static pressure MED-LO MED-HI HIGH HIGH Blower speed at 0.2" W.C. static pressure MED-LO MED-HI HIGH HIGH Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size
RATING AND PERFORNACE
(1) 20 X 20
55 - 85 Degr.F
AFG-F3 (TUBE INSERTION 5 3/16")
YES
2 3/4 #3383
F3 (TUBE INSERTION 5 1/4")
FAFC-2 (TUBE INSERTION 5 3/8")
1/3 HP / 4 speeds
10 X 10
BLOWER DATA
ELECTRICAL SYSTEM
115 - 60 - 1
104 - 132
11.4
12.8 15
0.2 0.4
MED-LO
1300 1150
MED-HI
1350 1225
HIGH
1400 1250
MBO115DABR-B, MBOV115DABR-B, MBOV115DABRU-B & MBOV115DBU-C
EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED
14
TABLE # 3.2
Technical specifications, LBO125DABR13-B (BECKETT, RIELLO AND AERO BURNER)
TABLE # 4.2
Air delevery - CFM with air filter
Firing rate USGPH 0.75 0.85 1.00 1.10 Input (BTU/h) 105 000 119 000 140 000 154 000 Heating capacity (BTU/h) 84 525 95 795 112 700 123 970 Maximum heating temperature rise (degr.F)
BURNER BECKETT (3450 RPM)
Low firing rate baffle Static disc, model Nozzle - 100 PSIG pump pressure (Delavan) 0.75 - 70W 0.85 - 70W 1.00 -70W 1.10 - 70W Combustion air adjustment (band / shutter) 1 / 1 1 / 4 2 / 2 3 / 3
RIELLO BURNER; MODEL 40
Nozzle (Delavan) 0.60 - 60W 0.75 - 60W 0.85 - 60W 0.85 - 60W Pump pressure (PSIG) 155 130 140 170 Combustion air adjustment (turbulator / damper) 2 / 3.25 2.5 / 4 2 / 2.5 3 / 2.5
AERO BURNER (1725 RPM)
Nozzle - 100 PSIG pump pressure (Delavan) 0.75 - 70W 0.85 - 70W 1.00 - 70W 1.10 - 70W
Volts - Hertz - Phase Operating voltage range Rated current (Amp.) Minimum ampacity for wiring sizing Max. fuse size (Amps)
Blower speed at 0.4" W.C. static pressure MED-LO MED-HI HIGH N / A Blower speed at 0.2" W.C. static pressure MED-LO MED-HI HIGH HIGH Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size
F5 (Tube insertion 5 1/4")
2 3/4 #3383
F3 (Tube insertion 5 1/4")
(2) 15 X 20
115 - 60 - 1
104 - 132
11.4
12.8 15
1/3 HP / 4 speeds
10 X 10
FAFC-2 (TUBE INSERTION 5 3/8")
55 - 85 Degr.F
AFG-F3 (TUBE INSERTION 5 3/16")
YES
ELECTRICAL SYSTEM
BLOWER DATA
RATING AND PERFORMANCE
0.2 0.4
MED-LO
1175 1000
MED-HI
1250 1200
HIGH
1375 1300
LBO125DABR13-B
EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED
15
TABLE # 3.3
Technical specifications, LBO145DABR12-B (BECKETT, RIELLO AND AERO BURNER)
TABLE # 4.3
Air delevery - CFM with air filter
Firing rate USGPH 1.00 1.10 1.20 1.25 1.30 Input (BTU/h) 140 000 154 000 168 000 175 000 182 000 Heating capacity (BTU/h) 112 700 123 970 135 240 140 875 146 510 Maximum heating temperature rise (degr.F)
BURNER BECKETT (3450 RPM)
Low firing rate baffle Static disc, model Nozzle - 100 PSIG pump pressure (Delavan) 1.00 - 70W 1.10 - 70W 1.25 - 70W Combustion air adjustment (band / shutter) 2 / 3 2 / 6 6 / 6
RIELLO BURNER; MODEL 40
Nozzle (Delavan) 0.85 - 60W 0.85 - 60W 1.00 - 60W 1.10 - 60W Pump pressure (PSIG) 140 170 145 140 Combustion air adjustment (turbulator / damper) 2 / 2.25 2.5 / 2.75 3 / 2.75 3.5 / 2.75
AERO BURNER (1725 RPM)
Nozzle - 100 PSIG pump pressure (Delavan) 1.00 - 70W 1.10 - 70W 1.25 - 70W
Volts - Hertz - Phase Operating voltage range Rated current (Amp.) Minimum ampacity for wiring sizing Max. fuse size (Amps)
Blower speed at 0.4" W.C. static pressure MED-HI HIGH N/A N/A N/A Blower speed at 0.2" W.C. static pressure MED-HI MED-HI HIGH HIGH HIGH Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size
14.7
16.8 20
1/2 HP / 4 speeds
BLOWER DATA
12 X 9
(2) 15 X 20
RATING AND PERFORNACE
F5 (TUBE INSERTION 5 1/4")
FAFC-3 (TUBE INSERTION 5 3/8")
115 - 60 - 1
104 - 132
ELECTRICAL SYSTEM
55 - 85 Degr.F.
AFG-F3 (TUBE INSERTION 5 3/16")
YES
2 3/4 #3383
0.2 0.4
MED-LO
1100 1025
MED-HI
1400 1375
HIGH
1775 1675
LBO145DABR12-B
EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED
16
TABLE # 3.4
Technical specifications, LBO145DABR34-B and OLR182A16A (BECKETT, RIELLO AND AERO BURNER)
TABLE # 4.4
Air delevery - CFM with air filter
Firing rate USGPH 1.00 1.10 1.20 1.25 1.30 Input (BTU/h) 140 000 154 000 168 000 175 000 182 000 Heating capacity (BTU/h) 112 700 123 970 135 240 140 875 146 510 Maximum heating temperature rise (degr.F)
BURNER BECKETT (3450 RPM)
Low firing rate baffle Static disc, model Nozzle - 100 PSIG pump pressure (Delavan) 1.00 - 70W 1.10 - 70W 1.25 - 70W Combustion air adjustment (band / shutter) 2 / 3 2 / 6 6 / 6
RIELLO BURNER; MODEL 40
Nozzle (Delavan) 0.85 - 60W 0.85 - 60W 1.00 - 60W 1.10 - 60W Pump pressure (PSIG) 140 170 145 140 Combustion air adjustment (turbulator / damper) 2.5 / 2.5 3 / 2.75 3 / 3 3.5 / 3.25
AERO BURNER (1725 RPM)
Nozzle - 100 PSIG pump pressure (Delavan) 1.00 - 70W 1.10 - 70W 1.25 - 70W
Volts - Hertz - Phase Operating voltage range Rated current (Amp.) Minimum ampacity for wiring sizing Max. fuse size (Amps)
Blower speed at 0.4" W.C. static pressure MED-LO MED-HI HIGH HIGH HIGH Blower speed at 0.2" W.C. static pressure MED-LO MED-HI MED-HI HIGH HIGH Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size
AFG-F3 (TUBE INSERTION 5 3/16")
RATING AND PERFORNACE
55 - 85 Degr.F.
104 - 132
16.4
19.1 20
(2) 15 X 20
YES
2 3/4 #3383
F5 (TUBE INSERTION 5 1/4")
FAFC-3 (TUBE INSERTION 5 3/8")
ELECTRICAL SYSTEM
BLOWER DATA
3/4 HP / 4 speeds
12 X 9
115 - 60 - 1
0.2 0.4
MED-LO
1725 1600
MED-HI
1850 1725
HIGH
1975 1850
LBO145DABR34-B & OLR182A16A
EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED
17
TABLE # 3.5
Technical specifications, FLO115DABR-A and OLF140C12A (BECKETT, RIELLO AND AERO BURNER)
TABLE # 4.5
Air delevery - CFM with air filter
Firing rate USGPH 0.75 0.85 1.00 Input (BTU/h) 105 000 119 000 140 000 Heating capacity (BTU/h) 85 000 97 000 114 000 Maximum heating temperature rise (degr.F)
BURNER BECKETT (3450 RPM)
Low firing rate baffle Static disc, model Nozzle - 100 PSIG pump pressure (Delavan) 0.75 - 70W 0.85 - 70W 1.00 - 70W Combustion air adjustment (band / shutter) 0 / 5 0 / 7 1 / 5
RIELLO BURNER; MODEL 40
Nozzle (Delavan) 0.60 - 60W 0.75 - 060W 0.85 - 60W Pump pressure (PSIG) 155 130 140 Combustion air adjustment (turbulator / damper) 1.5 / 2.75 2.5 / 3.25 3 / 4.25
AERO BURNER (1725 RPM)
Nozzle - 100 PSIG pump pressure (Delavan) 0.75 - 70W 0.85 - 70W 1.00 - 70W
Volts - Hertz - Phase Operating voltage range Rated current (Amp.) Minimum ampacity for wiring sizing Max. fuse size (Amps)
Blower speed at 0.4" W.C. static pressure MED-LO MED-HI HIGH Blower speed at 0.2" W.C. static pressure MED-LO MED-HI HIGH Motor (HP) / number of speeds Blower wheel size (in.) Filter quantity and size
115 - 60 - 1
ELECTRICAL SYSTEM
55 - 85 Degr.F
AFG-F3 (TUBE INSERTION 5 3/16")
YES
2 3/4 #3383
F3 (TUBE INSERTION 5 1/4")
FAFC-2 (TUBE INSERTION 5 3/8")
16.8 20
BLOWER DATA
1/2 HP / 4 speeds
10 X 10
RATING AND PERFORNACE
(1) 10 X 20 & (1) 20 X 20
104 - 132
14.7
0.2 0.4
MED-LO
1225 1075
MED-HI
1450 1275
HIGH
1550 1375
FLO115DABR-A & OLF140C12A
EXTERNAL STATIC PRESSURE WITH AIR FILTER
SPEED
FIGURE # 3.1
18
DNS-0596 Rev. D
FIGURE # 3.2
Models: MBOV115DABR-B, MBOV115DABRU-B & MBOV115DBU-C
Model: MBO115DABR-B
DNS-0590 Rev. D
19
DNS-0576 Rev. D
FIGURE # 3.3
Models : LBO125DABR13-B, LBO145DABR12-B, LBO145DABR34-B & OLR182A16A
Model : FLO115DABR-A & OLF140C12A
FIGURE # 3.4
DNS-0666 Rev. B
20
FIGURE # 4.1
DNS-0578 Rev. D
Wiring diagram, MBO115DABR-B, MBOV115DABR-B, LBO125DABR13-B,
LBO145DABR12-B, LBO145DABR34-B & OLR182A16A
21
FIGURE # 4.2
Wiring diagram, MBOV115DABRU-B & MBOV115DBU-C
DNS-0593 Rev. B
22
Wiring diagram, FLO115DABR-A & OLF140C12A
FIGURE # 4.3
DNS-0658 Rev. B
23
PART LIST
Model : MBO115DABR-B
DNS-0597 Rev. E
24
Model : MBO115DABR-B
PART LIST
ITEM DESCRIPTION NUMBER COMMENTS
1
Complete heat exchanger
B40119-01
Item 16 included and item 38 not included
2
Top baffle
B40067
3
Electrical box cover ass'y
B40110
Wiring diagram label included
4
Observation door
B00403
5
Burner panel ass'y
B40048
Items 4 & 9 included
6
Washer 3/8" AA zinc
F06F005
Quantity required per unit: 4
7
Hexagonal nut 3/8-16NC brass
F07F024
Quantity required per unit: 4
8
Hexagonal flange nut 3/8-16NC brass
F07O001
Quantity required per unit: 18
9
Air supply door
B40120
10
Gasket, burner panel
B40030
11
Heat shield ass'y
B40099
Insulation included
12
Corner conduit
B40070-02
13
Strain reliefs bushing SR-34-2
L04I005
14
Front panel ass'y
B40130-01
Item 15 included
15
Front panel insulation
B40126
16
Combustion chamber
B40160
17
Combustion chamber strap
Z05F008
18
Combustion chamber strap seal
Z05F009
19
Floor ass'y
B40129
Item 20 included
20
Floor insulation
B01526-78
21
Divison panel ass'y
B40133
Central support, rear baffle and item 22 included
22
Sealing strip
B01291-02
Quantity required per unit: 3
23
Bushing 7/8" UB-875
L04G001
24
Left side panel ass'y
B40131-02
Items 25 & 35 included
25
Left side panel insulation
B40125-02
26
20 X 20 X 1 paper filter
Z04F004
27
Blower door ass'y
B40132
Item 28 included
28
Door handle
Z99F050
29
Top rear panel
B40049
30
Gasket, smoke outlet
B40032
31
Smoke outlet ass'y
B40046
32
Baffle ass'y
B40054-01
Quantity required per unit: 5
33
Plenum divider
B40043
34
Top division panel
B40076
35
Filter rack assembly
B40410
36
Right side panel ass'y
B40131-01
Items 35 & 37 included
37
Right side panel insulation
B40125-01
38
Gasket, extruded 1/2" X 1/8" x 25'
J06L001
39
1/3 HP direct drive motor
L06G011
40
Motor mount ass'y
B01888
Legs, band and screws included
41
Rubber grommet # 19
Z01F006
Quantity required per unit: 4
42
Blower support bracket
B01756
43
Blower electrical kit
B40081
44
Strain reliefs bushing SR-9P-2
L04I010
45
Terminal strip cover
B40059
Item 49 not included
46
Terminal plug-in .250
L03J005
47
Terminal block 4 positions
L99F003
48
Terminal strip support
B40074
49
Bushing 7/8" OCB-875
L04G013
Quantity required per unit: 2
50
Capacitor holder
B01024
51
10 MF capacitor
L01I003
52
Blower ass'y
B40127
Items 39 to 54 included
53
Blower 10 X 10
Z01I001
Housing and wheel included
54
Blower wheel 10 X 10
Z01L004
55
Rocker switch SPST
L07F003
56
Electrical box
B40066
Box only
57
Burner electrical kit
B40080
58
Terminal strip, 6 positions
A00294
59
Relay SPDT 120VAC
L01H011
60
Fan limit control
R02I006
25
PART LIST
Model : MBOV115DABR-B
DNS-0598 Rev. D
26
Model : MBOV115DABR-B
PART LIST
ITEM
DESCRIPTION
NUMBER
COMMENTS
1
Complete heat exchanger
B40119-01
Item 24 included and item 46 not included
2
Top baffle
B40067
3
Fan limit control
R02I006
4
Composant panel
B40137
Items 5 & 6 not included
5
Relay SPDT 120VAC
L01H011
Quantity required per unit: 2
6
Terminal strip, 6 positions
A00294
7
Observation door
B00403
8
Burner panel ass'y
B40048
Items 7 & 14 included
9
Hexagonal flange nut 3/8-16NC brass
F07O001
Quantity required per unit: 18
10
Electrical box ass'y
B40144-01
Item 14 not included
11
Electrical cover ass'y
B40145-01
Item 12 not included, labels included
12
Rocker switch
L07F003
13
Vestibule burner ass'y
B40148
14
Burner electrical kit
B40080
15
Hexagonal nut 3/8-16NC brass
F07F024
Quantity required per unit: 4
16
Washer 3/8" AA zinc
F06F005
Quantity required per unit: 4
17
Air supply door
B40120
18
Gasket, burner panel
B40030
19
Heat shield ass'y
B40099
Insulation included
20
Corner conduit
B40070-02
21
Strain reliefs bushing SR-34-2
L04I005
22
Front panel ass'y
B40130-01
Item 23 included
23
Front panel insulation
B40126
24
Combustion chamber
B40160
25
Combustion chamber strap
Z05F008
26
Combustion chamber strap seal
Z05F009
27
Floor ass'y
B40129
Item 28 included
28
Floor insulation
B01526-78
29
Divison panel ass'y
B40133
Central support, rear baffle and item 30 included
30
Sealing strip
B01291-02
Quantity required per unit: 3
31
Left side panel ass'y
B40131-02
Item 32 & 43 included
32
Left side panel insulation
B40125-02
33
Bushing 7/8" UB-875
L04G001
34
20 X 20 X 1 paper filter
Z04F004
35
Blower door ass'y
B40132
Item 36 included
36
Door handle
Z99F050
37
Top rear panel
B40049
38
Gasket, smoke outlet
B40032
39
Smoke outlet ass'y
B40046
40
Baffle ass'y
B40054-01
Quantity required per unit: 5
41
Plenum divider
B40043
42
Top division panel
B40076
43
Filter rack assembly
B40410
44
Right side panel ass'y
B40131-01
Item 43 & 45 included
45
Right side panel insulation
B40125-01
46
Gasket, extruded 1/2" X 1/8" x 25'
J06L001
47
1/3 HP direct drive motor
L06G011
48
Motor mount ass'y
B01888
Legs, band and screws included
49
Rubber grommet # 19
Z01F006
Quantity required per unit: 4
50
Blower support bracket
B01756
51
Blower electrical kit
B40081
52
Strain reliefs bushing SR-9P-2
L04I010
53
Terminal strip cover
B40059
Item 57 not included
54
Terminal plug-in .250
L03J005
55
Terminal block 4 positions
L99F003
56
Terminal strip support
B40074
57
Bushing 7/8" OCB-875
L04G013
Quantity required per unit: 2
58
Capacitor holder
B01024
59
10 MF capacitor
L01I003
60
Blower ass'y
B40127
Items 47 to 62 included
61
Blower 10 X 10
Z01I001
Housing and wheel included
62
Blower wheel 10 X 10
Z01L004
27
PART LIST
Models : MBOV115DABRU-B & MBOV115DBU-C
DNS-0605 Rev. D
28
Models : MBOV115DABRU-B & MBOV115DBU-C
PART LIST
ITEM
DESCRIPTION
NUMBER
COMMENTS
1
Complete heat exchanger
B40119-01
Item 30 included and item 54 not included
2
Top baffle
B40067
3
Fan limit control
R02I006
4
Composant panel
B40137
Items 5 and 12 not included
5
Relay SPDT 120VAC
L01H011
Quantity required per unit: 2
6
Bushing 7/8" OCB-875
L04G013
Quantity required per unit: 3
7
Witness light
L01L003
8
Rocker switch SPDT
L07F015
9
Simple electrical plug 120V
L05H003
10
Time delay relay
L01H020
11
Electrical support
B40138
Items 6 to 10 not included
12
Terminal strip, 6 positions
A00294
13
Observation door
B00403
14
Burner panel ass'y
B40048
Items 13 and 23 included
15
Hexagonal flange nut 3/8-16NC brass
F07O001
Quantity required per unit: 18
16
Electrical box ass'y
B40144-01
Item 20 not included
17
Electrical cover ass'y
B40145-01
Item 18 not included, labels included
18
Rocker switch
L07F003
19
Vestibule burner ass'y
B40148
20
Burner electrical kit
B40080
21
Hexagonal nut 3/8-16NC brass
F07F024
Quantity required per unit: 4
22
Washer 3/8" AA zinc
F06F005
Quantity required per unit: 4
23
Air supply door
B40120
24
Gasket, burner panel
B40030
25
Heat shield ass'y
B40099
Insulation included
26
Corner conduit
B40070-02
27
Strain reliefs bushing SR-34-2
L04I005
28
Front panel ass'y
B40130-01
Item 29 included
29
Front panel insulation
B40126
30
Combustion chamber
B40160
31
Combustion chamber strap
Z05F008
32
Combustion chamber strap seal
Z05F009
33
Floor ass'y
B40129
Item 34 included
34
Floor insulation
B01526-78
35
Divison panel ass'y
B40133
Central support, rear baffle and item 36 included
36
Sealing strip
B01291-02
Quantity required per unit: 3
37
Left side panel ass'y
B40168-02
Items 38 and 53 included
38
Left side panel insulation
B40167-02
39
Bushing 7/8" UB-875
L04G001
40
Insulation support
B40169
Quantity required per unit: 2
41
20 X 20 X 1 paper filter
Z04F004
42
Blower door ass'y
B40166
Item 43 included
43
Door handle
Z99F050
Quantity required per unit: 2
44
Blower door insulation
B40165
45
Top rear panel
B40049
46
Gasket, smoke outlet
B40032
47
Smoke outlet ass'y
B40046
48
Baffle ass'y
B40054-01
Quantity required per unit: 5
49
Plenum divider
B40043
50
Top division panel
B40076
51
Right side panel ass'y
B40168-01
Items 52 and 53 included
52
Right side panel insulation
B40167-01
53
Filter rack assembly
B40410
54
Gasket, extruded 1/2" X 1/8" x 25'
J06L001
55
1/3 HP direct drive motor
L06G011
56
Motor mount ass'y
B01888
Legs, band and screws included
57
Rubber grommet # 19
Z01F006
Quantity required per unit: 4
58
Blower support bracket
B01756
59
Blower electrical kit
B40081
60
Strain reliefs bushing SR-9P-2
L04I010
61
Terminal strip cover
B40059
Item 6 not included
62
Terminal plug-in .250
L03J005
63
Terminal block 4 positions
L99F003
64
Terminal strip support
B40074
65
Capacitor holder
B01024
66
10 MF capacitor
L01I003
67
Blower ass'y
B40127
Items 55 to 69 included
68
Blower 10 X 10
Z01I001
Housing and wheel included
69
Blower wheel 10 X 10
Z01L004
29
PART LIST
Model : LBO125DABR13-B
DNS-0585 Rev. D
30
PART LIST
Model : LBO125DABR13-B
ITEM
DESCRIPTION
NUMBER
COMMENTS
1
Complet heat exchanger
B40117-01
Item 20 included and item 41 not included
2
Top baffle
B40067
3
Electrical box cover ass'y
B40110
Label "electrical diagram" included
4
Observation door
B02282
5
Burner panel ass'y
B40048
Items 4 and 9 included
6
Hexagonal flange nut 3/8-16NC brass
F07O001
Quantity: 18
7
Washer 3/8" AA zinc
F06F005
Quantity: 4
8
Hexagonal nut 3/8-16NC brass
F07F024
Quantity: 4
9
Air supply door
B40120
10
Gasket, burner panel
B40030
11
Heat shield ass'y
B40099
Insulation included
12
Corner conduit
B40070-01
13
Strain reliefs bushing SR-34-2
L04I005
14
Front panel ass'y
B40105-01
Item 15 included
15
Front panel insulation
B40096
16
Left side panel ass'y
B40362-02
Items 17, 18 and 44 included
17
Left side panel insulation
B40095-02
18
Left angle filter support
B40229-02
19
Combustion chamber strap
Z05F009
Sold in feet
20
Combustion chamber
B40160
21
Combustion chamber strap seal
Z05F009
22
Floor ass'y
B40111-01
Item 23 included
23
Floor insulation
B01526-77
24
Rubber grommet #19
Z01F006
Quantity: 4
25
Blower support bracket
B40072-02
26
Bushing 7/8" UB-875
L04G001
27
Blower support bracket
B40072-01
28
15 X 20 X1 paper filter
Z04F012
Quantity: 2
29
Blower door ass'y
B40107
Item 30 included
30
Door handle
Z99F050
Quantity: 2
31
Top rear panel
B40049
32
Gasket, smoke outlet
B40032
33
Smoke outlet ass'y
B40046
34
Inlet baffle
B40071
Quantity: 2
35
Plenum divider
B40043
36
Baffle ass'y
B40054-01
Quantity: 5
37
Division panel ass'y
B40108
Central support, rear baffle and item 38 included
38
Sealing strip
B01291-02
Quantity: 4
39
Right angle filter support
B40229-01
40
Top division panel
B40076
41
Gasket, extruded 1/2" X 1/8" x 25'
J06L001
42
Right side panel ass'y
B40362-01
Items 39, 43 and 44 included
43
Right side panel insulation
B40095-01
44
Horizontal filter support
B40028
45
1/3 HP direct drive motor
L06G011
46
Motor mount ass'y
B01888
Legs, band and screws included
47
10 MF capacitor
L01I003
48
Capacitor holder
B01024
49
Terminal strip cover
B40059
Item 53 not included
50
Terminal strip
B40074
Items 51 and 52 not included
51
Terminal plug-in .250
L03J005
52
Terminal block
L99F003
53
Bushing 7/8" OCB-875
L04G013
Quantity: 2
54
Blower electrical kit
B40081
55
Blower ass'y
B40114-01
Items 45 to 57 included
56
Blower 10 X 10
Z01I001
Housing and wheel included
57
Blower wheel 10 X 10
Z01L004
58
Rocker switch SPST
L07F003
59
10 MF capacitor
L01I003
Box only
60
Burner electrical kit
B40080
61 Terminal strip, 6 positions
A00294
62 Relay SPDT 120VAC
L01H011
Quantity: 2
63 Fan limit control
R02I006
31
PART LIST
Models : LBO145DABR12-B, LBO145DABR34-B & OLR182A16A
DNS-0586 Rev. B
32
Models : LBO145DABR12-B, LBO145DABR34-B & OLR182A16A
PART LIST
ITEM DESCRIPTION NUMBER COMMENTS
1
Complet heat exchanger
B40118-01
Item 19 included. Item 35 not included
2
Top baffle
B40067
3
Electrical box cover ass'y
B40110
Electrical diagram label included
4
Observation door
B00403
5
Burner panel ass'y
B40048
Items 4 and 9 included
6
Hexagonal flange nut 3/8-16NC brass
F07O001
Quantity: 18
7
Hexagonal nut 3/8-16NC brass
F07F024
Quantity: 4
8
Washer 3/8" AA zinc
F06F005
Quantity: 4
9
Air supply door
B40120
10
Gasket, burner panel
B40030
11
Heat shield ass'y
B40099
Insulation included
12
Corner conduit
B40070-01
13
Strain reliefs bushing SR-34-2
L04I005
14
Front panel ass'y
B40105-01
Item 15 included
15
Front panel insulation
B40096
16
Left side panel ass'y
B40362-02
Items 17, 18 and 38 included
17
Left side panel insulation
B40095-02
18
Left angle filter support
B40229-02
19
Combustion chamber
B40161
20
Combustion chamber strap
Z05F008
Sold in feet
21
Combustion chamber strap seal
Z05F009
22
Floor ass'y
B40111-02
Item 23 included
23
Floor insulation
B01526-77
24
Bushing 7/8" UB-875
L04G001
25
Division panel ass'y
B40109
Central support, rear baffle and item 26 included
26
Sealing strip
B01291-02
Quantity: 4
27
15 X 20 X 1 paper filter
Z04F012
Quantity: 2
28
Blower door ass'y
B40107
Item 29 included
29
Door handle
Z99F050
30
Top rear panel
B40050
31
Gasket, smoke outlet
B40031
32
Smoke outlet
B40047
33
Baffle ass'y
B40054-02
Quantity: 7
34
Plenum divider
B40043
35
Gasket, extruded 1/2" X 1/8" x 25'
J06L001
36
Top division panel
B40076
37
Right angle filter panel
B40229-01
38
Horizontal filter support
B40028
Quantity: 2
39
Right side panel ass'y
B40362-01
Items 37, 38 and 40 included
40
Right side panel insulation
B40095-01
41
Terminal strip
B40074
Items 56 and 57 not included
42
Terminal strip cover
B40059
Item 55 not included
43
Capacitor holder
B01024
44
10 MF capacitor
L01I003
45
Motor mount ass'y
B40134
Legs, band and screws included
46
Strain reliefs bushing SR-34-2
L04I005
47A
1/2 HP direct drive motor
B40113-01
For LBO145DABR12-A
47B
3/4 HP direct drive motor
B40113-02
For LBO145DABR34-A
48
Blower support bracket
B40072-02
49
Rubber grommet #19
Z01F006
Quantity: 4
50
Blower support bracket
B40072-01
51A
Blower wheel 120-9T (1/2 HP motor)
N/A
For LBO145DABR12-A
51B
Blower wheel 120-9T (3/4 HP motor)
N/A
For LBO145DABR34-A
52A
Blower 120-9T (1/2 HP motor)
Z01I015
For LBO145DABR12-A (Housing and wheel)
52B
Blower 120-9T (13/4 HP motor)
Z01I012
For LBO145DABR34-A (Housing and wheel)
53A
Blower ass'y (1/2 HP motor)
B40135-01
For LBO145DABR12-A (item 42 to 57 included)
53B
Blower ass'y (3/4 HP motor)
B40135-02
For LBO145DABR34-A (item 42 to 57 included)
54
Blower electrical kit
B40081
55
Bushing 7/8" OCB-875
L04G013
Quantity: 2
56
Terminal block
L99F003
57
Terminal plug-in .250
L03J005
58
Electrical box
B40066
Box only
59
Fan limit control
R02I006
60
Relay SPDT 120VAC
L01H011
Quantity: 2
61
Terminal strip, 6 positions
A00294
62
Burner electrical kit
B40080
63
Rocker switch SPST
B01291-02
33
DNS-0663 Rev. C
Model : FLO115DABR-A & OLF140C12A
PART LIST
34
Model : FLO115DABR-A & OLF140C12A
PART LIST
ITEM DESCRIPTION NUMBER COMMENTS
1 Paper filter 20 x 20 x 1 Z04F004 2 Blower door B40381 3 Top back panel B40356 4 Paper filter 10 x 20 x 1 Z04F001 5 Fan limit control 5" R02I006 6 Plenum divider B40353 7 Division panel B40382 8 Heat exchanger B40385 "Combustion chamber " included
9 Right side panel ass'y B40380-01Item 10, 11, included 10 Side panel insulation B01526-82 11 Right filter rack B40374-01 12 Side deflector B40358 Quantity required per unit: 2 13 Gasket, smoke outlet B40360 14 Rocker switch SPST L07F003 15 Electric box B40066 Box only 16 Relay SPDT 120 vac L01H011 Quantity required per unit: 2 17 Terminal block 6 positions A00294 18 Bushing 7/8 L04G001 19 Burner electrical kit B40080 20 Electric box cover B40384 Label "electrical diagram " included 21 Gasket, burner panel B40359 22 Burner panel B40376 23 Observation door B02282 "Observation door gasket" included 24 Observation door spring A00183-01 25 Vis TYP F Hex 1/4-20 x 11/4 F03F023 26 Hex nut 3/8-16NC zinc F07F011 Quantity required per unit: 4 27 Washer 3/8 zinc F06F005 Quantity required per unit: 4 28 Corner conduit B40070-01 29 Strain relief bushing L04I013 30 Front panel B40378-01 Insulation" included 31 Front panel insulation B40379 32 Heat shield B40371 33 Combustion chamber B40161 34 Floor ass'y B40383 35 Left side panel ass'y B40380-02 36 Left filter rack B40374-02 37 Strain relief bushing L04I005 38 Blower electrical kit B40081 39 Left blower support B40072-02 40 Right blower support B40072-01 41 Motor 1/2 HP B40112-02 "Motor mount" included 42 Motor mount Z01I016 43 Terminal block 6 positions L99F003 44 Terminal strip B40074 45 Capacitor holder B01024 46 10 MF capacitor L01I003 47 Terminal plug-in .250 L03J005 48 Electric box cover B40059 49 Strain relief bushing L04G013 50 Blower wheel 10 X 10 Z01L004 51 Blower 10 X 10 Z01I001 "Blower wheel" included 52 Blower 10 X 10 ass'y B40386 53 Grommet Z01F006 Quantity required per unit: 4
Loading...