ICP C8DNL050B12B1, C8DNL075F16B1, C8DNL100F14B1, C8DNL100L20B1, C8DNL125L20B1 Installation Guide

...
80+SingleStage
DedicatedDownflow
*8DNL
CategoryI Furnace
See section 4 for Category I definition.
* Denotes Brands (C, H, T)
SAFETY REQUIREMENTS
Recognize safety information. This is the safety-alert symbolZl._. When you see this symbol on the furnace and in instruction manuals be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards, those that will result in severe personal injury or death. WARNINGsignifiesahazardthatcouldresultinpersonalinjuryor
death. CAUTIONis used to identify unsafe practices that may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions that will result in enhanced installation, reliability, or operation.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels at-
tached to or shipped with the furnace and other safety precautions that may apply. Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) ANSI Z223.1-2002/NFPA
54-2002. In Canada, refer to the National Standard of Canada Natural Gas and Propane Installation Code (NSCNGPIC) CSA B149.1-05. Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instruc- tions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We
require these instructions as a minimum for a safe installation.
International Comfort Products, LLC Lewisburg, TN 37097
INSTALLER: Affix these instructions on or adjacent to the furnace.
CONSUMER: Retain these instructions for future reference.
Table of Contents
1. Safe Installation Requirements ................ 3
2. Installation ............................... 4
3. Combustion & Ventilation Air ................. 6
4. Gas Vent Installation ........................ 9
5. Horizontal Venting ......................... 11
6. Masonry Chimney Venting ................... 13
Portions ofthe textand tablesare reprinted from NFPA54 / ANSI Z223,1-2002©, with permission ofNational Fire Protection Association, Quincy, MA 02269 andAmerican Gas Association, Washington, DC 20001. Thisreprinted material is not the complete and official position ofthe NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
PrintedinU.S.A. 11/10/2005 441 01 2314 (02)
7. GasSupplyandPiping ....................... 16
8. ElectricalWiring ........................... 18
9. Ductworkand Filter ......................... 19
10.Checks and Adjustments..................... 23
11.FurnaceMaintenance........................ 27
12.Sequence of Operation&Diagnostics ........... 28
TechSupportand Parts......................... 31
CARBON MONOXIDE POISONING AND FIRE
HAZARD. Failure to follow safety warnings exactly could
result in serious injury, death, and/or property damage.
This furnace is not designed for use in mobile
homes, trailers or recreational vehicles.
START-UP CHECK SHEET
(Keep this page for future reference)
Recommended, but not required,
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone: Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Type of Gas:
Blower Motor H.P,:
Supply Voltage:
Limit Opens at...(°F) or(°C).
Natural: _1 LP: _1
Business Card Here
Manual Gas Shut-Off Upstream of Furnace/Drip- Leg?
Drip-Leg Upstream of Gas Valve?
Blower Speed Checked? YES _1
All Electrical Connections Tight?
Gas Valve turned ON? YES _1
Measured Line Pressure When Firing Unit:
Calculated Firing Rate:(See Checks and Adjustments
Section).
YES_I NO_I
YES_I NO_I
NO [_I
YEs_I NO[31
NO[_I
Limit Closes at,,,(°F)___or(°C)
Which blower speed tap is used? (Heating) (Cooling).
Temperature of Supply Air: (°F)___or(°C)
Temperature of Return Air: (°F) or(°C)__
Rise (Supply Temp.-Return Temp.): (°F) or(°C)__
Filter Type and Size:
Fan "Time ON" Setting:.
Fan "Time OFF" Setting:
Dealer Comments:
Measured Manifold Pressure:
Thermostat OK? YES _1
Subbase Level? YES _1
Anticipator Set? YES _1
Breaker On? YES _1
Date of Installation:
Date of Start-Up:
NOE_
NOE_I
NO E_ Set At?:
NoE_I
441 01 2314 02
1. Safe Installation Requirements
FIRE, EXPLOSION, AND ASPHIXIATION HAZARD Improper adjustment, alteration, service,
maintanence or installation could cause death, personal injury, and/or property damage.
Installation or repairs made by unqualified persons could result in hazards to you and others.
Installation MUST conform with local codes or, in
the absence of local codes, with codes of all
governmental authorities havingjurisdiction.
The information contained in this manual is
intended for use by a qualified service agency that is experienced in such work, is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools
and test instruments.
This furnace is NOT approved for installation in mobile homes, trailers or recreation vehicles.
Seal around supply and return air ducts.
Install correct filter type and size.
Unit MUST be installed so electrical components are pro- tected from direct contact with water.
Safety Rules
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However,
abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
A,
The U.S. Consumer Product Safety Commission encourages installation of carbon monoxide alarms. There can be various
sources of carbon monoxide in a building or dwelling. The sources could be gas-fired clothes dryers, gas cooking
stoves, water heaters, furnaces, gas-fired fireplaces, wood fireplaces.
NOTE: This furnace is design-certified by CSA International (for- merly AGA and CGA) for installation in the United States and Can-
dada. Refer to the appropriate codes, along with this manual, for proper installation.
Use onlythe Type of gas approved for this furnace (see Rat- ing Plate on unit). Overfiring will result in failure of heat ex- changer and cause dangerous operation. (Furnaces can be converted to L.P. gas with approved kit.)
Install this furnace only in a location and position as speci- fied in "2. Installation"of these instructions.
Provide adequate combustion and ventilation air to the fur- nace as specified in "3. Combustion and Ventilation Air" of
these instructions.
Combustion products must be discharged outdoors. Con- nect this furnace to an approved vent system only, as speci- fied in "4. Gas Vent Installation, 5, Horizontal Venting and 6. Masonry Chimney Venting"of these instructions.
Never test for gas leaks with an open flame. Use a commer- cially available soap solution made specifically for the detec-
tion of leaks to check all connections, as specified in "7. Gas Supply and Piping, Final Check"of these instructions.
Always install furnace to operate within the furnace's in- tended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in" Technical Support Manual"of these instruc- tions. See furnace rating plate.
Carbon monoxide can cause serious bodily injury and/or death. Carbon monoxide or "CO" is a colorless and odorless
gas produced when fuel is not burned completely or when the flame does not receive sufficient oxygen.
Therefore, to help alert people of potentially dangerous ca rbon monoxide levels, you should have a commercially available
carbon monoxide alarm that is listed by a nationally recog- nized testing agency in accordance with Underwriters Labora- tories Inc. Standard for Single and Multiple Station Carbon
Monoxide Alarms, ANSI/UL 2034 or the CSA 6.19-01 Resi- dential Carbon Alarming Devices installed and maintained in
the building or dwelling concurrently with the gas- fired furnace installation (see Note below). The alarm should be installed as
recommended by the alarm manufacturer's installation in- structions.
B,
There can be numerous sources of fire or smoke in a building or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have
fire extinguisher and smoke alarms listed by Underwriters Lab- oratories installed and maintained in the building or dwelling
(see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type of alarms.
C. To ensure safe and efficient operation of your unit, you should
do the following:
When a furnace is installed so that supply ducts carry air cir- culated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed as specified in "2. Installation"of these in-
structions.
This furnace is not to be used for temporary heating of build- ings or structures under construction. See "2, Installation,
item 10 "
441 01 2314 02
1. Thoroughly read this manual and labels on the unit. This will help you understand how your unit operates and the haz- ards involved with gas and electricity.
Do not use this unit if any part has been under water. Im- mediately call a qualified service agency to inspect the unit and to replace any part of the control system and any gas control
which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide air to the unit. Air must be provided for proper combustion and ventilation of flue gases.
Frozen Water Pipe Hazard .yourfurnace remains off for an extended time, the pipes in your
WATER DAMAGE TO PROPERTY HAZARD
Failure to protect against the risk of freezing could result in property damage.
Do not leave your home unattended for long periods during freezing weather without turning off
home could freeze and burst, resulting in serious water damage.
If the structure will be unattended during cold weather you should take these precautions.
Turn off the water supply to the structure and drain the water lines if possible and add an antifreeze for potable water to
drain traps and toilet tanks. Open faucets in appropriate areas.
-or-
water supply and draining water pipes or otherwise
protecting against the risk of frozen pipes and resultant damage.
Your furnace is designed solely to provide a safe and comfortable living environment. The furnace is NOT designed to ensure that
water pipes will not freeze. It is equipped with several safety de- vices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.
Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes
from freezing. Instruct them on a service agency to call to provide service, if required.
-or-
3. Install a reliable remote sensing device that will notify some- body of freezing conditions within the home.
2. Installation
Do NOT install furnace directly on carpeting, tile or other com- bustible material. See 9, Ductwork and Filter Sub-base for
CARBON MONOXIDE POISONING HAZARD.
Failure to properly vent this furnace or other appliances could result in death or personal injury.
If this furnace is replacing a previously common- vented furnace, it may be necessary to resize the existing vent system to prevent oversizing prob-
lems for the other remaining appliances(s). See
Venting and Combustion Air Check in the 4. Gas Vent Installation section of this instruction.
Location and Clearances
If furnace is a replacement, it is usually best to install the furnace where the old one was. Choose the location or evaluate the exist-
ing location based upon the minimum clearance and furnace di- mensions (Figure 1).
CARBON MONOXIDE POISONING HAZARD.
Failure to follow safety warnings exactly could result in death or personal injury.
Do NOT operate furnace in a corrosive atmosphere containing chlorine, fluorine or any other damaging chemicals, which could shorten
furnace life.
Refer to 3. Combustion & Ventilation Air section,
Contaminated Combustion Air for combustion air evaluation and remedy.
Installation Requirements
1,
Install furnace level.
2.
This furnace is NOT to be used for temporary heat of buildings or structures under construction.
3.
Install furnace as centralized as practical with respect to the heat distribution system.
4.
Install the vent pipes as short as practical. (See 4. Gas Vent Installation section).
Combustible Floors.
6. Maintain clearance for fire safety and servicing. A front clear- ance of 24" is minimum for access to the burner, controls and
filter. See clearance requirements in Figure 1.
7. Use a raised base if the floor is damp or wet at times.
8. Residential garage installations require:
Burners and ignition sources installed at least 18" (457 mm) above the floor.
Furnace must be located or physically protected from possible damage by a vehicle.
9. If the furnace is to be suspended from the floorjoists in a base- ment or a crawl space or the rafters in an attic, it is necessary to use steel pipe straps or an angle iron frame to attach the fur- nace. These straps should be attached to the furnace bottom side with sheet metal screws and to the rafters or joists with
bolts. The preferred method is to use an angle iron frame bolted to the rafters or joists.
10. This furnace may be used for construction heat provided that:
The furnace is permanently installed with all electrical wir- ing, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative
pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion prod-
ucts into the structure. The furnace is controlled by a thermostat. It may not be
"hot wired" to provide heat continuously to the structure without thermostatic control.
Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the entrain- ment of drywall dust into combustion air, which can cause
fouling and plugging of furnace components.
The temperature of the return air to the furnace is main- tained between 55 ° F (13 ° C) and 80 ° F (27 ° C), with no
evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to
the rating plate value.
441 01 2314 02
The filters used to clean the circulating air during the construction process must be either changed or thorough-
ly cleaned prior to occupancy. The furnace, ductwork and filters are cleaned as neces- sary to remove drywall dust and construction debris from
all HVAC system components after construction is com-
pleted.
Dimensions and Clearances (*8DNL)
Verify proper furnace operating conditions including igni- tion, gas input rate, air temperature rise, and venting ac- cording to these installation instructions.
281/2
_-J 313116
LEFT SIDE
fl°'T i
11/16
_ 213/16
2415/16
0"
FRONT
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL FURNACES
REAR 0 FRONT (combustion air openings 3"
in furnace and structure)
_E
11/16
Required For Service *24"
ALL SIDES Of SUPPLY PLENUM 1" SIDES 0 VENT
Single-Wall Vent 6" Type B-1 Double-Wall Vent 1"
TOP OF FURNACE 1"
"30" clearancerecommendedfor casingremoval.
See Section9.DuctworkandFiiter, Sub-basesforCombustibleFloors-
FurnaceONLYandDownflowCoilAdapterBox sectionsofthismanual
for installationoncombustibleconstruction.
-- 181/2
RIGHTSIDE
Drawing is representative, but some models may vary
165/8 nil 6
NOTE: Evaporator "A" coil drain pan dimen- sions may vary from furnace duct opening size. Always consult evaporator specifica- tions for duct size requirements.
Furnace is designed for top return ONLY.
Return air through back of furnace is NOT allowed.
DIMENSIONAL INFORMATION
Unit Cabinet Top Bottom
Capacity A B C D
*8DNL050B12 151/2 14 5
*8DNL075B12
*8DNLO75F16 191/8 175/8 73/4 1711116
*8DNL1OOF14 8DNL1OOL20 241/2 23 107116 231/8
*8DNL125L20 Dentoes Brand
Furnace Installation
Inspect the rating plate to be certain the model number begins with "*8DNL". This identifies the furnace as a dedicated downflow fur-
nace that is permitted to be Installed in a Downflow position. (see Figure 2).
* Denotes Brand
24 3/16
5/16 141/8
121/16 _3
3/4
DIMENSIONS IN INCHES
Downflow
FIRE HAZARD. Failure to install furnace on noncombustible
subbase could result in death, personal injury and/or property damage.
Place furnace on noncombustible subbase on downflow applications, unless installing on
noncombustible flooring.
40
441 O1 231402 [_
The minimum clearances to combustion construction MUST be maintained between the furnace and adjacent construction, as
shown in Figure 1. In addition to clearances in Figure 1, clearance for the vent pipe
must be considered. A su bbase for combustible floors MUST be used when the furnace
is installed on combustible material. See "9. DuctworkandFilter't
3. Combustion & Ventilation Air
CARBON MONOXIDE POISONING HAZARD.
Failure to provide adequate combustion and
ventilation air could result in death or personal
injury. Use methods described here to provide
combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open- ings for supplying combustion and ventilation air must comply with the gas codes, or in the absence of local codes, the applicable na-
tional codes.
Combustion and ventilation air must be supplied in accordance with one of the following:
1. Section 8.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, (NFGC), ANSI Z223.1-2002/NFPA 54-2002 in the U.S.,
2. Sections 7.2, 7.3, 7.5, 7.6, 7.7, and 7.8 of National Standard of Canada, Natural Gas and Propane Installation Code
(NSCNGPIC), CSA B149.1-05 in Canada,
3. Applicable provisions of the local building code.
When the installation is complete, check that all appliances have adequate combustion air and are venting properly. See Venting
And Combustion Air Check in "4. Gas Vent Installation "Section in this manual.
Contaminated Combustion Air
Installations in certain areas or types of structures could cause ex- cessive exposure to contaminated air having chemicals or halo- gens that will result in safety and performance related problems
and may harm the furnace. These instances must use only out- door air for combustion.
The following areas or types of structures may contain or have ex- posure to the substances listed below. The installation must be
Typical Downflow Installation
RETURN
AIR
GAS SUPPLY
SUPPLY
AIR
25-24-38
evaluated carefully as it may be necessary to provide outdoor air for combustion.
Commercial buildings.
Buildings with indoor pools.
Furnaces installed in laundry rooms.
Furnaces installed in hobby or craft rooms.
Furnaces installed near chemical storage areas.
Permanent wave solutions for hair.
Chlorinated waxes and cleaners.
Chlorine based swimming pool chemicals.
Water softening chemicals.
De-icing salts or chemicals.
Carbon tetrachloride.
Halogen type refrigerants.
Cleaning solvents (such as perchloroethylene).
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid.
Sulfuric Acid.
Solvent cements and glues.
Antistatic fabric softeners for clothes dryers.
Masonry acid washing materials.
Outdoor Combustion Air Method
A space having less than 50 cubic feet per 1,000 BTUH input rating for all gas appliances installed in the space requires outdoor air for
combustion and ventilation.
Air Openings and Connecting Ducts
1. Total input rating for all gas appliances in the space MUST be considered when determining free area of openings.
2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings MUST be no smaller than 1/4" mesh.
4. The minimum dimension of air ducts MUST NOT be less than
3 _ .
When sizing a grille, louver, or screen use the free area of opening. If free area is NOT stamped or marked on grill or lou-
ver, assume a 20% free area for wood and 60% for metal. Screens shall have a mesh size not smaller than 1/4".
441 01 2314 02
Requirements
1. Provide the space with sufficient air for proper combustion and ventilation of flue gases using horizontal or vertical ducts or openings.
2. Figure 3 illustrates how to provide combustion and ventilation
Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
air when two permanent openings, one inlet and one outlet, are used.
a. One opening MUST commence within 12" of the floor and
the second opening MUST commence within 12" of the ceiling.
b. Size openings and ducts per Table 1.
ThisinstallationNOTapprovedinCanada
GasVent GableVent)
/
.,1'
Gas Vent j_Gable Vent
VentilatedAttic'S.
SoffitVent J_utlet Air(1) Outle_
II _. Air(1) [_
I F...... _G%
Air(1) _' _ _ -- Inlet
;pace
MinimumOne InletandOneOutlet AirSupply is Required
May be in andCombination Shown Inlet Air OpeningMustbeWithin12"(300mm)offloor OutletAir OpeningMustbe Within12"(300mm)ofceiling
(1) 1 SquareInch (6cm2) per 4000 BTUH (2) 1 Square Inch(6cmz) per 2000 BTUH
c. Horizontal duct openings require I square inch of free area
per 2,000 BTUH (1,100 mmZ/kW) of combined input for all
gas appliances in the space (see Table 1).
d. Vertical duct openings or openings directlycommunicating
with the outdoors require 1 square inch of free area per
4,000 BTUH (550 mm2/kW) for combined input of all gas
appliances in the space (see Table 1).
3. When one permanent outdoor opening is used, the opening requires:
a. 1 sq. in of free area per 3,000 BTUH (700 mm2/kW) for
combined input of all gas appliances in the space (see Table 1) and
b. not less than the sum of the areas of all vent connectors in
the space.
The opening shall commence within 12" of the top of the enclo- sure. Appliances shall have clearances of at least I "from the sides
and back and 6" from the front. The opening shall directly commu-
II " SoffitVent
-- Air (2) Inlet
nicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
4. Combination of Indoor and Outdoor Air shall have:
a.
Indoor openings that comply with the Indoor Combus-
-, i I I,n,e`
Air(1)
_ '_ _ _ Air (2)
tion Air Method below and
b.
Outdoor openings located as required in the Outdoor Combustion Air Method above and
C.
Outdoor openings sized as follows.
1) Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method.
2) Outdoor opening size reduction Factor is 1 minus the Ratio in 1) above.
3) Minimum size of Outdoor openings shall be the size re- quired in Outdoor Combustion Air Method above multi- plied by reduction Factor.
Area
BTUH MinimumFree Area RequiredforEachOpeningor Ductto Outdoors
Input TwoHorizontalDucts SingleOpening Openings (sq. in./4,000
Rating (sq.in./2,000BTUH) (sq. in./3,000BTUH) (sq.in./4,000 BTUH) BTUH)
50,000 25sq. in. 16.7sq. in, 12.5sq. in, 4" 75,000 37,5 sq. in. 25sq. in. 1825 sq. in. 5"
100,000 50sq, in. 33.3sq.in, 25sq. in. 6" 125,000 62.50sq. in. 41.7sq. in. 31.25 sq. in. 7" 150,000 75sq. in. 50sq. in. 37.5sq. in. 7"
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input 100,000 + 30,000 (130,000 + 4,000) 32.5 Sq. In. Vertical
Furnace Water Heater Total Input 100,000 + 30,000 (130,000 + 2,000) 65 Sq. In. Horizontal
44101 231402
TwoVerticalDuctsor RoundDuct
Indoor Combustion Air Standard and Known-Air-Infiltration Rate Methods
© NFPA&AGA
Indoor air is permitted for combustion and ventilation, if the Stan- dard or Known-Air-Infiltration Rate Method is used.
CARBON MONOXIDE POISONING HAZARD.
Failure to supply adequate combustion air could result in death or personal injury.
Most homes will require additional air from outdoors for combustion and ventilation. A space
with at least 50 cubic feet per 1,000 BTUH input
rating or homes with tight construction may need outdoor air, supplied through ducts, to supplement air infiltration for proper combustion and
ventilation of flue gases.
iiiiiiiiiiiiiiiiiiiii_i;_;:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_i:_:i_!!!!_ii!#_;i!_#_;i!i!;i_iiiii_ii_iiiiiiiiiii;i#;ii;ii;ii;ii;ii;i
ACH
0.60 1,050 1,400 1,750 1250 3,125 3,750
0.50 1,260 1,680 2,100 1,500 3,750 4,500
0.40 1,575 2,100 2,625 1,875 4,688 5,625
0.30 2,100 2,800 3,500 2,500 6250 7,500
0.20 3,150 4200 5,250 3,750 9,375 11,250
0.10 6,300 8,400 10,500 7,500 18,750 22,500
0.00 NP NP NP NP NP NP
MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS (ft 3)
Other Than Fan-Assisted Total
(1,OOO'sBtuh)
30 40 50 50 125 150
The Standard Method may be used, if the space has no less vol-
ume than 50 cubic feet per 1,000 BTUH input rating for all gas ap- pliances installed in the space. The standard method permits
indoor air to be used for combustion and ventilation air. The Known Air Infiltration Rate Method shall be used if the in-
filtration rate is known to be less than 0.40 air changes per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates
greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and
add the volumes together to get the total minimum required vol- ume for the space.
Fan-assistedTotal
(1,000'sBtuh)
75 100
1,875 2,500 2,250 3,000
2,813 3,750 3,750 5,000 5,625 7,500
11,250 15,000
NP NP
NP = Not Permitted Table 2 Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54-2002, 8.3.3.2:
1. For other than fan-assisted appliances such as a draft
hood-equipped water heater,
Volume other - ACH 1000Btu / hr
2. For fan-assisted appliances such as this furnace,
Volume fan = ACH 1000Btu ! hr
21 ft 3 ( ! other )
15ft3 ( Iran )
If:
[ other = combined input of all other than fan-assisted
appliances in Btu/hr
[ ran = combined input of all fan-assisted appliances in Btu/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to
the Known Air Infiltration Rate Method.
Adjoining rooms can be considered part of a space, if there
are no closable doors between rooms.
Combining spaces on the same floor level. Each opening
shall have a free area of at least 1 square inch/1,000 BTUH (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 square inch (0.06 m2). Once opening shall commence within 12" (300 mm) of the
ceiling and the second opening shall commence within 12" (300 mm) of the floor. The minimum dimension of air open-
ings shall be at least 3 in. (80 mm).
An attic or crawl space may be considered a space that freely communicates with the outdoors provided there are adequate ventilation openings directly to outdoors. Openings MUST re- main open and NOT have any means of being closed off. Ven- tilation openings to outdoors MUST be at least I square inch of free area per 4,000 BTUH of total input rating for all gas ap- pliances in the space.
In spaces that use the Indoor Combustion Air Method, in- filtration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings
with unusually tight construction, additional air MUST be pro-
vided using the methods described in section titled Outdoor
Combustion Air Method:
Unusually tight construction is defined as Construction with:
1. Walls and ceilings exposed to the outdoors have a continu- ous, sealed vapor barrier. Openings are gasketed or
sealed and
2,
Doors and openable windows are weather stripped and
3.
Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Ventilation Air
Some provincial codes and local municipalities require ventilation or make-up air be brought into the conditioned space as replace-
ment air. Whichever method is used, the mixed return air tempera- ture across the heat exchanger MUST not fall below 60 ° continuously, or 55 ° on an intermittent basis so that flue gases will
not condense excessively in the heat exchanger. Excessive con- densation will shorten the life of the heat exchanger and possibly void your warranty.
441 O1 2314 02
4. Gas Vent Installation
CARBON MONOXIDE POISONING, FIRE AND
EXPLOSION HAZARD.
Failure to properly vent this furnace could result in death, personal injury and/or property damage.
Read and follow all instructions in this section.
Install the vent in compliance with codes of the country havingju- risdiction, local codes or ordinances and these instructions.
This Category ] furnace is fan-assisted. A fan assisted appliance
is an appliance equipped with an integral mechanical means to ei- ther draw or force products of combustion through the heat ex- changer.
Category ] furnace definition: A central furnace which operates 8. with a non-positive vent static pressure and with a flue loss not
less than 17 percent. These furnaces are approved for common- venting and multi-story venting with other fan-assisted or draft 9.
hood-equipped appliances in accordance with the NFGC or NSCNGPIC.
Category [ Safe Venting Requirements
Category [ furnace vent installations shall be in accordance with Parts 10 and 13 of the National Fuel Gas Code (NFGC), ANSI
Z223.1-2002/N FPA 54-2002; and/or Section 7 and Appendix C of the CSA B149.1-05, National Standard of Canada, Natural Gas
and Propane Installation Code; the local building codes; furnace and vent manufacturer's instructions.
NOTE: The following instructions comply with the ANSI Z223.1/NFPA 54 National Fuel Gas Code and CSA B149.1 Natu-
ral Gas and Propane Installation code, based on the input rate on the furnace rating plate.
1,
If a Category ] vent passes through an attic, any concealed space or floor, use ONLY Type B or Type L double wall vent pipe. If vent pipe passes through interior wall, use Type B vent
pipe with ventilated thimble ONLY.
2,
Do NOT vent furnace into any chimney serving an open fire- place or solid fuel burning appliance.
3.
Use the same diameter Category ] connector or pipe as per- mitted by:
the National Fuel Gas Code Code (NFGC) ANSI Z223.1-2002 / NFPA 54-2002 sections 10 and 13 venting
requirements in the United States
or
the National Standard of Canada Natural Gas and Pro- pane Installation Code (NSCNGPIC) CSA B149.1-05
section 7 and appendix C venting requirements in Canada.
Push the vent connector onto the furnace flue collar of the venter assembly until it touches the bead (at least 5/8" overlap)
and fasten with at least two field-supplied, corrosion-resist- ant, sheet metal screws located at least 140 ° apart.
5. Keep vertical Category [ vent pipe or vent connector runs as short and direct as possible.
6,
Vertical outdoor runs of Type-B or ANY single wall vent pipe below the roof line are NOT permitted.
7.
Slope all horizontal runs up from furnace to the vent terminal a minimum of 1/4" per foot (21 ram/m).
Rigidly support all horizontal portions of the venting system ev- ery 6' or less using proper clamps and metal straps to prevent sagging and ensure there is no movement after installation.
Check existing gas vent or chimney to ensure they meet clear- ances and local codes. See Figure 1
10.
The furnace MUST be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction. Venting into an unlined ma-
sonry chimney or concrete chimney is prohibited. See the
6. Masonry Chimney Venting section in these instruc-
tions.
11.
Fan-assisted combustion system Category [ furnaces shall not be vented into single-wall metal vents.
12.
Category [ furnaces must be vented vertically or nearly verti- cally, unless equipped with a listed mechanical venter.
13.
Vent connectors serving Category I furnaces shall not be con- nected into any portion of mechanical draft systems operating
under positive pressure.
A 4-to-3 inch reducer is permitted at the flue collar when installing a 50,000 Btuh gas input furnace, if the installation meets all the fol-
lowing requirements for sizing the vent connectors and vents:
1. The National Fuel Gas Code, ANSI Z223.1/NFPA-54-2002, sections 10.5.3.1(1),
10.6.3.1(2), 10.10.3.1, 13.1.2, 13.1.10, and 13.2.21(1) through (3) in the U.S. or
2. The Natural Gas and Propane Installation Code CSA B149.1-05, sections 7.13.1 (b), 7.13.2(b), 7.18.5(b), and Appendix C-GVR no. 2. in Canada.
441 01 2314 02 [_
Venting and Combustion Air Check
NOTE: When an existing Category I furnace is removed or re- placed, the original venting system may no longer be sized to prop-
erly vent the attached appliances, and to make sure there is adequate combustion air for all appliances, MAKE THE FOL-
LOWING CHECK.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation, could result in carbon monoxide poisoning or death:
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the
venting system are not in operation:
1.Seal any unused openings in the venting system.
2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI
Z223. 1/NFPA 54 or CSA B 149. 1,Natural Gas a nd Propane
Installation Code and these instructions. Determine that
there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3.As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4.Close fireplace dampers.
5.Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, sothey are operating at maximum speed. Do not operate a summer exhaust fan.
6.Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7.Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. (Figure 4)
8.If improper venting is observed, during any of the above tests, the venting system must be corrected in accordance
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149, 1, Natural Gas and Propane Installation
Code.
9.After it has been determined that each applia nce connected to the venting system properly vents when tested as out-
lined above, return doors, windows, exhaust fans, fireplace
dampers and any other gas-fired burning appliance to their
previous conditions of use.
Vent Check
VentPipe _1 I A/ Draft Hood
Typical Gas Water Heater
! !
NOTE: If Elaine p_ulls towards draft hoo_, this indicates sufficient infiltration air.
Venting to Existing Masonry Chimney
Dedicated venting of one fan assisted furnace into any ma- sonry chimney is restricted. A chimney must first be lined with
either Type B vent sized in accordance with NFGC tables 13.1 or
13.2 or a listed metal lining system, sized in accordance with the NFGC section 13.1.7 for a single appliance or 13.2.19 for multiple appliances, or NSCNGPIC Appendix C, section 10. (See Section 6
Masonry Chimney Venting of these instructions.)
Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized in the U.S. by using NFGC tables per
13.1.7 for dedicated venting and per 13.2.19 for common venting with the maximum capacity reduced by 20% (0.80 X maximum ca- pacity) and the minimum capacity as shown in the applicable table. Corrugated metal vent systems installed with bends or offsets re-
quire additional reduction of 5% of the vent capacity for each bend up to 45 ° and 10% of the vent capacity for each bend from 45 ° up to
90 °. In Canada, use the NSCNGPIC.
NOTE: Two(2) 45 ° elbows are equivalent to one (1) 90 ° elbow.
Combined Venting into a Masonry Chimney
Venting into a masonry or concrete chimney is only permitted as outlined in the NFGC or NSCNGPIC venting tables. Follow
all safe venting requirements.
Note: See section "6. Masonry Chimney Venting'.
_] 441 01 2314 02
5. Horizontal Venting
Category I Furnaces With External Power Venters
In order to maintain a Category ] classification of fan-assisted fur- naces when vented horizontally with sidewall termination, a power
venter is REQUIRED to maintain a negative pressure in the vent- ing system.
In the U.S.: Per the NFGC, a listed power venter may be used, when approved by the authority having jurisdiction.
In Canada: Only power venters approved by the appliance manufacturer and where allowed by the authority having jurisdic-
tion may be used.
Please consult the Fields Controls Co. or Tjernlund Products, Inc. for power venters certified for use with this furnaces.
Vent Termination
Venting Through a Non-Combustible and Combustible Wall
Consult External Power Venter manufacturer instructions.
Select the power venter to match the Btuh input of the furnace be- ing vented. Follow all of the power venter manufacturer's installa- tion requirements included with the power venter for:
venting installation,
vent terminal location,
preventing blockage by snow,
protecting building materials from degradation by flue gases,
see Figure 5 for required vent termination. NOTE: It is the responsibility of the installer to properly terminate
the vent and provide adequate shielding. This is essential in order to avoid water/ice damage to building, shrubs and walkways.
441 01 2314 02 [_
iiiiiiiiiiiiiiiiii;ii_;;_i:_i:_i;!;!:;!_i_ii!_!ii_i:_:i::_;_i_!_!_i!ii!ii!ii!ii!ii!ii!ii!ii!ii!ii!ii!_i!;iiiiiiiii_iiiiiiiiiiiiiiiiiiiiiii_!!!;!_i¸ii;ilililiiiiiiiiiiiiiiiiiiiiiiii_i_i_ii!!!iiiii
Other than Direct Vent Termination Clearance
r_ VENT TERMINAL
Item Clearance Descriptions
A Clearance above grade, veranda, porch, deck, balcony, or
anticipated snow level
B Clearance to a window or door that may be opened
(_ AIR SUPPLYINLET
Canadian Installation(1)
12" (30cm)#
6" (lfi cm) for appliances_<10,000BTUH(3kW), 12" (30 cm)forappliances> 10,000Btub(3kW) and _<100,000Btub
AREA WHERE TERMINAL IS NOT PERMITED
U.S. Installation (2)
12" (30 cm)
4' (1.2 m) below or to the side of the opening. 1' (30 cm)
above lhe opening.
(30 kW),36" (01 cm) forappliances> 100,000Btuh(30kW)
C
Clearance to a permanently closed window
D
Vertical clearance to a ventilated soffit located above the terminal within a horizontal distance of 2' (61cm) from the
centedine of the terminal
E
Clearance to an unventilated soffit
F
Clearance to an outside corner
G
Clearance to an inside corner
H
Clearance to each side of the centefline extended above electrical meter or gas service regulator assembly
I
Clearance to service regulator vent outlet
J
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
K
Clearanceto amechanicalair supplyinlet
L
Clearanceundera veranda,porch,deck,or balcony
M
Clearance to each side of the centefline extended above or below vent terminal of the furnace to a dryer or water heater
vent, or other appliance's direct vent intake or exhaust.
N
Clearance from a plumbing vent stack
0
Clearanceabovea pavedsidewalkor paveddrivewaylocated
3' (91 cm) within 15' (4.5 m) above the meter/regulator assembly
3' (01 cm)
6" (15cm)forappliances_<lO,OOOBTUH (3kW),12" (30 cm) for appliances > 10,000 Btuh (3 kW) and _<100,000 Btuh
(30 kW), 36" (01 cm) for appliances > 100,000 Btuh (30 kW)
6' (1.83 m)
12" (30 cm) +
3' (01cm) 7' (2.13m)
3' (91 cm) within 15' (4.5 m) above the meter/regulator
assembly
4' (1.2 m) below or to the side of opening: 1' (30 cm) above
opening.
3' (91 cm) above if within 10' (3m) horizontally
3' (01cm) 7' (2.13m)
on publicproperty.
(1.) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code (2,) In accordance with the currem ANSI Z223.1/NFPA fi4, National Fuel Gas Code
# 18" (46 cm) above roof surface + Permitted only if veranda, porch, deck, or balcony isfully open on a minimum of two sides beneath the floor.
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B140.1, clearances shall be in accordance with local installation codes and the requiremenls of the gas supplier and the manufacture's installation instructions.
A vent shall nol terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
Notes:
1, The vent for this appliance shall not terminate
a. Over public walkways; or b. Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard or property damage; or c. Where condensate vapor could cause damage or could be detrimental to the operafion of regulators, relief valves, or other equipment.
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combusfiob products of adjacent vents. Recirculafion can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
441 01 2314 02
6. Masonry Chimney Venting
Chimney Inspection
All masonry chimney construction must conform to Standard ANSI/NFPA 211-2003 and to any state or local codes applicable. The chimney must be in good condition and a complete chimney
inspection must be conducted prior to furnace installation. If the in- spection reveals damage or abnormal conditions, make neces- sary repairs or seek expert help. See "The Chimney Inspection
Chart" Figure 6. Measure inside area of tile-liner and exact height of chimney from the top of the chimney to the highest appliance
flue collar or drafthood outlet.
Connector Type
To reduce flue gas heat loss and the chance of condensate prob- lems, the vent connector must be double-wall Type B vent.
Venting Restrictions for Chimney Types
Interior Chimney - has no sides exposed to the outdoors below the roofline. All installations can be single furnace or common vented with another draft hood equipped Category ] appliance.
Exterior Chimney - has one or more sides exposed to the out- doors below the roof line. All installations with a 99% Winter De-
sign Temperature* below 17°F must be common vented only with a draft hood equipped Category I appliance.
The99%WinterDesignDry-Bulb(db)temperaturesarefoundinthe1993ASHRAE
FundamentalsHandbook,Chapter24, Table1(UnitedStates)and2(Canada),or usethe99.6%heatingdbtemperaturesfound inthe1997or2001ASHRAEFunda- mentalsHandbook,ClimaticDesignInformationchapter,Table1A (UnitedStates)
and 2A (Canada).
Ifa claytile-lined masonry chimney is being used and it is exposed to the outdoors below the roof line, relining might be required.
Chimneys shall conform to the Standard for Chimneys, Fire- places, Vents, and Solid Fuel Burning Appliances ANSI/NFPA
211-2003 in the United States and to a Provincial or Territorial Building Code in Canada (in its absence, the National Building
Code of Canada) and must be in good condition.
U.S.A.- Refer to Sections 13.1.9 or 13.2.20 of the N FGC or the au- thority having jurisdiction to determine whether relining isrequired.
If relining is required, use a properly sized listed metal liner, Type-B vent, or a listed alternative venting design.
This model (*8DNL) is NOT listed for use with Chimney Adapter kits. A multi-position furnace in the downflow position that is listed
for use with one of the Chimney Adapter Kits NAHAOOIDH or NAHAOO2DH may be used with a masonry chimney.
Canada (and U.S.A.)-This furnace is permitted to be vented into a clay tile-lined masonry chimney that is exposed to the outdoors
below the roof line, provided:
1. Vent connector is Type-B double-wall, and
2. This furnace is common vented with at least 1 draft hood-
equipped appliance, and
The combined appliance input rating is less than the maxi- mum capacity given in Table A, and
CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD.
Failure to properly vent this furnace could result in death, personal injury and/or property damage.
These furnaces are CSA (formerly AGA and CGA design-certified for venting into exterior clm
tile-lined masonry chimneys with a factory accesso ry Chimney Adapter Kit. Refer to the furnace rating
31atefor correct kit usage. The Chimney Adapter Kits
are for use with ONLY furnaces having a Chimne_ Adapter Kit number marked on the furnace ratin i
plate.
The input rating of each space-heating appliance is greater than the minimum input rating given in Table B for Masonry Chimneys for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table B,
and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting de- sign shall be used, such as a listed chimney-lining system, or a
Type-B vent.
441 01 2314 02 [_
Exterior Masonry Chimney,
FAN+NAT Installations with
Type-B Double-Wall Vent Connectors
© NFPA&AGA
Table A-
Combined Appliance
Maximum Input Rating in
Thousands of Btu per Hr
VENT
HEIGHT
(FT)
6
8 10 15
20 30
INTERNAL AREA OF
(SQ IN.) 12 19 28 74 119 178
80 130 193 84 138 207
NR 152 233 NR NR 250 NR NR NR
CHIMNEY
38
257 279 299 334 368 404
Table B-
Minimum Allowable Input Rating of
Space-Heating Appliance in
Thousands of Btu per Hr
VENT
HEIGHT
(FT)
Local 99% Winter Design Temperature: 17 to 26 ° F*
6
8
o 10
2O 30
Local 99% Winter Design Temperature: 5 to 16° F*
_" 10
0
,_ 15
20 30
Local 99% Winter Design Temperature: -10 to 4° F*
6
8
o 10
o is
i
2O
30
-11 ° F Local 99% Winter Design Temperature: -11 ° F or or lower*
lower Not recommended for any vent configuration
The 99% Winter Design Dry-Bulb (db) temperatures are found in the 1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and 2 (Canada), or use the 99.6% beating db temper-
atures found in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A
(Canada).
INTERNAL AREA OF CHIMNEY
(SQ IN.)
12 19 28 38
0 55 99 141
52 74 111 154
NR 90 125 169 NR NR 167 212 NR NR 212 258
NR NR NR 362
NR 78 121 166 NR 94 135 182 NR 111 149 198
NR NR 193 247 NR NR NR 293
NR NR NR 377
NR NR 145 196 NR NR 159 213
NR NR 175 231 NR NR NR 283 NR NR NR 333
NR NR NR NR
Inspections before the sale a nd at the time of installation will deter- mine the acceptability of the chimney or the need for repair and/or
(re)lining. Refer to the Chimney Inspection Chart to perform a chimney inspection.
If the inspection of a previously used tile-lined chimney:
a. Shows signs of vent gas condensation, the chimney should
be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner or Type-B vent to reduce condensation. If a condensate drain is required by local code, refer to the
NEGC, Section 10.9 for additional information on conden- sate drains.
b. Indicates the chimney exceeds the maximum permissible
size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equipment being installed and the authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good con- dition, shall be rebuilt to conform to AN SI/N FPA 211 or be lined with
a UL listed (ULC listed in Canada) metal liner or UL listed Type-B vent. Relining with a listed metal liner or Type-B vent is consid-
ered to be a vent-in-a-chase. If a metal liner or Type-B vent is used to line a chimney, no other
appliance shall be vented into the annular space between the chimney and the metal liner.
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, ad-
justed, and operated properly, the venting system and/or the ap-
pliances should not suffer from condensation and corrosion. The venting system and all appliances shall be installed in accordance
with applicable listings, standards, and codes. The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates
can be made using approved methods available from Air Condi- tioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air-Conditioning Engineers; or other
approved engineering methods. Excessive oversizing of the fur- nace could cause the furnace and/or vent to fail prematurely.
When a metal vent or metal liner is used, the vent or liner must be in good condition and be installed in accordance with the vent or liner
manufacturer's instructions. To prevent condensation in the furnace and vent system, the fol-
lowing precautions must be observed:
1. The return-air temperature must be at least 60°F db except for brief periods of time during warm-up from setback at no
lower than 55°F db or during initial start-up from a standby condition.
Adjust the gas input rate per the installation instructions. Low gas input rate causes low vent gas temperatures, ca us- ing condensation and corrosion in the furnace and/or vent-
ing system. Derating is permitted only for altitudes above 2000'.
3. Adjust the air temperature rise to the midpoint of the rise range or slightly ahove. Low air temperature rise ca n ca use
low vent gas temperature and potential for condensation problems.
4. Set the thermostat heat anticipator or cycle rate to reduce short cycling.
Air for combustion must not be contaminated by halogen com- pounds which include chlorides, fluorides, bromides, and iodides.
These compounds are found in many common home products such as detergent, paint, glue, aerosol spray, bleach, cleaning sol-
vent, salt, and air freshener, and can cause corrosion of furnaces and vents. Avoid using such products in the combustion-air sup-
441 01 2314 02
ply. Furnace use during construction of the building could cause the furnace to be exposed to halogen compounds, causing prema-
ture failure of the furnace or venting system due to corrosion. Vent dampers on any appliance connected to the common vent
CHIMNEY INSPECTION CHART
Foradditionalrequirementsreferto theNationalFuelGasCodeNFPA54/ANSIZ223.1-2002 andANSIINFPA211-2003Chimneys,Fire-
places,Vents,andSolid Fuel BurningAppliancesintheU.S.A. orto theCanadianInstallationCodeCSAB149.1-05 in Canada.
condition: Rebuild
Missing mortar crown
orbrick?
I
,_ withclay tile No
Yes
can cause condensation and corrosion in the venting system. Do not use vent dampers on appliances common vented with this fur-
Race.
linerand top sealingood
metalvent, fuel oil
residue?
Remove metal vent or liner.
_,,_stile n_isalignrnent, Yes p-
ingsections,
No No adapter venting Not Suitable
lineror top seal
orreline chimnei'as_
IRepair
Reline
Mortar or Remove mortar
file debris? and tile debris?
- _ instructions for / i,
/ _ \ application/
Condensate /,sObi e, " tab,iy
drainage atbottom _ < _:_r _'-]Vl Suitable
ofchimney? _ TvDe-Bven_/ vo_[ _ Linechim!ywitbpropedy
"' / '_[ InstallchimneyI sized,listedflexiblemetal
_. / I adaprerper I linerorType-BventperNFGCor
No Tv^_ I andlinerorventmanufacturer's
T. I _ NSCNGPICVentSizingTables
._ [ /_ Not Suitable instal]ationinstructions.
Chimney . , / IsChimnevto _ t,,_J_ /PartCofchimney_
be,owroof,ine? Yes _. U_nUalUe'_u;nace./ j_rT-"_, _ ,nstructionsfor |
/ _ , / Consul__
_.3,_ _ _2_uT ' _ adapter venting S_le
\ _ / I \ apl_!ica!i°n / _'
/ [ _,uitability/ I installchimney
441 01 2314 02 [_
7. Gas Supply and Piping
CARBON MONOXIDE POISONING, FIRE AND
EXPLOSION HAZARD. Failure to follow safety warnings exactly could
result in death, personal injury and/or property damage.
Models designated for Natural Gas are to be used
with Natural Gas ONLY, unless properly converted to use with LP gas.
Listed Flexible GasAppliance
Connector if
11o4
Se_c%
IO]
Typical Gas Piping ('8DNL)
GasSupply Requirements
Use only the Type of gas approved for this furnace. See rating plate for approved gas type.
Gas input must not exceed the rated input shown on the rating plate. Overfiring will result in failure of heat exchanger and
cause dangerous operation.
Do not allow minimum supply pressure to vary downward. Do- ing so will decrease input to furnace. Refer to Table 3 for gas supply. Refer to Table 5 or Table 6 for manifold pressures.
i I Pressures
Gas Type Supply Pressure
Recommended Max.
Natural 7" 14"
Propane 11" 14"
GasPiping Requirements
NOTE: The gas supply line must be installed bya qualified service
technician in accordance with all building codes. NOTE: In the state of Massachusetts.
a. Gas supply connections MUST be performed by a li-
censed plumber or gas fitter).
b. When flexible connectors are used, the maximum length
shall not exceed 36" (915 ram).
c. When lever handle type manual equipment shutoff valves
are used, they shall be T-handle valves.
d. The use of copper tubing for gas piping is NOT approved.
1,
Install gas piping in accordance with local codes, or in the ab- sence of local codes, the applicable national codes.
2.
It is recommended that a manual equipment shutoff valve be installed in the gas supply line outside the furnace. Locate
valve as close to the furnace as possible where itis readily ac-
cessible. Refer to Figure 7.
Min, 4,5"
11"
union
Drip leg & pipe cap _.
\
Gas control valve
Elbows & 25-25-17
short nipples
3. Use black iron or steel pipe and fittings or other pipe approved by local code.
4. Use pipe thread compound which is resistant to natural and LP gases.
5. Use ground joint unions and install a drip leg no less than 3" long to trap dirt and moisture before it can enter gas control
valve inside furnace.
6. Provide a 118" NPT plugged tapping for test gauge connection immediately up stream of gas supply connection to furnace.
7. Use two pipe wrenches when making connections to prevent gas valve from turning.
NOTE: If local codes allow the use of a flexible gas appliance con- nector, always use a new listed connector. Do not use a connector which has previously served another gas appliance.
8. Flexible corrugated metal gas connector may NOT be used in- side the furnace or be secured or supported by the furnace or
ductwork.
9. Properly size gas pipe to handle combined appliance load or run gas pipe directly from gas meter or LP gas regulator.
10. Install correct pipe size for run length and furnace rating.
11. Measure pipe length from gas meter or LP second stage regu- lator to determine gas pipe size.
Left Side Gas Supply Piping
Gas line can be installed directly to the gas valve through the hole provided in the left side of the cabinet. See Figure 7
Right Side Gas Supply Piping
FIRE HAZARD Failure to follow safety warnings exactly could
result in death, personal injury and/or property damage.
Use wrench to hold furnace gas control valve when
turning elbows and gas line to prevent damage to the
gas control valve and furnace.
_] 441 01 2314 02
Two(2) 90 ° street elbows or two(2) 90 ° standard elbows and two(2) close nipples are required for right side gas supply. See Figure 7.
Piping with Street Elbows
1. Assemble the elbows so that the outlet of one(l) elbow is 90 ° from the inlet of the other. The elbows should be tight enough
to be leak proof. An additional 1/4 turn will be required at the end of step 2, see Figure 8.
2. Screw elbow assembly into gas valve far enough to be leak proof. Position el bow assembly so that the inlet of the el bow is
at the bottom of the gas valve. An additional 1/2 turn will be re- quired in step 3. Turn open end of inlet elbow to face the right side of the furnace (1/4 turn), see Figure 9.
3. Turn assembly an additional 1/2 turn to position inlet near the top of the gas valve and in line with gas opening on right side of
furnace, see Figure 7 and Figure 10.
iiiiiiiiiiiiiiiiiiiiiiiii:iiiiiii;;;i_i¸!!iii!ilil!!!!!!!i!!!iiiii¸;I i!iliiii¸i¸Ii;¸
E,bows *aDNL
25-23-23c
Gas Valve with Elbows (*8DNL)
25-25-03
Gas Valve with Elbows (*aDNL)
FIRE OR EXPLOSION HAZARD. Failure to properly install metal gas connector could
result in death, personal injury and/or property damage.
A flexible corrugated metal gas connector must be
properly installed, shall not extend through the side of the furnace, and shall not be used inside the
furnace.
Black iron pipe shall be installed at the furnace gas
control valve and extend a minimum of 2" outside furnace.
Additional LP Piping Requirements
Have a licensed LP gas dealer make all connections at storage tank and check all connections from tank to furnace.
If copper tubing is used, it MUST comply with limitation set in Local Codes, orin the absence of local codes, the gas codes of the country having jurisdiction.
Two-stage regulation of LP gas is recommended.
FIRE OR EXPLOSION HAZARD.
A natural gas or LP gas leak ignited by an open flame or spark could result in death, personal injury
and/or property damage. Natural gas is lighter than air and will rise. Liquefied
petroleum (LP) gas is heavier than air and will settle and remain in low areas and open depressions.
Thoroughly ventilate area and dissipate gas. Do
NOT use a match or open flame to test for leaks, or attempt to start up furnace before thoroughly
ventilating area.
25-25-12
4. Gas supply line then can be run directly into opening of elbow.
Piping with Close Nipples and Standard Elbows
1. Assemble elbows and nipples similar to street elbows shown in Figure 8.
2. Follow steps 2 through 4 Piping with Street Elbows.
FinalCheck
Test all pipes for leaks.
If orifices were changed, make sure they are checked for leaks.
During pressure testing of gas supply piping system:
a. If test pressure does not exceed 1/2 psi, isolate the
furnace from the gas supply piping system by closing the equipment shutoff valve.
b. If test pressure exceeds 1/2 psi, the furnace and its
manual equipment shutoff valve must be disconnected from the gas supply piping system.
To check for leaks apply soap suds or a liquid detergent to each joint. Bubbles forming indicate a leak.
Do not use an open flame to test for gas leaks. Fire or explo- sion could occur.
Correct even the smallest leak at once.
441 01 2314 02 [_
8. Electrical Wiring
ELECTRICALSHOCK HAZARD. Failure to follow safety warnings exactly could
result in death or personal injury.
Turn OFF electrical power at fuse box or service
panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
7. Position all wires away from sharp edges and moving parts. Do not pinch J-box or other wires when reinstalling blower compartment door.
Thermostat
Thermostat location has an important effect on the operation of the furnace. Follow instructions included with thermostat for correct
mounting and wiring.
Low voltage connections to furnace must be made on terminal board of furnace control. (See Figure 11)
Power Supply Wiring
The furnace MUST be electrically wired and grounded in accor- dance with local codes, or in the absence of local codes, with the
National Electrical Code (NEC), ANSI/NFPA 70-2002 in the U.S., or the Canadian Electrical Code (CEC), CSA C22.1 in Canada.
The power supply to the furnace connections must be between 104 VAC and 127 VAC during furnace operation for acceptable
performance.
Field wiring connections must be made inside the furnace connec- tion box. A suitable strain relief should be used at the point the wires exit the furnace casing.
Copper conductors shall be used. Line voltage wires should conform to temperature limitation of 63 ° F (35 ° C) rise. Wire and circuit breaker sizing shall be based on the ampacity of the furnace
electrical components plus the amps for all installed accessories (1.0 amps toni for EAC and HUM). Ampacity can be determined by using the NEC or CEC.
NOTE: Furnace will not have normal operation is line polarity is re- versed. Check ALL field and control connections prior to opera-
tion.
Furnace must be installed so the electrical components are pro- tected from water and connected to its own separate circuit.
J- Box Relocation
The J-box is installed on left side of casing. An alternate J-box location on right side can be used.
1. Remove bag containing two hole plugs and two self-tapping screws from loose parts bag in blower compartment.
2. Remove and discard two screws holding J-box to casing.
3. Move large hole plug from right to left J-box location.
4. Move J-box to alternate location and attach using two self- tapping screws from bag.
5. A wire tie may need to be cut for additional wire length.
6. Apply two hole plugs from bag at left J-box location.
If cooling is used, the Y from the thermostat must be connected to the control board Y to energize cooling blower speed.
Set thermostat heat anticipator in accordance with the Technical
Support Manual.
Heat anticipator setting will need to be measured if 24VAC humidi- fier is installed. Measure currentin series from R to W at thether-
mostat. Be sure 24VAC humidifier is wired up to control. Allow furnace to operate for 2 minutes before recording the AC amper-
age reading. Set anticipator on thermostat to recorded value.
Optional Equipment
All wiring from furnace to optional equipment MUST conform to lo- cal codes or, in the absence of local codes, the applicable national
codes. Install wiring in accordance with manufacturer's instruc- tions.
Humidifier/Electronic Air Cleaner
The furnace is wired for humidifier and/or electronic air cleaner connection.
REDUCED FURNACE LIFEHAZARD
Failure to follow caution instructions may result in reduced furnace life.
Do NOT exceed 115V/1.0 amp. maximum current load for both the EAC terminal and the HUM
terminal combined.
HUMIDIFIER - The HUM (115VAC) is energized when the pressure switch closes on a call for heat. The HUM is ener-
gized when the inducer is energized.
ELECTRONIC AIR CLEANER - EAC is energized when there
is a blower speed call, except is NOT energized when blower operates in the hard-wired continuous fan mode.
_] 441 01 2314 02
llSV. 60Hz.
-- BOX
Ground
_tat
Therm°_ i @
t i t i i i i i
1 'I'
, I,I
Electrical Connections
24VAC HUM_4 P
Jumperi
FUSE
Control Connections
%
DiagnosticLight
HUM
Low Voltage Terminal Board
O
NOTE: 115 VAC/6OHz/single-phase 25-25-13
Operating voltage range*: 127 VAC max, 104 VAC min.
* Permissible limits of voltage at which unit will operate satisfactorily
Furnace Control
The furnace control is preset at the factory with ON delay of 30 sec- onds in the heating mode. The blower OFF timing is preset at 140 seconds. If desired, the fan OFF delay can be reset to obtain the longest delay times while still maintaining comfort levels. See "Furnace Wiring Diagram".
9. Ductwork and Filter
CARBON MONOXIDE POISONING HAZARD.
Failure to properly seal duct could result in death or personal injury.
Do NOT draw return air from inside a closet or utility room where furnace is located. Return air duct
MUST be sealed to furnace casing.
FIRE HAZARD. Failure to install furnace on noncombustible
subbase could result in death, personal injury and/or property damage.
Place furnace on noncombustible subbase on downflow applications, unless installing on
non-combustible flooring.
Duct Connections
This furnace may be installed in only a top return-air application. Return air duct connection through the side(s) or back of the fur-
44101 231402
25-24-98
Furnace Control Fuse
The 24V circuit contains a 5-amp, automotive-type fuse located on furnace control. (See Figure 12) Any electrical shorts of 24V wiring during installation, service, or maintenance may cause fuse
to blow. If fuse replacement is required, use only a fuse of identical size (5 amp.).
nace is NOT permitted. Supply duct connection is permitted to ONLY the bottom of the furnace.
Duct Design
Design and install the air distribution system to comply with Air Conditioning Contractors of America manuals or other approved methods that conform to local codes and good trade practices.
When the furnace is located in an area near or adjacent to the living area, the system should be carefully designed with returns to mini-
mize noise transmission through the supply and return air grilles. Any blower moving a high volume of air will produce audible noise
which could be objectionable when the unit is located very close to a living area. It is often advisable to route the supply air ducts un-
der the floor and return air ducts through the attic.
Refer to furnace Technical Support Manual (BlowerData) for airflow information.
Size ductwork to handle airflow for heating and air conditioning if used.
Duct Installation Requirements
When a furnace is installed so that supply ducts carry air circu- lated by the furnace to areas outside of the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space
containing the furnace.
Eil
CARBON MONOXIDE POISONING HAZARD.
Failure to follow safety warning exactly could result in death or personal injury.
Install cooling coil on furnace discharge. Cool air
passing over heat exchanger could cause condensate to form resulting in heat exchanger failure.
When the furnace is used with a cooling unit, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element.
With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled
air from entering the furnace. Chilled air going through the fur- nace could cause condensation and shorten furnace life.
Dampers (purchased locally) can be either automatic or manu- al. Manually or automatically operated dampers MUST be equipped with a means to prevent furnace or air conditioning
operation, unless damper is in the full heat or cool position
Installation of locking-type dampers is recommended in all branches, or in individual ducts to balance system's air flows.
Non-combustible, flexible duct connectors are recommended for return and supply connections to furnace.
If air return grille is located close to the fan inlet, install at least one, 90 ° air turn between fan and inlet grille to reduce noise.
Ductwork installed in attic, or exposed to outside temperatures requires a minimum of 2" of insulation with outdoor type vapor
barrier.
Ductwork installed in an indoor unconditioned space requires a minimum of 1" of insulation with indoor type vapor barrier.
Inspection Panel on Some Models
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that the heat excha nger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air stream. This access cover shall be attached in such a manner as
to prevent air leaks.
Sub-Bases for Combustible Floors - Furnace Only
The Subbase for Combustible Floors MUST be used when a downflow furnace is set on a combustible floor, even when the fur-
nace is installed on a coil box. NOTE: Supply opening is 37/8" from the rear of the furnace.
Therefore maintain a 37/8 ', clearance from a wall behind the fur- nace (where applicable).
1. Cut the opening in the floor according to the dimensions in Table 4 because the base is equipped with locating tabs that
center the base over the opening. The opening in the base is 11/4" shorter and 11/8" narrower
than the minimum required size of the opening in the floor. This is done to maintain a 1" clearance between the floor and the
plenum.
2. Fabricate the plenum to the dimensions given in Table 4. Note that the dimensions given are outside dimensions.
Table 4
sub-base for
Combustible Floors
Part Number
Furnace Only
NAHHOOISB NAHHOO2SB
NAHHOIOSB
Subbase for Coil Box
NAHHOO4SB NAHHOOSSB NAHHOO9SB
Outside Dimension
_ Base Spacer Side To Side
3.
Set the base over the opening in the floor, centering the open- ing in the base over the opening in the floor. Fasten the base to the floor with screws or nails. See Figure 13 and Figure 14.
4,
Drop the plenum through the opening in the base. The flange of the plenum should rest on top of the combustible floor base.
Sub-bases for Combustible Floors Dimensions
sub-base for Combustible
Floor Dimensions
N _
1511/16
195/16
24J/4
1511/16
195/16
24]]/16
J* K**
283/4 149/16 283/4 183/16
28J/4 239/16
209/16 149/16 209/16 183/16
209/16 239/16
Opening In Floor
L M N
16 16114 14518 16 16114 18114
16 16]/4 235/8
16 161/4 145/8 16 161/4 181/4
16 16]/4 235/8
Opening In
Base For Plenum
P R
15 131/2 15 171/8
15 221/2
15 131/2 15 171/8
15 221/2
Typical Plenum
Dimensions
15 15
15
15 15 15
131/2 171/8
221/2
131/2 171/8
221/2
_] 441 01 2314 02
Exploded View of Sub-Base for Furnace ONLY
Plenum
S
H
J
Exploded View of Base for Downflow Cased Coil
Plenum
Subbase Insulation
Combustible Floor Base
25-21-46b
Setting the Base
Plenum
Wood Floor
25-20-46A
Combustible
Floor Base
25-21-46b
Consideration must be given to the height of the base to allow for easy installation of the condensate drain. See Figure 17. This
subbase for combustible floors has been designed so that the height of the subbase ra ises the downflow coil off the floor to allow easy installation of the condensate drain
Setting the Base
co,
Subbase
Insulation /
Wood Screw _ _ _ Plenum 25-20-46A
Sub-base for Combustible Floors- Downflow Coil Adapter Box
The subbase for combustible floors is required when a downflow furnace, used with a downflowcoilbox, is set on combustible
flooring.
NOTE: Supply opening is 3 /8' from the rear of the furnace. There- fore maintain a 37/8 " clearance from wall (where applicable).
1,
Cut the opening in the floor according to the dimensions in Table 4 because the base is equipped with locating tabs that center the base over the opening.
The opening in the base is 11/4" shorter and 11/8" narrower than the minimum required size of the opening in the floor. This
is done to maintain a 1" clearance between the floor and the plenum.
2,
Fabricate the plenum to the dimensions in Table 4. Note that the dimensions given are outside dimensions.
3.
Set the base over the opening in the floor, centering the open- ing in the base over the opening in the floor. Fasten the base to
the floor with screws or nails. See Figure 15 and Figure 16.
4.
Drop the plenum through the opening in the base. The flange of the plenum should rest on top of the combustible floor base.
44101 231402
7
Condensate Line Raised by Base
25-20-52
Non-Combustible Floor:
Set the furnace over the opening in the floor. If necessary, grout around the base to seal air leaks between the base and the floor.
Filters:
A filter MUST be used. The 181/4" X 1 53/4" framed high-velocity filters supplied with the
furnace may be installed in the return air plenum above the fur- nace. A filter rack is supplied with each furnace. See Figure 18.
Use either filter type:
Washable, high-velocity filters are based on a maximum air flow rating of 600 FPM.
Disposable,lowvelocityfiltersarebasedonamaximumair flowof300FPMwhenusedwithexternalfiltergrille.
i See page 33, Circulation Air Blower Data for additional infor-
mation.
REDUCED FURNACE LIFE HAZARD Failure to follow caution instructions may result in
reduced furnace life.
Use of excessively dirty and/or restrictive air filters may increase furnace operating temperatures and shorten the life of the furnace.
Filters supplied with the furnace are rated at a maximum of 600 fpm air velocity and sized for the furnace's airflow rate. Replacement filters must be of
equivalent type, size, and rating except as described below.
Disposable, low-velocity filters may be used to replace washable, high-velocity filters, providing
they are sized for 300 FPM or less.
Filter Rack Installation
If there is insufficient plenum height for this type of installation, fil- ters may be installed in any accessible location in the return air
system. In such a case, the filters should be of equivalent size and style as originally supplied with the furnace.
Filter Installation
Version "A'"
,,A,, l 14" (350mm)
25-25-14
OR
Version "B"
Version "A"
factory-attached to the top of the blower housing
25-25-14a
OR
Version "B"
factory-supplied but field installed
NOTE: The return air plenum MUST extend a sufficient height above the furnace (dimension "A" in Figure 19) to provide for the
attachment of a return air duct or grille above the filters.
NOTE: Plenum must be fitted as close to the return air flange of the furnace as possible to eliminate any air bypassing the filters.
Filters can only be installed through the right hand side of the fur- nace blower opening. Slide filter into furnace until it is in position to
be pushed up and over into place on the left hand side of furnace. See Figure 19.
Slide remaining filter into furnace and up into place on right hand side of furnace. See Figure 19.
16"
(400mm)
The redesigned filter bracket needs to be centered on top of the flanges spanning the depth of the flange opening. Position it sothe
"V" portion is between the inner sides of the flanges with the flat tabs are resting on top of the flange edges. The tabs can then be
bent over the flanges on both ends by hand or by tapping lightly with a hammer to secure the bracket to the top of the furnace. (see Figure 18)
No further attachment is necessary. Once the plenum is attached to the top of the furnace the bracket will not move. The bracket will look like Figure 18 after being formed onto the flanges.
Filter Removal
1. Remove blower compartment door.
2. Reach up above right side of blower and lift dirty filters out of rack at top of furnace.
3. Straighten up filters and pull straight down at side of blower. Pull out through right door opening.
4. Vacuum clean or wash with warm water and dry thoroughly be- fore replacing.
_] 441 O1 2314 02
NOTE: If filters are only suitable for heating application, ad- vise homeowner that filter size may need to be increased if air
conditioning is added.
Addition Of Air Conditioning
When a refrigeration coil is used in conjunction with this furnace, it must be installed on the discharge side of the furnace to avoid con- densation on the heat exchanger. The coil installation instructions
10. Checks and AdJustments
Startup
NOTE: Refer to startup procedures in the Users Information Manual.
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZRD. Failure to follow safety warnings exactly could result
in death, personal injury, and/or property damage. If any sparks, odors or unusual noises occur,
immediately shut OFF gas and power to furnace. Check for wiring errors or obstruction to blower.
must be consulted for proper coil location and installation proce- dures. With a parallel flow arrangement, dampers must be
installed to prevent chilled air from entering the furnace. If ma nual- ly operated dampers are used, they must be equipped with a means to prevent operation of either unit unless the damper is in
full heat or full cool position.
Copper or plastic tubing may be used for the condensate drain line.
iiiiiiiil!!!!! ii¸I¸iiiiii_¸I¸ !!i!!iiil;;i;;iiiiiiiiiiiiiiii;iiiiiii
Typical Gas Control Valve
RegulatorAdjustment UnderCa
Inlet Pressure
Tap1/8NPT
HONEYWELL
©o
Outlet Pressure
Tap
1/8NPT
/
OUTLET
25-24-98a
GasSupplyPressure
Gas supply pressure should be within minimum and maximum val- ues listed on rating plate. Pressures are usually set by gas suppli-
ers.
(See L.P. Gas Conversion Kit instruction manual for furnaces con- verted to L.P. gas)
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners oper- ating.
FIRE OR EXPLOSION HAZARD.
Failure to turn OFF gas at shut off before connecting manometer could result in death, personal injury and/or property damage.
Turn OFF gas at shut off before connecting
manometer.
1. With gas OFF, connect manometer to manifold pressure tap on outlet of gas control valve. See Figure 20. Use a manome- ter with a 0" to 12" water column range.
2.
Turn gas ON. Operate the furnace by using a jumper wire on the R to W thermostat connections on the control.
3.
Remove manifold pressure adjustment screw cover on fur- nace gas control valve. Turn screw counterclockwise to de-
crease manifold pressure and clockwise to increase pressure. See Figure 20.
NOTE: Adjustment screw cover MUST be replaced on gas control valve before reading manifold pressure and operating furnace.
44101 231402
4. Set manifold pressure to value shown in Table 5 or Table 6.
5. When the manifold pressure is properly set, replace the adjust- ment screw cover on the gas valve.
Remove jumper wire from thermostat connection on control. Remove manometer connection from manifold pressure tap,
6.
and replace plug in gas valve.
7. Check for leaks at plug.
Natural Gas Input Rating Check
The gas meter can be used to measure input to furnace. Check with gas supplier for actual BTU content.
1. Turn OFF gas supply to all appliances other than furnace and start furnace. Use jumper wire on R to W.
2. Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution.
Note: If meter uses a 2 cubic foot dial, divide results (seconds) by two.
Refer to Example. The Example is based on a natural gas BTU content of 1,000 BTU's per cubic foot.
Example
Natural Gas No. of Seconds Time Per Cubic BTU Per
BTU Content Per Hour Foot in Hour
per cu, foot Seconds
1,000 3,600 48 75,000
1,000 x 3,600 + 48 = 75,000 BTUH
Refer to Example. The Example is based on a natural gas BTU content of 1,000 BTU's per cubic foot.
3. Remove jumper wire from R to W.
4. Relight all appliances and ensure all pilots are operating.
Orifice Sizing
NOTE: Factory sized orifices for natural and LP gas are listed in the furnace Technical Support Manual.
Ensurefurnaceisequippedwiththe correct main burner orifices.
Refer to Table 5 or Table 6 for correct orifice size and manifold pressure for a given heating value and specific gravity for natural
and propane gas.
Operation Above 2000' Altitude
FIRE, EXPLOSION, CARBON MONOXIDE POISONING HAZARD.
Failure to follow safety warnings exactly could result in death, personal injury and/or property damage.
This high-altitude gas-conversion shall be done by a
qualified service agency in accordance with the
Manufacturer's instructions and all applicable codes and requirements, or in the absence of local codes, the applicable national codes.
These furnace may be used at full input rating when installed at al- titudes up to 2000'. When installed above 2000', the input must be decreased 2% (natural gas) or 4% (LP gas) for each 1000' above
sea level in the USA. In Canada, the input rating must be derated 5% (natural) or 10 _ (LP) for each 1000' above sea level. This may be accomplished by a simple adjustment of manifold pressure or an orifice change, or a combination of a pressure adjustment and
an orifice change. The changes required depend on the installa- tion altitude and the heating value of the fuel. Table 5 & Table 6
show the proper furnace manifold pressure and gas orifice size to achieve proper performance based on elevation above sea level for both natural gas and propane gas.
o
To use the natural gas table, first consult your local gas utility for the heating value of the gas supply. Select the heating value in the
first column and follow across the table until the appropriate eleva- tion for the installation is reached. The value in the box at the inter-
section of the altitude and heating value provides not only the manifold pressure but also the orifice size. In the natural gas
tables, the factoy-shipped orifice size is in bold (42). Other sizes must be obtained from service parts.
High Altitude Input Rate =
NamElevationeplate Sea Level Input Rate x (Multiplier)[USA]
Elevation
2001'-3000' 3001'-4000'
4001'-5000' 5001'-6000' 6001'-7000' 7001'-8000'
* Based on mid-range of elevation.
High Altitude Multiplier
Natural Gas
0.95
0.93
0.91
0.89
0.87
0.85
LP Gas
0.90
0.86
0.82
0.78
0.74
0.70
MANIFOLD PRESSUREAND ORIFICE SIZE FOR HIGH ALTITUDEAPPLICATIONS
NATURAL GAS MANIFOLD PRESSURE (" w.c.)
MEAN ELEVATION FEET ABOVE SEA LEVEL
HEATING
VALUE
at ALTITUDE
BTU/CU. FT.
7OO 725 75O 775 8OO 825 85O 875 9OO 925 95O
975 1000 1050 1100
NOTE: Natural gas data is based on 0.60 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1-2002/NFPA 54-2002 or National Standard of Canada, Natural Gas And Propane Installation Code CSA B149.1-05.
0 to 2001 to 3001 to 4001 to 5001 to
2000 3000 4000 5000 6000
Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold
No. Pressure No. Pressure No. Pressure No. Pressure No. Pressure
41 3.6 42 3.6 42 3,3
42 3.7 42 3.4 42 3.1 41 3.7 41 41 3.5 41
41 3.6 42 3.6 42
42 3,7 42 3,4 42 41 3.7 42 3.5 42 3.3 42 41 3.5 42 3,3 42 3,1 42 42 3.7 42 3.2 42 2.9 42 42 3,5 42 3,0 42 2.8 42 42 3,2 42 2,7 42 2,5 44 43 3.6 42 2.5 44 3.2 45 3.6
3.6 42 3,5 42 3.2 42 2,9
3.4 42 3.3 42 3.0 42 2.8
3.4 42 3.1 42 2.8 42 2.6
3.2 42 2,9 42 2.7 42 2,5
3.0 42 2,8 42 2.5 44 3.3
2.9 42 2.6 42 2.4 44 3.1
2.7 42 2.5 44 3.2 45 3.6
2.6 42 2.4 45 3.7 45 3.4
3.3 45 3.6
6001 to 7001 to
7000 8000
Orifice Manifold Orifice Manifold
No. Pressure No. Pressure
41 3.7 41 3.7 41 3.4 41 3.5 42 3,6
_] 441 01 2314 02
LPG or PROPANE GAS MANIFOLD PRESSURE (" w.c.)
HEATING VALUE
at ALTITUDE
BTU/CU, FT.
2500
Orifice Size
NOTE: The derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design-certified by CSA. In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 above sea level. Use
the 2001 to 3000 column in Table 5 and Table 6.
NOTE: The derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design-certified by CSA.
0 to 2001 to 3001 to 4001 to 5001 to
2000 3000 4000 5000 6000
10.0 10.0 9.0 10.0 9.4 #54 #54 #54 #55 #55
The burner orifice part nos. are as follows: Orifice #41 1096942 Orifice #42 1011351
Orifice #43 1011377 Orifice #44 1011352 Orifice #45 1011353 Orifice #54 1011376 Orifice #55 1011354 Orifice #56 1011355
MEAN ELEVATION FEET ABOVE SEA LEVEL
6001 to 7001 to
7000 8000
8.5 10.0
#55 #56
Clearances
Measure from face of orifice to the
( I back side of the manifold,
High Altitude Air Pressure Switch
The factory-installed pressure switch need NOT be changed for any furnace installations from sea level up to and including 8,000'
altitude. See service parts for use above 8,000' altitude.
Changing Orifices
1. After disconnecting power and gas supply to the furnace, re- move the burner compartment door, exposing the burner compartment.
2. Disconnect gas line from gas control valve so manifold can be removed.
3. Disconnect wiring at gas control valve. Be sure to note the proper location of all electrical wiring before being discon-
nected.
4.
Remove the four (4) screws holding the manifold and gas con- trol valve to the manifold supports. Do not discard any screws.
See Figure 21.
5. Carefully remove the manifold assembly.
8. Reassemble all parts in reverse order as removed. Be sure to engage the main burner orifices in the proper openings in the
burners.
9. After reassembling, turn gas on and check all joints for gas leaks using a soapy solution. All leaks must be repaired imme-
diately.
LP Conversion
the furnace rating plate for the LP conversion accessory kit part An accessory kit shall be used to convert to propane gas use, see
number.
Manifold
O
6.
Remove the orifices from the manifold and replace them with proper sized orifices. See Figure 22.
7.
Tighten orifices so they are seated and gas-tight. See Figure 22.
44101 231402
25-25-15
CARBON MONOXIDE HAZARD. Failure to follow this warning can result in
death, property damage and/or personal
injury. Nox inserts for use with Natural Gas units
ONLY. If LP Gas is required, NOx inserts must be removed.
FIRE, EXPLOSION, UNIT DAMAGE HAZARD. Failure to follow this warning can result in
death, property damage and/or personal injury.
An LP conversion accessory kit is required
when operating the furnace with LP gas.
For LP conversion remove screws that secure the NOx insert and discard insert.
Reinstall screws. See Figure 23
NOTE: It is very important to reinstall the NOx insert mounting Air Temperature Rise Check screws.
iiiiiiiiiiiiiiiiiiiiiiiiiiiii_i_i!:!!!!i_!ill¸II¸II¸I¸;i;_i!i_i_i_i_ii!i!i!!!!!!i!_;_;_;_;_;_;_;_;_;_i_i!iiiiiiiiiiiiiii_iii!!_iiiiiiiii_i;;i_i_i!i!_!;;!iiiiii!_
Removing NOx inserts
REDUCED FURNACE LIFE HAZARD Failure to properly set the air temperature rise may
result in reduced furnace life. Use ONLY the blower motor speed taps marked "Y" for
YES for setting air temperature rise.
Main Burner Flame Check
Allow the furnace to run approximately 10 minutes. Then inspect the main burner and pilot flames. See Figure 24.
Check for the following (Figure 24):
Stable and blue flames. Dust may cause orange tips or wisps of yellow, but flames MUST NOT have solid, yellow tips.
Flames extending directly from burner into heat exchanger.
Flames do NOT touch sides of heat exchanger
If any problems with main burner flames are noted, it may be nec- essary to adjust manifold gas pressure, or check for drafts.
Main Burner
Blower Motor Speed Taps for
ModelSizes
050B12 Y N 075B12 Y Y 075F16 Y Y
100F14 Y Y 100J20 Y Y
100L20 Y Y 125L20 Y Y
The blower speed MUST be set to give the correct air temperature rise through the furnace as marked on the rating plate. Tempera-
ture rise is the difference between supply and return air tempera-
tures.
To check temperature rise, use the following procedure:
1. Place thermometers in supply and return air registers as close to furnace as possible, avoiding direct radiant heat from heat
exchangers.
2. Operate furnace for 10 minutes with all the registers and duct dampers open by using ajumper wire on R to W thermostat
connections on the fan board.
3. Take readings and compare with range specified on rating plate.
4. If the air temperature rise is not in the correct range, the blow- er speed must be changed. A higher blower speed will lower the temperature rise. A lower blower speed will increase the
temperature rise.
5. Remove the jumper wire after the adjustments are complete.
"8DNL ModelSizes
LO M LO
RED BLUE
N Y N Y N N
N N N Y
Y Y Y Y
M HI HI ORN BLK
NOTE: For Ignitor location see Figure 25.
Ignitor Location
21/16
NOTE: Flame sensor has a different orientation in all 050 models.
25-25-08
Changing Blower Speed
ELECTRICAL SHOCK HAZARD.
Failure to disconnect power could result in death or personal injury.
Turn OFF power to furnace before changing speed
taps.
NOTE: The speed taps that the manufacturer sets at the factory for this furnace are based on a nominal 400 CFM per ton cooling
and the basic mid range on the temperature rise for heating. Since the manufacturer cannot predict the static pressure
that will be applied to the furnace, it is the responsibility of the installer dealer/contractor to select the proper speed tap
leads for the application when the furnace is installed. If it is necessary to change speeds, refer to steps below.
1. Refer to Furnace Hhking Diagram for location of the heating and cooling speed taps located on the furnace control as well
44101 2314 02
aslocationofunusedblowermotorspeedleads.Usethe
chart (Table 7) to determine the blower motor speed settin( s.
Blower Speed Chart
Wire Color
Black
Orange*
Blue
Red
* Med-High speed may not be provided on all models.
2,
Change the heat or cool blower motor speed by removing the motor speed lead from the "Heat" or "Cool" terminal and re- place it with the desired motor speed lead from the "MI" or
"M2" location. Connect the wire previously removed from the
"Heat" or "Cool" terminal to the vacated "M1" or "M2" termi-
nal.
3,
If the same speed must be used for both heating and cooling, remove the undesired motor speed lead from the "Heat" or "Cool" terminal and connect that lead to the open terminal at "M1" or "M2" location or tape off. Attach ajumper between
the "Heat" and "Cool" terminals and the remaining motor
speed lead. Note: When using the same speed on motors with (4) speed
leads, it will be necessary to tape off the terminal of the motor speed lead removed from the "Heat" or "Cool" terminal with electrical tape since an open terminal will not be available at
the "MI" or "M2" location.
Thoroughly check the system after modification to ensure the proper operation of the circulating air blower in all modes of opera-
tion.
Continuous-Fan Operation using "G"
Energizing the"G" terminal on the furnace control provides contin- uous fan operation. This is done by connecting the G terminal of
Motor Speed
High
Med-High
Med- Low
Low
the thermostat to the G terminal on the furnace control. When the FAN switch is turned from auto to ON the fan will operate continu-
ously at "HEAT" speed. EAC will be energized in this mode.
NOTE: In heating, the fan will turn off during furnace ignition and warm up then restart at heating speed.
Hard Wired Continuous-Fan Operation
A terminal is provided on the furnace control located in the circulat- ing air blower compartment for operation of the continuous-fan option. This connection is intended for the low speed motor tap,
and has a lower contact rating (8 amps) than the heat and cool taps. When the low speed blower lead is connected to this termi-
nal, this will provide low speed blower operation whenever the oth- er two speeds (Heat or Cool) are not energized. EAC not powered
in this mode.
Thoroughly check the system after modification to ensure the proper operation of the circulating air blower in all modes of opera-
tion.
Separate speed selections for Heat, Cool, and Continuous-Fan
Connect low speed lead from circulating air motor to the "Cont" terminal at the furnace control. The appropriate motor leads
should already be connected to the "Heat" and "Cool" terminals.
Heating and Continuous-Fan Speed the Same
If it is necessary to operate the heating speed and continuous -fan speed using the same blower speed, connect a jumper between
the "Heat" and "Cont" terminals on the furnace control.
Note: There should be only ONE motor lead going to the "Heat" and "Cont" terminals.
11. Furnace Maintenance
FIRE, EXPLOSION, OR CARBON MONOXIDE POISONING HAZARDS
Failure to have the furnace inspected and maintained could result in death, personal injury and/or property damage.
It is recommended that the furnace be inspected and serviced on an annual basis (before the heating season) by a qualified service agency.
See "User's Information Manual".
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, death, personal injury or property damage.
Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to
disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
441 01 2314 02 [_
12. Sequence of Operation & Diagnostics
The following is the normal operating sequence.
Cooling (Y) Request:
24VAC signals applied to Y & G terminals of FCB (furnace control board)
Cool motor speed is energized after 5 second Cool Fan On Delay time.
Y & G signals removed from FCB
Cool motor speed is de-energized after 90 second Cool Fan Off Delay time.
Continuous Circulating Fan (G) Request:
24 VAC signal is applied to G terminal of the FCB.
Heat motor speed is energized without delay.
G signal removed from FCB.
Heat motor speed is de-energized after 5 second delay.
NOTE 1) Furnace de-energizes the fan during the heat exchanger warm-up period on a call for Heating that occurs during a G request unless a blower motor lead is connected to the Cont terminal on the FCB, in which case see NOTE 2).
NOTE 2) Heating or Cooling requests received during a Fan request cause the fan speed to change to the appropriate heat or cool speed after the Fan on Delay time expires. The fan returns to continuous circulating speed after the selected Fan Off Delay time ex pires
following loss of the Heating or Cooling request.
Continuous Circulating Fan Hard-Wired (Cont) Request:
Field selected low speed motor tap installed on "CONT" terminal.
Low speed is energized when power applied to furnace. Operates at this speed continuously while there are no other blower demands from furnace control. Fan demands from furnace control for heat, cool or "G" will override hard-wired speed tap.
NOTE 3) EAC is NOT active for hard-wired mode but IS active for fan demands from furnace control for heat, cool and "G".
Heating (W) Request:
Heating (W) Request:
24 VAC signal applied to W terminal of FCB.
Inducer motor turns on and the pressure switch(es) close(s).
Following a 15 second prepurge delay after the pressure switches closes, the igniter begins a 17 second warm-up.
The gas valve is energized, the main burners light and flame is sensed.
The igniter is de-energized after the main burners ignite.
FCB will delay blower operation for the 30 seconds timed from the opening of the gas valve.
W signal removed from FCB.
The gas valve de-energizes and the main burners go out.
The inducer runs for a 15 second postpurge period.
The fan stays at Heat speed.
The fan de-energizes after the selected Heat Fan Off Delay time expires, timed from the gas valve de-energizing. HUMIDI FIE R - The 24V HUM is energized when the pressure switch closes on a call for heat. The 115V HUM (called HUM on Control)
is energized when the inducer is energized.
ELECTRONIC AIR CLEAN E R - EAC is energized when there is a blower speed call. It is NOT energized when blower operates in the hard-wired continuous fan mode.
NOTE 4) If a new Heating request arrives while the control is waiting in the Heat Fan Off Delay time, the FCB will wait for the selected Heat Fan Off Delay then start a new heating cycle as long as the heat call remains.
_] 441 01 2314 02
Heating Request with Gas Shut Off:
24 VAC signal applied to W terminal of FCB. The FCB will attempt 4 cycles for ignition then go to soft lockout for 3 hours then try for ignition again as long as the heat call remains.
Power reset will clear lockout.
Inducer motor turns on
Following a 15 second prepurge delay, the igniter begins warm up.
The igniter glows red-hot for 22 seconds, then turns off. The FCB flashes error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FCB continues flashing error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FCB continues flashing error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FCB proceeds to soft lockout and stops flashing error code 6 and begins flashing error code 6 + 1.
The inducer motor de-energizes after a 15 second post purge.
Control Board Diagnostic Codes (See Figure 26)
OFF = 24VAC or 115VAC is off, fuse is open Heartbeat = Normal operation or no previous Diagnostic Code
ON SOLID = Soft Lockout - Furnace Control Error (1 hr delay)
1 Flash = Not used 2 Flashes = Pressure switch(es) closed when should be open
3 Flashes = Pressure switch open when should be closed 4 Flashes = Limit or roll-out switch open 5 Flashes = Flame sensed out of sequence 6 Flashes = Failure to ignite or flame sense lost while running
6 + 1 Flashes = Soft Lockout - Max trials for ignition reached (3hr delay) 7 Flashes = Soft Lockout - Limit or roll-out switch open longer than 2 minutes (1 hr delay)
8 Flashes = Permanent Lockout - Gas valve relay contact stuck closed or miswired gas valve (power reset only) 10 Flashes = Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions
* If status code recall is needed, briefly (2-3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored status code. Do not remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared after 72 hours or upon power reset.
If code repeats immediately following power reset then replace control
(roll-out switch requires manual reset)
* Proper flame sense microamps: 0.7 microamps D.C. minimum 2.0 - 4.0 microamps nominal
Control Board
441 01 2314 02 [_
_] 44101231402
Save This Manual For Future Reference
Models
+8DNL050B12B1 +8DNL075B12B1 +8DNL075F16B1 +8DNL100F14B1 +8DNL100L20B1 +8DNL125L20B1
+Denotes Brand
International Comfort Products, LLC Lewisburg, TN 37097
Fast Parts Division (866) 380-3278
441 01 2314 02 [_
/
Model Specifications
Manufacturers Number (Mfr No-See RatingPlate) ALL Models
Specifications
*8DNLO5OB12 *8DNLO75B12 *8DNLO75F16 *8DNLIOOF14 *8DNLIOOL20 *8DNL125L20
General Input(8tuh) 50,000 75,000 75,000 100,000 100,000 125,000
Output(Btuh) 40,000 61,000 61,000 81,000 81,000 101,000
Temp.Rise(F) 35-65 35-65 35-65 35-65 30-60 35-65
Electrical(Volts/Hz) 115/60 115/60 115/60 115/60 115/60 115/60 RatingPlateAmps 9.2 9.0 12.0 9.2 13.5 13.2
GasType NatI,P NatI LP NatI'P NatI'P Nat Nat
Transformer Size (VA) 40 T'statHeatAnticipator .50
Gas& Ignition Std.MainOrifices(No/Size) 2I#42 2t#54 3I#42 3/#54 3/#42 3/#54 4/#42 4/#54 4/#42 4/#54 5/#42 5/#54
GasValve Honeywell VR8205S RegulationType) SNAP
ManifoldPress.(Inch'sWC) 3.5 110.0 3.5 110.0 3.5 110.0 3.5 110.0 3.5 110.0 3.5 110.0 IgnitionTypelSeries HotSurface
Combustion
FlueOutlet Size (Inches) 4 4 4 4 4 4 Std.OutletTemp(F) <480 <480 <480 <480 <480 <480
Limits &Controls
ThermalSensor (F) 300 300 300 300 300 300
LimitControl See PartsList See PartsList SeePartsList See PartsList See PartsList SeePartsList Std.PressureSw. (PartNo) 1013529
Press(Close) -0.69
Press(Open) -0.59 HighPressureSw. (PartNo) 1014051 FurnaceControl(Type) Integrated
FurnaceControl On 30 (Timed-secs) Off 60,100,140,180
Blower Data
Type& Size 11-8 11-8 11-10 11-10 11-10 11-10
MotorAmps/Rpm 8/1050 811050 10/1050 8/900 11.91900 11.91900 MotorTypelH.p. PSC/II2 PSC/II3 PSC/I/2 PSC/II2 PSC/314 PSC/3/4
Cap.Mfd/Volts 7.51370 5.01370 10/370 7.51370 40/370 40/370 FilterType(600FPM) Washable Washable Washable Washable Washable Washable
FilterSize (") 16x18xl (2) 16x18xl (2) 16x18x1(2) 16x18xl(2) 16x18xl (2) 16x18x1(2) Min.CoolCap. (Tons) 1.5 1.5 3 2 3 3 Max.CoolCap. (Tons) 3 3 4 3.5 5 5
GasConversion Kits Natto LP NAHA001LP(1172958*)
LPtoNat NAHA001NG(1172960*)
* MustbeorderedfromServiceParts
THIS DATA IS SUBJECT TO CHANGE WITHOUT NOTICE 44101231402
Circulation Air Blower Data (CFM #)
*8DNLO50B12 *8DNLIOOF14
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED H HIGH
_-_5, .10 702 963 1260 1537
,30 624 845 1183 1416
No
_ .60 510 760 1088 1308 =u ,70 412 617 917 1111
_ .90 310 468 664 948
uJ
1,00 249 436 529 808
_-_5, .10 756 1012 1372 1881
,30 585 888 1273 1724
No
_ .50 491 780 1176 1606 =u ,70 387 697 1035 1481
x .90 255 561 873 1281
uJ
TAP LOW MED L MED H HIGH
Air Delivery in Cubic Feet per Minute (C.F.M.)
(Furnace Rated @0.5" WC ESP)
1.0 210 444 767 1132
*8DNLO75B12
Air Delivery in Cubic Feet per Minute (C.F.M,)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED H HIGH
•_O' ,10 634 728 975 1353
.30 533 653 936 1307
_o
_ ,50 454 559 861 1225 =u .70 373 473 737 1087
"_ ,90 255 392 605 884
ua
1,00 232 294 529 764
*8DNL075F16
Air Delivery in Cubic Feet per Minute (C.F.M.)
= TAP LOW MED L MED H HIGH
5 .10 648 900 1285 1789
,30 628 916 1328 1747
_ .50 611 889 1309 1680 =u ,70 557 843 1240 1588
x
_J
Denotes Brand
.90 485 748 1122 1452
1,00 441 680 1041 1374
(Furnace Rated @0.5" WC ESP)
*8DNL100L20
Air Delivery in Cubic Feet per Minute (C.F.M,)
(Furnace Rated @0.5" WC ESP)
TAP LOW MED L MED H HIGH
•_ O' ,10 1798 2024 2212 2375
'-£ .30 1709 1896 2081 2205 To
_ ,50 1614 1774 1922 2026 =u .70 1470 1614 1752 1860
x ,90 1282 1428 1548 1645
uJ
1.00 1065 1263 1407 1508
*8DNL125L20
Air Delivery in Cubic Feet per Minute (C.F.M.)
= TAP LOW MED L MED H HIGH
5 .10 1936 2165 2319 ---
,30 1845 2028 2246 2334
_ .50 1728 1902 2061 2172 =u ,70 1536 1695 1856 1952
x
_J
.90 1331 1490 1800 1687
1.00 1215 1352 1424 1537
(Furnace Rated @0.5" WC ESP)
I # CFM - Cubic feet per minute airflow.
Filter required for each return-air inlet. Airflow performance includes 1" washable (600 FPM max) filter media.
44101231402 THIS DATA IS SUBJECT TO CHANGE WITHOUT NOTICE [_
f
ROLLOUTSWITCH1TO2
'NSE_hSM_D'NGM_NL'M'T _VSsSE _.,,T&.E O.LY
CONNECTION DIAGRAM DISCONNECT BEFORE SERVICING
LP PRESSURE CAPACITOR COPPER CONDUCTORS
(WHEN USED) (WHEN USED) (SOME MODELS)
WARNING: ELECTRICAL SHOCK HAZARD LADDER DIAGRAM =oo "
--I--(_)--_.R7_o--_-(_--..(:_-, _ HOTNEUTRALG,D
NOTE #g | I
I -_'_¢JSTET_'U_E--S;_--.----_NDU(ER % GRN/Y IGNITER %" I "
y I TO21NSERIES _ nN_ | I"
DEPENDINGON MODEL MOTOR /_ JUUL BK I Z
.OTE._ %-_ ''_l °
--W_SENSOR I_;]_P4 I I_
,..-t wr:-r2
IND -- _ _ I JUNCTION
_:= 100 18( I ×. =11 _ :ZoJ_
_1_1_- _i I _1__U _(>X)_w_
I
m moo
TO 115VAC FIELD DISCONNECT
OT J.NEUTRAL _ _
H NOTE #2 EQUIPMENT GROUND _ Oo O
L1_-"V/'sNwT,_T_C'H°oK 7]- _:CO:E mr_m_mr_
n 2 "" fT_NDU_ER_I_1CAPACITOR m_ o_:<"
RELAY P2 (SOME MODELS _ o
INDUCER P4 _ © _ _
_ ]_.- _ _ :: _ om o
I IGNI,T_ON I NOTT#13 /'_ ... C)
RELAY -- HEAT MHI (O)
I P3 1
MLO (BL) _> _< 60 SEC
M1 PSC
_LOWER 9_
> >00
©+ Zmz
Zr_ :<>_<
m_rn
B
8
z_
x_'_' _ I _7.g I _--,
_ _ _I_-- _ _ TR_R
2 ,'_"-_ _ MOTOR _ "m,',,",,-
_ _
_
, HEAT_OO:"'--WW ]- .....'-*'
I R BL"
RELAY _EAC _ IN
., CONT FAN
I._. .q,o_t, U= _ ,oo,_o
ROLLOUT SWITCH 1 TO3
IN SE RIES DEPENDING TRANSFOR MER
ON MODEL P1 6 FUSE 5A --
MAIN LIMIT NOTE #6 24VAC COM J 1 _O
COM O J1
NL _ Z
_m
XF _ 100SEC
Ill
- w
1. If any of the original equipment wire is replaced use wire rated 105° C.
2. Use only copper wire between the disconnect switch and the furnace junction box.
3. This wire must be connected to furnace sheet metal for contlol to
prove flame.
4. Symbols are electdcat representation only.
5. Solid lines inside circuit board are printed circuit board tlaces and are
not depicted as shown in the legend.
6. Replace only with a 5 amp fuse.
7. Blower motor speed selections are for average conditions, see
installation taatrdctions for details on optimum speed selection.
8. Factory connected when LP Pressure Switch and BVSS (Chimney
Adapter Accessory Kit) are not installed.
9. Btawer off-delay, gas heating selections are (60, 100,146, and 180)
seconds, cooling or heat pump 90 seconds.
10. Ignition lockout will occur after four consecutive unsuccessful tdals for
ignition. Control will auto-reset after three hours.
11. Blower motor and inducer motor contain internal auto-reset thermal
overload switches.
12. Flame sensor: 0.7 pA D.C. minimum, 2.0 - 4.0 pA nominal.
13. Depending on model, P4 inducer motor leads may be in a single connector
2
4_
SPEEDTAP CODE COLOR CODE
BLACK HI BLUE BL ORANGE MHI BROWN BR
BLUE MLO GREEN/YELLOW GRN/Y RED LO RED R
i i . LINE VOLTAGE FIELD
O UNMARKED TERMINAL
I CONTROL TERMINAL
BLACK BK
ORANGE O WHITE W
YELLOW Y
LOW VOLTAGE FACTORY LOW VOLTAGE FIE LD LINE VOLTAGE FACTORY
CONDUCTOR ON CONTROL
JUNCTION
I .... _,4 ,TO_INSERIE__J_l-a
CPU RELAY BVSS _q
_C _zO_Z_--_ i _--_ I1___1_'-- _" _NOTE #3(FIELDINSTALLED _ _
m_m_ _)P13 SENSOR
P SS SWITCH
-4_1/ (LPMODELSONLY) I P1 8 NOTE#8 ,_
VALVE ___! O J1
GAS .... ,
m_ 100 180
[ CONTROL_OARD ._=_>_]
o
Parts for *8DNL
II
19
6
CC
BB
18
A
\
KK
JJ
\
O
BB
AA
DD
\
16
25-25-11-1
441 01 231402 [_
I Replacement Parts - *8DNL (Natural Gas) I
Models - *8DNLO50B12B1, *SDNLO75B12B1, *SDNLO75F16B1, *8DNL100F14B1, *SDNLIOOL2OB1, *SDNL125L20B1
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Functional Parts Part
No, Description Number
Heat Exchanger
2 Switch, Pressure 3 Wheel, Blower
4 Mount, Motor kit*
5 Motor, BIr 1/115
6 Capacitor 7.SuF
7 Transformer 8 Control
9 Switch, Interlock
10 Burner Assembly
11 Flame Sensor
12 Igniter 14 Orifice, Burner # 42
15 Valve, Gas 16 Switch, Limit (Rollout) 17 Switch, Limit (Main)
18 Blower, Combustion
19 Filter, Air
*See Table below for bell,
Bellyband Location
on Motor
Model *8DNL A(in.) O50B12B1 1.38" 075B12B1 1.65"
075F16B1 1.81"
100F14B1 1.38"
100L20B1 1.65"
125L20B1 1.65"
1/2 COW
1/115
1/3 COW
1/115
1/2 COW
1/115
3/4 CCW
5uF 10uF
40 uF
band location on motor
1014316 1014317 1014318 1014319 1014320
1014321 1013529
1013011 1011420
1014824 1014825 1014823
1172487 1172493 1172488 1172489
1171728 1171727
1171729 1171982
1172810 1172550 1171981
1172884 1172965 1172966 1179667
1172827 1172533 1011351
1172821
1013102
34335001
1009169 1008417 1065294 1320362
1014433 1013517
1009750
050B12B1
1
1 1
1 1 1
1
1 1 2
1 2 1
1
2
075B12B1
1
1 1
1 1 1
1 1 3
1 2 1
1
2
075F16B1 100F14B1
*8DNL
1
1 1
1 1
1
1
1
1 1 1 1 1 1
1
1 1 1 1 3 4
1 1 2 2
1
1 1
2 2
100L20B1
1
1
1
1
1
1
1
1 1 1 1
1
1 1
4
1
2
1
1
1
2
125L20B1
1 1
1 1 1 1
1 1 1 5
1 2
1
1 2
441 01 231402
I Replacement Parts - *8DNL (Natural Gas) I
Models - "8DNL050B12B1, *8DNL075B12B1, *8DNL075F16B1, "8DNL100F14B1, *8DNL100L20B1, *8DNL125J20B1
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Non-Functional Part
No, Description Number 100L20B1 125L20B1
Panel, Top
B Box, Junction C Cover, Junction box D Partition, Blower
E
Housing, Blower
F
Hanger, Blower
G
Panel, Blower Cutoff
H
Clamp, Capacitor
J
Bracket, Control Mounting
L
Door, Blower (Hell Only)
Bracket, Door
Door, Louver (Hell Only)
Manifold, Gas
S Bracket, Manifold Support
T Top, Burner Box
U Bracket, Burner Box Sides V Baffle, Burner Box
W Bottom, Burner Box
Collector Box
Z Gasket, Combustion Blower 1
(Hell Only) (Hell Only) (Comfortmaker Only)
(Comfortmaker Only) (Comfortmaker Only) (Tempstar Only) (Tempstar Only) (Tempstar Only)
(Hell Only) (Hell Only)
(Comfortmaker Only) (Comfortmaker Only) (Comfortmaker Only) (Tempstar Only) (Tempstar Only) (Tempstar Only)
1013593 1013594
1014410
1172860
1012350 1013571
1013572 1014416
1172885 1172969
1012328
721020013 721020008
1170643
1014315
1172846 1173028
1173029 1173030 1173025 1173026 1173027 1173031 1173032
1173033 1172267
1172268 1172269
1173020 1173021 1173022 1173017 1173018 1173019 1173023
1173024
1014435 1013478
1013479 1013480 1013481
1012377 1013705
1013015 1013016
1012532 1012338
1012339 1012340
1172847 1172848 1172849 1172850
1014033 1013483
1013484 1013485
1013540
050B12B1
1
1 1
1
1
2 1
1
1 1
1
1
1
1
2 1
2 1
078B12B1
1
1 1
1
1
2
1
1
1 1
1
1
1
2
1
2
1
1
1
078F16B1 100F14B1
*8DNL
1 1
1 1 1 1
1 1
1 1 2 2
1 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1
2 2 1
2 2 1
1
1
1 1
1 1
1
1
1 2
1
1 1
1
1
1
1
1
1
1
1
1
2
1
2
1
1
1
1 1
1
1
1 2
1
1 1
1
1
1
1 2
1 2
1 1
441 01 231402
I Replacement Parts - "8DNL (Natural Gas) I
Models - "8DNLO50B12B1, 'SDNLO75B12B1, 'SDNLO75F16B1, "8DNL100F14B1, '8DNLIOOL2OB1, 'SDNL125J20B1
Replacement part supplied will be current active )art. For parts not listed, consult place of purchase.
Key Non-Functional Part
No, Description Number
AA Partition, Front Heat Exchanger
BB Gaskets, Heat Exchanger
CC Tubing, Silicone
DD
Baffle, Nox
JJ
Shield, Flue Pipe
KK
Pipe, Flue
LL
Rack, Filter (Version A)
I L2
Rack, Filter (Version B)
MM
Sightglass PARTNOTILLUSTRATED
)(
)(
Fuse, 5 Amp
)(
Harness, Wire
Manual, Installation
)(
Manual, Users
1013543 1013521 1013545 1013548 1013547 1013548
1013991 1013992 1013993 1013994
1172190
1172191 1014019 1013975
1014031 1014020
1173903
1172768
1083348
1172819
1172820
441 01 2314 02 441 02 2011 01
080B12B11075B12B1
1
2 1
1 1 1
1
1 1
1 1
3
1 1
1 1
1
1 1
1 1
075F16B1 100F14B1
"SDNL
100L20B1
1
3 1
1 1 1
1
1 1
1 1
1
1 4 1
1 1 1
1
1 1
1
4
1
1
1
1
1
1
1
1
125L20B1
1 5 1
1 1 1
1
1 1
1
_] 441 01 231402
Loading...