ICP GNE050B12A1, GNE050B12G1, GNE075B12A1, GNE075B12G1, GNE075F16A1 Installation Guide

...
NTC6/GNE
Upflow/Horizontal
220V-1ph-50Hz
SAFETY REQUIREMENTS
Recognize safety information. This is the safety-alert symbol/ ._\,. When you see this symbol on the furnace and in instructions manuals be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards, those that will result in severe personal injury or death. WARNING signifies a hazard that could
result in personal injury or death. CAUT__Nisusedt_identifyunsafe_racticesthatc_u_dresu_tinmin_r_ers_na_injury_r_r_ductand property damage.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person- nel should install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety precautions that may apply. Follow all national and local safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas
Code (NFGC) NFPA No. 54/ANSIZ223.1. In Canada, refer to the current edition of the National Standard Canada CAN/CGA-B149.1 - and .2-M91 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher
available during start-up and adjustment procedures and service calls. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
,IX
Table of Contents
1.Installation ............................... 2
2.Combustion&VentilationAir ................. 4
3.GasVentInstallation ....................... 6
4.HorizontalVenting ......................... 8
5.GasSupply andPiping...................... 8
Manufactured by:
International Comfort Products Corporation (USA) Lewisburg, TN USA 37091
6. ElectricalWiring ........................
7. DuctworkandFilter .....................
8. ChecksandAdjustments .................
9. FurnaceMaintenance....................
homes, trailers or recreational vehicles. Such use could result in property damage, bodily in-
I his furnace is not designed for use in mobile
jury and/or death.
12 13
14 16
LP1 2/4/2002 441 01 2307 01
1. Installation
Installation or repairs made by unqualified persons
can result in hazards to you and others. Installation
MUST conform with local codes or, in the absence of local codes, with codes of all governmental authorities having jurisdiction.
The information contained in this manual is
intended for use by a qualified service technician who is experienced in such work, who is familiar with all precautions and safety procedures
required in such work, and is equipped with the
proper tools and test instruments.
Failure to carefully read and follow all instructions
in this manual can result in furnace malfunction,
property damage, personal injury and/or death.
NOTE: Refer to the appropriate codes, along with this manual, for proper installation.
water heaters, furnaces, gas-fired fireplaces, wood fire- places, and several other items. Carbon monoxide can cause serious bodily injury and/or death. Therefore, to
help alert people of potentially dangerous carbon monox- ide levels, you should have carbon monoxide detectors listed by a nationally recognized agency (e.g. Underwrit- ers Laboratories or International Approval Services) installed and maintained in the building or dwelling (see
Note below).
B,
There can be numerous sources of fire or smoke in a build- ing or dwelling. Fire or smoke can cause serious bodily in-
jury, death, and/or property damage. Therefore, in order to
alert people of potentially dangerous fire or smoke, you should have fire extinguisher and smoke detectors listed
by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any detec-
tors and makes no representations regarding any brand or type of detector.
This furnace is NOT approved for installation in mo- bile homes, trailers or recreation vehicles.
Do NOT use this furnace as a construction heater or to heat a building that is under construction.
Use only the Type of gas approved for this furnace (see Rating Plate on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation. (Furnace can be converted to L.R gas with approved kit.)
Do NOT use open flame to test for gas leak.
Ensure adequate combustion and ventilation air is pro-
vided to the furnace.
Seal supply and return air ducts.
The vent system MUST be checked to determine that it is
the correct type and size.
Install correct filter type and size.
Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
It is the suggestion of this manufacturer to install fire and carbon monoxide detectors.
C. To ensure safe and efficient operation of your unit, you
should do the the following:
1. Thoroughly read this manual and labels on the unit. This will help you understand how your unit operates and
the hazards involved with gas and electricity.
2. Do not use this unit if any part has been under water. Immediately call a qualified service technician to inspect
the unit and to replace any part of the control system and any gas control which has been under water.
3. Never obstruct the vent grilles, or any ducts that pro- vide air to the unit. Air must be provided for proper com-
bustion and ventilation of flue gases. Carbon monoxide or"CO" is a colorless and odorless gas
produced when fuel is not burned completely or when the flame does not receive sufficient oxygen.
Freezing Temperatures and Your Structure
Freeze warning.
Turn off water system. If your unit remains shut off during cold weather
the water pipes could freeze and burst, resulting in serious water damage.
Safety Rules
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. Howev-
er, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission recom-
mends that users of gas-burning appliances install car- bon monoxide detectors. There can be various sources of
carbon monoxide in a building or dwelling. The sources could be gas-fired clothes dryers, gas cooking stoves,
Your unit is equipped with safety devices that may keep it from operating if sensors detect a bnormal conditions such as clogged exhaust flues.
If the structure will be unattended during cold weather you should take these precautions.
1. Turn off main supply water into the structure and drain the water lines if possible. Open faucets in appropriate areas.
2. Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes
from freezing. Suggest they call qualified service agency, if required.
44101230701
Location and Clearances
Poison carbon monoxide gas hazard. If this furnace is replacing a previously
common-vented furnace, it may be necessary to
resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances(s). See applicable codes
and Venting and Combustion Air Check in Gas
Vent Installation section.
Failure to properly vent this furnace or other appliances can result in property damage, personal injury and/or death.
Figure 1 Dimensions and Clearances
IIIIIIIII0
=
i
1
30" rain. (762rata)
25-2(]-29a
If furnace is a replacement, it is usually best to install the furnace
where the old one was. Choose the location or evaluate the exist-
ing location based upon the minimum clearance and furnace di- mensions (Figure 1).
Do NOT operate furnace in a corrosive atmosphere containing chlorine, fluorine or any other damaging
chemicals. Refer to Combustion & Ventilation Air sec- tion, Contaminated Combustion Air.
150,000BTUONLY AirBaffleDONOTREMOVE
CAUTION
MINIMUM CLEARANCES TO
COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR 0 FRONT 3" (75ram)*
For Service 30" (760mm)
ALL SIDES Of SUPPLY PLENUM 1" (25mm)
SIDES 0
VENT
Single Wall Vent 6" (150mm)
Type B-1 Double Wall Vent 1" (25ram)
TOP OF FURNACE 6" (150mm)
6" (152mm) with accessory Masonry Chimney drafthood
kit installed.
DIMENSIONAL INFORMATION
MODEL
A K L M
050 / 075 40 281/4 26 23_/8
100 40 281/4 26 237/8 125 / 150 40 281/4 26 237/8
mm Equivalents 40=1016 14 = 356 178/8=448 211/4 = 539 231/8 = 587 125/8 = 311 17= 432 221/2 = 572
281/4 = 717 26 = 660 237/8 = 606
B C D
151/2 281/2 181/2 191/8 281/2 181/2 223/4 281/2 181/2
151/2 = 394 191/8 = 486
SUPPLY AIRCABINET
E F G
14 231/8 125/8 175/8 231/8 143/4 211/4 231/8 183/4
223/ =578 281/2=724
143/4 = 375
ALL DIMENSIONS IN INCHES (mm)
183/4 = 476 121/4 = 311
BOTTOM
Installation Requirements
1. Install furnace level.
2.
Install furnace as centralized as practical with respect to the heat distribution system
The 150,000 Btuh furnace is manufactured with an air baffles to equalize air flow through the heat exchanger.
(See Figure 1). DO NOT REMOVE THESE AIR
BAFFLES
3.
Install the vent pipes as short as practical. (See Gas Vent Installation section).
44101230701
RETURN AIR
SIDE
H J
121/4 221/2 141/2 221/2 141/2 221/2
181/2 = 470 141/2 = 368
4.
Do NOT install furnace directly on carpeting, tile or other
GAS CONNECTION
combustible material other than wood flooring.
5.
Maintain clearance for fire safety and servicing. A front clearance of 30" (760mm) is minimum for access to the
burner, controls and filter.
6. Use a raised base if the floor is damp or wet at times.
7. Residential garage installations require:
Burners and ignition sources installed at least 18" (457mm) above the floor.
[33
Furnace must be located or physically protected from pos- sible damage by a vehicle.
Horizontal Furnace Installation
IMPORTANT
NOTE: Inspect unit rating plate to be certain model number be-
gins with "NTC6 or GNE', This identifies unit as horizontally mountable, If unit does NOT bear this designation, you may NOT mount this unit horizontally, Horizontal furnace may not be
mounted on its back,
If you purchased a horizontally mountable furnace, it can be installed horizontally in an attic, basement, crawl space, alcove, or suspended from a ceiling in a basement or utility room in either a right or left airflow position. See Figure 2.
Thirty inches (30") (760mm) between the front of the furnace and adjacent construction or other appliances MUST be maintained
for service clearance.
Keep all insulating materials clear from Iouvered door. Insulating materials may be combustible.
The horizontal furnaces may be installed directly on combustible
wood flooring or supports, however it is recommended for further
fire protection that cement board or sheet metal is placed be- tween the furnace and the combustible wood floor and extend
12" (300mm) beyond the front of the furnace louver door. (This is a recommendation only, not a requirement).
This furnace MUST NOT be installed directly on carpeting or tile or other combustible material other than wood flooring or sup- ports.
Figure 2 Typical Horizontal Installation
The following minimum clearances to combustibles MUST be maintained between the furnace and adjacent construction. As
shown in Figure 1, ONLY the corner of the cabinet is allowed to contact the rafters Figure 2. All other clearances MUST be ob- served as shown in Figure 1.
If the furnace is to be suspended from the floor joists in a crawl space or the rafters in an attic, it is necessary to use steel pipe
straps or an angle iron frame to attach the furnace. These straps should be attached to the furnace with sheet metal screws and to
the rafters or joists with bolts. The preferred method is to use an angle iron frame bolted to the rafters or joists.
If the furnace is to be installed ground level in a crawl space, con- sult local codes. A concrete pad 1" to 2" (25 to 50ram) thick is rec-
ommended.
Pressure Switch Relocation
If the furnace is installed in a right to left airflow position (left side of furnace facing down), the pressure switch will remain in the
same position as installed by the factory (see Figure 3). If the furnace is installed in a left to right airflow position (right side of furnace facing down), the pressure switch MUST be relocated to the left side of the furnace using the holes provided in the top pan-
el. Position the pressure switch in the same orientation as the original location. To prevent possible kinking of the pressure
switch hose, trim the hose to remove excess.
Note: Care MUST be taken not to cut the tube too short.
Figure 3 [
Optional pressure switch location for
Right to Left Airflow
Pressure Switch Relocation
Shown As
right side, relocate
same orientation as originally mounted.
2. Combustion & VentilationAir
Poison carbon monoxide gas hazard. Use methods described here to provide
combustion and ventilation air.
Failure to provide adequate combustion and
ventilation air can result in personal injury
and/or death.
D
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open- ings for supplying combustion and ventilation air must comply
with the gas codes, or in the absence of local codes, the applica-
ble national codes.
When the installation is complete, check that all appliances have adequate combustion air and are venting properly. See Venting
And Combustion Air Check in this manual.
44101230701
Contaminated Combustion Air
Confined Space Installation
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the fur- nace. These instances must use only outside air for combustion.
The following areas or types of structures may contain or have exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air
for combustion.
Commercial buildings.
Buildings with indoor pools.
Furnaces installed in laundry rooms.
Furnaces installed in hobby or craft rooms.
Furnaces installed near chemical storage areas.
Permanent wave solutions for hair.
Chlorinated waxes and cleaners.
Chlorine based swimming pool chemicals.
Water softening chemicals.
De-icing salts or chemicals.
Carbon tetrachloride.
Halogen type refrigerants.
Cleaning solvents (such as perchloroethylene).
Printing inks, paint removers, varnishes, etc..
Hydrochloric acid.
Sulfuric Acid.
Solvent cements and glues.
Antistatic fabric softeners for clothes dryers.
Masonry acid washing materials.
NOTE: A confined space is defined as an area with less than 50 cubic feet(1.4m 3) per 1,000 BTUH input rating for all gas ap- pliances installed in the area.
Air Openings and Connecting Ducts
1. Total input rating for all gas appliances MUST be considered when determining free area of openings.
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, the openings MUST be no smaller than 114" (6mm) mesh.
4. The minimum dimension of rectangular air ducts MUST NOT be less than 3" (75mm).
5. When sizing grille or louver, use the free area of opening. If free area is NOT stamped or marked on grill or louver, as-
sume a 20% free area for wood and 60% for metal.
Requirements
1. Provide confined space with sufficient air for proper com- bustion and ventilation of flue gases using horizontal or ver- tical ducts or openings.
2. Figure4 illustrateshowtoprovidecombustionandventila- tion air. A minimum of two permanent openings, one inlet
and one outlet, are required.
Figure 4 Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
ThisinstallationNOTapprovedinCanada
Gas Vent
MinimumOne Inlet andOne Outlet AirSupply isRequired
InletAir OpeningMust be Within12"(300mm)of floor OutletAir OpeningMustbe Within12"(300mm)of ceiling
(1) 1Square Inch(6cmz)per4000BTUH (2) 1Square Inch(6cmz)per2000BTUH
3,
May be inand Combination Shown
One opening MUST be within 12" (300mm) of the floor and the second opening within 12" (300mm) of the ceiling.
Gable Vent
Soffit Vent
.4,
JI
I I ' N So_flt_ent
I ut'etAir")II
I _ J_ H I Outlet
J _ III Air(')_
Inlet
._J_'"_°l F;_I r-,,.,r'_" Inlet
Air (1)
J"l I I I _ _ Air(2)
5. Horizontal duct openings require 1 square inch(25sq, mm) of free area per 2,000 BTUH of combined input for all gas appliances in area (see Table 1).
iFurnace
Inlet
Air(1}
_ 3as m
'atel _ eat_ rim
Outlet Air (2)
Inlet
Air (2)
4. Size openings and ducts per Table 1.
44101230701
Vertical duct openings or openings directly to outside re-
u 3
q ire 1 square inch(6.5mm ) of free area per 4,000 BTUH for combined input of all gas appliances in area (see Table
1).
CZl
Loading...
+ 11 hidden pages