ICP GDJ050M12A1, GDJ050M12B1, GDJ050M12C1, GDJ050M12C2, GDJ075M12A1 Installation Guide

...
NDN5/GDJ
Downflow Only
Series
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert symbol _. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
UnderstandthesignalwordDANGER, WARNING, orCAUTION. Thesewordeareusedwiththesafety-alertsymbol. DANGERidenti-
injuryor death. CAUT__Nisusedt_identifyunsafepracticeswhichw_u_dresu_tinmin_rpers_na_injury_rpr_ductandpr_pertydam-
age.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person- nel should install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions inthe literature, on tags,
and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas Code (NFGC) NFPA No. 54/ANSIZ223.1. In Canada, refer to the current edition ofthe National Standard Canada CAN/CGA-Bt 49.1 - and .2-M91 Natural
Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Havefire extinguisher available during start-
up and adjustment procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential
construction practices. We require these instructions as a minimum for a safe installation.
/k
Table of Contents
1.Installation............................... 2
2.Combustion&VentilationAir ................. 4
3.GasVent Installation ....................... 6
4.Horizontal................................ 7
5.GasSupplyandPiping ...................... 8
Design Certified
byAGA
Manufactured by:
Inter- City Products Corporation (USA)
Lewisburg, TN USA 37091
6.ElectricalWiring ........................
7.DuctworkandFilter ......................
8.ChecksandAdjustments..................
9.FurnaceMaintenance ....................
This furnace is not designed for use in mobile homes, trailers or recreational vehicles. Such use could result in property damage, bodily in-
jury and/or death.
LP3 4/14/97 441 01 2201 02
11 12 15
16
1.Installation
Installation or repairs made by unqualified persons can result in hazards to you and others.
Installation MUST conform with local codes or, in
the absence of local codes, with codes of the
country having jurisdiction. The information contained in this manual is
intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instruc-
tions in this manual can result in furnace
malfunction, property damage, personal injury and/or death.
NOTE: This furnace is design certified by the American Gas
Association and the Canadian Gas Association for installation in the United States and Canada. Refer to the appropriate codes,
along with this manual, for proper installation.
This furnace is NOT approved for installation in mobile
homes, trailers or recreation vehicles.
Do NOT use this furnace as a construction heater.
Poison carbon monoxide gas hazard.
If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances(s). See applicable codes and Venting and Combustion Air Check in Gas
Vent Installation section.
Failure to properly vent this furnace or other appliances can result in property damage,
personal injury and/or death.
Locationand Clearances
1. Refer to Figure 1for typical installation and basic connect- ing parts required. Supply and return air plenums and duct are also required.
Figure 1 1 Typical Installation
To ElectricaI Service
Entrance Panel
__ Roof Line
Use only the Type of gas approved for this furnace (see Rating Plate on unit). Overfiring will result infailure of heat exchanger and cause dangerous operation.
Do NOT use open flame to test for gas leak.
Ensure adequate combustion and ventilation air is pro- vided to the furnace.
Seal supply and return air ducts.
The vent system MUST be checked to determine that it is the correct type and size.
Install correct filter type and size.
Unit MUST be installed so electrical components are pro- tected from direct contact with water.
It is the suggestion of this manufacturer to install fire and carbon monoxide detectors.
May be vented with
another gas appliance.
VentPipe _ _Return __-GasLine
_ _///////////:
ischarge
2.
Iffurnace isa replacement, it is usually best to install the fur-
nace where the old one was. Choose the location or evalu- ate the existing location based upon the minimum
clearance and furnace dimensions (Figure 2).
25-20-58
CAUTION
Do NOT operate furnace in a contaminated atmosphere con- taining chlorine, fluorine or any other damaging chemicals.
Refer to Combustion & Ventilation Air section, Contami- nated Combustion Air.
Figure 2 [ Dimensions and Clearances
DIMENSIONAL INFORMATION
MODEL
050BF 075BF 100BH 125BK
Equivalents Inches (mm)
t51/2 t51/2 t91/6
223/4
19118(486)
I 151/2 394
223/4(578)
CABINET
A
B
281/2 281/2 281/2 281/2
281/2(724)
C
40 40 40 40
40 (1016) 179/16(446)
BOTTOM
OPENING
D E
14 151_
14 151_ 17_16 151_ 2t_16 151_
I 14(356)
213/16(538)
ALL DIMENSIONSIN INCHES(ram)
151_(394)
RECOMMENDED CLEARANCES TO
COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR 0 FRONT 3" (75mm)
Single Wall Vent 6" (150mm) Type B-1 Double Wall Vent 3" (75mm)
For Service 30" (760mm)
ALL SIDES OF 1" (25mm) SUPPLY PLENUM
SIDES 0 VENT
Single Wall Vent 6" (150mm) Type B-1 Double Wall Vent 1" (25mm)
Thermoplastic Pipe 4" (102mm)
TOP OF FURNACE 6" (150mm)
RETURN
OPENING
F G
t4 1817/32
t4 1817/32 179/16 1817/32 213/16 1817/32
14(356) I 179/16(446) I 1817/32(47t)213/16(538)
GAS CONNECTIONS
H
913/16 913/16 913/16 913/16
913/16 (249)
J
21/2 21/2 21/2 21/2
21/2(64)
K
411/16 411/16 411/16 411/16
411t16(119)
Installation Requirements
1. Install furnace level.
Install fumace as centralized as practical with respect to the
heat distribution system.
Install the vent pipes as short as practical. (See Gas Vent
Installation section).
Do NOT install furnace directly on combustible floors un-
less using a special noncombustible subbase. See Duct- work and Filter section later in this manual.
Fire Hazard.
Place furnace on noncombustible cement board or sheet metal.
Failure to install unit on noncombustible cement
board or sheet metal can result in property damage, personal injury and/or death.
5. Maintain clearance for fire safety and servicing. A front clearance of 30" (760mm) is recommended for access to
the burner, controls and filter.
6. Use a raised base if the floor is damp or wet at times.
7. Residential garage installations require:
Burners and ignition sources installed at least 18" (457mm) above the floor.
Located or physically protected from possible damage by a vehicle.
G3
2. Combustion& VentilationAir
Poison carbon monoxide gas hazard. Use methods described here to provide
combustion and ventilation air.
Failure to provide adequate combustion and
ventilation air can result in personal injury and/or death.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open-
ings for supplying combustion and ventilation air must comply with the gas and electrical codes, or inthe absence of local codes, the applicable national codes.
When the installation is complete, check that all appliances have adequate combustion air and are venting properly. See Venting
And Combustion Air Check in this manual.
ContaminatedCombustionAir
Installations in certain areas or types of structures will increase the exposure to chemicals or Halogens which may harm the fur-
nace. These instances must use only outside air for combustion.
The following areas or types of structures may contain or have ex-
posure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion.
Commercial buildings.
Buildings with indoor pools.
Furnaces installed in laundry rooms.
Furnaces installed in hobby or craft rooms.
Furnaces installed near chemical storage areas.
Permanent wave solutions for hair.
Chlorinated waxes and cleaners.
Chlorine based swimming pool chemicals.
Water softening chemicals.
De-icing salts or chemicals.
Carbon tetrachloride.
Halogen type refrigerants.
Cleaning solvents (such as perchloroethylene).
Printing inks, paint removers, varnishes, etc..
Hydrochloric acid.
Sulfuric Acid.
Solvent cements and glues.
Antistatic fabric softeners for clothes dryers.
Masonry acid washing materials.
Confined SpaceInstallation
NOTE: A confined space is defined as an area with less than 50 cubic feet(1.4m s) per 1,000 BTUH input rating for all gas ap-
pliances installed in the area.
Air Openingsand Connecting Ducts
1. Total input rating for all gas appliances MUST be consid- ered when determining free area of openings.
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, they MUST be no less than 1/4" (6ram) mesh.
4. The minimum dimension of rectangular air ducts MUST NOT be less than 3" (75mm).
5. When sizing grille or louver, use the free area of opening. If free area is NOT stamped or marked on grill or louver, as- sume a 20% free area for wood and 60% for metal.
Requirements
1. Provide confined space with sufficient air for proper com- bustion and ventilation of flue gases using horizontal or ver-
tical ducts or openings.
2. Figure 3 illustrates howto provide combustion and ventila- tion air. A minimum of two permanent openings, one inlet and one outlet, are required.
/33
Figure 3 Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
ThisinstallationNOTapprovedin Canada Gas Vent
GasVent . GableVent)
=/
E_
Soft, Vent
Outlet Air (1)
Inlet Air(1
Furnace
' ieat_
Gas
fatal
Outlel Air (2',
m
Inlet Air (2
MinimumOneInlet andOne OutletAirSupplyinRequired
InletAir OpeningMustbe Within12"(300mm)of floor
OutletAir OpeningMustbe Withint2"(300ram)of ceiling
(t) 1Square Inch(6cm2)per4000 BTUR (2)1Square Inch(6cm2)per2000 BTUH
3.
One opening MUST be within 12" (300mm) of the floor and
May be inand CombinationShown
the second opening within 12" (300mm) of the ceiling.
4.
Size openings and ducts per Table 1.
5.
Horizontal duct openings require 1 square inch(25sq, mm)
of free area per 2,000 BTUH of combined input for all gas appliances in area (see Table 1).
Vertical duct openings or openings directly to outside re-
I 3
qu're 1 square inch(6.5mm ) of free area per 4,000 BTUH for combined input of all gas appliances in area (see Table
t).
Table1
BTUHIn-
putRat- HorizontalDuct
ing (2,000BTUH)
50,000 161cm2(25 sq. in.)
75,000 242cm2(35.5sq.in.)
100,000 323 cm 2 (50 sq. in.) 125,000 403 cm 2 (62.5 sq. in.) 150,000 484 cm 2 (71 sq. in.)
FreeArea
MinimumFreeArea RequiredforEach Opening
VerticalDuctoropenings
to outside
(4,000BTUH)
81 cm2(12.5sq.in.)
121cm2(18.75sq. in.)
161 cm 2(25 sq. in.)
202 cm 2 (31.25 sq. in.)
242 cm2 (37.5 sq. in.) 7"
Round
Duct
(4,000
BTUH)
4"
5"
6"
7"
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input 100,000 + 30,000 = (130,000 + 4,000) = 210 cm2
Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 + 2,000) = 210 cm 2
One permanent opening, commencing within 12" (30 cm) of the
top of the enclosure, shall be permitted where the equipment has clearances of at least 1" (2.5 cm) from the sides and back and 6"
(32.5 Sq. In.) Vertical
(65 Sq. In.) Horizontal
GasVent
11
Inlet t
Air(t)
._, GableVent
f VentilatedAttic_
Top Above Insulatio_h_=
I I _ I_"
OutletAir (1) II I SoffitVent
_ Inlet
Air(2)
(16 cm) from the front of the appliance. The opening shall directly
communicate with the outdoors or shall communicate through a vertical orhorizontal duct to the outdoors or spaces (crawl or attic)
that freely communicate with the outdoors, and shall have a mini- mum free area of:
1 sq. in per 3000 Btu per hr (7cm2per kW) of the total input rating of all equipment located in the enclosure, and
Not less than the sum of the areas of all vent connectors in
the confined space.
UnconfinedSpace Installation
Poison carbon monoxide gas hazard. Most homes will require additional air.
An unconfined space or homes with tight construc- tion may not have adequate air infiltration for proper
combustion and ventilation of flue gases. Failure to supply additional air by means of ventila-
tion grilles or ducts could result in personal injury
and/or death.
An unconfined space is defined as an area having a minimum vol- ume of 50 cubic feet(1.4m 3)per 1,000 Btuh total input rating for all gas appliances in area.
Adjoining rooms can be considered part of an unconfined area if there are no doors between rooms.
An attic or crawl space may be considered an unconfined space provided there are adequate ventilation openings directly to out- doors. Openings MUST remain open and NOT have any means
of being closed off. Ventilation openings to outdoors MUST be at
Loading...
+ 11 hidden pages