These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and
NOTE
ThesignalwordsDANGER,WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manuals that may
apply to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE - Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
!
The signal word CAUTION is used throughout this
manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
INTRODUCTION2...............................
LOCATION2....................................
HEATER PACKAGES2...........................
AIR DUCTS7...................................
ELECTRICAL CONNECTIONS7..................
REFRIGERANT TUBING10........................
REFRIGERANT FLOW- CONTROL DEVICE10......
REFRIGERANT METERING DEVICE11.............
CONDENSATE DRAINS11........................
ACCESSORIES12................................
SEQUENCE OF OPERATIONS13..................
START- UP PROCEDURE13......................
CARE AND MAINTENANCE13.....................
AIRFLOW PERFORMANCE TABLES14.............
R- 410A QUICK REFERENCE GUIDE17............
!
PERSONAL INJURY, AND/OR PROPERTY DAMAGE
HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons could
result in equipment malfunction, property damage,
personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test
instruments.
Installation must conform with local building codes and
with the National Electrical Code NFPA70 current edition.
WARNING
496 01 5503 014/20/18Specifications are subjec t to change without notice.
Models FEM4X, FEM4P, and REM4X are for R- 410A
refrigerant and can be used for upflow, horizontal left or right,
and downflow applications (accessory kit required for
downflow). FEM and FXM units aredesigned to meet cabinet
air leakage of less than 2% at 0.5 inches W.C. and cabinet
air leakage less than 1.4% at 0.5 inches W.C. when tested
in accordance with ASHRAE 193 standard.
FEM4P models are available for system sizes 1- 1/2 - 4 tons
(18,000 - 48,000 BTUH) nominal cooling capacity. FEM4P
use a refrigerant piston metering device with an ECM.
FEM4X and FXM models are available for system sizes
1- 1/2 - 5 tons (18,000 - 60,000 BTUH) nominal cooling
capacity. All models use an ECM motor and have a
factory- installed and appropriately sized hard shut- off TXV
metering device and are for R- 410A refrigerant ONLY.
REM4X models are available for system sizes 1- 1/2 through
5 tons (18,000 - 60,000 BTUH) nominal cooling capacity. All
models use an ECM motor and have a factory- installed and
appropriately sized hard shut- off R- 410A TXV metering
device used for R- 410A refrigerant ONLY.
FEM and REM models require a field supplied air filter.
Factory approved electric heater packages are available in
sizes 3kW through 30kW. See Product Specification
literature for available accessory kits.
LOCATION
Select the best position which suits the installation site
conditions. The location should provide adequate structural
support, space in the front of the unit for service access,
clearance for return air and supply duct connections, space
for refrigerant piping connections and condensate drain line
connections. If heaters are being installed make sure
adequate clearance is maintained from supply duct work.
Nuisance sweating may occur if the unit is installed in a high
humidity environment with low airflow. On these installations a
wrap of 2” (51mm) fiberglass insulation with a vapor barrier is
recommended.
NOTE: Internal filter can be accessed from separate filter
door. If the filter can NOT be easily accessed, a remote filter
is recommended. Refer to ACCA Manual D for remote filter
sizing.
requirements of less than 2% cabinet leakage rate at 0.5
inches W.C. and 1.4% cabinet leakage rate at 0.5 inches
W.C. when tested in accordance with ASHRAE 193
standard.
NOTE: FEM Units that require a kit to meet low leak
requirements have a gasket kit automatically included with
shipment.
Table 1 - Gasket Kit Requirement
Unit Size
018YesYes
024YesYes
030YesYes
036YesYes
042YesYes
048NoYes
060NoNo
See Clearances
REQUIRED CLEARANCES - ALL MODELS inches
No
Heaters
With
Heaters
From First 3 feet of Supply Duct to
From Supply Duct to Combustibles
FEM - Kit Needed ?FXM - Kit Needed?
(mm)
All Sides0
From Supply Duct0
All Sides0
Combustibles
after 3 feet
1 (25)
0
HEATER PACKAGES
Factory approved, field installed, UL listed heater packages
are available from the equipment supplier. See unit rating
plate for a list of factory approved heaters. Heaters that are
not factory approved could cause damage which would not
be covered under the equipment warranty.
POSITION UNIT
Unit can stand or lie on floor, or hang from ceiling or wall.
Allow space for wiring, piping, and servicing unit.
!
FIRE HAZARD
Failure to maintain proper clearances could result inpersonal
injury, death, and/or property damage.
When heaters are installed, maintain clearances from combustible materials as specified on unit rating plate. Do not use
plastic lined or combustible flexible ducting within 36 inches
of the supply end of the fan coil.
Refer to Table 1. Install the FEM fan coil with the
accompanying kit to ensure compliance with low leak
2496 01 5503 01
WARNING
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property
damage.
A field fabricated auxiliary drain pan, with a separate drain
is REQUIRED for all installations over a finished living
space or in any area that may be damaged by overflow
from a restricted main drain pan. In some localities, local
codes require an auxiliary drain pan for ANY horizontal
installation.
Specifications are subjec t to change without notice.
If return air is to be ducted through a floor, set unit on floor
over opening and use 1/8 to 1/4 inch thick (3 to 6 mm thick)
fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening
per dimensions shown in Figure 2. A field- supplied bottom
closure is required.
SLOPE COIL UNITS
MODELA
FEM18, REM1812” (305mm)
FXM18, FEM24, FXM24, REM24,
FEM30, REM30, FEM36, REM36
17” (432mm)
FXM3019” (483mm)
B. MODULAR UNITS
FEM4X6000B, REM4X6000B, and FXM4X4800/6000 fan
coils are two- piece modular units. This allows for modular
units to be disassembled andcomponents moved separately
toinstallationareaforreassembly.Thisprocess
accommodates small scuttle holes and limiting entrances to
installation sites (Figure 1).
Figure 2
POWER ENTRY
OPTIONS
FRONT SERVICE CLEARANCE
18 - 48 models = 21” (533 mm)
60 model = 24” (610 mm)
A- COIL
UNITS
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
UPFLOW/DOWNFLOW
SECONDARY DRAIN
Upflow Installation
1½”
19”(483mm)
2½”
(64mm)
FIELD SUPPLIED
SUPPLY DUCT
LOW VOLT
ENTRY
OPTIONS
FIELD MODIFIED
SIDE RETURN
A
LOCATION FOR
SLOPE COIL
UNITS ONLY
UPFLOW/DOWNFLOW
PRIMARY DRAIN
496 01 5503 013
Specifications are subjec t to change without notice.
Failure to follow this caution may result in product or
property damage.
The conversion of the fan coil to downflow requires special
procedures for the condensate drains on both A- coil and
Slope- coil units. The vertical drains have an overflow hole
between the primary and secondary drain holes. This hole
is plugged for all applications except downflow, and must
be used for downflow.
Failure to follow instructions could result in personal injury
or product and property damage.
!WARNING
STRUCTURAL DAMAGE
Failure to follow this warning could result in personal
injury or death, or property damage.
Combustible floor base is required when installing in a
downflow application with electric heat strips.
Structuraldamagecouldoccurifmanufacturer’s
downflow base accessory kit is not use when installing in
a downflow application.
In this application, field conversion of the evaporator coil is
required using accessory Downflow Kit along with an
accessory Base Kit. Set unit on floor over opening and use
1/8” to 1/4” thick fireproof resilient gasket between duct, unit,
and floor. Refer to installation instructions packaged with
accessory kit. See Product Specification literature for kit part
numbers.
During the conversion process, remove the plastic cap
covering the vertical drains only and discard.
Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the
vertical pan fitting to door joint to retain low air leak
performance of the unit.
NOTE: Gasket kit number(EBAC01GSK) is also required for
all downflow applications to maintain low air leak/low sweat
performance.
D. HORIZONTAL INSTALLATION
Unit must NOT be installed with access panels facing up or
down. Access panels must only face to the side.
All models arefactory built for horizontal left installation (refer
to Figure 3 and Figure 4). They can be field converted to
horizontal right (accessory Gasket Kit required, see Product
Specification literature for part number). Refer to Figure 5
and Figure 6.
NOTE: When suspending unit from ceiling, dimples in casing
indicate suitable location of screws for mounting metal
support straps (refer to Figure 3).
NOTE: For optimum condensate drainage performance in
horizontal installations, unit should beleveled along its length
and width.
Figure 3
LOW VOLT
ENTRY
OPTIONS
Slope Coil In Horizontal Left Application (factory configuration)
A- COIL
HORIZONTAL LEFT
FIELD
SUPPLIED
HANGING
STRAPS
SECONDARY
DRAIN
SECONDARY
DRAIN
FRONT SERVICE CLEARANCE
(FULL FACE OF UNIT)
18 - 48 models = 21” (533mm)
60 model = 24” (610mm)
1¾” (45mm)
FILTER ACCESS
CLEARANCE
PRIMARY
DRAIN
POWER
ENTRY
OPTIONS
4496 01 5503 01
Specifications are subjec t to change without notice.
A- Coil in Horizontal Left Application (factory configuration)
A
COIL
BRACKET
COIL
SUPPORT
B
C
BRACKET
HORIZONTAL
DRAIN PAN
AIR SEAL
ASSEMBLY
REFRIGERANT
CONNECTIONS
HORIZONTAL LEFT
RAIL
DRAIN PAN
SUPPORT
BRACKET
COIL
PRIMARY DRAIN
SECONDARY DRAIN
HORIZONTAL LEFT
Horizontal Right Conversion of Units With Slope Coils
1. Remove blower and coil access paneland fitting panel
(refer to Figure 5).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
4.Lay fan coil unit on its right side and reinstall coil
assembly with condensate pan down (refer to Figure 5).
Figure 5
COIL SUPPORT RAIL
SLOPE COIL
COIL MOUNTING
SCREW
Conversion for Horizontal Right Applications - Slope Coil
5. Attach coil to casing flange using coil mounting screw
previously removed.
6. Align holes with tubing connections and condensate
pan connections, and reinstall access panels and
fitting panel. After brazing, make sure liquid and
suction tube grommets are in place to prevent air
leaks and cabinet sweating.
BLOWER
ASSEMBLY
DRAINPAN
496 01 5503 015
REFRIGERANT
CONNECTIONS
Specifications are subjec t to change without notice.
Horizontal Right Conversion of Units With A- Coils
1. Remove blower and coil access paneland fitting panel
(refer to Figure 6).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil
assembly with condensate pan down (refer to
Figure 6).
5. Remove horizontal drain pan support bracket from coil
support rail on left side of unit and reinstall on coil
support rail on right side of unit.
6. Convert air- seal assembly for horizontal right (refer to
Figure 6).
a. Remove air- seal assembly from coil by removing 4
screws.
b. Remove coil drip flanges from A- coil and reinstall on
right side of coil (same side as horizontal drain pan).
c. Remove filler plate (A) and install air splitter (B) in
place of filler plate.
d. Install filler plate (A) as shown in horizontal right
application.
e. Remove condensate troughs (C) and install on
opposite tube sheets.
f. Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket on
each corner of vertical pan engages coil support rails.
9. Reinstall 2 snap- in clips to correctly position and
secure coil assembly in unit. Be sure clip with large
offsets is used on right side of unit to secure horizontal
pan.
10. Remove 2 oval coil access panel plugs and reinstall
into holes on left side of coil access panel and fitting
panel.
11. Remove insulation knockouts on right side of coil
access panel.
12. Reinstall access fitting panels, aligning holes with
tubing connections and condensate pan connections.
Be sure to reinstall metal clip between fitting panel and
vertical condensate pan.
13. After brazing, make sure liquid and suction tube
grommets are in place to prevent air leaks and cabinet
sweating.
Figure 6
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
SUPPORT
RAIL
COIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIAMRY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
REFRIGERANT
CONNECTIONS
Conversion for Horizontal Right Applications - A- Coil
A
AIR SEAL
ASSEMBLY
HORIZONTAL
RIGHT
APPLICATION
B
C
6496 01 5503 01
Specifications are subjec t to change without notice.
1. Fan coil unit must be secured to the structure using
field- supplied hardware.
2. Allow a minimum of 24 inches (610mm) clearance
from access panels.
3. Recommended method of securing for typical
applications:
a. If fan coil is away from wall, attach pipe strap to top
of fan coil using No. 10 self tapping screws. Angle
strap down and away from back of fan coil, remove
all slack, and fasten to wall stud of structure using
5/16” lag screws. Typical both sides of fan coil.
b. If fan coil is against wall, secure fan coil to wall stud
using 1/8” (3mm) wide right- angle brackets. Attach
brackets to fan coil using No. 10 self tapping screws
and to wall stud using 5/16” lag screws (refer to
Figure 7).
NOTE: Modular units can be disassembled and compo-
nents moved separately to installation area for reassembly. This process accommodates small scuttle
holes and limiting entrances to installation sites (refertoFigure8).
Figure 8
2 SCREWS
REAR CORNER
BRACKET
Removal of Brackets on
Modular Units
BLOWER BOX
2 SCREWS
2 SCREWS
COIL BOX
Figure 7
Mobile Home or Manufactured
Housing Applications
4” (102mm) MAX
SECURE FAN COIL TO STRUCTURE
UNIT AWAY FROM WALL
PIPE STRAP
(TYPICAL BOTH SIDES)
OR
UNIT AGAINST WALL
1/8” (3mm) INCH THICK ANGLE
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
DOWN FLOW
BASE KIT
SECURE UNIT TO FLOOR
ANGLE BRACKET O R PIPE STRAP
4” (102mm) MAX
AIR DUCTS
Connect supply- air duct over the outside of 3/4” flanges
provided on supply- air opening. Secure duct to flange using
proper fasteners for type of duct used, and seal duct- to- unit
joint.
It is a recommendation, but not a requirement, to use flexible
connections between ductwork and unitto prevent
transmission of vibration. When electric heater is installed,
use heat- resistant material for flexible connector between
duct work and unit at discharge connection. Duct work
passing through unconditioned space must be insulated and
covered with vapor barrier.
Duct Work Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and
10 feet of main duct before first branch takeoff may require
internal acoustical insulation lining. As an alternative, fibrous
duct work may be used if constructed and installed in
accordance with the latest edition of SMACNA construction
standard on fibrous glass ducts. Both acoustical lining and
fibrous duct work shall comply with National Fire Protection
Association as tested by UL Standard 181 for Class 1 air
ducts.
496 01 5503 017
Specifications are subjec t to change without notice.
These Fan Coils do not have a printed circuit board (PCB), they
have a low voltage circuit protective fuse (3 amp) inline on the
wire harness. Speed selections are made at the fan motor with
the Blue wire. The motor is pre- programmed with the
time- delay circuit on some of the speed taps. (See Page 9,
Section D)
Before proceeding with electrical connections, make certain
that supply voltage, frequency, phase, and circuit ampacity are
as specified on the unit rating plate. See unit wiring label for
proper field high and low voltage wiring.
!
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD
Failure to follow this warning couldresult in personal injury,
death, and/or unit damage.
If a disconnect switch is to be mounted on unit, select a
location where drill and fasteners will not contact electrical
or refrigeration components.
Make all electrical connections in accordance with the NEC
and any local codes or ordinances that may apply. Use
copper wire only. The unit must have a separate branch
electric circuit with a field- supplieddisconnect switch located
within sight of and readily accessible from the unit.
NOTE: When a pull- out type disconnect is removed from the
unit, only the Load side of the circuit is de- energized. The
Line side remains live until the main (remote) disconnect is
turned off.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Turn off the main (remote) disconnect device before
working on incoming (field) wiring.
Incoming (field) wires on the line side of the disconnect
found in the fan coil unit remain live, even when the
pull- out is removed. Service and maintenance to
incoming (field) wiring cannot be performed until the main
disconnect switch (remote to the unit) is turned off.
A. LINE VOLTAGE CONNECTIONS
Fan Coils installed without electric heat require the use of a
factory- authorized Power Plug Kit (accessory part number
EBAC01PLG). This kit provides the electrical connections
necessary to supply the unit with 208/230V power when
electric heat is not present. For units without electric heat:
1. Connect 208/230V power leads from field disconnect
to yellow and black stripped leads on Power Plug
(accessory part number EBAC01PLG).
2. Connect ground wire to unit ground lug.
WARNING
WARNING
3. When installing an electric heater, remove and discard
power plug (if equipped) from fan coil and connect
male plug from heater to female plug from unit wiring
harness.(SeeElectricHeaterInstallation
Instructions.)
B. 24V CONTROL SYSTEM
Connection to Unit
Wire low- voltage in accordance with wiring label on the
blower (also refer to Figure 9 through Figure 12). Use 18
AWG color- coded, insulated (35 °C minimum) wire to make
the low- voltage connections between the thermostat, the
unit, and the outdoor equipment. If the thermostat is located
more than 100 feet from the unit (as measured along the low
voltage wire), use 16 AWG color- coded, insulated (35 ° C
minimum) wire. All wiring must be NEC Class 1 and must be
separated from incoming power leads. Refer to outdoor unit
wiring instructions for additional wiring recommendations.
Heater Staging
If electric heat staging is required, a multi- stage heating
room thermostat is required. Consult your equipment
supplier for a suitable thermostat.
Manufactured Housing
In manufactured housing applications, the Code of Federal
Regulations, Title 24, Chapter XX, Part 3280.714 requires
that supplemental electric heat be locked out at outdoor
temperatures above 40_F(4_C), except for a heat pump
defrost cycle. Refer to Figure 12 for typical low- voltage
wiring with outdoor thermostat.
Figure 9
THERMOSTAT
Wiring Layout - Air Conditioning
Unit (Cooling Only)
FAN COIL
(CONTROL)
WHT
RED
GRY
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
AIR COND.
C
Y
R
G
W
Y
8496 01 5503 01
Specifications are subjec t to change without notice.
Transformer is factory wired for 230V operation. For 208V
applications, disconnect the black wire from the 230V terminal
on transformer and connect it to the 208V terminal (refer to
Figure 13).
Figure 13
SECONDARY
C
208
Transformer Connections
BROWN
RED
YELLOW
230
BLACK
PRIMARY
C. GROUND CONNECTIONS
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground
could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground
in order to minimize potential for personal injury or death
if an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground
wire must be used.
NOTE: Use UL listed conduit and conduit connectors for
connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs
provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum CFM.
Refer to the unit wiring label to ensure that the fan speed
selected is not lower than the minimum fan speed indicated.
Fan speed selection is done at the fan motor. To change motor
speeds, reposition wire at fan motor speed terminals labeled
1- 2- 3 (see Figure 14). Units with or without electric heaters
require a minimum CFM. Refer to the unit wiring label to ensure
that the fan speed selected is not lower than the minimum fan
speed indicated.
SPEED TAP SELECTION AT MOTOR CONNECTOR
Ta p 1Low90 sec off delay
Ta p 2Medium90 sec off delay
Ta p 3High90 sec off delay
Ta p 4Electric Heat †0 sec off delay
Ta p 5Max ‡0 sec off delay
† Electric heat airflow is same CFM as Tap 3, but with 0
sec off delay.
‡ For high static applications, see Airflow Performance
Tables for max airflow.
496 01 5503 019
Specifications are subjec t to change without notice.
To change motor speeds disconnect the BLUE fan lead from
motor connector terminal #2 (factory default position) and
move to desired speed tap; 1, 2, 3, or 5 (see Figure 14).
Speed taps 1, 2, and 3 have a 90 second blower off time
delay pre- programmed into the motor. Speed tap 4 is used
for electric heat only (with 0 second blower time delay) and
the WHITE wire should remain on tap 4. Speed tap 5 is used
for high static applications, but has a 0 second blower time
delay pre- programmed into the motor (see Airflow
Performance Tables for actual CFM for each tap). Also, see
Figure 14 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap should
be used to reduce possibility of water being blown off coil.
REFRIGERANT TUBING
Refrigerant Tubing Connection and Evacuation
Use accessory tubing package or field- supplied tubing of
refrigerant grade. Suction tube must be insulated. Do not use
damaged, dirty, or contaminated tubing because it may plug
refrigerant flow- control device. ALWAYS evacuate the coil
and field- supplied tubing to 500 microns before opening
outdoor unit service valves.
Units have sweat suction and liquid tube connections. Make
suction tube connection first.
1. Cut tubing to correct length.
2. Insert tube into sweat connection on unit until it
bottoms.
3. Braze connection using silver bearing or non- silver
bearing brazing materials. Do not use solder (materials
which melt below 800_F / 427_C). Consult local code
requirements.
4. Evacuate coil and tubing system to 500 microns using
deep vacuum method.
Size and install refrigerant lines according to information
provided with outdoor unit. Route refrigerant lines to the fan
coil in a manner that will not obstruct service access to the
unit or removal of the filter.
Figure 14
12345
Speed Taps may be located on motor,
or on plug close to motor.
12345
1. Find the liquid tube grommet in the small- parts bag
and slide it onto the liquid refrigerant line (field
line- set).
2. Remove the lower door. Remove the tubing plate (with
suction tube grommet) and slide the plate with
grommet onto the refrigerant lines (field line- set), away
from braze joints.
3. Remove rubber plugs from coil stubs using a pulling
and twisting motion. Hold coil stubs steady to avoid
bending or distorting.
4. Wrap TXV and nearby tubing with a heat- sinking
material such as a wet cloth.
5. Fit refrigerant lines into coil stubs. Wrap a heat sinking
material such as a wet cloth behind braze joints.
6. Braze using a Sil- Fos or Phos- copper alloy.
7. After brazing, allow joints to cool. Slide tubing plate
back into place and position grommets around suction
and liquid tubes to ensure air seal.
Motor Speed Selection
CLGN
L11S018
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or
property damage.
Wrap a wet cloth around rear of fitting to prevent
damagetopistonassemblyorTXVand
factory- made joints.
10496 01 5503 01
Specifications are subjec t to change without notice.
metering device with Teflon ring. If a piston replacement is
required, check piston size shown on indoor unit rating plate
to see if it matches required outdoor piston size. The outdoor
piston size will be found on the outdoor unit rating plate,
product data or installation instructions depending on the
model shown on outdoor unit rating plate. If the fan coil piston
does not match, replace indoor piston with correct outdoor
piston. With some outdoor units a piston is shipped with
outdoor unit.
When changing piston, use a back- up wrench. Hand tighten
hex nut, then tighten with wrench 1/2 turn. Do not exceed 30
ft- lbs.
NOTE: The indoor piston contains a Teflon ring (or seal)
which is used to seat against the inside of distributor body,
and must be installed properly to ensure proper seating in the
direction for cooling operation.
Always use outdoor units designed to match indoor fan coil
applications.
factory installed Piston
REFRIGERANT METERING DEVICE
FEM4X, REM4X, FXM4X Models:
These Fan Coils have a factory installed hard shut- off TXV
designed only for use with R- 410A refrigerant. Use only with
outdoor units designed for R- 410A.
TXV is factory set and not field adjustable.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
This Fan Coil has a hard shut- off TXV metering device. A
compressorHard Start Kit is REQUIRED in all
applications where the matching outdoor unit has a
single- phase reciprocating compressor.
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
If using a TXV in conjunction with a single- phase reciprocating compressor, a compressor start capacitor and relay
are required. Consult outdoor unit pre- sale literature for
start assist kit part number.
CAUTION
CAUTION
Figure 15Refrigerant Flow- Control Device
BRASS
HEX NUT
TEFLON SEAL
PISTON
RETAINER
STRAINER
TEFLON RING
PISTON
FLOW IN
COOLING
DISTRIBUTOR
BRASS
HEX BODY
CONDENSATE DRAINS
Unit is provided with primary and secondary 3/4” (19mm)
NPT drain connections. Refer to Figure 2, Figure 3,
Figure 4, Figure 5, and Figure 6 to identify the primary and
secondary locations. To prevent property damage and
achieve optimum drainage performance, BOTH primary and
secondary drain lines should be installed and include
properly sized condensate traps (refer to Figure 16).
Factory approved condensate traps are available (accessory
part number EBAC01CTK).
To connect drainlines, the drain connection knock- outs must
be removed. Use a knife to start the opening near the tab and
using pliers, pull the tab to remove the knock- out. Clean the
edge of the opening if necessary. After drain fittings are
installed, caulk the seam between the fitting and the cover to
retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic
condensate pan. Do not over- tighten. Finger- tighten plus
1- 1/2 turns. Use pipe dope to ensure proper seal.
Install traps in the condensate lines as close to the coil as
possible (refer to Figure 18), but avoid blocking filter access
panel.
Install drain lines below the bottom of the drain pan and pitch
the drain lines down from the coil at least 1/4 inch per foot of
run (6mm per 0.3m). Horizontal runs over 15 feet (5m) long
must also have an anti- siphon air vents (stand pipes),
installed ahead of the horizontal runs. Extremely long
horizontal runs may require oversized drain lines to eliminate
air trapping.
Route primary drain line to the outside or to a floor drain.
Check local codes before connecting to a waste (sewer) line.
Route the secondary drain line to a place in compliance with
local installation codes where it will be noticed when unit is
operational. Condensate flowing from secondary (overflow)
drain indicates a plugged primary drain - unit requires
service or water damage will occur.
496 01 5503 0111
Specifications are subjec t to change without notice.
Prime all traps, test for leaks, and insulate in areas where
sweating of the traps and drain lines could potentially cause
waterdamage.Consultlocalcodesforadditional
requirements or precautions.
If a gravity drain cannot be used, install a condensate pump.
Install the pump as close to the indoor section as possible.
!
CAUTION
PRODUCT or PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or
property damage.
Use only full size P- traps in the condensate line (refer to
Figure 16). Shallow, running traps are inadequate and
DO NOT allow proper condensate drainage (refer to
Figure 17).
Figure 16Recommended Condensate Trap
UNIT
2” MIN (51mm)
2” MIN (51mm)
Figure 17Insufficient Condensate Trap
Figure 18Condensate Drain
FILTER
ACCESS
PANEL
SECONDARY DRAIN WITH
APPROPRIATE TRAP REQUIRED
(USE FACTORY KIT OR
FIELD- SUPPLIED TRAP)
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR
FIELD- SUPPLIED TRAP OF PROPER DEPTH.
STANDARD P- TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
ACCESSORIES
A. HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as shown in
Figure 19 and Figure 20.
Figure 19
THERMOSTAT
W
Wiring Layout of Humidifier to Heat
Pump
FAN COIL
(CONTROL)
WHT
RED
GRY
BRN
WHT
BLU
VIO
R
G
C
W
2
W
3
E
R
G
C
2
E
L
O
Y
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
FAN HUMIDIFIER
115V M
DO NOT USE SHALLOW RUNNING TRAPS!
12496 01 5503 01
Specifications are subjec t to change without notice.
Thermostat closes R to G. G sends signal direct to motor which
completes circuit to indoor blower motor. When G is
de- energized, there is a 90 second off delay before indoor
blower motor stops.
B. COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat pump
only). G sends signal direct to motor, which completes circuit to
indoor blower motor. When G is de- energized, there is a 90
second
C. HEAT PUMP HEATING MODE
Thermostat energizes R to G and R to Y. G sends signal direct
to motor, which completes circuit to indoor blower motor. When
G is de- energized, there is a 90 second
blower motor stops.
D. HEAT PUMP HEATING WITH AUXILIARY
Thermostat energizes R to G, R to Y, and Rto W. G energizes
indoor blower motor. W energizes electric heat relay(s) which
completes circuit to heater element(s). When W is
de- energized, electric heat relay(s) open, turning off heater
elements. When G is de- energized, the indoor blower motor
is de- energized and stops.
off delay before indoor blower motor stops.
off delay before indoor
ELECTRIC HEAT
E. ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat relay(s)
which completes circuit to heater element(s). W also
energizestheindoorblowermotor.WhenWis
de- energized, electric heat relay(s) opens and the indoor
blower motor is de- energized and stops.
START- UP PROCEDURE
Refer to outdoor unit Installation Instructions for system
start- up instructions and refrigerant charging method
details.
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified
service technician. Consult the servicing dealer for
recommended frequency.
Between visits, the only consumer service recommended or
required is air filter maintenance and condensate drain
operation.
Air Filter
Inspect air filters at least monthly and replace or clean as
required. Disposable type filters should be replaced.
Reusable type filters may be cleaned by soaking in mild
detergent and rinsing with cold water. Install filters with the
arrows on the side pointing in the direction of air flow.
Condensate Drain
During the coolingseason check at least monthly for free flow
of drainage and clean if necessary.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit
performance and/or product damage.
Never operate unit without a filter. Factory authorized filter
kits must be used when locating the filter inside the unit.
For those applications where access to an internal filter is
impractical, a field- supplied filter must be installed in the
return duct system.
CAUTION
496 01 5503 0113
Specifications are subjec t to change without notice.
1. Airflow based upon dry coil at 230v with factory- approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes
4200 through 6000). For FEM4X, FEM4P, and REM4X models, airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a
constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 4200 - 6000 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 4800 - 6000 size could result in condensate blowing off coil or splashing out of drain pan.
Ta p 3701660616581537499
Ta p 2614569534486436398
Ta p 1410350304261228203
Ta p 5969936892835763676
Ta p 4826795766743706660
Ta p 3826795766743706660
Ta p 2701660616581537499
Ta p 1617592552507472420
Ta p 5965920870823780740
Ta p 4820783740680630575
Ta p 3820783740680630575
Ta p 2720655610555485450
Ta p 1716600540495430328
Ta p 511081090106510341009974
Ta p 410261000969938899865
Ta p 310261000969938899865
Ta p 2909873842799762724
Ta p 1825795757722674634
Ta p 5130112761245121811761121
Ta p 4122711911169114311051074
Ta p 3122711911169114311051074
Ta p 21087106210301001966930
Ta p 110261000969938899865
Ta p 5156015441507146414241358
Ta p 4141913971358132012791239
Ta p 3141913971358132012791239
Ta p 2124912201184114210931052
Ta p 1124212051158111010691026
Ta p 5174317121679164216101574
Ta p 4166916341599156415311499
Ta p 3166916341599156415311499
Ta p 2145214131377133913081271
Ta p 1130012561221118211421101
Ta p 5189718671836180817741736
Ta p 4181717851757172416931655
Ta p 3181717851757172416931655
Ta p 2165716211589155715181474
Ta p 1144314121377133212861243
0.100.200.300.400.500.60
TOTAL STATIC (inches water column)
14496 01 5503 01
Specifications are subjec t to change without notice.
FXM AIRFLOW PERFORMANCE - CFM at a given Speed and Static reading
ModelBlower Speed
Ta p 5776745696660609572
Ta p 4683644589548494461
FXM4X1800
Ta p 3683644589548494461
Ta p 2631563500443409361
Ta p 1625524457417367319
Ta p 5956920891851816780
Ta p 4825795757722674634
FXM4X2400
Ta p 3825795757722674634
Ta p 2726695635598543509
Ta p 1631563500443409361
Ta p 511891151110410501003959
Ta p 41041998944886837772
FXM4X3000
Ta p 31041998944886837772
Ta p 2924876817752704660
Ta p 1779693628571526476
Ta p 5136313321294125312071157
Ta p 4123712061160112110701013
FXM4X3600
Ta p 3123712061160112110701013
Ta p 2109510581007951888824
Ta p 11014885773673609549
Ta p 5151914901454141913791332
Ta p 4143714031366133312941245
FXM4X4200
Ta p 3143714031366133312941245
Ta p 2125712261191114110901033
Ta p 1123712061160112110701013
Ta p 5175717251693165316141576
Ta p 4166416261593155215171477
FXM4X4800
Ta p 3166416261593155215171477
Ta p 2145914201379133612981259
Ta p 1130112411195115011021039
Ta p 5203019951961192718881842
Ta p 4181117751740170316641613
FXM4X6000
Ta p 3181117751740170316641613
Ta p 2166516321593155615071453
Ta p 1146214181371132712781228
NOTES:
1. Airflow based upon dry coil at 230v with factory approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes 4200 through
6000).
2. Airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds the
motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal
applications of 4200 - 6000 sizes must have supply static greater than 0.20 in. wc.
4. Airflow above 400 cfm/ton on 4800 - 6000 size could result in condensate blowing off coil or splashing out of drain pan.
5. Not recommended for use above 0.60 inches water column external static pressure.
6. Shading - Airflow outside 450 cfm/ton.
Measured Static Pressure, inlet to outlet (inches water column)
0.100.200.300.400.500.60
496 01 5503 0115
Specifications are subjec t to change without notice.