ICP FEM4P1800A1, FEM4P1800AT1, FEM4P2400A1, FEM4P2400AT1, FEM4P3000A1 Installation Guide

...
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate
throughout this manual and other manuals that may
apply to the product. DANGER - Immediate hazards which will result in
severe personal injury or death. WARNING - Hazards or unsafe practices which
could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Introduction .................................... 2
Location ....................................... 2
Clearances and Dimensions ................... 3-4
Heater Packages ............................... 5
Position Unit ................................. 5-9
Air Ducts ..................................... 10
Electrical Connections ...................... 10-14
Refrigerant Tubing ............................. 15
Refrigerant Flow-Control Device ................ 15
Condensate Drains ............................ 16
Accessories .................................. 17
Sequence of Operation ......................... 18
Start-up Procedure ............................ 18
Care and Maintenance ......................... 18
Airflow Performance ........................ 19-20
R-410A Quick Reference Guide ................. 21
PERSONAL INJURY, AND/OR PROPERTY DAM- AGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per- sons could result in equipment malfunction, prop- erty damage, personal injury and/or death.
The information contained in this manual is in- tended for use by a qualified service technician fa-
miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code
NFPA70 current edition.
496 01 5501 01 April 2011
INTRODUCTION
Models FEM4P, FSM4P, and FSU4P are for R-410A refrigerant.
Models FEM4P and FSM4P are designed for maximum
flexibility and can be used for upflow, horizontal left or
right, and downflow applications (accessory kit required
for downflow).
Model FSU4P is designed for upflow installation, and can be field modified for downflow applications (accessory kit required).
LOCATION
Select the best position which suits the installation site conditions. The location should provide adequate structural support, space in the front of the unit for service
access, clearance for return air and supply duct connections, space for refrigerant piping connections and condensate drain line connections. If heaters are being
installed make sure adequate clearance is maintained
from supply duct work. See Clearances in Figure 1 and
Figure 2. If the unit is located in an area of high humidity, nuisance
sweating of casing may occur. On these installations a wrap of 2" (51mm) fiberglass insulation with a vapor barrier is
recommended.
FEM4P models are available for system sizes 1-1/2 - 4
tons (18,000 - 48,000 BTUH) nominal cooling capacity.
FEM4P uses a refrigerant piston metering device with an ECM integral electronically commutated motor for
efficiency. FSM4P and FSU4P models are available for system
sizes 1-1/2 - 4 tons (18,000 - 48,000 BTUH) nominal
cooling capacity. FSM4P and FSU4P use a refrigerant piston metering device with 2-speed PSC (permanent
split capacitor) motors. All models require a field supplied air filter. Factory
approved electric heater packages are available in sizes 5kW through 30kW. See Product Specification literature for available accessory kits
NOTE: Internal filter can be accessed from separate filter
door. If the filter can NOT be easily accessed, a remote filter is recommended. Refer to ACCA Manual D for
remote filter sizing.
FIRE HAZARD Failure to maintain proper clearances could result in
personal injury, death, and/or property damage. When heaters are installed, maintain clearances from
combustible materials as specified on unit rating plate. Do not use plastic lined or combustible flexible
ducting within 36 inches of the supply end of the fan coil.
2 496 01 5501 01
Figure1 [
ClearancesandUnitDimensions- FEM4P
(OPENING)
B
C
A
_" GJ(SERVICE ACCESS)
i ("(_OPENING)_G_.
38-11-82
! !!
No All Sides 0
Heaters From Supply Duct 0
With
Heaters
All Sides 0
From First 3 feet of Supply Duct to Combustibles 1 (25) From Supply Duct to Combustibles after 3 feet 0
M !!!!!
Unit Size A B C D E F G H
1800 42-11/16 14-5/16 12-7/16 12-5/8 22-1/16 11 21 19-13/16 2400 42-11/16 14-5/16 12-7/16 12-5/8 22-1/16 11 21 19-13/16 3000 49-5/8 17-5/8 15-3/4 15-5/8 22-1/16 11 21 19-13/16 3600 49-5/8 17-5/8 15-3/4 15-5/8 22-1/16 11 21 19-13/16 4200 49-5/8 21-1/8 19-1/4 19-1/8 22-1/16 11 21 19-13/16 4800 49-5/8 21-1/8 19-1/4 19-1/8 22-1/16 11 21 19-13/16
Unit Size A B C D E F G H
1800 1084 364 316 313 560 279 533 503 2400 1084 364 316 313 560 279 533 503 3000 1261 448 400 397 560 279 533 503 3600 1261 448 400 397 560 279 533 503 4200 1261 537 489 486 560 279 533 503 4800 1261 537 489 486 560 279 533 503
496 01 5501 01 3
Figure
2 J ClearancesandUnitDimensions- FSM4P,FSU4P
OPENING)
A
J
_" GJ-__SERVICE ACCESS)
38-11-82
!!!!!!!!!!!!!_!_!_!!!!!i!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!!_!_!_!_!_!:_!b!!!_!_@N!_!_!!!!!_!!_!!_!_!!!__!_!i_!!!!!i!!!_!!
No All Sides 0
Heaters From Supply Duct 0
With
Heaters
All Sides 0
From First 3 feet of Supply Duct to Combustibles 1 (25) From Supply Duct to Combustibles after 3 feet 0
_ _!_!_! _ !!_!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
Unit Size A B C D E F G H
1800 47-5/8 17-5/8 15-3/4 15-5/8 22-1/16 11 21 19-13/16
2400 49-5/8 17-5/8 15-3/4 15-5/8 22-1/16 11 21 19-13/16 3000 53-7/16 21-1/8 19-1/4 19-1/8 22-1/16 11 21 19-13/16 3600 53-7/16 21-1/8 19-1/4 19-1/8 22-1/16 11 21 19-13/16 4200 49-5/8 21-1/8 19-1/4 19-1/8 22-1/16 11 21 19-13/16 4800 53-7/16 24-11/16 22-3/4 22-11/16 22-1/16 11 24 19-13/16
!!!!!!!!!!!_!_!i!!!!i!_ __i!:!!!_!i_!_!!!!!!!!!!_!!!!!!_i_ !!!!i!!!!i!!!!i!!
Unit Size A B C D E F G H
1800 1210 448 400 397 560 279 533 503 2400 1261 448 400 397 560 279 533 503 3000 1357 537 489 486 560 279 533 503 3600 1357 537 489 486 560 279 533 503 4200 1261 537 489 486 560 279 533 503 4800 1357 627 578 576 560 279 610 503
4 496 01 5501 01
HEATER PACKAG ES
Factory approved, field installed, UL listed heater packages are available from the equipment supplier. See unit rating plate for a list of factory approved heaters.
POSITION UNIT
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in proper-
ty damage A field fabricated auxiliary drain pan, with a sepa-
rate drain is REQUIRED for all installations over a
finished living space or in any area that may be damaged by overflow from a restricted main drain
pan. In some localities, local codes require an aux- iliary drain pan for ANY horizontal installation.
Figure 3 [
POWER
OPTIONS
FRONT SERVICE CLEARANCE
18 - 48 models = 21" (533 mm)
60 model = 24" (610 mm)
UPFLOW/_
Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty.
A. UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor over opening and use 1/8 to 1/4 inch thick (3 to 6 mm
thick) fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per dimensions shown in Figure 3. A
field-supplied bottom closure is required.
Upflow Installation
S SUPPLY DUCT
LOW VO LT
tl ENTRY
OPTIONS FIELD SUPPLIED
11/2"
SLOPE COIL UNITS
MODEL SIZE A
18 12" (305mm) 24 12" (305mm)
30 17" (432mm) 36 17" (432mm)
)
SECONDARY DRAIN
/4 -
( 483mm)
II _ SIDE RETURN
2W'
IlL _4mm) [ UNITS ONLY
FIELD MODIFIED LOCATION FOR
SLOPE COIL
/
PRIMARY DRAIN
FIELD SUPPLIED RETURN PLENUM
/
496 01 5501 01 5
B.DOWNFLOWINSTALLATION
PRODUCT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product
or property damage The conversion of the fan coil to downflow re-
quires special procedures for the condensate drains on both A-coil and Slope-coil units. The vertical drains have an overflow hole between the
primary and secondary drain holes. This hole is plugged for all applications except downflow, and
must be used for downflow. Failure to follow instructions could result in per-
sonal injury or product and property damage.
In this application, field conversion of the evaporator coil is required using accessory Downflow Kit along with an
accessory Base Kit. Set unit on floor over opening and use 1/8" to 1/4" thick fireproof resilient gasket between
duct, unit, and floor. Refer to installation instructions packaged with accessory kit. See Product Specification literature for kit part numbers.
During the conversion process, removed the plastic cap covering the vertical drains only and discard.
Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain low air leak
performance of the unit. NOTE: Gasket kit number (EBACO1GSK) is also
required for all downflow applications to maintain low air leak/low sweat performance.
C. HORIZONTAL INSTALLATION
Unit must NOT be installed with access panels facing up or down. Access panels must only face to the side.
FEM4P and FSM4P models are factory built for horizontal left installation (refer to Figure 4 and Figure 5).
They can be field converted to horizontal right (accessory
Gasket Kit required, see Product Specification literature
for part number). Refer to Figure 6 and Figure 7.
NOTE: When suspending unit from ceiling, dimples in casing indicate suitable location of screws for mounting metal support straps (refer to Figure 4).
NOTE: For optimum condensate drainage performance in horizontal installations, unit should be leveled along its
length and width.
Figure 4 J Slope Coil In Horizontal Left Application (FEM4P & FSM4P factory configuration)
A-COIL
HORIZONTAL LEFT
FIELD SUPPLIED
LOW VOLT
ENTRY OPTIONS
HANGING STRAPS
SECONDARY DRAIN
SECONDARY PRIMARY DRAIN DRAIN
FRONT SERVICE CLEARANCE (FULL FACE OF UNIT)
18 - 48 models = 21" (533mm)
60 model = 24" (610mm)
1¾"(45mm) FILTER ACCESS
CLEARANCE
POWER ENTRY
OPTIONS
PRIMARY
DRAIN
6 496 01 5501 01
Figure5 [ A-Coil in HorizontalLeftApplication(FEM4P& FSM4Pfactoryconfiguration)
FACTORY SHIPPED
HORIZONTAL LEFT
APPLICATION
HORIZONTAL.
DRAIN PAN
AIR SEAL
Horizontal Right Conversion of Units With Slope Coils 5.
1.
Remove blower and coil access panel and fitting panel (refer to Figure 6).
2.
Remove coil mounting screw securing coil assembly to right side casing flange.
3.
Remove coil assembly.
4.
Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down (refertoFigure 6).
-- BRACKET
BRACKET
HORIZONTAL LEFT
REFRIGERANT
CONNECTIONS
COIL
COIL
SUPPORT
RAI L
DRAIN PAN
SUPPORT
BRACKET
COIL
PRIMARY DRAIN
SECONDARY DRAIN
HORIZONTALLEFT
Attach coil to casing flange using coil mounting screw previously removed.
6.
Align holes with tubing connections and
condensate pan connections, and reinstall access panels and fitting panel. After brazing, make sure
liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
Figure 6 [ Conversion for Horizontal Right Applications - Slope Coil
COIL MOUNTING
COIL SUPPORT RAIL
SLOPE
:{EFRIGERANT
CONNECTIONS
SECONDARY DRAIN
496 01 5501 01 7
BLOWER
ASSEMBLY
DRAIN
Horizontal Right Conversion of Units With A-Coils
1. Remove blower and coil access panel and fitting panel (refer to Figure 7).
2. Remove coil mounting screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down (refer to Figure 7).
5. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on
coil support rail on right side of unit.
6. Convert air-seal assembly for horizontal right (refer to Figure 7).
a. Remove air-seal assembly from coil by removing
4 screws.
b. Remove coil drip flanges from A-coil and reinstall
on right side of coil (same side as horizontal drain pan).
c. Remove filler plate (A) and install air splitter (B)
in place of filler plate.
d. Install filler plate (A) as shown in horizontal right
application.
e. Remove condensate troughs (C) and install on
opposite tube sheets.
f. Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil
support rails.
9. Reinstall 2 snap-in clips to correctly position and
secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit to secure
horizontal pan.
10. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel
and fitting panel.
11. Remove insulation knockouts on right side of coil
access panel
12. Reinstall access fitting panels, aligning holes with
tubing connections and condensate pan connections. Be sure to reinstall metal clip
between fitting panel and vertical condensate pan.
13. After brazing, make sure liquid and suction tube
grommets are in place to prevent air leaks and cabinet sweating.
Figure 7 J Conversion for Horizontal Right Applications - A-Coil
SEAL
SUPPORT
RAI L
BRACKET
DRAIN
SUPPORT
BRACKET
COIL_
SUPPORT
RAIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIAMRY
HORIZONTAL RIGHT
SECONDARY DRAIN HORIZONTAL RIGHT
CONNECTIONS ASSEMBLY
HORIZONTAL RIGHT APPLICATION
8 496 01 5501 01
D. MANUFACTUREDHOUSINGANDMOBILEHOME
APPLICATIONS
.
Fan coil unit must be secured to the structure using field-supplied hardware.
2.
Allow a minimum of 24 inches (610mm) clearance from access panels.
3.
Recommended method of securing for typical applications:
a. If fan coil is away from wall, attach pipe strap to
top of fan coil using No. 10 self tapping screws. Angle strap down and away from back of fan coil,
remove all slack, and fasten to wall stud of structure using 5/16" lag screws. Typical both
sides of fan coil.
b.
If fan ooil is against wall, secure fan coil to wall stud using 1/8" (3mm) wide right-angle brackets.
Attach brackets to fan coil using No. 10 self tapping screws and to wall stud using 5/16" lag
screws (refer to Figure 8).
Figure 8
---...._..
Mobile Home or Manufactured
Housing Applications
4" (102mm) MAX
/
-_ SECURE FAN COILTO STRUCTURE
I UNIT AWAY FROM WALL
PIPE STRAP
i_ (TYPICAL BOTH SIDES)
_ OR
UNIT AGAINST WALL
1/8" (3mm) INCH THICK ANGLE
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
4/_7 DOWN FLOW
BASE KIT
/ _ SECURE UNIT TO FLOOR _/ ANGLE BRACKET OR PIPE STRAP
4" (102ram) MAX
NOTE: Modular units can be disassembled and
components moved separately to installation area for reassembly. This process
accommodates small scuttle holes and limiting entrances to installation sites (refer to Figure 9).
Figure 9
BRACKET
Removal of Brackets on
Modular Units
BLOWER BOX
, , SO EWS
2 SCREWS
COIL BOX
496 01 5501 01 9
AIR DUCTS
Connect supply-air duct over the outside of 3/4"flanges provided on supply-air opening. Secure duct to flange using proper fasteners for type of duct used, and seal
duct-to-unit joint. Use flexible connectors between duct work and unit to
prevent transmission of vibration. When electric heater is installed, use heat-resistant material for flexible
connector between duct work and unit at discharge connection. Duct work passing through unconditioned
space must be insulated and covered with vapor barrier.
ELECTRICAL CONNECTIONS
FSM4P and FSU4P Fan Coil models utilize a printed circuit board (PCB) which has a low voltage circuit protective fuse (5 amp), fan motor speed tap terminal
(SPT), and time-delay relay (TDR). To disable the TDR
feature, snip the jumper wire JWl (refer to Figure 10).
FEM4P Fan Coil models do not have a printed circuit board (PCB), they have a low voltage circuit protective fuse (3
amp) inline on the wire harness. Speed selections are made at the fan motor with the Blue wire. The motor is
preprogrammed with the time-delay circuit on some of the speed taps. (See Section D)
Before proceeding with electrical connections, make certain that supply voltage, frequency, phase, and circuit ampacity
are as specified on the unit ratingplate. See unit wiring label
for proper field high and low voltage wiring.
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD
Failure to follow this warning could result in per- sonal injury, death, and/or unit damage.
If a disconnect switch is to be mounted on unit, se- lect a location where drill and fasteners will not
contact electrical or refrigeration components.
Duct work Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 feet of main duct before first branch takeoff may
require internal acoustical insulation lining. As an alternative, fibrous duct work may be used if constructed
and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts.
Both acoustical lining and fibrous duct work shall comply
with National Fire Protection Association as tested by UL
Standard 181 for Class 1 air ducts.
Make all electrical connections in accordance with the NEC and any local codes or ordinances that may apply.
Use copper wire only. The unit must have a separate branch electric circuit with a field-supplied disconnect
switch located within sight from and readily accessible from the unit.
NOTE: When a pull-out type disconnect is removed from the unit, only the Load side of the circuit is de-energized. The Line side remains live until the main (remote)
disconnect is turned off.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in per-
sonal injury or death.
Turn off the main (remote) disconnect device be-
fore working on incoming (field) wiring. Incoming (field) wires on the line side of the dis- connect found in the fan coil unit remain live, even
when the pull-out is removed. Service and main-
tenance to incoming (field) wiring cannot be per-
formed until the main disconnect switch (remote
to the unit) is turned off.
Figure 10 J Fan Coil Printed Circuit Board
FSM4P, FSU4P
10 496 01 5501 01
A. LINE VOLTAGE CONNECTIONS Fan Coils installed without electric heat require the use of
a factory-authorized Power Plug Kit (accessory part number EBAC01PLG). This kit provides the electrical connections necessary to supply the unit with 208/230V
power when electric heat is not present. For units without electric heat:
1. Connect 208/230V power leads from field disconnect to yellow and black stripped leads on
Power Plug (accessory part number EBAC01 PLG).
2. Connect ground wire to unit ground lug.
3. When installing an electric heater, remove and discard power plug (if equipped) from fan coil and
connect male plug from heater to female plug from unit wiring harness. (See Electric Heater
Installation Instructions.)
B. 24V CONTROL SYSTEM Connection to Unit
Wire low voltage in accordance with wiring label on the
blower (also refer to Figure 11 through Figure 16). Use 18
AWG color-coded, insulated (35 °C minimum) wire to
make the low-voltage connections between the
thermostat, the unit, and the outdoor equipment. If the thermostat is located more than 100 feet from the unit (as
measured along the low voltage wire), use 16 AWG color-coded, insulated (35 °C minimum) wire. All wiring
must be NEC Class 1 and must be separated from incoming power leads. Refer to outdoor unit wiring instructions for additional wiring recommendations.
Heater Staging
The controls are factory circuited for single-stage
operation (refer to Figure 12). When 2 stages are desired, cut W3 at the W2 wire nut, strip, and reconnect according to the thermostat kit instruction (refer to
Figure 14 - outdoor thermostat optional). When 3 stages are desired, cut the W2 wire nut off and discard. Strip W2,
W3, and E, and reconnect according to the thermostat kit
instructions (refer to Figure 15 outdoor thermostats optional).
UNIT OPERATION HAZARD Failure to follow this caution may result in
improper product operation. If W2, W3, and E on any 3 stage heater (18, 20, 24,
or 30kW) are individually connected - as with outdoor thermostats or any other situation - emergency heat relay must be used. If relay is not used, blower may not operate when heaters are
energized.
Manufactured Housing In manufactured housing applications, the Code of
Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40°F (4°C), except for a
heat pump defrost cycle. Refer to Figure 16 for typical low
voltage wiring with outdoor thermostat.
496 01 5501 01 11
Figure11
THERMOSTAT (CONTROL)
WiringLayout- Air Conditioning
Unit(CoolingOnly)
FAN COIL
_ RED R
/ BLA_w 3
/_o E
AIR COND.
..........................C
Figure 12 Unit (Cooling and 1-Stage Heat)
Wiring Layout - Air Conditioning
Figure 14
THERMOSTAT
E_ E_
[] []
[]---
Wiring Layout - Heat Pump Unit
(Cooling and 2-Stage Heat with
One Outdoor Thermostat)
FAN COIL
(CONTROL)
HEAT PUMP
(CONTROL)
g_'-R
G
C
W2
W3 ODTS
g:l g:l
c
w2
o
g_._¥
THERMOSTAT (CONTROL)
FAN COIL
E__ G
WHT/_w3
E
AIR COND.
Wiring Layout - Heat Pump Unit
Figure 13 (Cooling and 2-Stage Heat with
No Outdoor Thermostat)
THERMOSTAT (CONTROL)
FAN COIL
[__R
E__ G
[:__c
/ BkAL_w3
[] L_£E
[]
HEAT PUMP (CONTROL)
p--
25__iR
Z_ic
Wiring Layout - Heat Pump Unit
Figure 15 (Cooling and 2-Stage Heat with
Two Outdoor Thermostats)
THERMOSTAT (CONTROL)
FAN COIL
[_---_ R
_S:_ARZ G
[]-
Z_R
HEAT PUMP
(CONTROL)
--_ C _::1_w_
[]
_W3 BLU
ODTS1
E_ []
[]
EMERGENCY HEAT RELAY
Wiring Layout - Heat Pump Unit
Figure 16 (Cooling and 2-Stage Heat for
C3
Manufactured Housing)
o
Y
[39-_
Za_iy
THERMOSTAT FAN COIL HEAT PUMP
[] []
[]
(CONTROL) (CONTROL)
..............................................................................................................._ R
_-- G
....................................C C
I_-- []
[] gX_
0
D-
12 496 01 5501 01
TransformerInformation
Transformer is factory wiredfor 230V operation. For 208V applications, disconnect the black wire from the 230V
terminal on transformer and connect it to the 208V terminal
refer to Figure 17).
Figure 17 [ Transformer Connections
BROWN
RED
YELLOW
BLACK
C. GROUND CONNECTIONS
ELECTRICAL SHOCK HAZARD Failure to establish uninterrupted or unbroken
ground could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an uninterrupted or
unbroken ground in order to minimize potential
for personal injury or death if an electrical fault should occur. The ground may consist of electri-
cal wire or metal conduit when installed in accor- dance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground wire must be used.
FEM4P models: fan speed is selected at the motor
connector. Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure
that the fan speed selected is not lower than the minimum fan speed indicated.
Tap 1 Low 90 sec off delay Tap 2 Medium 90 sec off delay
Tap 3 High 90 sec off delay Tap 4 Electric Heat 1- 0 sec off delay
Tap 5 Max $ 0 sec off delay
1-Electric heat airflow is same CFM as Tap 3, but with 0
sec off delay. For high static applications, see Airflow Performance
Tables for max airflow.
To change motor speeds disconnect the BLUE fan lead from motor connector terminal #2 (factory default
position) and move to desired speed-tap; 1,2, 3, or 5. Speed-taps 1,2, and 3 have a 90 second blower off time
delay pre-programmed into the motor. Speed tap 4 is used for electric heat only (with 0 second blower time
delay) and the WHITE wire should remain on tap 4. Speed-tap 5 is used for high static applications, but has a 0 second blower time delay pre-programmed into the motor (see Airflow Performance Tables for actual CFM for
each tap). Also, see Figure 18 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap
should be used to reduce possibility of water being blown off
coil.
NOTE: Use UL listed conduit and conduit connectors for connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs provided in control box. D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure that the fan
speed selected is not lower than the minimum fan speed indicated.
FSM4P and FSU4P models: fan speed selection is done at the fan relay printed circuit board. To change motor speeds, disconnect fan lead used on relay terminal (SPT) and replace with motor speed lead desired (refer to Figure 19). Save insulating cap and place on motor lead removed from relay.
NOTE: In low static applications, lower motor speed tap should be used to reduce possibility of water being blown off
coil. Units have 2 motor speed taps. Low speed (red) and high
speed (black). See Table 2 - FSM4P, FSU4P Airflow Performance (CFM) for each setting.
496 01 5501 01 13
Figure18 J FEM4PMotorSpeedSelection
/ 1 2345
t
\
Figure 19
FSM4P & FSU4P Fan Coil Relay
and Speed Tap Terminal
(_ (:C) O
co c)
OO O
o o
I
L11S018
,wo_S_E_0 T_,_,
COMMON YELLOW
/ J_'_--FAN DECK
SPEED TAP _
I
14 496 01 5501 01
REFRIGERANT TUBING
Refrigerant Tubing Connection and Evacuation
Use accessory tubing package or field-supplied tubing of refrigerant grade. Suction tube must be insulated. Do not
use damaged, dirty, or contaminated tubing because it may plug refrigerant flow-control device. ALWAYS
evacuate the coil and field-supplied tubing to 500 microns before opening outdoor unit service
valves.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are
being brazed to the unit connections to prevent damage
to the unit surface and condensate pan fitting caps.
REFRIGERANT FLOW-CONTROL DEVICE
FEM4P, FSM4P, and FSU4P Models:
These units come equipped with a factory installed Piston metering device with Teflon ring. Ifa piston replacement if
required, check piston size shown on indoor unit rating plate to see if it matches required piston shown on
outdoor unit rating plate. If it does not match, replace indoor piston with piston shipped with outdoor unit. The
piston shipped with outdoor unit is correct for any approved indoor coil combination (See Figure 20).
When changing piston, use a back-up wrench. Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not
exceed 30 ft-lbs.The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of
distributor body, and must be installed properly to ensure proper seating in the direction for cooling operation.
Units have sweat suction and liquid tube connections. Make suction tube connection first.
1. Cut tubing to correct length.
2. Insert tube into sweat connection on unit until it bottoms.
3. Braze connection using silver bearing or non-silver bearing brazing materials. Do not use solder
(materials which melt below 800°F / 427°C). Consult local code requirements.
4. Evacuate coil and tubing system to 500 microns using deep vacuum method.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or
property damage. Wrap a wet cloth around rear of fitting to prevent
damage to piston assembly or TXV and factory-made
joints.
Figure
BRASS'='_ _ DiSTRiBUTOR
HEX NUT\ TEFLON SEAL \
ill I °OOLIN \
IJ_l_ _-- BRASS
/
20 ] Refrigerant Flow-Control Device
\ _ TEFLONRING \
PIESTAONER HEX BODY
PRODUCT OPERATION HAZARD Failure to follow this caution may result in improper product
operation.
Ifusing a TXV in conjunction with a single-phase reciprocat- ing compressor, a compressor start capacitor and relay are required. Consult outdoor unit pre-sate literature for start as-
sist kit part number.
f STRAINER
496 01 5501 01 15
CONDENSATE DRAINS
Unit is provided with primary and secondary 3/4" (19mm) NPT drain connections. Refer to Figure 3, Figure 4, Figure 5, Figure 6, and Figure 7 to identify the primary
and secondary locations. To prevent property damage and achieve optimum drainage performance, BOTH
primary and secondary drain lines should be installed and include properly sized condensate traps (refer to
Figure21). Factory approved condensate traps are available (accessory part number EBAC01CTK).
To connect drainlines, the drain connection knock-outs
must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the
knock-out. Clean the edge of the opening if necessary.
After drain fittings are installed, caulk the seam between
the fitting and the cover to retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic condensate pan. Do not over-tighten. Finger-tighten
plus 1-1/2 turns. Use pipe dope, to ensure proper seal. Install traps in the condensate lines as close to the coil as
possible (refer to Figure 23), but avoid blocking filter access panel.
Install drain lines below the bottom of the drain pan and pitch the drain lines down from the coil at least 1/4 inch per
foot of run (6mm per 0.3m). Horizontal runs over 15 feet
(5m) long must also have an anti-siphon air vents (stand pipes), installed ahead of the horizontal runs. Extremely
long horizontal runs may require oversized drain lines to eliminate air trapping.
Route primary drain line to the outside or to a floor drain. Check local codes before connecting to a waste (sewer)
line. Route the secondary drain line to a place in compliance
with local installation codes where it will be noticed when unit is operational. Condensate flowing from secondary
(overflow) drain indicates a plugged primary drain - unit requires service or water damage will occur.
Prime all traps, test for leaks, and insulate drain lines where sweating could cause water damage. Consult local
codes for additional requirements or precautions. If a gravity drain cannot be used, install a condensate pump.
Install the pump as close to the indoor section as possible.
Figure 21 I Recommended Condensate Trap
2 MIN (51mm)
m)
Figure 22 1 Insufficient Condensate Trap
DO NOT USE SHALLOW RUNNING TRAPS!
Figure 23 1 Condensate Drain
! o
¢q
o o o s
PRODUCT or PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product
or property damage. Use only full size P-traps in the condensate line
(refer to Figure 21). Shallow, running traps are in- adequate and DO NOT allow proper condensate
drainage (refer to Figure 22).
16 496 01 5501 01
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR FIELD-SUPPLIED TRAP OF PROPER DEPTH. STANDARD P-TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
(USE FACTORY KIT OR
_x,xFI ELD-SU PPLI ED TRAP)
UIRED
ACCESSORIES
A. ELECTRONIC AIR CLEANER
The Electronic Air Cleaner may be connected to fan coils as shown in Figure 24. This method requires a field
supplied transformer. See Electronic Air Cleaner literature for kit requirements.
Wiring Layout of Electronic Air
Figure 24 Cleaner to Fan Coil (FSM & FSU)
CONTROL BOARD
R G T C C C
II
I FAN RELAY
SPT NO NC
Figure
THERMOSTAT
ED- D-
D- D
Fq D
D
T
25 | Wiring Layout of Humidifier to
I
I
Heat Pump
FAN COIL
(CONTROL)
R
G
C
W2 W3
HEAT PUMP
(CONTROL)
R
C
W2
o
I
Y
208/230V COM
CONVERSION KIT
TRANSFORMER
TO BLOWER
MOTOR
208/230V
TO EAC
FROM MOLEX
PLUG AND
TRANSFORMER
(IN UNIT)
B. HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as shown in Figure 25 and Figure 26.
FANH-"_ _
Figure 26
THERMOSTAT
_ _i_, RED R
12b
D L
I ,_____, I I
I I
I.....
Wiring Layout of Humidifier to
Fan Coil with Electric Heat
FAN COIL
(CONTROL)
/ _L_w_
II /_ vlo E
I -- c
I _:{N
I ,
I I
I
I
___ _
HUMIDISTAT
AIR COND.
Ca._c
115V
-----0
496 01 5501 01 17
SEQUENCE OF OPERATIONS
A. CONTINUOUS FAN
Thermostat closes R to G. G energizes fan relay on PCB
(FSM4P, FSU4P) or sends signal direct to motor (FEM4P), which completes circuit to indoor blower motor. When G is
de-energized, there is a 90 second off delay before relay opens.
B. COOLING MODE
Thermostat energizes Rto G, Rto Y,and R to O (heat pump
only). G energizes fan relay on PCB (FSM4P, FSU4P) or sends signal direct to motor (FEM4P), which completes
circuit to indoor blower motor. When G is de-energized, there is a 90 second offdelay before fan relay opens.
C. HEAT PUMP HEATING MODE
Thermostat energizes R to G and R to Y. G energizes fan
relay on PCB (FSM4P, FSU4P) or sends signal direct to motor (FEM4P), which completes circuit to indoor blower
START-UP PROCEDURE
Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method
details.
CARE AND MAINTENANCE
motor. When G is de-energized, there is a 90 second off delay before fan relay opens.
D. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G
energizes fan relay on PCB which completes circuit to indoor blower motor. W energizes electric heat relay(s)
which completes circuit to heater element(s). When W is
de-energized, electric heat relay(s) open, turning off heater elements. When G is de-energized there is a 90
second off delay before fan relay opens.
E. ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat
relay(s) which completes circuit to heater element(s). Blower motor is energized through normally closed
contacts on fan relay. When W is de-energized, electric heat relay(s) opens.
The system should be regularly inspected by a qualified
service technician. Consult the servicing dealer for recommended frequency.
Between visits, the only consumer service recommended or required is air filter maintenance and condensate drain operation.
Air Filter
Inspect air filters at least monthly and replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned by soaking in mild
detergent and rinsing with cold water. Install filters with the arrows on the side pointing in the direction of air flow.
Condensate Drain
During the cooling season check at least monthly for free
flow of drainage and clean if necessary.
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor
unit performance and/or product damage. Never operate unit without a filter. Factory autho-
rized filter kits must be used when locating the fil-
ter inside the unit. For those applications where
access to an internal filter is impractical, a field- supplied filter must be installed in the return duct system.
18 496 01 5501 01
AIRFLOW PERFORMANCE TABLES
Table 1 - FEM4P Airflow Performance (CFM)
MODEL & SIZE
FEM4P1800
FEM4P2400
FEM4P3000
FEM4P3600
FEM4P4200
FEM4P4800
BLOWER SPEED
Tap 5 669 620 565 Tap 4 614 569 534 486 436 398
Tap 3 660 616 581 537 499 Tap 2 614 569 534 486 436 398
Tap 1 614 569 534 486 436 398 Tap 5 892 835 763 676
Tap 4 826 795 766 743 706 660 Tap 3 826 795 766 743 706 660
Tap 2 701 660 616 581 537 499 Tap 1 617 592 552 507 472 420 Tap 5 1108 1090 1065 1034 1009 974
Tap 4 1026 1000 969 938 899 865 Tap 3 1026 1000 969 938 899 865
Tap 2 909 873 842 799 762 724 Tap 1 825 795 757 722 674 634
Tap 5 1301 1276 1245 1218 1176 1121 Tap 4 1227 1191 1169 1143 1105 1074
Tap 3 1227 1191 1169 1143 1105 1074 Tap 2 1087 1062 1030 1001 966 930 Tap 1 1026 1000 969 938 899 865
Tap 5 1560 1544 1507 1464 1424 1358 Tap 4 1419 1397 1358 1320 1279 1239
Tap 3 1419 1397 1358 1320 1279 1239 Tap 2 1249 1220 1184 1142 1093 1052
Tap 1 1242 1205 1158 1110 1069 1026 Tap 5 1743 1712 1679 1642 1610 1574 Tap 4 1669 1634 1599 1564 1531 1499
Tap 3 1669 1634 1599 1564 1531 1499 Tap 2 1452 1413 1377 1339 1308 1271
Tap 1 1300 1256 1221 1182 1142 1101
0.10 0.20 0.30 0.40 0.50 0.60
TOTAL STATIC (inches water column)
Table 2 - FSM4P and FSU4P Airflow Performance (CFM)
MODEL &
SIZE
FSM4P1800 High 642 568 648 466 FSU4P1800 Low 541 608 480 564 417 511 357 431 299
FSM4P2400 High _,111_ _03_ 888 774 791 573
BLOWER
SPEED
0.10 0.20 0.30 0.40 0.50 0.60
208V 230V 208V 230V 230V 208V 230V
:(
FSU4P2400Low 874 781 868684740506
FSM4P3000 High 1071 1132 952 1005 704 FSU4P3000 Low 965 1117 949 1074 916 1019 805 902 575
FSM4P3600 High 1306 1264 1207 1338 1135 1241 1043 FSU4P3600 Low 1164 1335 1144 1290 1108 1226 1052 1148 970
FSM4P4200 High 1544 1576 1435 1465 1309 FSU4P4200 Low 1387 1543 1358 1488 1311 1410 1237 1315 1137
FSM4P4800 High 1803 1706 1767 1593 1648 1472 FSU4P4800 Low 1671 1777 1630 1711 1563 1630 1479 1528 1370
- Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factory-approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes 4200 through 4800). For FEM4P models, airflow at 208 volts is approximately the same as 230 volts
because the ECM motor is a constant torque motor. The torque doesn't drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 4200 - 4800 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 4800 size could result in condensate blowing off coil or splashing out of drain pan.
TOTAL STATIC (inches water column)
208V 230V 208V 230V 208V
526 403 434 363 iilli:i_/aii!ilill304
654 341 438 573 341 418
791 459 482 637 396 447
1127 842 937 1048 697 855
1340 1144 1182 1200 997 1047
1512 1303 1371 1412 1218 1266
496 01 5501 01 19
Table3- FEM4PAir DeliveryPerformanceCorrectionComponentPressureDrop(in.wc)atIndicated
Airflow(DrytoWetCoil)
UNIT SIZE CFM
18 0.034 0.049 0.063 ........................
24 0.034 0.049 0.063 0.076 0.089 ....................
30 .... 0.049 0.059 0.070 0.080 ................
36 ........ 0.070 0.080 0.090 0.099 ............
42 ............ 0.049 0.056 0.063 0.070 ........
48 ................ 0.063 0.070 0.076 0.083 0.090 --
Table 4 - FSM4P and FSU4P Air Delivery Performance Correction Component Pressure Drop (in. wc) at
UNIT SIZE CFM
18 0.016 0.027 0.038 ........................
24 0.016 0.027 0.038 0.049 0.059 ....................
30 .... 0.036 0.046 0.055 0.064 ................
36 ........ 0.055 0.064 0.073 0.081 ............
42 ............ 0.049 0.056 0.063 0.070 ........
48 ................ 0.038 0.043 0.049 0.054 0.059 --
UNIT SIZE
18,24 30,36 42,48
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
Indicated Airflow (Dry to Wet Coil)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
Table 5 - FEM4P Electric Heater Static Pressure Drop (in. wc)
CFM
400 600 800 1000 1200 1400 1600 1800 2000
0.020 0.044 0.075 ............
.... 0.048 0.072 O.1 O0 ........
...... 0.070 0.092 0.120 0.152 --
2000
2000
Table 6 - FSM4P and FSU4P Electric Heater Static Pressure Drop (in. wc)
UNIT SIZE
18,24
30,36,42
48
400 600 800 1000 1200 1400 1600 1800 2000
0.020 0.044 0.075 0.110 0.1 O0 ........
.... 0.048 0.072 O.1O0 O.130 O.120 ....
........ 0.092 0.120 0.152 0.187
CFM
Table 7 - Electric Heater Static Pressure Drop (in. wc)
FEM4R FSM4P, and FSU4P 1800 - 3600 FEM4R FSM4P, and FSU4P
HEATER EXTERNAL STATIC HEATER EXTERNAL STATIC
ELEMENTS CORRECTION ELEMENTS CORRECTION
0 0 + .02 0 0 + .04
1 3, 5 +.01 2 8, 10 +.02 2 8, 10 0 3 9, 15 0 3 9, 15 -.02 4 20 -.02 4 20 -.04 6 18, 24, 30 -.10
kW PRESSURE kW PRESSURE
4200 - 6000
20 496 01 5501 01
R-410A QUICK REFERENCE GUIDE
R-410A refrigerant operates at 50% - 70% higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A.
R-410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
° Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard. ° Use hoses with 750 psig service pressure rating. ° Leak detectors should be designed to detect HFC refrigerant. ° R-410A, as with other HFC refrigerants, is only compatible with POE oils.
° POE oils absorb moisture rapidly. Do not expose oil to atmosphere. ° POE oils may cause damage to certain plastics and roofing materials.
° Vacuum pumps will not remove moisture from oil. ° A liquid line filter-drier is required on every unit. ° Do not use liquid line filter-driers with rated working pressures less than 600 psig.
° Do not install a suction line filter-drier in liquid line. ° Wrap all filter-driers and service valves with wet cloth when brazing.
° Do not use capillary tube indoor coils. ° Never open system to atmosphere while it is under a vacuum. ° When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers.
° Do not vent R-410A into the atmosphere. ° Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
International Comfort Products, LLC
496 01 5501 01 Lewisburg, TN 37091 USA 21
Loading...