
HJJ(J|)i(i)))_J))1))
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manual that may
apply to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE - Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
TABLE OF CONTENTS
SAFETY CONSiDERATiONS ....................................... 3
iNTRODUCTiON ............................................... 4
CODES AND STANDARDS ........................................ 4
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE ........... 5
DIMENSIONS ................................................. 6
LOCATION ................................................... 7
LOCATION RELATIVE TO COOLING EQUIPMENT ........................ 9
AiR FOR COMBUSTION AND VENTiLATiON ............................ 9
CONDENSATE TRAP ............................................ 12
iNSTALLATION ................................................ 18
UPFLOW INSTALLATION ......................................... 18
DOWNFLOW INSTALLATION ....................................... 19
HORIZONTAL INSTALLATION ...................................... 22
FILTER ARRANGEMENT ......................................... 24
AiR DUCTS ................................................... 26
GAS PiPiNG .................................................. 26
ELECTRICAL CONNECTIONS ...................................... 28
J-BOX iNSTALLATION ........................................... 29
VENTING .................................................... 35
SPECIAL VENTING REQUIREMENTS FOR INSTALLATIONS iN CANADA ........ 35
DIRECT VENT / 2-PIPE SYSTEM ................................... 41
VENTILATED COMBUSTION AiR .................................... 41
TERMINATION REQUIREMENTS FOR THE
PROVINCES OF ALBERTA AND SASKATCHEWAN ....................... 41
iNSTALLING THE VENT TERMINATION ............................... 46
MAXIMUM EQUIVALENT VENT LENTH ............................... 50
Signal Words in Manuals
The signal word WARNING is used throughout
this manual in the following manner:
The signal word CAUTION is used throughout
this manual in the following manner:
Signal Words on Product Labeling
Signal words are used in combination with
colors and/or pictures or product labels.
Z_ Safety-alert symbol
When you see this symbol on the unit and in
instructions or manuals, be alert to the
potential for personal injury.
MAXIMUM ALLOWABLE EXPOSED VENT LENGTHS iN
UNCONDITIONED SPACE - SINGLE STAGE .......................... 51
MAXIMUM ALLOWABLE EXPOSED VENT LENGTHS iN
UNCONDITIONED SPACE - TWO-STAGE ............................ 52
IS09001)
Use of the AHRI Certified TM Mark indicates a
manufacturer's participation in the program,
For verification of certification for individual
products, go to www,ahridirectory.org .
INSTALLER: Affix these instructions on or adjacent to the
furnace,
CONSUMER: Retain these instructions for future
reference.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2009_;P, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington, DC
20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety,
PrintedinU.S.A. 440 01 4001 02 Sept.2011

Required Notice for Massachusetts Installations
Important
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA-54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
(a)
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1,
INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the
installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor
level where the gas equipment is to be installed, in addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired
carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified license professionals
for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirement; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless,
upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the
Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c)
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by
the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the
following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed
installation instructions.
(e)
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas
Fitters, 239 Causeway Street, Boston, MA 02114. 617-727-9952
2 Specifications are subject to change without notice. 440 01 4001 02

Safety Considerations
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous
operation, personal injury, death, or property damage.
Improper installation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide
poisoning, explosion, fire, electrical shock, or other
conditions which may cause personal injury or property
damage. Consult a qualified service agency, local gas
supplier, or your distributor or branch for information or
assistance. The qualified service agency must use
only factory-authorized and listed kits or accessories
when modifying this product.
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit
component damage.
Application of this furnace should be indoors with
special attention given to vent sizing and material, gas
input rate, air temperature rise, unit leveling, and unit
sizing.
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause personal injury or property
damage. Consult a qualified service agency, local gas supplier,
or your distributor or branch for information or assistance. The
qualified installer or agency must use only factory-authorized
and listed kits or accessories when modifying this product.
Refer to the individual instructions packaged with the kits or
accessories when installing.
Installing and servicing heating equipment can be hazardous
due to gas and electrical components. Only trained and
qualified personnel should install, repair, or service
heating equipment. Untrained personnel can perform basic
maintenance functions such as cleaning and replacing air
filters. All other operations must be performed by trained
service personnel. When working on heating equipment,
observe precautions in literature, on tags, and on labels
attached to or shipped with furnace and other safety
precautions that may apply.
These instructions cover minimum requirements and conform
to existing national standards and safety codes. In some
instances, these instructions exceed certain local codes and
ordinances, especially those that may not have kept up with
changing residential construction practices. We require these
instructions as a minimum for a safe installation.
Follow all safety codes. Wear safety glasses, protective
clothing, and work gloves. Have a fire extinguisher available.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit.
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts, and servicing
furnaces.
This is the safety-alert symbol /N •When you see this symbol
on the furnace and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies a
hazard which could result in personal injury or death.
CAUTION is used to identify hazards which may result in minor
personal injury or product and property damage. NOTE is used
to highlight suggestions which will result in enhanced
installation, reliability, or operation.
1. Use only with type of gas approved for this furnace.
Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in the "Location" section of these instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in "Air for Combustion and
Ventilation" section.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only,
as specified in the "Venting" section of these
instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in the "Gas Piping" section.
6. Always install furnace to operate within the furnace's
intended temperature-rise range with a duct system
which has an external static pressure within the
allowable range, as specified in the "Start-Up,
Adjustments, and Safety Check" section. See furnace
rating plate.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be
handled by duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
See "Air Ducts" section.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in the warning box
in the "Location" section. (See Figure 4)
9. The furnace may be used for construction heat provided
that the furnace installation and operation complies with
the first CAUTION in the LOCATION section on page 7
of these instructions.
10. These Multipoise Gas-Fired Furnaces are CSA
design-certified for use with natural and propane gases
(see furnace rating plate) and for installation in alcoves,
attics, basements, closets, utility rooms, crawlspaces,
and garages. The furnace is factory-shipped for use
with natural gas. A CSA (A.G.A. and C.G.A.) listed
accessory gas conversion kit is required to convert
furnace for use with propane gas.
11. See Table 1 for required clearances to combustible
construction.
440 01 4001 02 Specificati ..... bject to change without notice. 3

12.
Maintain a 1-in. (25 mm) clearance from combustible
materials to supply air ductwork for a distance of 36-in.
(914 mm) horizontally from the furnace. See NFPA 90B
or local code for further requirements.
Minimum Clearances to
Table 1 Combustible Materials for All Units
POSITION
CLEARANCE
In(mm)
REAR 0
FRONT (Combustion air openings in
furnace and in structure) 1 (25)
Required for service 24 (610)
All Sides of Supply Plenum 1 (25)
Sides 0
Vent 0
Top of Furnace 1 (25)
13. These furnaces SHALL NOT be installed directly on
carpeting, tile, or any other combustible material other
than wood flooring. In downflow installations, factory
accessory floor base MUST be used when installed on
combustible materials and wood flooring. Special base
is not required when this furnace is installed on
manufacturer's CoilAssemblyorwhen Coil Box is used.
See Table 1 for clearance to combustible construction
information.
Introduction
The 4-way multipoise Category IV condensing furnace is CSA
design-certified as a direct (2-pipe) or non-direct vent (1-pipe)
furnace. (See Figure 3) The furnace is factory-shipped for use
with natural gas. The furnace can be converted in the field for
use with propane gas when a factory-supplied conversion kit is
used. Refer to the furnace rating plate for conversion kit
information.
Single Stage furnace is approved for installation in a mobile
home when a factory-supplied accessory mobile home
conversion kit is used. The conversion kit is required for use
with both natural and propane gas. The furnace must also be
installed on a factory-supplied accessory combustible floor
base or evaporator coil casing.
This furnace is designed for minimum continuous return-air
temperature of 60°F (15°C) db or intermittent operation down to
55°F (15°C) db such as when used with a night setback
thermostat. Return-air temperature must not exceed 80°F
(27°C) db. Failure to follow these return-air temperature limits
may affect reliability of heat exchangers, motors, and controls
(See Figure 1)
The furnace should be sized to provide 100 percent of the
design heating load requirement plus any margin that occurs
because of furnace model size capacity increments. Heating
load estimates can be made using approved methods available
from Air Conditioning Contractors of America (Manual J);
American Society of Heating, Refrigerating, and
Air-Conditioning Engineers; or other approved engineering
methods. Excessive oversizing of the furnace could cause the
furnace and/or vent to fail prematurely.
For accessory installation details, refer to the applicable
instruction literature.
NOTE: Remove all shipping materials, parts assemblies and
literature before operating the furnace.
Figure 1
I Freeze Protection and Return Air
Temperature
SUPPLY MAX80°F/27°C
_AIR
FRONT
MIN 60°F/16°C
32° F/0° C MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
J
Codes and Standards
Follow all national and local codes and standards in
addition to these instructions. The installation must comply
with regulations of the serving gas supplier, local building,
heating, plumbing, and other codes. In absence of local codes,
the installation must comply with the national codes listed
below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and
standards for the following:
Safety
• US: National Fuel Gas Code (NFGC) NFPA
54-2009/ANSI Z223.1-2009 and the Installation
Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B
• A manufactured (Mobile) home installation must
conform with the Manufactured Home Construction
and Safety Standard, Title 24 CFR, Part 3280, or
when this standard is not applicable, the Standard for
Manufactured Home Installation (Manufactured Home
Sites, Communities, and Set-Ups),ANSI/NCS A225.1,
and/or CAN/CSA-Z240, MH Series Mobile Homes
• CANADA: National Standard of Canada, Natural Gas
and Propane Installation Code (NSCNGPIC)
CAN/CSA B149.1-2010
General Installation
• US: NFGC and the NFPA 90B. For copies, contact the
National Fire Protection Association Inc.,
Batterymarch Park, Quincy, MA 02269; or for only the
NFGC contact the American Gas Association, 400 N.
Capitol, N.W., Washington DC 20001.
• CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard,
Etobicoke (Toronto), Ontario, M9W 1R3, Canada.
Combustion and Ventilation Air
• US: Section 9.3 ofthe NFPA54/ANSI Z223.1-2009,
Air for Combustion and Ventilation
• CANADA: Part 8 of the CAN/CSA B149.1-2010,
Venting Systems and Air Supply for Appliances
Specificati ..... bject to change without notice. 440 01 4001 02

Duct Systems
• US and CANADA: Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and Air
Conditioning Contractors National Association
(SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE)
2005 Fundamentals Handbook Chapter 35.
Acoustical Lining and Fibrous Glass
Duct
• US and CANADA: current edition of SMACNA, NFPA
90B as tested by UL Standard 181 for Class I Rigid Air
Ducts
Gas Piping and Gas Pipe Pressure
Testing
• U.S.A.: NFPA 54/ANSI Z223.1-2009, NFGC; Chapters
5, 6, 7, and 8 and national plumbing codes.
• CANADA: CAN/CSA-B149.1-2010, Parts 4, 5, 6 and
9.
In the state of Massachusetts:
• This product must be installed by a licensed plumber or
gas fitter.
• When flexible connectors are used, the maximum
length shall not exceed 36-in. (914 mm).
• When lever type gas shutoffs are used they shall be
T-handle type.
• The use of copper tubing for gas piping is not
approved by the state of Massachusetts.
Electrical Connections
• U.S.A.: National Electrical Code (NEC) ANSI/NFPA
70-2011
• CANADA: Canadian Electrical Code CSA C22.1
Electrostatic Discharge (ESD)
Precautions Procedure
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit com-
3onent damage.
Electrostatic discharge can affect electronic compon-
ents. Take precautions during furnace installation and
servicing to protect the furnace electronic control. Pre-
cautions will prevent electrostatic discharges from per-
sonnel and hand tools which are held during the pro-
cedure. These precautions will help to avoid exposing
the control to electrostatic discharge by putting the
furnace, the control, and the person at the same elec-
trostatic potential.
1. Disconnect all power to the furnace. Multiple
disconnects may be required. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL PRIOR TO DISCHARGING YOUR BODY'S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held
in a person's hand during grounding will be satisfactorily
discharged.
3. After touching the chassis, you may proceed to service
the control or connecting wires as long as you do nothing
to recharge your body with static electricity (for example;
DO NOT move or shuffle your feet, do not touch
ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your
body with static electricity), firmly touch a clean,
unpainted metal surface of the furnace again before
touching control or wires.
5. Use this procedure for installed and uninstatled
(ungrounded) furnaces.
6. Before removing a new control from its container,
discharge your body's electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers
before touching ungrounded objects.
7. An ESD service kit (available from commercial sources)
may also be used to prevent ESD damage.
Accessories
See Specification Sheets for a list of accessories for this
product.
Table 2
QUANTITY COMPONENT NAME
1 Air Intake Pipe Flange
1 Vent Pipe Flange
2 Coupling Flange Gaskets
10 Sharp Tip Screws (Vent and Inlet Flanges)
1 Vent Pipe Coupling
2 Vent Pipe Coupling Clamps
1 Pressure Switch Tube
1
1 Drain Tube Elbow
1 Drain Extension Tube
2 Drain Tube Clamps
1 Drain Line Grommet
1 Gas Line Grommet
1 Gas Line Knockout Plug
1 Junction Box Cover
1 Junction Box Base
1 Green Ground Screw
3 Blunt Tip Screws (Junction Box)
1 Thermostat Wire Grommet
Loose Parts Bag Contents
(shipped in blower compartment)
Outlet Choke Plate (used with 40k BTUH
furnaces, only)
440 01 4001 02 Specificati ..... bject to change without notice. 5

Figure 2
LOCATION
JDimensions
615/1(
[17&1] 23/10
611116
[17o41
NOlle; ALL DIMENSIONS IN INCH [MM]
OUTLET WIDTH
AIR FLOW
[22.2]POWERCONN
(F/G)9MVT
FURNACE SIZE
40,000
60,000
80,000
100,000
120,000
(F/G)9MXT
FURNACE SIZE
40,000
60,000
80,000
100,000
120,000
(F/G)9MXE
FURNACE SIZE
40,000 14-3/16 (361) 12-1/2 (319) 7-1/8 (181)
60,000 17-1/2 (445) 15-7/8 (403) 8-3/4 (222)
80,000 17-1/2 (445) 15-7/8 (403) 8-3/4 (222)
100,000 21 (533) 19-3/8 (492) 10-1/2 (267)
120,000 24-1/2 (622) 22-7/8 (581) 12-1/4 (311)
A
CABINET WIDTH
14-3/16 (361)
17-1/2 (445)
17-1/2 (445)
21 (533)
24-1/2 (622)
A
CABINET WIDTH
14-3/16 (361)
17-1/2 (445)
17-1/2 (445)
21 (533)
24-1/2 (622)
A
CABINET WIDTH
B
OUTLET WIDTH
12-1/2 (319)
15-7/8 (403)
15-7/8 (403)
19-3/8 (492)
22-7/8 (581)
B
OUTLET WIDTH
12-1/2 (319)
15-7/8 (403)
15-7/8 (403)
19-3/8 (492)
22-7/8 (581)
B
OUTLET WIDTH
C
BOTTOM
INLET WIDTH
12-9/16 (322)
16 (406)
16 (406)
19-1/2 (495)
23 (584)
C
BOTTOM
INLET WIDTH
12-9/16 (322)
16 (406)
16 (406)
19-1/2 (495)
23 (584)
C
BOTTOM
INLET WIDTH
12-9/16 (322)
16 (406)
16 (406)
19-1/2 (495)
23 (584)
D
AIR INTAKE
7-1/8 (181)
8-3/4 (222)
8-3/4 (222)
10-1/2 (267)
12-1/4 (311)
D
AIR INTAKE
7-1/8 (181)
8-3/4 (222)
8-3/4 (222)
10-1/2 (267)
12-1/4 (311)
D
AIR INTAKE
NOTE: Doors may vary by model.
a. For 800 CFM 16-in. (406 mm) round or 14 ½ x 12-in. (368 x 305 mm) rectangle.
b. For 1200 CFM 20-in. (508 mm) round of 14 ½ x 19 ½-in. (368 x 495 mm) rectangle.
c. For 1600 CFM 22-in. (559 mm) round or 14 ½ x 22 1/16-in. (368 x 560 mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Installation Instructions for specific use of single side
inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only return air openings may be
required for airflow requirements above 1800 CFM at 0.5 in. w.c. ESP
SHIP WT,
LB (KG)
121 (54)
142 (63)
152 (68)
166 (75)
190 (86)
SHIP WT,
LB (KG)
125 (56)
146 (66)
156 (70)
171 (77)
195 (88)
SHIP WT,
LB (KG)
120 (54)
141 (63)
151 (68)
179 (80)
203 (91)
6 Specificati ..... bject to change without notice. 440 01 4001 02

Location
PERSONAL INJURY AND/OR PROPERTY DAMAGE
HAZARD
Improper use or installation of this furnace may result in
3remature furnace component failure. This gas furnace
may be used for heating buildings under construction
3rovided that:
-The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is
3rovided, sealed to the furnace casing, and terminated
outside the space containing the furnace. This prevents
a negative pressure condition as created by the
circulating air blower, causing a flame rollout and/or
drawing combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be
"hot wired" to provide heat continuously to the structure
without thermostatic control.
-Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which
can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is
maintained between 55°F (13°C) and 80°F (27°C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on
the furnace rating plate, and the gas input rate has been
set to the nameplate value.
-The filters used to clean the circulating air during the
construction process must be either changed or
thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as
necessary to remove drywall dust and construction
debris from all HVAC system components after
construction is completed.
-Verify proper furnace operating conditions including
ignition, gas input rate, air temperature rise, and venting
according to these installation instructions.
General
These furnaces are shipped with the following materials to
assist in proper furnace installation. These materials are
shipped in the main blower compartment.
See Table 2 for loose parts bog contents.
This furnace must:
• be installed so the electrical components are protected
from water.
• notbe installeddirectlyon any combustiblematerial other
than wood flooring (refer to SAFETY
CONSIDERATIONS).
be located close to the chimney or vent and attached to an
air distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning.
Always comply with minimum fire protection clearances
shown in Table 1 or on the furnace clearance to
combustible construction label.
CARBON MONOXIDE POISONING / COMPONENT
DAMAGE HAZARD
Failure to follow this warning could result in personal in-
jury or death and unit component damage.
Corrosive or contaminated air may cause failure of parts
containing flue gas, which could leak into the living
space. Air for combustion must not be contaminated by
halogen compounds, which include fluoride, chloride,
bromide, and iodide. These elements can corrode heat
exchangers and shorten furnace life. Air contaminants
are found in aerosol sprays, detergents, bleaches, clean-
ing solvents, salts, air fresheners, and other household
products. Do not install furnace in a corrosive or contam-
inated atmosphere. Make sure all combustion and circu-
lating air requirements are met, in addition to all local
codes and ordinances.
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms, and
• Chemical storage areas
If air is exposed to the following substances, it should not be
used for combustion air, and outdoor air may be required for
combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must
be made between the furnace cabinet and the return-air duct
to prevent pulling air from the burner area.
440 01 4001 02 Specificati ..... bject to change without notice. 7

Figure 3 1Multipoise Orientations
THE BLOWER iS LOCATED
TOTHE RIGHT OFTHE
BURNER SECTION, AND
AIR CONDiTiONED AiR iS
DISCHARGED TO THE LEFT.
AIRFLOW
THE BLOWER iS
LOCATED BELOW THE
BURNER SECTION, AND
CONDiTiONED AIR iS
DISCHARGED UPWARD.
I HORIZONTAL RIGHT/AIFF_LQW
THE BLOWER iS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDiTiONED AiR iS
DISCHARGED DOWNWARD AIRFLOW
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal in-
jury, death and/or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least
18-in. (457 mm) above the floor. The furnace must be
located or protected to avoid damage by vehicles. When
the furnace is installed in a public garage, airplane
hangar, or other building having a hazardous atmo-
sphere, the furnace must be installed in accordance with
the NFPA 54/ANSI Z223.1-2009 or CAN/CSA
B149.1-2010. (See Figure 4)
Figure 4 1Installation in a Garage
THE BLOWER iS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDiTiONED AiR iS
DISCHARGED TO THE RIGHT.
FIRE HAZARD
Failure to follow this warning could result in personal in-
jury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect re-
turn-air ducts to the back of the furnace. (See Figure 5)
Figure 5 _Prohibit Installations
BACK
18-1N. (457.2 mm)
MINIMUM TO BURNERS
8 Specificati ..... bject to change without notice. 440 01 4001 02
A10494
A93044

Location Relative to Cooling
Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers
or other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless
the damper is in the full-heat or full-cool position.
Air for Combustion and
Ventilation
Introduction
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace
damage.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide,
and iodide. These elements can corrode heat
exchangers and shorten furnace life. Air contaminants
are found in aerosol sprays, detergents, bleaches,
cleaning solvents, salts, air fresheners, and other
household products.
Direct Vent (2-pipe) Applications
When the furnace is installed as a direct vent (2-pipe) furnace,
no special provisions for air for combustion are required.
However, other gas appliances installed in the space with the
furnace may require outside air for combustion. Follow the
guidelines below to insure that other gas appliances have
sufficient air for combustion.
Non-Direct Vent (1-pipe) Applications
When the furnace is installed as a non-direct vent (1-pipe)
furnace, it wilt be necessary to insure there is adequate air for
combustion. Other gas appliances installed with the furnace
may also require air for combustion and ventilation in addition
to the amount of combustion air and ventilation air required for
the furnace. Follow the guidelines below to insure that the
furnace and other gas appliances have sufficient air for
combustion.
Ventilated Combustion Air Applications
When the furnace is installed using the ventilated combustion
air option, the attic or crawlspace must freely communicate with
the outdoor to provide sufficient air for combustion. The
combustion air pipe cannot be terminated in attics or
crawlspaces that use ventilation fans designed to operate
during the heating season. If ventilation fans are present in
these areas, the combustion air pipe must terminate outdoors
as a Direct Vent/2-Pipe system.
All air for combustion is piped directly to the furnace from a
space that is well ventilated with outdoor air (such as an attic or
crawlspace) and the space is well isolated from the living space
or garage. In addition, other gas appliances installed in the
space with the furnace may require outside air for combustion.
Follow the guidelines below to insure that the roof or
crawlspace walls have sufficient free area to provide sufficient
air for combustion and ventilation for the furnaces. The
guidelines below can be used to insure that other gas
appliances have sufficient air for combustion.
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
• U.S. Installations: Section 9.3 of the NFPA 54/ANSI
Z223.1-2009 , Air for Combustion and Ventilation and
applicable provisions of the local building codes.
• Canadian Installations: Part 8 of
CAN/CSA-B149.1-2010, Venting Systems and Air
Supply for Appliances and all authorities having
jurisdiction.
440 01 4001 02 Specificati ..... bject to change without notice. 9
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could
create a NEGATIVE PRESSURE CONDITION at the
furnace. Make-up air MUST be provided for the
ventilation devices, in addition to that required by the
furnace. Refer to the Carbon Monoxide Poisoning
Hazard warning in the venting section of these
instructions to determine if an adequate amount of
make-up air is available.
The requirements for combustion and ventilation air depend
upon whether or not the furnace is located in a space having a
volume of at least 50 cubic feet per 1,000 Btuh (4.8 cubic
meters per kW) input rating for all gas appliances installed in
the space.
• Spaces having less than 50 cubic feet per 1,000 Btuh (4.8
cubic meters per kW) require the OUTDOOR
COMBUSTION AIR METHOD.
• Spaces having at least 50 cubic feet per 1,000 Btuh (4.8
cubic meters per kW) may use the INDOOR
COMBUSTION AIR, STANDARD or KNOWN AIR
INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper
combustion, ventilation, and dilution of flue gases using
permanent horizontal or vertical duct(s) or opening(s)
directly communicating with the outdoors or spaces that
freely communicate with the outdoors.
2. Figure 6 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air openings to the outdoors.
a. One opening MUST commence within 12-in.
(300 mm) of the ceiling and the second opening
MUST commence within 12-in. (300 mm) of the floor.
b. Size openings and ducts per Figure 6 and Table 3.
c. TWO HORIZONTAL DUCTS require 1 square inch
(25.4 square mm) of free area per 2,000 Btuh (1,100
mm2/kW) of combined input for all gas appliances in
the space per Figure 6 and Table 3.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch (25.4 square mm)of free area per 4,000
Btuh (550 mm2/kW) for combined input of all gas
appliances in the space per Figure 6 and Table 3.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (25.4 square mm)of free area per 3,000 Btuh
(734 mm2/kW) for combined input of all gas
appliances in the space per Table 3 and

b. Not less than the sum of the areas of all vent
connectors in the space.
The opening shall commence within 12-in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at
least 1-in. (25 mm) from the sides and back and 6-in. (150 mm)
from the front. The opening shall directly communicate with the
outdoors or shall communicate through a vertical or horizontal
duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
Indoor Combustion Air ° NFPA & AGA
Standard and Known-Air-Infiltration Rate
Methods
Indoor combustion air is permitted for combustion, ventilation,
and dilution, if the Standard or Known-Air-Infiltration Rate
Method is used.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Many homes require air to be supplied from outdoors
for furnace combustion, ventilation, and dilution of flue
gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
Figure 6
(305_m/12"M_X]j
lseiN, ill
PER 2000 B
BTUH*
sa i .
PER 2000 A
(305mm)12"MAN | I
CIRCULATINGAIR DUCTS
*Minimum dimensions of 3-in.
NOTE: Use any of the following combinations
of openings:
A&B C&D D&E F&G
Air for Combustion, Ventilation,and Dilution for Outdoors
DUCTS ,
TO BTUH
OUiDOORS
I I Ii
D
VENT
THROUGH
ROOF
I
' 1
TO PER 4000
OUTDOORS BTUH*
12" MAX
(305mm)
1 SQ IN.
I SQ IN,
/
f
12/_X (305ram}
t
1 so IN.
PER
4000
BTUH*
09
n-
O
O
£
o
SQ IN,
PER
4000
BTUH*
_2j_X (aO5mm)
t
A03174
The Standard Method:
1. The space has no less volume than 50 cubic feet per
1,000 Btuh (4.8 cubic meters per kW) of the maximum
input ratings for all gas appliances installed inthe space
and
2. The air infiltration rate is not known to be less than 0.40
air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number
of ACH and shall be determined per Table 4 or Equations 1
and 2. Determine the minimum required volume for each
appliance in the space and add the volumes together to get the
total minimum required volume for the space.
Table 4 - Minimum Space Volumes were determined by
using the following equations from the National Fuel Gas Code
ANSI Z223.1/NFPA 54-2009, 9.3.2.2:
1. For other than fan-assisted appliances, such as a
draft hood-equipped water heater
Volume -21ft3 _f' I°ther
Other ACH _.000 Btu/hrJ
A04002
2. For fan-assisted appliances such as this furnace:
Volume Fan ACH 000 Btu/hr
A04003
If:
Iother=combined input of all other than fan-assisted
appliances in Btuh/hr
Itan=combined input of all fan-assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and
to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1-in.2/1,000 Btuh
(2,000 mm2/kW) of the total input rating of all gas
appliances in the space, but not less than 100-in. 2
(0.06 m2). One opening shall commence within 12-in.
(300 mm) of the ceiling and the second opening shall
commence within 12-in. (300 mm) of the floor. The
minimum dimension of air openings shall be at least
3-in. (80 mm). (See Figure 7)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be
considered as communicating spaces if connected by
one or more permanent openings in doors or floors
having free area of at least 2-in.2/1,000 Btuh
(4,400 mm2/kW) of total input rating of all
gas appliances.
2. An attic or crawlspace may be considered a space that
freely communicates with the outdoors provided there
are adequate permanent ventilation openings directly to
outdoors having free area of at least 1-in.2/4,000 Btuh of
total input rating for all gas appliances in the space.
10 Specificati ..... bject to change without notice. 440 01 4001 02

Airfor Combustion,Ventilation, 3.
Figure 7 and Dilution from Indoors
In spaces that use the Indoor Combustion Air Method,
infiltration should be adequate to provide air for
combustion, permanent ventilation and dilution of flue
gases. However, in buildings with unusually tight
CIRCULATING AIR VENT THROUGH ROOF
DUCTS
I
I
I
I I I I
I I I I
I I I I
_(305mm)
construction, additional air MUST be provided using
the methods described in the Outdoor Combustion Air
Method section.
4.
Unusually tight construction is defined as Construction
with:
a.
Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are
E_ ----_SQIN.
_" _ = PER 1000
_: _ BTUH* IN DOOR
_ ORWALL
INTERIOR
HEATED
SPACE
i C_ UNCONFINED
rr T 6" MIN (152ram)
u_ o0 (FRONT)0
z_
zZ PER 1000
g O___&_ALL
HHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHH
I i i - 12" MAX (305mm)
o
I I
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3-in.
1- Minimum of 3-in. when type-B1 vent is used.
Combination of Indoor and Outdoor Air
A03175
gasketed or sealed and
b.
Doors and openable windows are weatherstripped
and
C.
Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between walt-ceiling joints, between
wall panels, at penetrations for plumbing, electrical
and gas lines, etc.
1.
Indoor openings shall comply with the Indoor
Combustion Air Method below and,
2.
Outdoor openings shall be located as required in the
Outdoor Combustion Air Method mentioned previously
and,
3.
Outdoor openings shall be sized as follows:
a.
Calculate the Ratio of all Indoor Space volume
divided by required volume for Indoor Combustion
Air Method.
b.
Outdoor opening size reduction Factor is one minus
the Ratio in a. above.
C.
Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above
multiplied by reduction Factor in b. above. The
minimum dimension of air openings shall be not less
than 3-in. (80 mm).
Table 3 Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR
(1 SQ. IN./2,000 BTUH) (1 SQ. IN./3,000 BTUH)
FURNACE (1,100 SQ. MM/KW) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH)
INPUT
Round Round
VERTICAL DUCTS
(550 SQ. MM/KW)
(BTUH) Free Area of Duct Free Area of Open- Duct Free Area of Open- Round Duct
Opening and Duct In. (mm) ing and Duct In. (mm) ing and Duct In. (mm)
Sq. In (Sq. mm) Dia Sq. In (Sq. mm) Dia Sq. In (mm) Dia.
40,000* 20 (12904) 5 (127) 14 (8696) 5 (127) 10 (6452) 4 (102)
60,000 30 (19355) 6 (152) 20 (13043) 5 (127) 15 (9678) 5 (127)
80,000 40 (25807) 7 (178) 27 (17391) 6 (152) 20 (12904) 5 (127)
100,000 50 (32258) 8 (203) 34 (21739) 7 (178) 25 (16130) 6 (152)
120,000 60 (38709) 9 (229) 40 (26087) 7 (178) 30 (19355) 6 (152)
140,000" 70 (45161) 10 (254) 47 (30435) 8 (203) 35 (22581) 7 (178)
• Not all families have these models,
EXAMPLE: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
100,000 + 30,000 = (130,000 divided by 4,000)
60,000 + 40,000 = (100,000 divided by 3,000)
80,000 + 30,000 = (110,000 divided by 2,000)
440 01 4001 02 Specificati ..... bject to change without notice. 11
= 32.5 Sq. In. for each two Vertical Ducts or Openings
= 33.3 Sq. In. for each Single Duct or Opening
= 55.0 Sq. In. for each two Horizontal Ducts

Table 4 Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTEDTOTAL FAN-ASSISTEDTOTAL
(1,000'S BTUH GAS INPUT RATE) (1,000'S BTUH GAS INPUT RATE)
30 40 50 40 60 80 1O0 120 140
AOH Space Volume Ft3 (M3)
1,050 1,400 1,750 1,400 1,500 2,000 2,500 3,000 3,500
0.60 (29.7) (39.6) (49.5) (39.6) (42.5) (56.6) (70.8) (84.9) (99.1)
1,260 1,680 2,1 O0 1,680 1,800 2,400 3,000 3,600 4,200
0.50 (35.6) (47.5) (59.4) (47.5) (51.0) (67.9) (84.9) (101.9) (118.9)
1,575 2,1 O0 2,625 2,1 O0 2,250 3,000 3,750 4,500 5,250
0.40 (44.5) (59.4) (74.3) (59.4) (63.7) (84.9) (106.1 ) (127.3) (148.6)
2,1 O0 2,800 3,500 2,800 3,000 4,000 5,000 6,000 7,000
0.30 (59.4) (79.2) (99.1) (79.2) (84.9) (113.2) (141.5) (169.8) (198.1 )
3,150 4,200 5,250 4,200 4,500 6,000 7,500 9,000 10,500
0.20 (89.1) (118.9) (148.6) (118.9) (127.3) (169.8) (212.2) (254.6) (297.1)
6,300 8,400 10,500 8,400 9,000 12,000 15,000 18,000 21,000
0,10 (178.0) (237.8) (297.3) (237.8) (254.6) (339.5) (424.4) (509.2) (594.1)
0,00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
CONDENSATE TRAP
Condensate Trap - Upflow Orientation
tubing. Refer to Figure8 for upflow condensate trap
information. Refer to Condensate Drain section for information
how to install the condensate drain.
When the furnace is installed in the upflow position, it is not
necessary to relocate the condensate trap or associated
Figure 8 1Upflow Trap Configuration
Vent Pipe Clamp
Condensate Trap
Relief Port
Vent Elbow Clamp
Collector Box
Plugs
UPFLOW TRAP CONFIGURATION
Condensate Trap - Downflow
Orientation
When the furnace is installed in the downflow position, the
factory-installed trap will be located at the upper left corner of
the collector box. When the furnace is installed in the downflow
orientation, the factory-installed trap must be relocated for
proper condensate drainage.
To Relocate the Condensate Trap:
1. Orient the furnace in the desired position.
2. Figure 9 shows the condensate trap and tubing before
and after relocation.
3. Remove the relief tube from the condensate trap.
4. Remove the screw that secures the condensate trap to
the collector box.
5. Remove the trap.
1 & 2 Stage Units
6. Remove the relief tube from of the port on the collector
7. Remove the pressure switch tube from the front pressure
8. Loosen the clamp around the inlet of the vent elbow on
9. Remove the middle and bottom plugs from the lower
10. Refer to the appropriate figure to begin the trap
11. Install the two (2) plugs previously removed from the
Vent Elbow
Collector Box
Plug
Condensate Trap
Relief Port
Pressure Switch
Port
Outlet
P
Al1307
box. It is not necessary to remove the tube from the
inducer assembly.
switch and discard the tube. A new pressure switch tube
is shipped in the loose parts bag.
the inducer.
right side of the collector box and set aside. Do Not
Discard Plugs,
conversion.
collector box in the ports where the condensate trap was
removed.
12 Specificati ..... bject to change without notice. 440 01 4001 02

12. Install the trap over the ports on the lower right side of
the collector box.
13. Secure the trap to the collector box with the screw.
14. Connect the relief tube to the condensate trap to the
relief port of the condensate trap.
15. If necessary, slide the relief tube in the inducer stand-offs
to adjust the position of the tube.
16. Connect the relief tube to the relief port of the
condensate trap.
Figure 9
Unconverted Factory Configuration as viewed in the Downflow orientation
17. Connect the new pressure switch tube to the port on the
front pressure switch. Route the tube through the
stand-offs on the inducer assembly and connect to the
port on the collector box. Trim off any excess tube to
avoid sags or kinks in the tube.
18. Rotate the vent elbow to the desired position and tighten
the clamp 15 in.-Ibs.
19. Refer to Condensate Drain section for information how to
install the condensate drain.
Remove relief tube from relief Remove tube from relief port.
on condensate trap.
(_ emove trap from
collector box.
to vent elbow.
(_ Loosen clamp on inlet
(_ _ Remove pressure switch tube from
(1 and 2 Stage Units)
front pressure switch and discard.
Downflow Trap Configuration
Connect tube from Loose Parts bag
to port on front pressure switch.
Remove middle and bottom
plugs. DO NOT DISCARD.
Route tube through inducer
stand-offs.
(_ Install plugs inopen ports on
collector box.
(_ Connect relief tube
to port on collector
box.
desired position and
(_ otate elbow to
tighten clamp to
15 Ib-in.
(_ Slide tube in stand-offs
to adjust length.
Trim excess tube.
Connect pressure switch
tube to port on collector
box.
Attach condensate trap
with screw to collector box.
Connect relief tube to
relief port on condensate
trap.
(1 and 2 Stage Units)
Align condensate trap
over middle and bottom
ports of collector box.
Al1277
440 01 4001 02 Specificati ..... bject to change without notice. 13

Condensate Trap - Horizontal
Orientation
When the furnace is installed in the horizontal right position, the
factory-installed trap will be located at the bottom of the
collector box. When the furnace is installed in the horizontal left
position, the factory-installed trap will be located at the top of
the collector box. The trap must be repositioned on the
collector box for proper condensate drainage.
When the furnace is installed as a direct-vent furnace,a field
supplied, accessory Horizontal Installation Kit is required for all
horizontal installations. The kit contains a rubber casing
grommet designed to seal between the furnace casing and the
condensate trap. (See Figure 10)
Figure
NOTE: The condensate trap extends below the side of the
casing inthe horizontal position. A minimum of 2-in. (51 mm) of
clearance is required between the casing side and the furnace
platform for the trap to extend out of the casing in the horizontal
position.
To Relocate the Condensate Trap:
10 I Drain Trap Grommet
Remove knockout
Install grommet before
relocating condensate
trap
Horizontal Drain Trap Grommet
Al1348
1. Remove the knockout in the casing for the casing
grommet.
2. Install the grommet in the casing.
3. Orient the furnace in the desired position.
4. Allow for 2-in. (51 mm) of clearance underneath the
furnace for the condensate trap and drain line.
5. Figure 11 shows the condensate trap and tubing before
and after relocation in the horizontal right position.
6. Figure 12 shows the condensate trap and tubing before
and after relocation in the horizontal left position.
7. Refer to the appropriate figure to begin the trap
conversion.
8. Remove the relief tube from the condensate trap.
9. Remove the screw that secures the condensate trap to
the collector box.
10. Remove the trap.
11. Remove the relief tube from of the port on the collector
box. It is not necessary to remove the tube from the
inducer assembly.
For Horizontal Left only:
1. Remove the pressure switch tube from the front pressure
switch and discard the tube. A new pressure switch tube
is shipped in the loose parts bag.
For Horizontal Right only:
1. The pressure switch tube location is not modified.
2. Loosen the clamp around the inlet of the vent elbow on
the inducer.
3. Remove the plugs from the collector box and set aside.
Do Not Discard Plugs.
For Horizontal Left only:
1. Remove the middle and right plug from the ports at the
bottom of the collector box.
For Horizontal Right only:
1. Remove the plug to the right of the condensate trap.
2. Refer to the appropriate figure to begin the trap
conversion.
3. Install the plugs previously removed from the collector
box in the ports where the condensate trap was
removed.
4. Install the trap over the ports on the lower side of the
collector box.
5. Secure the trap to the collector box with the screw.
6. Connect the relief tube to the condensate trap to the
relief port of the condensate trap.
7. If necessary, slide the relief tube in the inducer stand-offs
to adjust the position of the tube.
8. Connect the relief tube to the relief port of the
condensate trap.
For Horizontal Left only:
1. Connect the new pressure switch tube to the port on the
front pressure switch. Route the tube through the
stand-offs on the inducer assembly and connect to the
port on the collector box. Trim off any excess tube to
avoid sags or kinks in the tube.
2. Rotate the vent elbow to the desired position and tighten
the clamp 15 in.-Ibs.
3. Refer to Condensate Drain section for information how to
install the condensate drain.
14 Specificati..... bject to change withoutnotice. 440 01 4001 02

Figure 11 _Unconverted Factory Configuration as viewed in the Horizontal Right Orientation
(_ emove plug from
(_ ttach condensate
collector box.
DO NOT DISCARD.
trap with screw to
collector box.
\
(1AND 2 STAGE UNITS)
Horizontal Right Trap Configuration
Slide relief tube in stand-offs
to adjust length.
If alternate vent position
is required, loosen clamp
on inlet of vent elbow.
Remove trap from
collector box.
Vent elbow shown in alternate
orientation. Tighten clamp on
inlet to vent elbow 15 lb.-in.
open port on
(_ Install plug in
collector box.
440 01 4001 02 Specificati..... bject to change withoutnotice. 15
(1 AND 2 8"rAGEuNrm)
Align trap over middle and
right-hand post on collector box.
Al1402

Figure 12 1Unconverted Factory Configuration as viewed in the Horizontal Left Orientation
Remove trap from collector
is required, loosen clamp
on vent elbow inlet.
t f alternate vent position box.
ID
from port on collector --
(_ emove relief tube
box.
(1 AND 2 STAGE UNITS)
Horizontal Left Trap Configuration
(_ otate elbow todesired position
and torque clamp
on inlet 15 Ib-in.
Remove relief tube from
relief port on condensate
trap.
Remove front pressure
switch tube and discard.
Remove middle and right
plug from collector box.
Install plug in open
ports on collector box.
Connect relief tube to port
on collector box.
(_ Slide relief tube instand-offs to adjust
length.
(_ ttach condensate
trap with screw to
collector box.
and right-hand port on
(_ Align trap over middle
collector box.
(1 AND 2 STAGE UNITS)
Condensate Drain Connection
Upflow/Downflow Orientation
In the Upflow or Downflow orientation, the condensate trap is
inside the furnace casing. The condensate drain must be
routed from the trap through the furnace casing. The
condensate drain can be routed through the left or right side of
the casing. (The left or right side is as you are viewing the
Connect tube from Loose
Parts bag to port on front
pressure switch.
Route pressure switch tube
underneath relief tube and
connect to port on
collector box.
Connect relief tube to relief
port on condensate trap.
Al1282
furnace.) The furnace condensate drain can be connected to
the Air Conditioning condensate drain as shown in Figure 13.
NOTE: On narrower casing, it may be easier to remove the
condensate trap, connect the drain line components and
re-install the condensate trap. Read the steps thoroughly to
familiarize yourself with the required steps.
16 specificati..... bject to change withoutnotice. 440 01 4001 02