ICP F8MTL, G8MTL Installation Insrtuctions

These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE
are used to identify levels of hazard seriousness. The signal word
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will
be used on product labels and throughout this manual and other manual that may apply to the product.
The signal word CAUTION is used throughout this manual in the following manner:
DANGER - Immediate hazards which will result in severe person-
al injury or death. WARNING - Hazards or unsafe practices which could result in
severe personal injury or death.
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures
CAUTION - Hazards or unsafe practices which may result in or product labels. minor personal injury or product or property damage, z_ Safety-alert symbol
NOTE - Used to highlight suggestions which wilt result in en-
When you see this symbol on the unit and in instructions or manu-
hanced installation, reliability, or operation, ats, be alert to the potential for personal injury.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ........................................ 3
INTRODUCTION .................................................. 4
CODES AND STANDARDS ......................................... 4
Safety .......................................................... 4
General Installation ............................................... 4
Combustion and Ventilation Air ..................................... 5
Duct Systems ................................................... 5
Acoustical Lining and Fibrous Glass Duct ............................ 5
Gas Piping and Gas Pipe Pressure Testing .......................... 5
Electrical Connections ............................................ 5
Venting ......................................................... 5
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE .... 5
LOCATION ....................................................... 6
AIR FOR COMBUSTION AND VENTILATION .......................... 7
INSTALLATION ................................................... 10
Upflow Installation ............................................. 10
Downflow Installation .......................................... 10
Horizontal Installation ........................................... 11
Filter Arrangement ............................................ 14
Air Ducts .................................................... 14
Gas Piping ................................................... 16
Electrical Connections ......................................... 18
Venting ...................................................... 22
START-UP, ADJUSTMENT, AND SAFETY CHECK .................... 31
General ....................................................... 31
Start-Up Procedures ............................................ 31
Adjustments ................................................... 32
Check Safety Controls ........................................... 36
Checklist ...................................................... 36
SERVICE AND MAINTENANCE PROCEDURES .................... 40
Introduction .................................................. 40
Care and Maintenance ......................................... 41
Sequence of Operation ........................................ 45
Wiring Diagrams .............................................. 48
Troubleshooting .............................................. 49
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage,
3ersonal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
3rocedures and equipped with proper tools and test instruments.
Installation must conform with local building codes and
with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI Z223.1, and National standards of Canada
CAN/CSA-B149.1 and .2 Natural Gas and Propane Installation Codes.
Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org .
IS0 9001
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-20096), with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington, DO 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
Printedin U.S.A. 441 01 2101 02 Aug. 2012
INSTALLER: Affixthese instructions on or adjacent tothe furnace. CONSUMER: Retain these instructions for future reference.
I-- 5 16/16 | [150.7]
/ r- s1/2
Figure 1 - Dimensional Drawing
i 1.;o.tt'1:'
27_
1"_-71
='"1 F
[i sl tit
?
L ......
7
I
I
I'
21.6 6.1
BOT._M[s'la.5]
INLET
28,39
['nl.2]
29
['n_
TOPOF_WNG I l l 418/10
P
[1_7]
ST_
[148.S] S_--
57110 [14,t.Sl
[lS'IH1 llVffl _
_ [40.21
/ /,i .=q
I-
_86/8
61_V16--
p7e.Sl
"l I ¢1a/4
[els]-7"1 A
s] L 1/1e
I [51.O] 1
___. [,k_s]
c
_-- _7/11
[=21=]
ACC_
t 1
[_vz.ojm_4] /
/ t" &BOXPROVISION
1
147/8
la_.a]
I
(nOTH=,DES)
I
t, .......... __4
--D_ _ _V4
BOTrOM RE11JRN [11kl]
WIDTH
NOTES:
1. Two additional 7/8-in. (22 mm) diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle. b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle. c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
VEHTING(6PLACE8)
[511O1
81DEINLET
(BOTHSlDF.m
Table 1 - Dimensions
A
FURNACE SIZE
0451412 0701412 0901714
1102122
1352422
135size furnace require a 5-in. or 6-in. (127 or 152mm) vent. Use a vent adapter between furnace and vent stack.
CABINET WIDTH
IN (mm)
14-3/16 (360) 14-3/16 (360)
17-1/2 (445)
21 (533)
24-1/2 (622)
OUTLET WIDTH
IN (rnm)
12-9/16 (319) 12-9/16 (319)
15-7/8 (403) 19-3/8 (492)
22-7/8 (581)
TOP AND BOTTOM
C
FLUE COLLAR
IN (mm)
9-5/16 (237)
9-5/16 (237) 11-9/16 (294) 13-5/16 (338)
15-1/16 (383)
D
BOTTOM INLET
WIDTH
IN (mm)
12-11/16 (322) 12-11/16 (322)
16 (406)
19-1/2 (495)
23 (584)
_A
1 [_1._] p_4]
VENT
CONNECTION
SIZE
IN (mm)
4 (102) 4 (102)
4 (102) 4 (102)
4 (102)*
L11/4
SHIP
WT
LB (KG)
107 (49) 115 (52)
127(58)
152 (69) 163 (74)
2
441 01 2101 02
SAFETY CONSIDERATIONS
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use could cause carbon monoxide
poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or
property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service
agency must use only factory-authorized and listed
kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with
special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicin,q furnaces.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical
shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with
the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or
cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel
Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
Recognize safety information. This is the safety-alert symbol /_. When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which
may result in minor personal injury or product and property
damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation,
reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the "Location" section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and
Ventilation" section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only,
as specified in the "Venting" section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as
specified in the "Gas Piping" section.
6. Always install furnace to operate within the furnace's intended temperature-rise range with a duct system
which has an external static pressure within the allowable range, as specified in the "Start-Up,
Adjustments, and Safety Check" section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace. See "Air Ducts" section.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in the warning
box in the "Location" section.
9. The furnace may be used for construction heat provided that the furnace installation and operation
complies with the first CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas-Fired Furnaces are CSA (formerly A.G.A. and C.G.A.) design-certified for use
with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements,
closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A
CSA (A.G.A. and C.G.A.) listed accessory gas conversion kit is required to convert furnace for use
with propane gas.
11. See Figure 2 for required clearances to combustible construction.
12. Maintain a 1-in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36
inches (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other
than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base
is not required when this furnace is installed on manufacturer's coil model numbers END4X, EN24X or
when the manufacturer's coil casing model number NAEA is used. See Figure2 for clearance to
combustible construction information.
441 01 2101 02 3
INTRODUCTION
F8MTL & G8MTL 4-way multipoise Category I fan-assisted
furnace is CSA (formerly A.G.A. and C.G.A.) design-certified. A Category I fan-assisted furnace is an appliance equipped with an integral mechanical means to either draw or force
products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory-shipped for
use with natural gas. This furnace is not approved for
installation in mobile homes, recreational vehicles, or
outdoors. These furnaces shall not be installed directly on carpeting,
tile, or any other combustible material other than wood flooring. For downflow installations, a factory accessory floor
base must be used when installed on combustible materials and wood flooring. This special base is not required when this
Figure 2 - Clearances to Combustibles
furnace is installed on the manufacturer's coil model numbers END4X, ENW4X, or when the manufacturer's coil casing
model number NAEA is used. See Figure 2 for clearance to combustible material information.
This furnace is designed for minimum continuous return-air temperature of 60°F (16°O) db or intermittent operation down
to 55_'F (13°O) db such as when used with a night setback thermostat. Return-air temperature must not exceed 80°F
(27°0) db. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls. (SeeFigure 3)
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
Improper adjustment, alteration, service, maintenance, or installation can cause
serious injury or death,
Read and follow instructions and precautions in User's Information Manual
provided with this furnace. Installation and service must be performed by a qualified service agency or the gas
supplier.
_k. CAUTION
Check entire gas assembly for leaks after lighting this appliance,
I INSTALLATION
1. This furnace must be installed in accordance with the manufacturer's instructions and local codes. In the absence of local codes, follow the National
Fuel Gas Code ANSI Z223.1 / NFPA54 or CSA B-149. 1 Gas Installation Code.
2. This furnace must be installed so there are provisions for combustion and ventilation
air. See manufacturer's installation information provided with this appliance.
I OPERATION I
This furnace is equipped with manual reset limit switch(es) in burner compartment to
protect against overheat conditions that can result from inadequate combustion air
supply or blocked vent conditions.
1. Do not bypass limit switches.
2. If a limit opens, call a quallified serviceman to correct the condition and reset limit switch.
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
I INSTALLATION
This forced air furnace is This furnace is approved for
equipped for use with natural UPFLOW, DOWNFLOW, and gas at altitudes 0 - 10,000 ft Clearancearrows
(O - 3,050m), do not changewith
An accessory kit, supplied by furnaceorientation,
the manufacturer, shall be used to convert to propane gas use
or may be required for some natural gas applications,
This furnace is for indoor
installation in a building constructed on site.
This furnace may be installed
on combustible flooring in alcove or closet at minimum clearance
as indicated by the diagram from combustible material.
This furnace may be used with Clearancein inches a Type B-1 Vent and may be Vent Clearance to combustibles: vented in common with other For SingleWallvents 6 inches (6 pc).
gas fired appliances. ForType B-1 vent type 1 inch (1 pc).
MINIMUM INCHES CLEARANCE TO
COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
1" Installation on non-combustible floors only.
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL or NAHA01101SB, Coil Assembly, Part No. CAR, CAP, CNPV, CNRV, END4X, ENW4X, WENC, WTNC, WENW OR WTNW.
18 inches front clearance required for alcove.
"k Indicates supply or return sides when furnace is in the horizontal
position. Line contact only permissible between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists, studs or framing.
HORIZONTAL installations.
CODES AND STANDARDS
Follow all national and local codes and standards in
addition to these instructions. The installation must comply
with regulations of the serving gas supplier, local building,
heating, plumbing, and other codes. In absence of local
codes, the installation must comply with the national codes
listed below and all authorities having jurisdiction. In the United States, follow all codes and standards for the
following:
Step 1 m Safety
National Fuel Gas Code (NFGC) NFPA 54-2009/ANSI
Z223.1-2009 and the Installation Standards, Warm Air
Heating and Air Conditioning Systems ANSI/NFPA 90B
Step 2 m General Installation
Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc.,
Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or
4 441 01 2101 02
for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington DC 20001
(www.AGA.org)
Figure 3 - Return Air Temperature
- - MAX 80 °F/27 °C
FRONT
MIN 60°F/16°0
A06745
Step 3 m Combustion and Ventilation Air Section 9.3 of the NFGC, NFPA 54/ANSI Z223.1-2009 Air
for Combustion and Ventilation Step 4 m Duct Systems
Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National
Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE)
2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Step 5 _ Acoustical Lining and Fibrous Glass Duct
Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 _ Gas Piping and Gas Pipe Pressure Testing
NFPA 54 / ANSI Z223.1-2009; chapters 5, 6, 7, and 8 and National Plumbing Codes
Step 7 _ Electrical Connections National Electrical Code (NEC) ANSI/NFPA 70-2008
Step 8 _ Venting NFGC; NFPA 54/ANSI Z223.1-2009 chapters 12 and 13
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY'S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools
held in a person's hand during grounding will be satisfactorily discharged.
Figure 4 - Multipoise Orientations
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do
nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not
touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean,
unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstatled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body's electrostatic charge to ground to
protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers
before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause premature furnace component failure.
Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same
electrostatic potential.
AIRFLOW
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE TH E
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
441 01 2101 O2 5
\
HORIZONTAL RIGHT [_>
AIRFLOW
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
THE BLOWER IS
DISCHARGED TO THE RIGHT.
A02097
LOCATION
GENERAL This multipoise furnace is shipped in packaged configuration.
Some assembly and modifications are required when used in any of the four applications shown in Figure 4.
NOTE: For high-attitude installations, the high-altitude
conversion kit MUST be installed at or above 5500 ft. (1676
M) above sea level. Obtain high-attitude conversion kit from
your area authorized distributor. This furnace must:
be installed so the electrical components are protected from water.
not be installed directly on any combustible material other than wood flooring for upftow applications. Downflow
installations require use of a factory-approved floor base, coil model numbers END4X, ENW4X, or the manufacturer's coil casing model number NAEA, when installed on combustible materials or wood flooring (refer to SAFETY CONSIDERATIONS).
be located close to the chimney or vent and attached to an air distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on
the furnace clearance to combustible construction label.
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Laundry rooms
Hobby or craft rooms, and
Chemical storage areas
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal
must be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area
and from draft safeguard opening.
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at
least 18 inches (457 mm) above the floor. The
furnace must be located or protected to avoid
damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC. (See Figure 5)
Figure 5 - Installation in a Garage
CARBON MONOXIDE POISONING AND UNIT
DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death, and furnace damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These
elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and
circulating air requirements are met, in addition to all local codes and ordinances.
If air is exposed to the following substances, it should not be
used for combustion air, and outdoor air may be required for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
18-iN. (457.2 mm)
MINIMUMTO BURNERS
A93044
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never
connect return-air ducts to the back of the furnace. (See Figure 6)
6 441 01 2101 02
Figure 6 - Prohibit Installation on Back
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with: U.S. installations: Section 9.3 of the NFPA 54 /A ANSI Z223.1-2009, Air for Combustion and Ventilation, and applicable provisions of the local building codes.
BACK J
A02054
PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause premature component failure. This gas furnace may be used for construction heat provided that:
-The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated
outside the space containing the furnace. This prevents a
negative pressure condition as created by the circulating air blower, causing a flame roll-out and/or drawing
combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be "hot wired" to provide heat continuously to the structure without thermostatic control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the entrainment of drywall dust into combustion air, which
can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with
no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been
set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as
necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed. -Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these
installation instructions.
LOCATION RELATIVE TO COOLING EQUIPMENT The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace,
dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated,
they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool
position.
FURNACE CORROSION HAZARD Failure to follow this caution may result in furnace
damage. Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat
exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other
household products.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could
create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the
ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make-up air is
available.
The requirements for combustion and ventilation air depend
upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating
for atl gas appliances installed in the space.
Spaces having less than 50 cubic feet per 1,000 Btuh require the Outdoor Combustion Air Method.
Spaces having at least 50 cubic feet per 1,000 Btuh may use the Indoor Combustion Air, Standard or Known Air
Infiltration Method.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using
permanent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Figure 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors. a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Figure 7 and Table 2. c. TWO HORIZONTAL DUCTS require 1 -in 2 of free
area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Figure 7
and Table 2.
441 01 2101 O2 7
d. TWO OPENINGS OR VERTICAL DUCTS require 1
-in 2 of free area per 4,000 Btuh (550 mm2/kW) for
b. Not less than the sum of the areas of all
connectors in the space.
combined input of all gas appliances in the space per
Figure 7 and Table 2
3. ONE OUTDOOR OPENING requires: a. One square inch of free area per 3,000 Btuh (734
mm2/kW) for combined input of all gas appliances in the space per Table 2 and
Table 2 - Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
FURNACE (1 SQ. IN./2,O00 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,O00 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,O00 BTUH) (550 SQ. MM/KW)
INPUT Free Area of Opening Round Duct Free Area of Opening Round Duct Free Area of Opening Round Duct
(BTUH) and Duct Dia. and Duct Dia. and Duct Dia.
Sq. In. (Sq. mm) In. (mm) Sq. In. (Sq. mm) In. (mm) Sq. In. (Sq. mm) In. (mm)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102) 66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127) 88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152)
110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152) 132,000 66 (42580) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178)
EXAMPLES: Determining Free Area
FURNACE WATERHEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening
vent
Figure 7 - Air for Combustion, Ventilation, and Dilution
for Outdoors
1 SQ IN.
SQ IN. PER
400O
BTUH*
cO rr
8
GI
o
1 SQ IN.
PER
4OOO
BTUH*
12" (305mm) MAX
(305mm) 12" MAX
1 SQIN. A PER 2000 BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN. PER 2000
BTUH*
(305mm) 12" MAX
DUCT,' PER 4000
TO BTUH*
OUTDOORS
D 12_X (305mm)
VENT THROUGH
ROOF
i
I
CIRCULATING AIR DUCTS
TO PER 4O00
OUTDOORS BTUH*
*Minimum dimensions of 3-in. (76 mm).
Note: Use any of the following combinations of openings:
A&BC&DD&EF&G
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at
least 1 in. (25 mm) from the sides and back and 6 in. (150
mm) from the front. The opening shall directly communicate
with the outdoors or shall communicate through a vertical or
horizontal duct to the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors.
1 SQ IN.
A03174
Figure 8 - Air for Combustion, Ventilation, and Dilution
from Indoors
DUCTS
CIRCULATING AiR !
I I I I I I I I I I
I I I I I
INTERIOR
HEATED
SPACE
i i
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. (64516 sq. mm) with minimum dimensions of 3 in. (76 ram)
1 Minimum of 3 in. (76 mm) when type-B1 vent is used.
VENT THROUGH ROOF
12" AX(305mm)
o *
_ 1 SQ IN.
PER 1000 BTUH* iN DOOR ORWALL
UNCONFINED SPACE
6" MIN (152mm) (FRONT)0
1 SQ iN. PER 1000
_: BTUH* iN DOOR
_-----OR WALL
12" MAX (305mm)
A03175
Indoor Combustion Air@ NFPA & AGA Standard and
Known-Air-Infiltration Rate Methods Indoor air is permitted for combustion, ventilation, and
dilution, if the Standard or Known-Air-Infiltration Method is used.
8 441 01 2101 02
CARBONMONOXIDE POISONING HAZARD
Failure to follow this warning could result in death
and/or personal injury.
Many homes require air to be supplied from outdoors
for furnace combustion, ventilation, and dilution of flue
gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas
appliances installed in the space and
Table 3 - Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL
ACH
0.60 1,050
0.50 1,260
0.40 1,575
0.30 2,100
0.20 3,150
0.10 6,300
0.00 NP
ACH =Air Changes/Hour NP = NotPermitted
Table 3-Minimum Space Volumes were determined by using the following equations from the National Fuel Gas
Code ANSI Z223.1-2009/NFPA 54-2009, 9.3.2.2:
1. For other than fan-assisted appliances, such as a
draft hood-equipped water heater:
Volume _ 21ft3 (f= [other ='_
2. For fan-assisted appliances such as this furnace:
Volume
If:
Iother
= combined input of all other than fan-assisted
Ifan
= combined input of all fan-assisted appliances in
ACH
= air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms. b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.2/1,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances
in the space, but not less than 100 in.2 (0.06 m2). One opening shall commence within 12 in. (300 mm) of the
ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum
(1,000s BTUH GAS INPUT RATE) (1,000s BTUH GAS INPUT RATE)
30 40 50 44 66 88 110 132 154
S _ace Volume (ft.3)
1,400 1,750 1,100 1,650 2,200 2,750 3,300 3,850
1,680 2,100 1,320 1,980 2,640 3,300 3,960 4,620 2,100 2,625 1,650 2,475 3,300 4,125 4,950 5,775 2,800 3,500 2,200 3,300 4,400 5,500 6,600 7,700 4,200 5,250 3,300 4,950 6,600 8,250 9,900 11,550 8,400 10,500 6,600 9,900 13,200 16,500 19,800 23,100
NP NP NP NP NP NP NP NP
Other ACH _000 Btu/hrJ
A04002
FaR
ACH 000 Btu/hrJ
A04003
appliances in Btuh/hr
Btuh/hr
2. The air infiltrationrate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the
number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume
for each appliance in the space and add the volumes together to get the total minimum required volume for the
space.
dimension of air openings shall be at least 3 in. (80 mm). (See Figure 8)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be
considered as communicating spaces if connected by one or more permanent openings in doors or floors
having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas appliances.
2.
An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there
are adequate permanent ventilation openings directly to outdoors having free area of at least 1-in.2/4,000 Btuh of total input rating for all gas appliances in the
space.
3.
In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for
combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight
construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air
Method section. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped
and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical
and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with
the Indoor
Combustion Air Method below and,
441 01 2101 02 9
2.Outdooropeningsshallbelocatedasrequiredinthe Outdoor CombustionAir Methodmentioned
previouslyand,
3.Outdooropeningsshallbesizedasfollows:
a.CalculatetheRatioofallIndoorSpacevolumedivided
by requiredvolumefor IndoorCombustionAir
Methodbelow.
b.OutdooropeningsizereductionFactoris1minusthe
Ratioina.above.
c.MinimumsizeofOutdooropeningsshallbethesize
requiredinOutdoorCombustionAirMethodabove
multipliedby reductionFactorin b. above.The minimumdimensionofairopeningsshallbenotless
than3in.(80mm).
INSTALLATION
UPFLOW INSTALLATION Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel
installed in bottom return-air opening. Remove and discard
this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet These furnaces are shipped with bottom closure panel
installed in bottom return-air opening. This panel MUST be in
place when only side return air is used.
NOTE: Side return-air openings can be used in UPFLOW
and most HORIZONTAL configurations. Do not use side
return-air openings in DOWNFLOW configuration.
Figure 9 - Removing Bottom Closure Panel
o
o
I
BOTTOM CLOSURE
PANEL
BOTTOM FILLER PANEL
Levelinq Leqs (If Desired)
In upflow position with side return inlet(s), leveling legs may
be used. (See Figure 10) Install field-supplied, 5/16 x 1-1/2
in. (8 x 38 mm) (max) corrosion-resistant machine bolts,
washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see item 1 in Bottom Return Air Inlet section in
Step 1 above. To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Figure 10)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and
tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
Figure 10 - Leveling Legs
(Smm)
1
(44ram)
I 3/4"
(44mm)
(Smm)
(Smm)
(44mm) 1 3/4"
(44mm) 1
A89014
DOWNFLOW INSTALLATION NOTE: For downflow applications, this furnace is approved
for use on combustible flooring when any one of the following two accessories are used:
Downflow combustible floor subbase
Coil model numbers END4X or ENW4X
Coil casing model number NAEA
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Figure 13.
3. Construct plenum to dimensions specified in Table 4
and Figure 13.
4. If downflow subbase is used, install as shown in Figure 11. If coil model numbers END4X, ENW4X or
coil casing model number NEAE is used, install as shown in Figure 12.
NOTE: It is recommended that the perforated supply-air duct flanges be completely folded over or removed from furnace
when installing the furnace on a factory-supplied cased coil or coil casing. To remove the supply-air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Figure 14)
10 441 01 2101 02
Figure 11 - Furnace, Plenum, and Subbase installed on
a Combustible Floor
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
HORIZONTAL INSTALLATION
The furnace can be installed horizontally in an attic or crawl
space on either the left-hand (LH) or right-hand (RH) side.
The furnace can be hung from floor joists, rafters or trusses or
installed on a non-combustible platform, blocks, bricks or pad.
Figure 13 - Floor and Plenum Opening Dimensions
A96283
A96285
Figure 12 - Furnace, Plenum, and Coil or Coil Casing
Installed on a Combustible Floor
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
_ COMBUSTIBLE
FLOORING x
SHEET METAL ====.._
PLENUM
FLOOR
OPENING
/
A08556
Bottom Return Air Inlet These furnaces are shipped with bottom closure panel
installed in bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom
closure panel, perform the following:
1. Tilt or raise furnace and remove two(2) screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never
connect return-air ducts to the back of the furnace.
Suspended Furnace Support
The furnace may be supported under each end with threaded
rod, angle iron or metal plumber's strap as shown. (See Figure 15 and Figure 16) Secure angle iron to bottom of
furnace as shown. Heavy-gauge sheet metal straps
(plumber's straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use
two (2) #8 x 3/4-in. (19 mm) screw into the side and 2 #8 x
3/4-in. (19 mm) screw in the bottom of the furnace casing for each strap. (See Figure 15 and Figure 16)
If the screws are attached to ONLY the furnace sides and not
the bottom, the straps must be vertical against the furnace
sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in
shear) for reliable support. Platform Furnace Support Construct working platform at location where all required
furnace clearances are met. (See Figure 2 and Figure 17) For furnaces with 1-in. (25 mm) clearance requirement on side,
set furnace on non-combustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended
from the floor joists, the ground underneath furnace must be
level and the furnace set on blocks or bricks.
Roll-Out Protection
Provide a minimum 17-3/4-in. x 22-in. (451 x 559 ram) piece of sheet metal for flame roll-out protection in front of burner
area for furnaces closer than 12 inches (305 mm) above the
441 01 2101 02 11
combustibledeckorsuspendedfurnacescloserthan12
inches(305mm)tojoists.ThesheetmetalMUSTextend
underneaththefurnacecasingby1in.(25mm)withthedoor
removed.
Thebottomclosurepanelonfurnacesofwidths17-1/2in.
(445mm)andlargermaybe usedfor flameroll-out
protectionwhenbottomof furnaceis usedfor returnair connection.SeeFigure17forproperorientationofroll-out
shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel
installed in bottom return-air opening. Remove and discard
this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two (2) screws holding bottom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet These furnaces are shipped with bottom closure panel
installed in bottom return-air opening. This panel MUST be in place when side return air inlet(s) are used without a bottom
return air inlet.
FURNACE
CASING
WIDTH
14-3/16
(376)
17-1/2
(445)
21
(533)
24-1/2
(622)
Table 4 - Opening dimensions - In.
APPLICATION
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring (subbase required)
Downflow Applications on Combustible Flooring with Coil
END4X, ENW4X or Coil Casing NAEA (subbase not required)
Figure 14 - Duct Flanges
U PFLOW DOWN FLOW
(mm)
PLENUMOPENING
A B
12-11/16 21-5/8
(322) (549)
12-9/16 19
(319) (483)
11-13/16 19
(284) (483)
12-5/16 19
(319) (483)
16 21-5/8
(406) (549)
15- 7/8 19
(403) (483)
15-1/8 19
(384) (483)
15-1/2 19
(394) (483)
19-1/2 21-5/8
(495) (549)
19-3/8 19
(492) (483)
18-5/8 19
(473) (483)
19 19
(483) (483)
23 21-1/8
(584) (537)
22- 7/8 19
(581) (483)
22-1/8 19
(562) (483)
22-1/2 19
(572) (483)
HORIZONTAL
FLOOR OPENING
C D
13-5/16 22-1/4
(338) (565)
13-3/16 19-5/8
(335) (498)
13-7/16 20-5/8
(34t) (600)
13-5/16 20
(338) (508)
16-5/8 22-1/4
(422) (565)
16-1/2 19-5/8
(419) (498)
16-3/4 20-5/8
(425) (600)
16-1/2 20
(419) (508)
20-1/8 22-1/4
(511) (565)
20 19-5/8
(508) (498)
20 - 1/4 20- 5/8
(514) (600)
20 20
(508) (508)
23 - 5/8 22- 1/4
(600) (565)
23-1/2 19- 5/8
(597) (498)
23-3/4 20-5/8
(603) (600)
23 - 1/2 20
(597) (508)
12 441 01 2101 02
YES
YES YES
NO Q/1 NO
YES
YES
120o\ YES
MIN
NO
A02020
Figure 15 - Horizontal Unit Suspension
4 REQ.
UTER DOOR
ASSEMBLY
c.
8" (203mm) MIN FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
l _/// 1/4" (6mm) THREADED ROD
SECURE ANGLE IRON TO BOTTOM
OF FURNACE WiTH 3 #8 xS/4'' (19ram) SCREWS
TYPICAL FOR 2 SUPPORTS
1" (25mm) SQUARE, 1-1/4"xl-1/4"xt/8" (32x32x3mm)
ANGLE IRON OR UNI-STRUT MAY BE USED
J
Figure 16 - Horizontal Suspension with Straps
OUTER DOOR
ASSEMBLY X III I
IIII
22 GAUGE GALVANIZED STRAPS TYPICAL
FOR 4 STRAPS
F
AIR
/OPENING
METHOD 2 USE (4) #8 x 3/4 (19 ram) SHEET
METAL SCREWS FOR EACH STRAR THE STRAPS SHQULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY
FROM THE FURNACE SIDES.
BACK OF FURNACE
METHOD 1 FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH (4) #8 x 3/4 (19 ram) SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
A10130
AIR OPENING
441 01 2101 02 13
A10131
Figure 17 - Typical Attic Installation
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS, STUDS, OR FRAMING.
ENTRY
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT UNION
TRAP
Not all horizontal furnaces are approved for side return air
connections. (See Figure 20)
FILTER ARRANGEMENT
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal
injury, or death. Never operate a furnace without a filter or with filter
access door removed.
There are no provisions for an internal filter rack in these furnaces. A field-supplied, accessory external filter rack is
required. Refer to the instructions supplied with the external filter rack
for assembly and installation options.
AIR DUCTS General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association
(SMACNA) or American Society of Heating, Refrigerating and
Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from
your local distributor. The duct system should be sized to
handle the required system design CFM at the design
external static pressure. The furnace airflow rates are provided in Table 5-Air Delivery CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside
the space containing the furnace. Secure ductwork with proper fasteners for type of ductwork
used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
17 3/4" (451 mm)OVERALL 4 3/4" (121mm) UNDER DOOR
1" (25mm) UNDER FURNACE
VENT
30-IN. (762mm)
MIN WORKAREA *WHEN USED WITH
EXTEND OUT 12" (305mm) FROM FACE OF DOOR
SINGLE WALL VENT CONNECTIONS
A10164
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air
conditioning is used, a vapor barrier is recommended. Maintain a 1-in. (25 mm) clearance from combustible
materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local
code for further requirements.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 _'elbow and
10 ft. (3 M) of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in
accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and
fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections For a furnace not equipped with a cooling coil, the outlet duct
shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and
shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a
probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces Connect supply-air duct to flanges on furnace supply-air
outlet. Bend flange upward to 90 ° with wide duct pliers. (See Figure 14) The supply-air duct must be connected to ONLY
the furnace supply-outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing
side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to
furnace main casing.
A02329
14 441 01 2101 02
Table 5 - Air Delivery - CFM (With Filter)*
FURNACE
SIZE
0451412
0701412
0901714
1102422
1352422
rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.
-- Indicates unstable operating conditions.
NOTE: For horizontal applications, the top-most flange may be bent past 90 ° to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
Downflow Furnaces Connect supply-air duct to supply-air outlet on furnace. Bend
flange inward past 90 ° with wide duct pliers. (See Figure 14) The supply-air duct must be connected to ONLY the furnace
supply outlet or air conditioning coil casing (when used). When installed on combustible material, supply-air duct must
be connected to ONLY the accessory combustible floor subbase or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST
be connected to duct external to furnace casing.
RETURN-AIR
INLET
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Bottom Sides or 1 Side & Bottom
1Side Only
Bottom
Only
Bottom Sides
or
1 Side & Bottom
1 Side Only
SPEED
High 1465 1400 1325 1250 1175 1085 980 860 725 560
Med-High 1295 1260 1210 1155 1090 1015 930 830 700 545
Medium 1150 1120 1085 1040 985 920 835 740 620 510
Med-Low 1030 1010 980 945 895 835 765 685 570 345
Low 860 835 810 780 745 700 635 555 445 260
High 1440 1400 1355 1300 1240 1170 1090 1000 890 745
Med-High 1180 1165 1150 1125 1085 1030 970 890 785 645
Medium 1015 1020 1010 990 965 925 875 800 700 560
Med-Low 885 885 880 865 845 815 770 700 605 475
Low 695 700 700 690 670 640 600 540 460 345
High 1650 1600 1535 1465 1385 1285 1175 1055 895 645
Med-High 1515 1485 1440 1380 1300 1220 1115 990 830 600
Med- Low 1385 1360 1320 1260 1195 1120 1025 915 710 565
Low 1205 1180 1160 1120 1065 1005 925 810 630 510
High 2530 2460 2380 2285 2200 2085 1970 1835 1695 1545
Med-High 2225 2190 2135 2075 1995 1910 1805 1695 1565 1430
Medium 1895 1885 1865 1820 1770 1700 1610 1520 1410 1290
Med-Low 1565 1555 1535 1505 1465 1410 1350 1265 1175 1050
Low 1320 1295 1265 1235 1205 1160 1105 1035 950 870
High .... 2415 2330 2235 2125 1995 1860 1735 1605
Med-High 2205 2175 2120 2065 1975 1900 1790 1685 1580 1460
High 2485 2430 2360 2270 2175 2070 1950 1825 1685 1535
Med-High 2155 2135 2100 2040 1970 1885 1790 1680 1560 1420
Medium 1830 1830 1810 1780 1730 1665 1595 1505 1395 1275
Med-Low 1520 1505 1490 1470 1430 1385 1330 1250 1165 1055
Low 1275 1260 1240 1210 1180 1135 1090 1025 930 840
High 2485 2400 2310 2215 2110 2000 1880 1725 1535 1355
Med-High 2195 2150 2090 2000 1920 1825 1720 1565 1405 1255
Med-Low 1880 1850 1820 1780 1715 1635 1540 1415 1290 1160
Low 1640 1635 1615 1585 1530 1465 1370 1255 1150 1040
High .... 2385 2305 2195 2085 1960 1825 1670 1465
Med-High 2180 2145 2060 2010 1945 1865 1765 1660 1515 1325
Med-Low 1880 1850 1820 1780 1715 1635 1540 1415 1290 1160
Low 1640 1635 1615 1585 1530 1465 1370 1255 1150 1040
High 2320 2250 2155 2055 1970 1855 1725 1600 1450 1280
Med-High 2125 2065 1995 1910 1815 1710 1610 1490 1340 1175
Med-Low 1845 1825 1765 1710 1650 1570 1475 1370 1240 1100
Low 1640 1620 1580 1540 1485 1410 1330 1220 1080 960
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
EXTERNAL STATIC PRESSURE (IN.W.C.)
Downflow Furnaces
The return-air duct must be connected to return-air opening
(bottom inlet) as shown in Figure 1. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow
and most horizontal furnaces. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to
furnace. (See Figure 19)
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left
or right), or a combination of bottom and side(s) of main
furnace casing as shown in Figure 1. Bypass humidifier may
be attached into unused return air side of the furnace casing. (See Figure 18 and Figure 20) Not all horizontal furnaces are approved for side return air connections. (See Figure 20)
GAS PIPING
Return Air Connections
accessoryfilter*A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized
FIRE HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return-air ducts to the back of the
furnace. Follow instructions below.
441 01 2101 02 15
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal
injury, death, and/or property damage. Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all
connections.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in )ersonat injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and a gas leak.
Figure 18 - Upflow Return Air Configurations and Restrictions
UPFLOW RETURN AiR CONFiGURATiONS AND RESTRICTIONS
AIR FLOW MODELS RETURN AIR RETURN AIR RETURN AIR RETURN AIR
GREATER * 5 TONS AND YES YES YES YES
ALL OTHER MODELS YES YES YES YES
2000 CFM AND GREATER AT .6 ESP HI COOLING SPEED
@
RETURN "i
AIR
RETURN
AiR
FIRE OR EXPLOSION HAZARD Failure to protect gas valve inlet from water and
debris could result in death, personal injury and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect
the valve from moisture and debris. Also, install a
sediment trap in the gas supply piping at the inlet to
the gas valve.
CONNECTION 1 CONNECTION 2 CONNECTION 3 COMBINATIONS ONLY ONLY ONLY OF 1,2, AND 3
RETURN / UPFLOW
AiR / RETURN AIR
RESTRICTIONS
Figure 19 - Downflow Return Air Configurations and Restrictions
,FI_ RETURN
_J AI R
RETURN
AIR AIR
DOWNFLOWRETURNAIRCONFIGURATIONSANDRESTRICq]ONS
AIR FLOW MODELS RETURN AIR RETURN AIR RETURN AIR RETURN AIR
5 TONS AND YES NO NO NO GREATER *
ALL OTHER MODELS YES NO NO NO
2000 CFM AND GREATER AT .6 ESP HI COOLING SPEED
CONNECTION 1 CONNECTION 2 CONNECTION 3 COMBiNATiONS ONLY ONLY ONLY OF 1, 2, AND 3
16 441 01 2101 02
Loading...
+ 35 hidden pages