ICP EDD2X18BA1, EDD2X18BAT1, EDD2X24BA1, EDD2X24BAT1, EDD2X24FA1 Installation Guide

...
Theseinstructionsmustbereadandunderstoodcompletelybeforeattemptinginstallation.
It is important that the Blower and Duct System be properly sized to allow the system to operate at full capacity. Poorly designed systems will not give satisfactory cooling or economy. They may even shorten the service life of the
compressor in the outdoor unit.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only used on product labels to signify an immediate haz- ard. The signal words WARNING, CAUTION, and
NOTE will be used on product labels and through- out this manual and other manuals that may apply
to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death. WARNING - Hazards or unsafe practices which
could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or opera-
tion.
Signal Words in Manuals
The signal word WARNING isused throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Installation .................................. 2 - 4
Condensate Drain ........................... 4 - 5
Waste Line Connection .......................... 5
Refrigerant Line Connections .................... 6
Refrigerant Metering Device ..................... 7
Check and Adjust Airflow ..................... 7 - 8
Start-Up Procedure ............................ 9
R-410A Quick Reference Guide .................. 9
ELECTRICAL SHOCK HAZARD Failure to turn off electric power could result in
personal injury or death. Before installing or servicing system, turn off
main power to the system. There may be more than one disconnect switch, including accessory heat- er(s).
484 01 3001 03 Nov 2007
INSTALLATION
EDA Loose Coils are shipped with a metal collar plate approximately the same size as the drain pan. The collar plate must be installed between the drain pan and the
furnace or air handler cabinet to prevent condensation
inside the cabinet. Position the collar plate as shown in Figure 1, with the flanges pointing down, towards the
furnace or air handler cabinet. Size the plenum or fabricate spacers to seal against the outside of the collar
and prevent air bypass.
Figure 1 [ EDA Collar Plate
Collar Plate under drain pan
Flanges down
EDM and EDD Cased Coils are designed to fit furnaces and air handlers of the same width with no modifications.
When an EDM or EDD Cased Coil is applied to a narrower
or wider furnace or air handler, a field fabricated adapter is required. Refer to Figure 2 for examples of field fabricated
adapters. EDM coils are designed for installation in any position -
upflow, downflow, horizontal left, or horizontal right -
without modification to the drain pans or casing. The
drain pans remain in the same positions in the casing no matter which direction the air moves.
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product
damage. When a narrower coil is installed on a wider gas
furnace (upflow, downflow, or horizontal), a field fabricated adapter must create 3" minimum space
between furnace and coil to allow airflow to dis-
tribute evenly.
When a loose coil is installed on any GAS furnace,
the drain pan must be at least 2"away from the fur-
nace heat exchanger to avoid drain pan damage. When a loose coil is installed on any OIL furnace,
the drain pan must be at least 5" away from the fur-
nace heat exchanger to avoid drain pan damage.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in proper-
ty damage A field fabricated auxiliary drain pan, with a sepa-
rate drain is REQUIRED for all installations over a finished living space or in any area that may be
damaged by overflow from a restricted main drain pan. In some localities, local codes require an aux- iliary drain pan for ANY horizontal installation.
2 484 01 3001 03
Figure2 1 Adapters for Coils Wider or Narrower than Furnace or Air Handler
0 0
NARROWER'
COIL
ADAPTER
(FIELD SUPPLIED)
(FIELD SUPPLIED)
WIDER FURNACE
NOTE: When coil is used in a heat pump application with electric heat, coil must be installed upstream of the
electric heater (refer to Figure 3). This prevents electric heat from driving up refrigeration system pressure during
heating cycle. NOTE: When coil is installed to a gas or oil furnace, coil
must be installed downstream of the furnace heat exchanger (refer to Figure 4). This reduces condensate
formation in the furnace heat exchanger during the cooling cycle. When the gas or oil furnace is in downflow
application on a combustible floor, Sub-Base accessory must be installed between coil and floor. Refer to
Product Specification literature for accessory part number.
O
O
WIDER COIL
ADAPTER
NARROWER
FURNACE
NOTE: When coil is installed with a Heat Pump in conjunction with a fossil fuel heating system, a Fossil
Fuel Kit must be used. Refer to Product Specification literature for kit part number.
NOTE: On furnace installations where the coil is located in an unconditioned space, nuisance sweating may
occur in the area around the cabinet to supply duct joint.
Wrap the joint between the cabinet and the supply duct with a 6" wide piece of insulation with vapor barrier.
Figure 3 1
UPFLOW POSITION
DOWNFLOW POSITION HORIZONTAL LEFT POSITION
ELECTRIC HEATER
Heat Pump Coil Position Relative to Electric Heat
HORIZONTAL RIGHT POSITION
BLOWER
38- 20-19a
484 01 3001 03 3
Loading...
+ 6 hidden pages