ICP EBX2400A1, EBX3600A1, EBX4800A1, EBX6000A1, EBXX2400A1 Installation Guide

...
These instructions must be read and understood
completely before attempting installation.
These instructions covers the installation of replacement coil kit into fan coils (see Figure 1) The kit is designed to
allow easy replacement of existing slope or A-coils. A 3/4 to 5/8 inch reducing bushing is included inthe coil kit for
use on the field vapor connection tube, when necessary.
SAFETY CONSIDERATIONS
maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause
death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or
branch for information or assistance. The qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the individual instructions packaged with the kits or
accessories when installing. Follow all safety codes. Wear safety glasses, protective
clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available.
Read these instructions thoroughly and follow all
warnings or cautions included in literature and attached to the unit. Consult local building codes and
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert
symbol/_ When you see this symbol on the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words
are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which would result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury or death. Before installing, modifying, or servicing
system, main electrical disconnect switch must be in the OFF position. There may be
more than one disconnect switch. Lock out and tag switch with a suitable warning label.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in proper-
ty damage R-410A systems operate at higher pressures than
R-22 systems. When working with R-410A sys- tems, use only service equipment and replace-
ment components specifically rated or approved for R-410A service.
ELECTRICAL SHOCK HAZARD Failure to turn off electric power could result in
personal injury or death. Before installing or servicing system, turn off
main power to the system. There may be more than one disconnect switch, including accessory heat- er(s).
484 01 5100 00 March2009
DESCRIPTION AND USAGE
Figure 1 JTypical Fan Coil
The replacement coil kit is designed for use when
replacement of an existing slope of A-coil is required. NOTE: Replacement of an indoor slope or A-coil must
include recovery and recycling of refrigerant currently in
the system. Provided the refrigerant has not been
contaminated with moisture, acid, solid particulate, or non-condensibles, it may be recovered by following the
procedures listed below. However, if the refrigerant is contaminated, recycling or reclaiming methods are required. If leaks are present in the system, meaning the
refrigerant may be contaminated, recycling or reclaiming methods MUST be used. Installation of new filter drier(s)
is required. The filter drier-type will depend up on the contaminants in the system. See Split-System
Residential Air Conditioners and Heat Pumps Service manuals for further information.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in person-
al injury or property damage Relieve pressure and recover all refrigerant before
system repair or final unit disposal to avoid per- sonal injury. Use all service ports and open all flow-control devices including the solenoid valves.
INSTALLATION
If it is determined that the system does not have leaks,
and the refrigerant is not contaminated, proceed as follows:
1. Recover system refrigerant a. Attach gage/manifold set to service valves.
b. Start unit in cooling mode. c. Front seat (close) liquid line service valve. d. Operate unit until vapor pressure reaches 5 psig
(35kPa), or until suction line LPS opens.
e. Turn off electrical supply to outdoor unit. f. Front seat (close) vapor service valve. g. Recover any remaining refrigerant.
NOTE: All condenser coils hold only a factory-supplied amount of refrigerant. Excess refrigerant, such as in
long-line applications, may cause compressor internal pressure relief valve to open (indicated by sudden rise in
vapor pressure) before refrigerant is recovered. If this occurs, turn off electrical supply to outdoor unit
immediately, front seat (close) vapor service valve, and recover any remaining refrigerant.
2. Turn off electrical supply to indoor unit.
3. Disconnect condensate drain line.
FIRE HAZARD Failure to follow this warning could result in per-
sonal injury or death. Use of torch may cause oil to catch fire. To remove
use tubing cutter only.
4. Disconnect liquid and vapor lines from indoor coil. Use a tubing cutter to cut the lines.
5. Remove coil access panel.
6. Remove clip securing fitting panel to condensate drain pan and remove fitting panel.
7. Remove all shipping clips (if present), including horizontal pan clip. Slide coil and condensate pan
assembly out of unit.
8. Remove horizontal condensate drain pan from coil (if present) and condensate pan assembly. (See Fig. 2.)
9. Remove 4 coil brackets if present. (See Fig. 2.)
10. Remove screws at delta plates and remove coil from
vertical condensate drain pan. (See Fig. 2.)
2 484 01 5100 00
11. Thermostatic Expansion Valve (TXV) units only-To
use original TXV with new coil, remove TXV from original coil and install onto new coil as follows:
a. If TXV has a sweat joint on the valve outlet, unbraze
sweat joint as shown in Fig. 3.
(1.) Remove equalizer tube. Use file to score and break
off tube at old coil suction header, or unbraze.
Remove bulb from old coil. The TXV should now be
completely separated from old coil.
(2.) Install TXV onto new coil. Remove liquid line fitting
tube from new coil, and remove piston from piston body. Use tubing cutters to cut off elbow. (See Fig. 4.)
(3.) Braze remaining tube and nut onto TXV outlet. (See
Fig. 5.)
(4.) Install resulting TXV/nut assembly onto new coil in
same location as on old coil.
(5.) Install equalizer tube onto new coil by scoring
extension tube near brazed tip of tube, and sliding equalizer tube into extension tube. Braze equalizer
tube to extension tube. (See Fig. 6.)
(6.) Install thermal bulb into suction header of new coil in
10 o'clock or 2 o'clock position.
b. If valve has a mechanical joint at valve outlet, use
wrenches to separate valve outlet from old coil.
(1.) Remove equalizer tube. Use file to score and break
off tube at old coil suction header, or unbraze.
Remove bulb from old coil. The TXV should now be
completely separated from old coil.
(2.) Install TXV onto new coil. Remove liquid line fitting
tube from new coil using wrenches. Remove piston.
Install valve onto new coil using wrenches. If TXV
outlet is flare type, use adapter tube provided.
(3.) Install equalizer tube onto new coil by scoring
extension tube near brazed tip of tube, and sliding equalizer tube into extension tube. Braze equalizer
tube to extension tube.
(4.) Install thermal bulb into suction header of new coil in
10 o'clock or 2 o'clock position.
c. If replacement coil has a mechanical connection with
no piston body, install TXV to flare nut or new coil.
(1.) Remove equalizer tube. Use file to score and break
off tube at old suction header, or braze. Remove bulb from old coil.
(2.) Install TXV onto new coil. Install valve onto new coil
onto coil using wrenches.
(3.) Install equalizer tube onto new coil by scoring and
breaking extension tube near brazed tip of tube. Slide equalizer tube into extension tube and braze connection.
(4.) Install thermal bulb onto suction header of new coil in
10 o'clock or 2 o'clock position.
12. Horizontal Applications Only--Remove coil top seal (attached with 4 screws) and J-shaped tube from original
coil, and install them in same position on new coil. (See Fig. 2.)
13. Place coil assembly in plastic condensate pan and
secure with 4 screws through delta plate. (See Fig. 2.)
14. Horizontal and Upflow Applications Only--Attach 4 coil brackets to coil and pan assembly. (See Fig. 2.)
15. Horizontal Applications Only--Place horizontal condensate pan into position on coil and pan assembly.
NOTE: Installation of horizontal condensate pan is not necessary for upflow or downflow applications.
16. Slide completed assembly into unit.
17. Reinstall fitting panel and reconnect clip securing
fitting panel to condensate drain pan.
18. Horizontal Applications Only--Reinstall horizontal pan clip and secure with 1 screw. (See Fig. 2.)
19. Reinstall coil access panel.
20. Reconnect liquid and vapor refrigerant lines and condensate drain line. Install new filter drier(s).
NOTE: If a torch is used to unbraze the line set, protect
the fitting panel with a wet cloth or braze shield as
necessary.
21. Evacuate line set and indoor coil to 500 microns, back
seat (open) liquid and vapor service valves.
22. Turn on electrical supplies to indoor and outdoor units.
23. Check system refrigerant charge and operation. See Split- System Residential Air Conditioners and Heat
Pump Service Manuals for further information.
UNIT DAMAGE HAZARD Failure to follow this caution may result in unit
damage When securing braces or supports to unit, select
a location where drill and fasteners will not con- tact refrigeration components.
484 01 5100 00 3
Loading...
+ 4 hidden pages