I Installation Instructions Fan Coils I
INSTALLATION
INSTRUCTIONS
Models
EBV
2-5 Ton
General Information / Installation ....... 2
Upflow Installations ................... 3
Downflow Installations ................ 3
Horizontal Installations ................ 3
Ductwork Connections ................ 4
Electrical Connections ................. 5
Diagrams ............................. 6
Transformer Information ............... 7
Refrigerant Tubing .................... 8
Refrigerant Flow Control ............... 8
Condensate Drains .................... 9
Condensate Drain Diagrams ........... 10
Start-Up Procedures .................. 11
Sequence of Operation ................ 13
Airflow Curve Charts .................. 14
Use ONLY factory listed electric heaters.
Variable Speed Fan Coils
Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAU-
TION are used to identify levels of hazard seriousness.
The signal word DANGER is only used on product la-
bels to signify an immediate hazard. The signal words
WARNING and CAUTION will be used on product la-
bels and throughout this manual and other manuals that
may apply to the product.
DANGER - Immediate hazards which WILL result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
COULD result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
COULD result in minor personal injury or product or
property damage.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels.
CAUTION
496 01 4113 00
September 2002
I Installation Instructions Fan Coils I
Figure 1
I Clearances & Dimensions
I
J
FI
J
Unit Size-,
2400
3600
4800
6000
A
15-3/4"
19-1/4"
19-1/4"
22-3/4"
B
11"
11"
11"
11"
NO HEATERS
All Sides ................................... 0"
From Supply Duct .......................... 0"
Recommended Service From Front .......... 20"
(Service for blower, filter if installed)
WITH HEATERS
All Sides .................................. 0"
From First Three Feet of Supply Duct to Combus-
tibles ...................................... 1"
From Duct after Three Feet ................. 0"
Recommended Service From Front .......... 20"
Fire Hazard
When heaters are installed maintain clearances
from combustible materials as specified on unit
rating plate. Do not use plastic lined or combustible
flexible ducting within 36 inches of the supply end of
the air handler.
C
1_1_1_'
1_1_1_'
1_1_1_'
1_1_1_'
CLEARANCES
D
15-5/8"
19-1/8"
19-1/8"
22-11/16"
E
22-1/16"
22-1/16"
22-1/16"
22-1/16"
F
17-5/8"
21-1/8"
21-1/8"
24-11/16"
G
47-11/16"
53-7/16"
53-7/16"
59-3/16"
J_nlet AEr
General Information
Installation or repairs made by unqualified persons
can result in hazards to you and others. Installation
MUST conform with local building codes and with the
National Electrical Code NFPA70 current edition.
The information contained in this manual is intended
for use by a qualified service technician familiar with
safety procedures and equipped with the proper
tools and test instruments.
Failure to carefully read and follow all instructions in
this manual can result in equipment malfunction,
property damage, personal injury and/or death.
Failure to do so can result in fire, property damage,
personal injury or death.
The blower cabinet may be used for cooling or heat pump operation with
or without electric heat. The cabinet can be installed in an upflow or
horizontal position (Figure 2, 3). EBV models are shipped with the hori-
zontal kit already installed.
Location
Select the best position which suits the installation site conditions. The
location should provide adequate structural support, space in the front of
the unit for service access, clearance for return air and supply duct con-
nections, space for refrigerant piping connections and condensate
drain line connections. If heaters are being installed make sure ade-
quate clearance is maintained from supply ductwork, (see Fig. 1).
NOTE: Internal filter can be accessed from separate filter door. If the
filter can NOT be easily accessed, a remote filter is recommended. Re-
fer to ACCA Manual D for remote filter sizing.
If the unit is located in an area of high humidity, nuisance sweating of
casing may occur. On these installations a wrap of 2" fiberglass insula-
tion with a vapor barrier is recommended.
UJ
I Fan Coils
INTRODUCTION
The EBV model is designed for flexibility and can be used for upflow,
horizontal, or downflow (kit required) applications. These units are avail-
able for systems of 24,000 through 60,000 Btuh nominal cooling capac-
ity. Factory authorized electric heater packages are available in sizes 5
through 30kw. See Product Specification Literature for available acces-
sory kits.
HEATER PACKAGES
A factory approved, field installed UL listed heater package is available
from your equipment supplier. See unit rating plate for a list of factory
approved heaters. Heaters that are not factory approved could cause
damage which would not be covered under the equipment warranty.
Installation Instructions
Figure 2 Slope Coil Unit In Upflow Application
SUPPLY DUCT
ENTRY
OPTIONS
018_06021 IN, FRONT SERVICE
070 24=1N CLEARANCE
UPFLOW/DOWNFLOW
Unit A
2400-3600 17 in
4200-6000 19 in
½-
INSTALLATION
PROCEDURE 1- CHECK EQUIPMENT
Unpack unit and move to final location. Remove carton taking care not
to damage unit. Inspect equipment for damage prior to installation. File
claim with shipping company if shipment is damaged or incomplete. Lo-
cate unit rating plate which contains proper installation information.
Check rating plate to be sure unit matches job specifications.
PROCEDURE 2- MOUNT FAN COIL
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space
for wiring, piping, and servicing unit.
NOTE: To ensure proper drainage for horizontal installations, unit must
be installed so it is within 1/8 in. level of the length and width of unit.
A. Upflow Installation
If return air is to be ducted, install duct flush with floor. Set unit on floor
over opening. Only use return-air opening provided. All return air must
pass through the coil. (See Fig. 2.)
B. Modular Units
The EBV Fan Coil in size 6000 is a 2-piece modular unit. Modular
construction allows installer to disassemble unit into 2 components, coil
box and blower box, for ease of installation. (See Fig. 4)
To disassemble unit, remove rear corner brackets by removing 2
screws which secure brackets. (See Fig. 4) Remove either 2 screws in
each front corner of coil box, or 2 screws in blower box. Do not remove
all 4 screws in each corner. (See Fig. 4) Sections may now be separated
by lifting top section from lower section. To reassemble, reverse above
procedure. Be certain to reinstall all fasteners when reassembling.
C. Horizontal Installation
Be sure installation complies with all applicable building codes that may
require installation of secondary condensate pan.
1. Arrange support for unit by setting it in or above secondary conden
sate drain.
2. When suspending unit from ceiling, dimples in casing indicate proper
location of screws for mounting metal support straps (See Fig. 3)
CAUTION
A field fabricated auxiliary drain pan, with a seperate drain is RE-
QUIRED for all installations over a finished living space or in any
area that may be damaged by overflow from a restricted main drain
pan. In some localities, local codes require an auxiliary drain pan
for ANY horizontal installation.
FIELD MODIFIED
A SIDE RETURN
LOCATION FOR
SLOPE COIL
UNITS ONLY
CAUTION: For optimum condensate drainage performance in
horizontal installations, unit should be leveled along it's length
or raised 1/4" at the air inlet. The unit should also be pitched for-
ward 1/4" to 1/2" toward the front condensate drains.
NOTE: Modular units can be disassembled and components moved
separately to installation area for reassembly. This process accommo-
dates small scuttle holes and limiting entrances to installation sites.
D. Horizontal-Right Conversion of Units with Slope Coils
1. Remove blower and coil access panels and fitting panel. (See Fig. 5.)
2. Remove screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil on its right side and reinstall coil assembly with conden-
sate pan down. (See Fig. 5.)
5. Attach coil to casing flange using coil mounting screw previously
removed.
6. Align holes with tubing connections and condensate pan connec-
tions, and reinstall access panels and fitting panel.
Make sure liquid and suction tube grommets are in place to prevent
air leaks and cabinet sweating, install after brazing.
E. Horizontal Right Conversion of Units With A-Coil
1. Remove blower and coil access panel and fitting panel.(See Fig. 6).
2. Remove metal clip securing fitting panel to condensate pan. Remove
fitting panel.
3. Remove 2 snap-in clips securing A-coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil support rail on
left side of unit and reinstall on coil support rail on right side of unit.
6. Convert air-seal assembly for horizontal right. (See Fig. 6).
A. Remove air-seal assembly from coil by removing 4 screws.
B Remove coil drip flanges from A-coil and reinstall on right side of
coil (same side as horizontal drain pan).
C. Remove filler plate (A) and install air splitter (B) in place of filler
plate.
D. Install filler plate (A) as shown in horizontal right application.
E. Remove condensate troughs (C) and install on opposite tube
sheets.
F. Install hose onto plastic spout.
7. install horizontal pan on right side of coil assembly.
I Installation Instructions Fan Coils I
F. Install hose onto plastic spout.
7. Install horizontal pan on right side of coi! assembly.
8. Slide coil assembly into casing. Be sure coil bracket on each corner
of vertical pan engages coil support rails.
9. Reinstall 2 snap-in clips to correctly position and secure coil assem-
bly in unit. Be sure clip with large offsets is used on right side of unit
to secure horizontal pan.
10. Remove 2 oval coil access panel plugs and reinstall into holes on left
side of coil access panel and fitting panel.
11. Remove insulation knockouts on right side of coil access panel
12. Reinstall access fitting panels, aligning holes with tubing connec-
tions and condensate pan connections. Be sure to reinstall metal
clip between fitting panel and vertical condensate pan.
Make sure liquid and suction tube grommets are in place to prevent air
leaks and cabinet sweating.
D. Manufactured and Mobile Home Housing Applications
1. Fan coil unit must be secured to the structure using field-supplied
hardware.
2. Allow a minimum of 24" clearance from access panels.
3. Recommended method of securing for typical applications
a. If fan coil is away from wall, attach pipe strap to top of fan coil
using No. 10 self tapping screws. Angle strap down and away
from back of fan coil, remove all slack, and fasten to wall stud of
Figure 3
Slope Coil In Horizontal Left Application
structure using 5/16-in. lag screws. Typically both sides of fan
coil.
b. If fan coil is against wall, secure fan coil to wall stud using
1/8-in. thick right-angle brackets. Attach brackets to fan coil us
ing No. 10 self tapping screws and to wall stud using 5/16-in. lag
screws. (See Fig. 9).
PROCEDURE 2-AIR DUCTS
Connect supply-air duct over the outside of 3/4-in. flanges provided on
supply-air opening. Secure duct to flange, using proper fasteners for
type of duct used, and seal duct-to-unit joint. If return-air flanges are
required, install factory authorized accessory kit.
Use flexible connectors between ductwork and unit to prevent transmis-
sion of vibration. When electric heater is installed, use heat-resistant
material for flexible connector between ductwork and unit at discharge
connection. Ductwork passing through unconditioned space must be in-
sulated and covered with vapor barrier.
Ductwork Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 ft. of main
duct to first branch takeoff may require internal acoustical insulation lin-
ing. As an alternative, fibrous ductwork may be used if constructed and
installed in accordance with the latest edition of SMACNA construction
standard on fibrous glass ducts. Both acoustical lining and fibrous duct-
work shall comply with National Fire Protection Association as tested by
UL Standard 181 for Class 1 air ducts.
FIELD DRAIN
If" II .
/Ifr ...... II II CLEARANCE
11II _"- -_ I I II, (FULL FACE
LOW VOLT
ENTRY
OPTIONS
'k",,llt 1 -,"_ _.11 FILTERACOESS
POWER DRAIN
ENTRY OPTIONS
..... SEOO 2 RyDRA,. '
1_ 'PRIMARY
018-060 21 -IN.
I Fan Coils
Installation Instructions
Figure 4 Removal of Brackets on Modular Units
_2SCREWSI_ _I
I .... ._4
_-_RE*RCORNER \ _-_
COiL BOX
PROCEDURE 4-ELECTRICAL CONNECTIONS
On units with a factory installed disconnect with pull-out removed, ser-
vice and maintenance can be safely performed on only the load side of
the control package.
WARNING: Field wires on the line side of the disconnect found in
the fan coil unit remain live, even when the pull-out is removed.
Service and maintenance to incoming wiring can not be per-
formed until the main disconnect switch (remote to the unit) is
turned off. Failure to do so will result in electrical shock causing
personal injury or death.
Before proceeding with electrical connections, make certain that supply
voltage, frequency, phase, and ampacity are as specified on the unit rat-
ing plate. See unit wiring label for proper field high- and low-voltage
wiring. Make all electrical connections in accordance with the NEC and
any local codes or ordinances that may apply. Use copper wire only. The
unit must have a separate branch electric circuit with a field-supplied
disconnect switch located within sight from and readily accessible from
the unit.
2 SCREWS
Figure 5
SLOPE COIL.
SKI
Conversion for Horizontal Right
Applications Using a Slope Coil
1
OOtL MOUNTING
- SCREW
PRIMARY DRAIN
-OVERFLOW HOLE
)RAIN
Conversion for Horizontal Right
Figure 6 Applications Using A-Coil
--AIR SEAL
SUPPORT
BRACKET
CONNECTIONS ASSEMBLY
RAIL
ASSEMBLY
HORIZONTAL
RIGHT
APPLICATION
SUPPORT
BRACKET
COIL--
SUPPORT
RAIL
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT