Single Point Wiring Kit Installation Instructions
EBP, EBX, EBV and EBW Fan Coils
INTRODUCTION
The single point wiring kit is designed to allow single circuit field wiring to 15 kw and 20 kw fused electric heaters. Refer tofan
coil specification sheet for electric heater kit numbers that can be converted from dual circuit to single circuit electrical supply.
NOTE: When using single point wiring kit, wire size and over-current protection device must be based on single circuit electri-
cal data. Consult specification sheet.
INSTALLATION
1. Install 15 kw or 20 kw fused electric heater kit per Installation Instruction.
2. Install lug adapters in fuse box lugs and tighten securely. (See Fig. 18.)
3. Connect single circuit field power supply wiring to lug adapters. (See Fig.18.)
4. Connect ground lead from field power supply to unit ground lug.
LUG ADAPTER KIT
BEFORE LUG ADAPTER
INSTALLATION
L3 L1 L2 L4
FUSE BLOCK
AFTER LUG ADAPTER
INSTALLATION
L3 L1 L2 L4
INSTALLATION MAY BE AIDED BY FIRST
ATTACHING ADAPTER LUGS TO WIRE
THEN POSITIONING LUGS TO FUSE BLOCK
SINGLE CKT
FIELD POWER
SUPPLY WIRES
Fig. 18 - Single Point Conversion
482 01 2228 00 II 1 I
September 2002