ICP EAIC1020B, EAIC1014B Installation & Operation Manual

EAIC High Efficiency
Electronic Air Cleaner Series 1014B and 1020B
J
anstaalation Operation o
Maintenance
o
:: ::::: ::: ::: ::!:::: :;: : ::::: : ::: :':: :::;:
155587-0099-D4 616 01 1003 O0
Table of Contents
Introduction ....................................................................................... I
Unit Components .......................................................................................2
Operation ...................................................................................................3
!) Regular Dusting & "White Dust"° ...........................................3
2) Ozone .................................................................................... 3
3) High Altitude Operation .................................................... 4
Maintenance of Your Electronic Air Cleaner ................................... 5
1) Washing the Cells and Pro-filter(s) .................................... 5
2) Replacing the Ionizer Wires ...................................................6
3) Cleaning the Air Flow Sensor (AFS) .................................. 6
Common Questions & Answers ...................................................................7
Common Troubleshooting Techniques ............................................. 9
Unit Dimensions .................................................................................. 10
HVAC INSTALLATION INSTP,UCTIONS.................................................... 11
(for use by authorized HVAC contractors only)
Technical Specifications ....................................................................... 11
Installation Considerations ................................................................... 12
Application ............................................................................... 12
Installation Requirements ...................................................... 12
Air Conditioning .................................................................................12
Evaporative Hure!differs .......................................................... 12
Atomizing Humidifiers ...............................................................13
Sheet Metal Installation .......................................................... 13
Transitions ............................................................................... 13
Outdoor Air ............................................................................ 13
Turning Vanes ........................................................................ 13
Location Selection ............................................................................ 14
Typical Mounting Positions .............................................................. 15
Mechanical Installation ....................................................................... 16
Electrical Installation ......................................................................... 18
System Checkout .............................................................................. 19
Troubleshooting .................................................................................... 20
Air Flow Sensor ....................................................................... 20
Primary Circuit .............................................................................21
Secondary Circuit - Ionizing-Collecting Cel! ..........................22
Secondary Circuit- Power Supply ........................................ 23
Unit Diagram & Parts List ........................................................................ 25
Warranty ................................................................................................ 26
INTRODUCTION
This Electronic Air Cleaner is a two-stage electrostatic precipitator. The air cleaner is designed to remove airborne particulates, including dust, dirt, smoke, pollen, virus, spores, bacteria, and mold from indoor air.
Air movement through the unit isprovided by the heating, air conditioning or ventilating system blower. As dirty air enters the air cleaner, the air passes through Metal Mesh Pre-filters_ The Pre- filters prevent lint, pet hair and other large particulates from entering the air cleaner, it is important that these filters be in place to prevent excessive dirt loading of the air cleaner Ionizing-Collecting Cells° These filters extend the time interval between scheduled maintenance of the air cleaner, which allows the Ionizing-Collecting Cells to provide clean air for a longer period between washings_
The pre-filtered air then passes through a two-stage Electronic Air Cleaner. In the first stage, alf airborne particulate, even submicron size, are electronically charged (positive) as they pass through the ionizer sectiom The ionizer field is a result of a corona discharge emanating from
the fine, tightly strung wires suspended between two adjacent flat piates, in the second stage,
the charged particulate passes through an intense electrical field established between alternately charged and grounded parallel collector plates. Here, the charged (positive) particulate is attracted to the ground (negative) plates and removed from the air stream.
POWER TRAY ASSEMBLY
COVER
ON-OFF SWITCH
INDICATING
LIGHTS
CELL CONTACT
POWER TRAY
ASSEMBLY
CABINET
COLLECTING CELL(S)
FRONT PANEL
ASSEMBLY
I
Cabinet
Mounts to existing ductwork; houses the Ionizing-Collecting Cells and Pre-fitters.
Ionizing-Collecting Cells
Collect the dust, dirt and other particulates in the air. They contain the ionizing and collecting sections_ The cells must be installed with the ionizing wires on the air intake side. A spring contact is located on the top of each cell and must be in the position to make contact with the contact board assemblies on the bottom of the Power Tray Assembly.
Pre-filters
Trap large particulates before they enter the Ionizing-Collecting Cell
Power Tray Assembly Contains the indicating lights, solid-state power supply, contact boards and electrical controls
including the ON/OFF switch and safety interlock switch. A power cord at the rear of the 120 volt Power Tray allows the unit to be connected to a standard 120 volt outlet° A wiring compartment isprovided on all models at the rear of the Power Tray allowing the option to permanently wire
the unit directly to the HVAC System Control° Air Flow Sensor (AFS)
Controls the operation of the unit by sensing the movement of air within the duct. This helps to reduce power usage,
THERMISTOff
\,
AIR FLOWSENSOR
The AFS is designed to provide an efficient and reliable
method of controlling the operation of the air cleaner when the installer is unable to wire the unit directly into the HVAC System Blower Control Circuit. The AFS utilizes a thermistor,
which when electrically powered, heats up to approximately
130° RThe AFS stabilizes at this temperature and while the HVAC System Blower is in operation, air flows through the ductwork, creating a vacuum effect that pulls cooler air over the hot surface of the thermistor. This air movement cools down the
thermistor which allows the AFS to register that the HVAC System blower is moving air and the
Electronic Air Cleaner must be powered to provide air cleaning Air Cleaner Model Identification
The model number and part number for your Electronic Air Cleaner can be found on the data label located on the inside of the Front Panel Assembly°
J
Regular Dusting and "White Dust"
Your new Electronic Air Cleaner will efficiently clean and filter your household air° It will not eliminate the need for regular dusting of your furniture and belongings_ Duct-mounted air cleaners can only clean air that reaches the air cleaner. Therefore, if the particulates are not
being carried to the air cleaner in the air stream, the air cleaner cannot remove them from
your home, Occasionally a "white dust" may be noticed in bedrooms or newly furnished rooms. This is
mainly composed of lint which, because it is heavier than other particulates, settles before it
reaches your unit. This "white dust" is not mixed with airborne dirt particles, therefore, it is clean and has no staining or soiling properties. Running the furnace blower continuously, day and night, will help reduce this from occurring_
Ozone
Under normal operating conditions, all Electronic Air Cleaners produce minute quantities of ozone as an incidental by-product. In fact, all electronic products, such as televisions, cordless telephones and refrigerators, produce some amount of ozone° The average homeowner can detect the smell of ozone concentrations as low as 25 to 100 ppb (parts per billion)° The design of this unit has been tested and ozone production is approximately half of the published permissible limits established by the Environmental Protection Agency. These limits recommend that the concentration of indoor ozone not exceed 50 ppb_ Ozone is not harmful
in these concentrations. In fact, the ozone level in major cities can sometimes reach as high as 100 ppb on a summer day_The addition of optional charcoal after-filters can help reduce the smell of ozone generated by the air cleaner.
Normally, a new unit will produce more ozone than one that has been in operation for several weeks_ This is due to sharp corners or manufacturing burrs on the ]onizing_Collecting Cell
Plates and is normal, As the Electronic Air Cleaner arcs and zaps, the voltage is vaporizing these areas and tends to round them off_ This is part of the breaking-in period and the issue
is self-correcting, Also, high-altitude locations can be more susceptible to noticing the presence of ozone,
An ionizing-Collecting Cell that has been damaged or bent (the designed spacing between electrically<harged and ground components has been decreased) may also produce an
abnormal amount of ozone.
HighAltitudeOperation Becausethe air is less dense at higher altitudes,
there is a possibility of nuisance arcing in the
Electronic Air Cleaner, The homeowner can quickly and easily correct this conditiom
1_ Make sure the HVAC System Blower is not
operating, the ONIOFF switch is in OFF position and the circuit breaker is turned OFF or input
power cord isdisconnected° 2_ Remove the Front Panel Assembly, 3_ Remove the cover from the Power Tray
Assembly by removing the two screws on top of
unit. (The entire Power Tray Assembly may be
removed from the cabinet by removing two
screws from inside the cabinet_)
4_
5.
Locate the jumper terminal°
With a pair of needle nose pliers, carefully
relocate the jumper settings from HIGH to MED.
Ensure that the jumper is firmly seated in the
terminal°
6, Replace the Power Tray Cover and secure it with
two screws°
7o Replace the Front Panel Assembly, turn circuit
breaker ON, reconnect input power cord and
turn ONtOFF switch ON,
This procedure will slightly reduce the output voltage, minimize arcing and reduce ozone
production° If the condition does not improve, repeat the above procedure and move the jumper setting from MED (M) to LOW (L).
This unit is produced at the factory with the jumpers
set in the HIGH (H) position. However, the output
voltage may be lowered in any situation where the
unit is arcing excessively or there is excessive ozone,
%
4
WASHINGIONIZING-COLLECTING CELLSAND PRE-FILTERS
Regu{ar washing of the Ionizing+Collecting Cells is necessary to ensure proper performance,
A thorough washing once every two months will be adequate for most installations, More frequent washing (once a month) may be necessary with some installations (new home for example) where there is new carpeting, plaster dust or excessive cigarette smoke.
To Remove the ionizing-Collecting Cells and Pre+filters from the Air Cleaner:
1, Turn air cleaner ON/OFF switch to OFF position_ Wait 15 seconds+Remove Front Panel Assembly+
2. Carefully remove the fonizing+Coliecting CeiL(s)and Pre-filter(s) and set aside in a safe place_ 3+Do not drop the Ionizing-Collecting Ce!loThis can cause damage to the cell plates or ionizing
wires which results in excessive arcing and poor performance.
To Wash Ionizing-Collecting Cells and Pre-filters:
We suggest you follow the instructions below to properly and thoroughly clean your
Ionizing-Collecting Cells.
1, Place enough hot water in a utility tub to cover the first cell+ Dissolve 2+4 oz, of granulated
automatic dishwasher detergent (NOT laundry detergent) in the water=,
2_ Allow the cell to soak for 30 minutes, Agitate it up and down in the solution until it appears
clean and remove_
3_
4+ 5,
+
Repeat with second cell (if applicable), Agitate the Pre-filters up and down in the solution until they appear clean. With a hose, rinse the ionizing-Collecting Cells and Pre-filters, The hose should be held
about 10" from the cell plates and at a slight angle for maximum cleaning results, Be careful
not to spray the ionizing wires directly with the hose as the water pressure can cause the wire(s) to stretch and break, The cell frame should be thoroughly rinsed along the edges to dislodge any trapped lint or dirt+ Carefully wipe a damp cloth or sandpaper (not emery cloth)
along the ionizing wires,
Stand Ionizing-Collecting Cells and Pre-filters in upright position and allow to dry two hours_ You may experience a slight discoloration of the a[uminum collector cell plates after washing_ This is a normal chemical reaction between the aluminum and detergent and will
not harm your unit or affect its performance+
To Replace Cells in the Air Cleaner;
1+ Replace Pre+filter and Ionizing-Collecting Cells in cabinet. Check that airflow arrow on Cells
point in same direction as air flows through the duct° (If you have to force the ceil past the
positioning screw in the cabinet bottom, the cell is probably in the incorrect position.)
2+ Replace Front Panel Assembly (engage tabs on lower edge of door into slots in cabinet),
Carefully close the Panel
3+ Turn air cleaner ON/OFF switch to ON position_
REPLACING THE IONIZING WIRES
Instances of the Ionizing Wires breaking are minimal due to the constant tension design and
fixed location of the lonizing Wire supports. When an Ionizing Wire breaks, the efficiency of the
Electronic Air Cleaner will decrease slightty_ However, the unit will continue to operate with a broken Ionizing Wire as long as the broken wire has not caused a short in the secondary circuit of the unit_ Remove all loose and broken wires as soon as they are identified.
We recommend contacting a qualified HVAC contractor for replacement parts and/or servicing.
ionizing Wires are supplied in a coiled spring configuration, with a clinch nut on each end of the wire. Replacement requires a pair of needle nose pliers° Exercise caution in removing any broken wires in the Ionizing-Collecting Cell. The removal of broken wires will prevent accidental shorting of the cell and reduce the need for further maintenance.
Use the following procedure when replacing an Ionizing Wire:
1o Turn Air Cleaner ON/OFF switch to OFF position,, Wait 15 seconds° Remove the Front Panel
Assembly and remove the Ionizing-Collecting Cells from the unit.
2. Carefully remove all remains of the broken wire from the cello 3_ Grip the new wire at each end with your thumb and index finger, While stretching the wire
to approximately 6", allow one end of the wire to uncoil between your thumb and index finger_
4. Place one end of the wire in the slot of the stainless steel wire support located on the
Ionizing-Collecting Cell asviewed from the front of the cell. This support ispartially covered by the cel! brace in front of the support°
5, Grip the other end of the tonizing Wire with needle nose pliers and insert the terminated
end of the wire into the slot in the wire support on the opposite end of the lonizing- Collecting Cell,
6. The wire should have sufficient tension to be self supporting and remain suspended between the slots in the wire supports.
CLEANING THE AIR FLOW SENSOR If the air cleaner is installed in a location that is dusty and dirty, the sensor (thermistor) on the
AFS can become coated with dirt and lint. This coating can insulate the AF5 and keep it from
operating properly, To clean the thermistor, turn the unit OFF, dip a cotton swab in rubbing alcohol and carefully insert into the 3/16" diameter hole located on the front right hand side of
the Power Tray Assembly (when facing the unit). Carefully twirl the cotton swab between your
fingers, making sure the tip is lightly in contact with the gray disc (thermistor), cleaning the insulating coating from the thermistor,
6
COMMON QUESTIONS AND ANSWERS
Q_
Am
a_
A,
a_
A_
Q.
Ao
Q,
Ao
a_
A_
Why isn't my Electronic Air Cleaner cleaning my air? The air cleaner is most likely working just like it was designed, However, many
factors can affect the performance of the unit_ Are air return registers located in the ceiling? If so, it will be difficult for the air flow to carry heavier particulates to the air cleaner. If the dirt does not get to the air cleaner, it cannot be removed from the air. Are both the Red and Green indicating lights illuminated? If not, the
unit may be in need of servicing. It still isn't cleaning my air the way 1want it to, What can 1do? It is recommended that you operate the HVAC system continuously so that the air
movement will carry the dirt to the air cleaner where it can be collected.
Unfortunately, there will always be some dirt that isleft behind on the appliances, furniture, etc. Regular dusting is recommended to stir up these pockets of dust so that they can enter the air stream and be removed by the Electronic Air Cleaner.
When t turn on my Electronic Air Cleaner, the lights come on for a couple of seconds and then turn off. The air cleaner isn't working!
The air cleaner is operating properly as long as both the Red and Green indicating
lights are illuminated. Try turning the HVAC blower ON and then turning the
Electronic Air Cleaner ON_This should solve the problem What is the zapping noise I am hearing from my unit? Should I be concerned? The zapping or popping noise that you are hearing isthe sound of larger particles
being "vaporized" by the Ionizing-Collecting Cel!oThis is normal and is no cause for alarm_ As your HVAC system blower moves the air through the ductwork and allows the Electronic Air Cleaner to clean the air, the noise will diminish, However, there will always be instances when larger particles enter the Ionizing-Collecting Cell, and are "vaporized",
Should 1hear this zapping noise all the time? All Electronic Air Cleaners will occasionally zap or pop as larger particles pass
through the lonizing_Colfecting Ceils° However, if the sound is constant or is repetitive in nature, then a large particle may have become lodged in the lonizing_ Collecting cell and may require removal by cleaning, If cleaning the Ionizing- Collecting Cell does not stop the noise and/or there are no large particles trapped in the ionizing-Collecting Cell, then the cause could be a broken/loose ionizing wire, bent collector plate or other mechanical fault.
What if I no longer hear any popping or zapping noises coming from my unit? Is
it still cleaning the air?
tf the zapping noises stop and the air cleaner is not in need of servicing, then one of two situations has occurred_ First, the Electronic Air Cleaner has successfully removed all larger particles from the air and is cleaning microscopic particles which do not cause the zapping noises° Second, the HVAC system blower is not operating and air is not flowing through the ductwork_ The Electronic Air Cleaner cannot remove particles if the air stream is not moving.
Loading...
+ 19 hidden pages