ICP DFS2A309J1A, DFS2A312J1A, DFS2H312J1A, DFS2H309J1A, DFS2A318K1A Installation, Start-up And Service Instructions Manual

...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc
Printed in Israel Pg 1
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Indoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . .6
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Leak Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
System Checks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
CARE AND MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . .11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Indoor Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
To Clean the Indoor Unit Front Panel . . . . . . . . . . . . . . .11
To Clean Indoor Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
. . . . . . . . . . . . . . . . . . . . . . . . . .11
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .12-15
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
GENERAL
System Requirements
 Consult local building codes and National Electrical
Code (NEC, U.S.A.) for special installation requirements.
 Use only type G or C fuses.  Use single length power cable without extension.  Allow sufficient space for airflow clearance on condens-
ing units for wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2 for minimum required distances between unit and walls or ceilings.
 Indoor and outdoor units should be installed at a
Maximum line length of 50 ft, and vertical separation of 30 ft.
 Do not install indoor units near a direct source of heat
such as direct sunlight, steam or flame.
Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect. There may be more than one disconnect switch. Electrical shock can cause personal injury.
IMPORTANT: The Indoor unit & the inter units cable voltage
is 30 VDC
IMPORTANT: Each refrigerant line must be insulated separately. See line sizing requirements in table 2.
Do not bury more than 36 in. of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refriger­ant slugging and could possibly damage the compressor at start-up.
DFS2A/H 09,12,18
Duct Free Systems
Fig. 1B  Outdoor Unit Clearances
Fig. 1A  Outdoor Unit Clearances
These instructions cover the installation, start-up and servicing of
DFC2A/DFC2H outdoor and DFF2A/DFF2H indoor units
cooling only and heat pump duct free systems. See Table 1 for parts included. See Tables 2 and 3 for Physical Data.
51302618915 0106
TOP (min.)
2 (0.6m)
LEFT (min.)
6 (0.15m)
RIGHT (min.)
2 (0.6m)
FRONT (min.)
2 (0.6m)
REAR (min.)
6 (0.15m)
Max. cable length
. Total voltage drop should not exceed 1V. Therefore max. length: For #18 AWG 24.3 Feet (7.4 m)
For #16 AWG 37.7 Feet (11.5 m) For #14 AWG 50.0 Feet (18 m)
Outdoor Units . . . .
Outdoor Unit Installation . . .
Air Filters for Indoor Units
LEFT(min.)
6 (0.15m)
TOP(min.)
2 (0.6m)
REAR(min.)
6 (0.15m)
RIGHT(min.)
2 (0.6m)
FRONT(min.)
2 (0.6m)
Cooling Model Heat Pump
DFS2A309J1ADFS2H309J1A DFS2A312J1A DFS2H312J1A DFS2A318K1ADFS2H318K1A
421 01 9217 00
2
Table 1  Parts List  High Wall Units
ITEM QTY DIAGRAM
Mounting Bracket 1
DFF2A/DFF2H 09, 12 or DFF2A/DFF2H 18
Long Screws 8
Outdoor Sensor
Connecting Cable
1
Absorption Cushions 4
Electric Terminals 8
Remote Controller Rack 1 rack with 2 screws
Remote Controller
and Batteries
1
1
Owners Manual 1
1
(Available for HEAT PUMP ONLY)
(OPTIONAL)
(Not included)
Insulation for indoor Fittings
Wall mounted Receiver RTX
NADA001TW
TURBO-JET
ECONOMY
3
Table 2  Physical Data  Cooling Only
LEGEND
*Units are shipped with a factory charge based on 25 ft of refrigerant lines.
Table 3  Physical Data  Heat Pump
LEGEND
*Units are shipped with a factory charge based on 25 ft of refrigerant lines. NOTE: Standard Ambient Operating Limitations  55
ºF to 125 ºF (12.7 ºC to 51.6 ºC).
INDOOR UNIT
DFF2AH09J1A DFF2AH12J1A DFF2AH18J1A
COOLING CAPACITY (Btuh)
SEER
SYSTEM CHARGE (lb)* 2.7 3.1 4.1 MOISTURE REMOVAL (pt/hr) AIRFLOW
High Cfm 350 400 670
DIMENSIONS L x H x W (in.) 32 3/32 x 10 15/64 x 7 9/32 32 3/32 x 10 15/64 x 7 9/32 42 1/2 x 11 5/8 x 7 9/32
NET WEIGHT (lb) 19.0 19.0 27.5
OUTDOOR UNIT
DFC2A309J1A DFC2A312J1A DFC2A318K1A
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft)
30/30/50 30/30/50 30/30/50
NOMINAL LINE SIZING
Mixed Phase...Suction (in.)
DIMENSIONS L x H x W (in.) 28 3/4 X 21 1/4 X 10 7/16 35 7/16 X 25 3/16 X 12 9/32 43 5/16 X 25 3/16 X 15 3/4
NET WEIGHT (lb) 73 114 136
SEER  Seasonal Energy Efficiency Ratio
COOLING CAPACITY (Btuh) 9,000 11,600 19,000
SEER 13.0 13.0 13.0
HEATING CAPACITY (Btuh) 8,600 11,800 18,300
HSPF 7.7 7.7 7.7
SYSTEM CHARGE* (lb) 2.7 3.1 4.1
MOISTURE REMOVAL (pt/hr)
AIRFLOW
High Cfm
350 400 670
DIMENSIONS L x H x W (in.)
NET WEIGHT (lb)
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft)
NOMINAL LINE SIZING
Mixed Phase...Suction (in.)
DIMENSIONS L x H x W (in.)
SHIPPING WEIGHT (lb)
HSPF  Heating Seasonal Performance Factor SEER  Seasonal Energy Efficiency Ratio
9,000
11,600
19,000
13 13 13
3
/8...5/
8
1
/4...1/
2
1
/4...1/
2
32 3/32 x 10 15/64 x 7 9/32 32 3/32 x 10 15/64 x 7 9/32 42 1/2 x 11 5/8 x 7 9/32
19.0 19.0 27.5
30/30/50 30/30/50 30/30/50
28 3/4 X 21 1/4 X 10 7/16 35 7/16 X 25 3/16 X 12 9/32 43 5/16 X 25 3/16 X 15 3/4
73 114 136
3
/8...5/
8
1
/4...1/
2
1
/4...1/
2
2.6 4.5 5.3
2.6 4.5 5.3
INDOOR UNIT DFF2HH09J1A DFF2HH12J1A DFF2HH18J1A
OUTDOOR UNIT DFC2H309J1A DFC2H312J1A DFC2H318K1A
4
INSTALLATION
Plan the installation carefully to avoid component failures
and make installation easier.
Indoor Unit Installation
REFRIGERANT LINE ROUTING  The refrigerant lines may be routed in any of the four directions shown in Fig. 3.
INSTALL THE MOUNTING BRACKET
1. Carefully remove the mounting bracket, which is connected to the back of the indoor units base with
screws.
2. Position the mounting bracket on the wall and level it using a spirit level (see Fig. 2 for minimum required clearance distances).
3. Mark the four drilling holes on the wall, as they appear in Fig. 4.
4. Drill the holes, insert the wall plugs and use four long screws to attach the mounting bracket to the wall.
5. Check that the bracket is leveled and securely fastened to the wall.
DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER-UNIT CONNECTIONS  To make the connections between the indoor and outdoor units, drill a 3-in. hole through the wall for the refrigerant lines, drainage hose and control cable passage as shown in Fig. 5.
1. Mark the center of the hole to be drilled according to the re­frigerant line routing used and dimensions shown in Fig. 4.
2. Make sure to drill outwards and downwards, so that the opening in the outside wall is at least
1
/2-in. lower than
the opening on the inside.
3. Make sure the drainage hose is at the bottom side of the hole.
4 . If refrigerant line route no. 1, 2 or 4 are used, use a small
saw blade to carefully remove the corresponding plastic covering on the side panel.
5. Run the outdoor sensor cable, electrical cable, refrigerant lines, and drainage tube through the hole.
6. Fill the remaining wall hole gap with an appropriate sealant material.
Fig. 2  Indoor Unit Clearances
Fig. 4 Mounting Bracket DFF2A/DFF2H 09, 12
Fig. 4 Mounting Bracket DFF2A/DFF2H 18
REFRIGERANT
LINES
DRAINAGE
TUBE
ELECTRICAL
CABLE
1/2.IN. MIN
3-IN.
INDOOR OUTDOOR
Fig. 5  Drill Holes
(Optional for HEAT PUMP SYSTEMS)
OUTDOOR SENSOR CABLE
6" (0.15m)
(1.8-2.5m)
min.
min.
min.
6'-8'3"
8"
(0.2m)
8"
(0.2m)
Fig. 3  Refrigerant Lines
4
2
3
1
35 15
2
2
1
6
18
13¾
10
5
10
3
25
2
2
09, 12
17
9
16
11
32
23
32
5
32
11
4
1
32
19
8
5
8
1
2. Put the control box cover and grille frame back on using the appropriate screws (Steps 3 and 4 of Wire the Indoor Unit section). Put the grille insert back on.
REASSEMBLE
Fig. 8  Indoor Unit Mounting
5
Fig. 9  Outdoor Sensor Connection
123456
ON
HEAT PUMP
Model-12 DIP Switches location
(on the Control Box side)
HEAT PUMP
Models-09,18 DIP Switches location
(on the Control Box side)
Inter unit cable clamp
TH1
TH2
TH3
Display
connection
Inter unit
terminal block
30 VDC
123456
ON
123456
ON
123456
ON
COOLING ONLY
Model-12 DIP Switches location
(on the Control Box side)
COOLING ONLY
Models-09,18 DIP Switches location
(on the Control Box side)
Standard Dip Switches
status from the factory
(Heat pump only)
MAKE DRAINAGE CONNECTIONS
1. Connect the unattached end of the drainage tube to the drainage hose outlet.
2. Seal the drainage connection to prevent leakage.
3. Make sure there are no kinks, U bends or flattened sections in the tube.
4. Check that the drainage functions properly. Fill the pan below the units coil with water and observe that it freely drains out.
5. Make sure the drainage hose is at the bottom side of the wall through-hole (see Fig. 5).
outdoor sensor cable towards the lower right hand corner
of the indoor unit.
WIRE THE INDOOR UNIT
2. Remove the unit's front panel by lifting the lower part
and pulling it gently outward and upward. See Fig. 6.
5. Pull downwards and outwardston the bottom of the grille and gently raise the frame of
the top of the unit.
3. Remove the two screws from the control box cover
and take off the cover. See Fig.
7. Save the screws to reassemble.
6 . Once all covers are off, mount the unit onto the wall
mounting bracket. See Fig. 8.
NOTE: Leave covers off until after the Making Drainage Connections section.
7 . Route the interconnecting units electric cable and the
Make sure that all wires and screws are firmly fastened. Loose wires or connections can cause damage and present a fire hazard.
1.Strip the cables back1/4 inch.
8. Make sure that the wires are connected in accordance with the wiring diagram on the inside of the unit front
cover or within this instruction manual.
9. Secure the control cables to the strain relief.
10. For heat pump systems only, connect the outdoor sensor
TH3 to its mating black terminal. See Fig.
9.
NOTE: In general wiring the indoor unit does not require the removal of the grille frame but in case of need do as follow:
4. Remove the two screws from the air discharge opening. Save the screws to reassemble. See Fig. 7A.
1. Connect the display connector to the display panel printed circuit board.
Fig. 6  Remove Grille Insert
Fig. 7  Remove Control Cover
Mount the indoor unit on the mounting bracket
Gently push with
the arrow direction
1
2
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
Fig. 7A---Remove the screws from the air discharge opening.
6
CONNECT REFRIGERANT LINES  Connect the ends of the refrigerant lines to their appropriate fittings, following these guidelines:
To connect the refrigerant lines use only L type sealed, dehydrated copper refrigerant tubing. No other type of tubing may be used. Use of other types of tubing will void the manu­facturers warranty.
Do not open service valves or remove protective caps from tubing ends until all the connections are made.
Take care to avoid kinks or flattening of the tubing.
Bend tubing with special bending tools to avoid the forma­tion of sharp bends.
Keep the tubing free of dirt, sand, moisture and other con­taminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation of oil traps.
Insulate both refrigerant lines separately with
3
/8-in. walled thermal pipe insulation. Inserting the tubing into the insulation before making the connections can save time and improve in­sulation. The suction and mixed phase lines should never come in direct contact.
ATTACH THE REMOTE CONTROLLER RACK
1. Use the two screws supplied with the controller to attach the rack to the wall in the location selected by the custom­er (see Fig. 10 ).
2. Install batteries in the remote control.
3. Place remote control into remote control rack.
4. For remote control operation, refer to the unit Owners Manual.
Outdoor Unit Installation
NOTE: The outdoor unit must be installed on a solid surface (mounting base).
1. Place the rubber absorption cushions (supplied with the outdoor unit) under the units feets to prevent vibrations.
2. Fasten the outdoor unit legs to the mounting base, as shown in Fig. 12. The cushion goes between the legs and the mounting base.
3.Be sure that the unit is leveled.
MAKE REFRIGERANT PIPING CONNECTIONS (OUT­DOOR UNIT)  To connect the refrigerant lines:
Use only L type sealed, dehydrated copper refrigerant tubing. No other type of tubing may be used. Use of other types of tubing will void the manufacturers warranty.
Do not open service valves or remove protective caps from tubing ends until all the connections are made.
Bend tubing with special bending tools to avoid the forma­tion of sharp bends. Take care to avoid kinks or flattening of the tubing.
Keep the tubing free of dirt, sand, moisture, and other con­taminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation of oil traps.
Insulate each tube with
3
/8-in. walled thermal pipe insula­tion. Inserting the tubing into the insulation before making the connections will save time and improve installation
The suction and mixed-phase lines should never come in direct contact.
Fig. 10  Attach Rack to the Wall
POWER SUPPLY
TERMINAL BLOCK
HIGH/LOW
VOLTAGE METAL
BARRIER
TH3 (HEAT PUMP ONLY)
METAL
CONDUIT
CONNECTION
PLATE
POWER SUPPLY CABLE
INTER UNIT CABLE
4 ABSORPTION CUSHION TO
BE PUT UNDER EACH
INTER UNIT
TERMINAL BLOCK
Fig. 11 Wall Mounted Unit - RTX
(OPTIONAL)
SENSOR
FEET
NADA001TW
L2 L1 280-230 VAC
1
2
3
4
5
24 VAC
FAN (H)
FAN (L)
R.V.S
COMP.
COMMON
L2 L1 208-230 VAC
1
2
3
4
5
6
24 VAC
FAN (H)
FAN (L)
R.V.S
COMP.
COMMON
1
2
3
4
5
24 VAC
FAN (H)
FAN (L)
R.V.S
COMP.
COMMON
REMOTE CONTROL
REMOTE CONTROL RACK
TURBO-JET
ECONOMY
Models: DFC2A/H 12, 18
Fig. 12 --- Legs Mounting Base and Wiring
Outdoor Units
7
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
FILTER
IR
RECEIVER
POWER/AIRCOND.
TIMER
INDOOR UNIT 09,12,18
PRESSURE
COMPRESSOR
IMPEDANCE
AUTO OFF REMOTE
FUSE
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
POWER/AIRCOND.TIMER
IR RECEIVERFILTER
1
2
3
4
5
6
7
8
9
HI speed
Comp RV S
Med speed
Low speed
Neutral
Contact
S(3ph)
T(3ph)
p.
Plastic Cover
L2
L1
115 V
AC
1
2
3 4
5
30 VDC
FA
N
RV
S
C
O
M
P
(+
3
0
V
)
DC RTN
6
TH1 TH2 TH3
*
1
2
3
4
5
6
FLARING AND CONNECTING REFRIGERANT LINES
1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the tubing and cut to the required length. Be sure that the cut is perpendicular and clean, without burrs.
3. Slip the flare nut on the tubing and flare the tube end using standard flaring tools.
4. Tighten the nut until resistance is met. Mark the nut and the fitting. Using a suitable wrench tighten an additional
1
/
4
turn. Use the following specified torque, according to
connection size:
Mixed-Phase line: Suction line:
1
/
4
-in.  (12.3 ft-lb)
1
/
2
-in.  (36 ft-lb)
3
/
8
-in.  (29 ft-lb)
5
/
8
-in.  (47 ft-lb)
NOTE: The service valves on the outdoor unit must remain closed until all 4 connections have been made.
EVACUATE TUBING AND CHARGE THE SYSTEM  When all the fittings are connected, air must be expelled, then refrigerant charge must be checked and adjusted. Follow the steps below.
1. Open the service port cap on the suction line valve (large valve).
2. Connect the vacuum pump to the service port via the pressure gage and evacuate to 500 microns to eliminate contamination and moisture.
3.Disconnect the vacuum pump. Unit should maintain 500 microns for 5 minutes.
5. Open the mixed-phase valve (small valve) with an Allen
wrench.
6. Open the suction line valve (large valve) with an Allen
wrench.
7. The outdoor unit is supplied with sufficient R-22 refriger-
an
t up to 25 ft piping length. Add 0.9 oz of refrigerant for
each additional 3 ft of tubing used.
8. Make sure that the valves are properly opened. Be careful not to open them more than required as this may damage the thread.
9. Replace the service port cap. Using refrigerant oil, lubri­cate the cap beam and hand tighten until resistance is met. Use a suitable wrench to tighten the cap by an additional
1
/
2
turn.
Power Supply 
See Tables 4 and 5 for electrical data
and Fig. 13-16 for system wiring diagrams.
Leak Test 
Leak test all fittings with appropriate test
equipment.
Model DFC2A/H 09
Fig. 12A --- Legs Mounting Base and Wiring
Outdoor Units
4. Remove the service port caps from the mixed-phase
valve and suction line valve
Fig. 12B --- Indoor unit Leds and Wiring
8
Table 4 — Electrical Data, Indoor Units — 115, 208/230-1-60
LEGEND
*If indoor unit is powered from outdoor terminal block, the MOCP for
the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice.
.
Table 5 — Electrical Data, Outdoor Units — 115, 208/230-1-60
LEGEND
*If indoor unit is powered from outdoor terminal block, the MOCP for
the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice.
UNIT MCA* MOCP* FULL LOAD AMPS FAN MOTOR AMPS
COMPRESSOR
AMPS
COMPRESSOR
LOCKED ROTOR
AMPS
DFF2A/DFF2H 09,12 0.1 10 1.8 1.2 NA
DFF2A/DFF2H 18 0.1 10 2.4 2.0 NA
MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
UNIT MCA* MOCP* FULL LOAD AMPS FAN MOTOR AMPS
COMPRESSOR
AMPS
COMPRESSOR
LOCKED ROTOR
AMPS
DFC2A/DFC2H 09,12 10 20 8 1 6 42, 58 DFC2A/DFC2H 18 10 20 8 1 6 42
MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
Fig. 13 Heat Pump System Wiring Schematic DFF2A/DFF2H 09 Fan Coil with
DFC2A/DFC2H 09 Condensing Unit
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal ther
mal
overloads.
9
TB 1
G
R
/
Y
E
L
OUTDOOR UNITINDOOR UNIT
B
L
K
W
H
T
HLTV
BLK
* BLUE
*BR
GR/YEL
FAN
J1
K4
K3
K2
K1
DC RTN
FAN
FUSE 6A
L1
L2
W
H
T
FAN
MOTOR
*
B
R
*
B
L
U
E
*
G
R
/
Y
E
L
0
Mains AC Supply
~
TH3
RVS
BLK
RVS
B
R
N
FC
TH2
**BLK
**WH
**YEL
**GREEN
COMP 1
CC
COMP.
*
B
R
*
B
L
U
E
*
B
L
K
*
B
R
C
S
R
PH-AC
COMP 1
30VDC
Power Supply
*OR
0
B
L
U
E
~ BR
*** GR/YEL
GREEN
GREEN
***GREEN
DC RTN
+30 VDC
HLTV
RVS
FAN
**RED
2
5 1974
B
L
K
Y
E
L
/
G
R
W
H
B
R
N
O
R
7130C
J12
J6 J7
J8
FAN
RVS
COMP.
BLK
J18
RED
K6
K5
K1
K2
STEPPER
MOTOR
BLUE
+30V WH
K8
K9
K7
J11
FANH
FAN T
FAN L
J14
BLK
RED
1
3
+12V
-12V
BLK
WH
RED
GREEN
BLDC
MOTOR
J1
J5
1
3
J3
12345
J4
12345
6
TH1
TAC 670 control
TAC 671 Main Board
TAC 672
Motor Control
TAC 673
Relay Board
M
R
E
D
132
YEL
GR/YEL
AC
IN
DC Out (+)
BLK
***RED
1
5
4
6
2
Y
E
L
V
S
P
23465
TB
DC RTN (-)
DC
RTN
~
0
DC
Out
TB
W
H
T
+
1
2
V
D
C
R
E
D
1
2
3
4
5
5
4
3
H.L.T.V
1
OR
COMP 1
**OR
RVS
HLTV
BLK
BLK
1
2
3
456
GRD
TH3
GRD
GRD
Model 09 Wiring Diagram
*** -16 AWG
** -14 AWG
*-12AWG
ALL OTHER WIRES 18 AWG
-Splice
-Terminal (Unmarked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
CC -Compressor Capacitor
COMP-Compressor
FC -Fan Capacitor
GRD -Ground
RVS -Reversing Valve Solenoid
HLTV -Heating Low Temp. Valve
TB -Terminal Block
TH -Thermistor
LEGEND
TH3
TB
GRD
Fig. 14 Heat Pump System Wiring Schematic
DFF2A/DFF2H 12,18
Fan Coil with DFC2A/DFC2H 12,18 Condensing Unit
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal ther
mal
overloads.
10
7137D
TB 1
G
R
/
Y
E
L
OUTDOOR UNITINDOOR UNIT
B
L
K
W
H
T
HLTV
BLK
*BLUE
*BR
GR/YEL
FAN
J1
K4
K3
K2
K1
DC RTN
FAN
FUSE 6A
L1
L2
W
H
T
FAN
MOTOR
*
B
R
*
B
L
U
E
*
G
R
/
Y
E
L
0
Mains AC Supply
~
TH3
RVS
BLK
RVS
B
R
N
FC
TH2
**BLK
**WH
**YEL
**GREEN
TH3
COMP 1
TB
CC
COMP.
*
B
R
*
B
L
U
E
*
B
L
K
*
B
R
C
S
R
PH-AC
COMP 1
30VDC
Power Supply
*OR
0
B
L
U
E
~ BR
*** GR/YEL
GREEN
GREEN
***GREEN
DC RTN
+30 VDC
HLTV
RVS
FAN
**RED
1
6
5432
B
L
K
Y
E
L
/
G
R
W
H
B
R
N
J12
J6 J7
J8
FAN
RVS
COMP.
BLK
J18
RED
K6
K5
K1
K2
STEPPER
MOTOR
BLUE
+30V WH
K8
K9
K7
J11
FANH
FAN T
FAN L
J14
BLK
RED
1
3
+12V
-12V
BLK
WH
RED
GREEN
BLDC
MOTOR
J1
J5
1
3
J3
12345
J4
12345
6
TH1
TAC 670 control
TAC 671 Main Board
TAC 672
Motor Control
TAC 673
Relay Board
M
R
E
D
+
3
0
V
D
C
B
L
K
D
C
R
T
N
132
YEL
GR/YEL
AC
IN
DC Out (+)
BLK
***RED
1
5
4
6
2
Y
E
L
V
S
P
23465
TB
DC RTN (-)
DC
RTN
~
0
DC
Out
TB
W
H
T
+
1
2
V
D
C
R
E
D
1
2
3
4
5
1
2
3
4
5
5
4
3
H.L.T.V
1
OR
COMP 1
**OR
RVS
HLTV
BLK
BLK
6
*** -16 AWG
** -14 AWG
*-12AWG
ALL OTHER WIRES 18 AWG
-Splice
-Terminal (Unmarked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
CC -Compressor Capacitor
COMP-Compressor
FC -Fan Capacitor
GRD -Ground
RVS -Reversing Valve Solenoid
HLTV -Heating Low Temp. Valve
TB -Terminal Block
TH -Thermistor
GRD
GRD
TH3
LEGEND
Models 12 / 18 Wiring Diagram
GRD
11
START-UP
System Checks
1. Conceal the tubing where possible.
2. Make sure that the drainage tube slopes downward along its entire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall.
5. Seal the hole through which the cables and tubing pass.
6. Connect the air conditioner to the power source and turn it on.
7. Check all air conditioner operating modes. Refer to Owners Manual for operating details.
INDOOR UNIT
1. Do all the remote controller buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drainage work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
2. Is noise, drain water or airflow from the unit likely to disturb the neighbors?
3. Are there any gas leaks?
EXPLAIN THE FOLLOWING ITEMS TO THE CUSTOMER, WITH THE AID OF THE OWNERS MANUAL:
1. How to turn the air conditioner on and off; selecting cool­ing, heating and other operating modes; setting a desired temperature; setting the timer to automatically start and stop air conditioner operation; and the other features of the remote controller and display panel.
2. How to remove and clean the air filter.
3. How to set the air deflection louver.
4. Explain care and maintenance.
5.Present the Owners Manual and installation instructions to the customer.
CARE AND MAINTENANCE
The following may be performed by the equipment owner.
Outdoor Units
CLEANING COILS  Coil should be washed out with water or blown out with compressed air. Clean coil annually or as required by location and outdoor air conditions. Inspect coil monthly and clean as required. Fins are not continuous through coil sections. Dirt and debris may pass through first section, become trapped between the row of fins and restrict outdoor unit airflow. Use a flashlight to determine if dirt or debris has collected between coil sections.
Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Using a garden hose or other suitable equipment, flush coil from the outside to remove dirt. Be sure to flush all dirt and debris from drain holes in base of unit. Fan motors are waterproof.
Indoor Units
To Clean the Indoor Unit Front Panel 
If the front panel of the unit becomes dirty or smudged, wipe the out­side of the panel with a soft dry cloth. Use a mild liquid deter­gent and wipe off carefully with a dry cloth.
To Clean Indoor Coil  To clean the coil, remove
indoor unit front panel and vacuum the coil fins, using care not to bend or damage fins.
LUBRICATION  The indoor-fan, automatic air sweep, and the outdoor-fan motors are factory lubricated and require no oiling.
Air Filters for Indoor Units
TO REMOVE AIR FILTERS 
Open the unit's front panel by lifting the lower part and pulling
TO CLEAN OR REPLACE FILTERS  Filters can be vac­uumed or washed in warm water. Shake filter to remove any excess water, and replace it back. If the filter has begun to break down or is torn, replace it. Replacement filters are available through a local dealer.
SERVICE
The following should be performed by a qualified service technician.
Clean Condensate Drains  Clean all drains and
drain pans at the start of each cooling season. Check the flow by pouring water into the drain.
Clean or Replace Drain Pan  The drain pan
should only be cleaned or replaced by a qualified service technician.
1. Place a plastic sheet on the floor to catch any water that may spill from the drain pan.
2. Remove the intake grille and distribution assembly.
3. Remove the condensate water in the drain pan by letting water drain into a 3-gallon bucket.
Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electric shock or injury from rotating fan blade.
To avoid the possibility of electric shock, before performing any cleaning and maintenance operations, always turn off power to the system by pressing the ON/OFF button
on the remote control and turn off the separate disconnect
switch located near the unit.
If the indoor unit is on a separate switch, be sure to turn this
disconnect off as well.
Do not wash filter in water over 120 F (to avoid shrinkage). Do not expose filter to fire (to avoid fire damage). Do not expose filter to direct sunlight. Clean filter more frequently when air is extremely dirty.
Do not attempt to clean or service components in control box.
Operating your system with dirty air filters may damage the indoor unit and, in addition, can cause reduced perfor­mance, intermittent system operation, frost build up on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly.
it gently outward and upward. Pull out the filters.
12
TROUBLESHOOTING (Tables 6-8, and Fig. 17)
Table 6  Service Indicators
Be sure to check for broken wires or loose cable lugs before troubleshooting system.
LAMP STATUS INDICATION CORRECTION ACTION
1 Flash Faulty TH1 Sensor
Check the TH1 thermistor for correct resistance. Check for proper connection. Replace thermistor if necessary.
2 Flashes Faulty TH2 Sensor Check the TH2 thermistor for correct resistance.
Check for proper connection. Replace thermistor if necessary.
3 Flashes Low Pressure Check system pressures.
Check refrigerant charge. Check thermistors (TH1 and TH2) for correct resistance.
4 Flashes High Pressure Check system pressures.
Check refrigerant charge. Check thermistors (TH1 and TH2) for correct resistance.
5 Flashes Low Voltage Check operating voltage.
Check electrical connections.
6 Flashes High Voltage Check operating voltage.
Check electrical connections.
V
AC
CLEAN FILTER INDICATOR. FLASHES AFTER 250 HOURS OF OPERATION
OPERATION LED. INDICATES ERROR
POWER LED. OFF WHEN SYSTEM IS OPERATING AND FLASHES WHEN SYSTEM IS IN ERROR. (DOES NOT INDICATE ERROR CODE)
Fig. 17  Indicator Lights
13
Table 7
DFS2A/DFS2H Thermistor TH-1, TH-2, and TH-3 Temperature to Resistance Conversion
NOTE: Resistance tolerance ± 3%.
TEMPEATURE
(0F)
TEMPERATURE
(0C)
TEMPERATURE
TOLERANCE
(0F)
TEMPERATURE
TOLERANCE
(0C)
MINIMUM
RESISTANCE
(K )
MEAN
RESISTANCE
(K )
MAXIMUM
RESISTANCE
(K )
4.0 20 ±2.0 ±1.1 30.89 32.44 34.05 2.2 19 ±2.0 ±1.1 29.46 30.93 32.45 0.4 18 ±2.0 ±1.1 28.12 29.51 30.94
1.4 17 ±2.0 ±1.1 26.84 28.16 29.51
3.2 16 ±2.0 ±1.1 25.64 26.88 28.15
5.0 15 ±2.0 ±1.1 24.49 25.66 26.87
6.8 14 ±2.0 ±1.1 23.40 24.52 25.66
8.6 13 ±2.0 ±1.1 22.38 23.43 24.50
10.4 12 ±2.0 ±1.1 21.40 22.39 23.41
12.2 11 ±2.0 ±1.1 20.47 21.41 22.38
14.0 10 ±1.8 ±1.0 19.59 20.48 21.40
15.8 9 ±1.8 ±1.0 18.74 19.59 20.45
17.6 8 ±1.8 ±1.0 17.94 18.74 19.56
19.4 7 ±1.8 ±1.0 17.17 17.93 18.71
21.2 6 ±1.8 ±1.0 16.44 17.16 17.90
23.0 5 ±1.8 ±1.0 15.75 16.43 17.13
24.8 4 ±1.8 ±1.0 15.10 15.74 16.40
26.6 3 ±1.8 ±1.0 14.47 15.08 15.71
28.4 2 ±1.8 ±1.0 13.87 14.46 15.05
30.2 1 ±1.8 ±1.0 13.31 13.86 14.42
32.0 0 ±1.8 ±1.0 12.77 13.29 13.83
33.8 1 ±1.8 ±1.0 12.25 12.74 13.25
35.6 2 ±1.8 ±1.0 11.75 12.22 12.70
37.4 3 ±1.8 ±1.0 11.28 11.73 12.18
39.2 4 ±1.8 ±1.0 10.83 11.25 11.68
41.0 5 ±1.8 ±1.0 10.40 10.80 11.21
42.8 6 ±1.8 ±1.0 9.986 10.370 10.76
44.6 7 ±1.8 ±1.0 9.595 9.960 10.33
46.4 8 ±1.8 ±1.0 9.222 9.569 9.921
48.2 9 ±1.8 ±1.0 8.866 9.196 9.530
50.0 10 ±1.8 ±1.0 8.526 8.840 9.157
51.8 11 ±1.8 ±1.0 8.197 8.496 8.797
53.6 12 ±1.8 ±1.0 7.883 8.167 8.453
55.4 13 ±1.6 ±0.9 7.583 7.853 8.125
57.2 14 ±1.6 ±0.9 7.296 7.553 7.812
59.0 15 ±1.6 ±0.9 7.022 7.267 7.513
60.8 16 ±1.6 ±0.9 6.761 6.993 7.227
62.6 17 ±1.6 ±0.9 6.510 6.731 6.954
64.4 18 ±1.6 ±0.9 6.271 6.481 6.693
66.2 19 ±1.6 ±0.9 6.042 6.242 6.444
68.0 20 ±1.6 ±0.9 5.822 6.013 6.205
69.8 21 ±1.6 ±0.9 5.611 5.793 5.975
71.6 22 ±1.6 ±0.9 5.408 5.581 5.755
73.4 23 ±1.6 ±0.9 5.214 5.379 5.544
75.2 24 ±1.6 ±0.9 5.028 5.185 5.343
77.0 25 ±1.6 ±0.9 4.850 5.000 5.150
78.8 26 ±1.6 ±0.9 4.675 4.821 4.968
80.6 27 ±1.6 ±0.9 4.508 4.650 4.793
82.4 28 ±1.6 ±0.9 4.347 4.486 4.626
84.2 29 ±1.8 ±1.0 4.193 4.329 4.466
86.0 30 ±1.8 ±1.0 4.046 4.179 4.312
87.8 31 ±1.8 ±1.0 3.904 4.033 4.163
89.6 32 ±1.8 ±1.0 3.767 3.894 4.020
91.4 33 ±1.8 ±1.0 3.637 3.760 3.884
93.2 34 ±1.8 ±1.0 3.511 3.631 3.752
95.0 35 ±1.8 ±1.0 3.391 3.508 3.626
96.8 36 ±2.0 ±1.1 3.275 3.390 3.505
98.6 37 ±2.0 ±1.1 3.164 3.276 3.389
Table 7
DFS2A/DFS2H Thermistor TH-1, TH-2, and TH-3 Temperature to Resistance Conversion (cont)
NOTE: Resistance tolerance ± 3%.
TEMPEATURE
(0F)
TEMPERATURE
(0C)
TEMPERATURE
TOLERANCE
(0F)
TEMPERATURE
TOLERANCE
(0C)
MINIMUM
RESISTANCE
(K )
MEAN
RESISTANCE
(K )
MAXIMUM
RESISTANCE
(K )
100.4 38 ±2.0 ±1.1 3.058 3.167 3.277
102.2 39 ±2.0 ±1.1 2.956 3.062 3.169
104.0 40 ±2.0 ±1.1 2.857 2.961 3.066
105.8 41 ±2.0 ±1.1 2.762 2.864 2.966
107.6 42 ±2.0 ±1.1 2.671 2.770 2.870
109.4 43 ±2.2 ±1.2 2.583 2.679 2.777
111.2 44 ±2.2 ±1.2 2.498 2.593 2.688
113.0 45 ±2.2 ±1.2 2.417 2.509 2.602
114.8 46 ±2.2 ±1.2 2.339 2.429 2.520
116.6 47 ±2.2 ±1.2 2.264 2.352 2.441
118.4 48 ±2.3 ±1.3 2.192 2.227 2.364
120.2 49 ±2.3 ±1.3 2.122 2.206 2.291
122.0 50 ±2.3 ±1.3 2.055 2.137 2.220
123.8 51 ±2.3 ±1.3 1.990 2.070 2.151
125.6 52 ±2.3 ±1.3 1.928 2.006 2.085
127.4 53 ±2.3 ±1.3 1.867 1.943 2.021
129.2 54 ±2.3 ±1.3 1.809 1.883 1.959
131.0 55 ±2.5 ±1.4 1.753 1.826 1.900
132.8 56 ±2.5 ±1.4 1.699 1.770 1.842
134.6 57 ±2.5 ±1.4 1.647 1.717 1.787
136.4 58 ±2.5 ±1.4 1.597 1.665 1.734
138.2 59 ±2.5 ±1.4 1.549 1.615 1.683
140.0 60 ±2.5 ±1.4 1.503 1.567 1.633
141.8 61 ±2.7 ±1.5 1.458 1.521 1.585
143.6 62 ±2.7 ±1.5 1.414 1.476 1.539
145.4 63 ±2.7 ±1.5 1.372 1.432 1.494
147.2 64 ±2.7 ±1.5 1.332 1.391 1.451
149.0 65 ±2.7 ±1.5 1.293 1.350 1.409
150.8 66 ±2.9 ±1.6 1.255 1.311 1.369
152.6 67 ±2.9 ±1.6 1.219 1.274 1.330
154.4 68 ±2.9 ±1.6 1.184 1.237 1.292
156.2 69 ±2.9 ±1.6 1.150 1.202 1.256
158.0 70 ±2.9 ±1.6 1.117 1.168 1.221
14
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Copyright 2006 ICP International Comfort Products
Table 8  General System Troubleshooting Guide
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
Unit Fails to Start.
Power supply to unit not connected (POWER LED Off).
Check for proper connection of power at disconnect.
Fuse blown (POWER LED Off). Reset circuit breaker or replace line fuse. ON/SEND button has not been pressed. Press ON/SEND button on remote control. Indoor unit does not receive transmitted
commands.
Make sure that nothing is blocking the remote control transmission to the unit.
Only Indoor Fan Works when Cooling or Heating is Desired.
NOTE: Indoor fan runs continuously in cooling mode.
The selected mode is Fan Only, or Cool when heating is desired.
Check if the remote control is in the desired mode. If not, select the correct mode (refer to User manual). Also note that every 15 minutes (maximum) the com­pressor will be switched minimally on for 3 minutes.
Temperature is set to a value which is too high (in Cool mode).
Observe the temperature setting on the remote control. Also note that each 15 minutes (maximum), the com­pressor will be switched on minimally for 3 minutes.
Only Indoor Fan Motor and Outdoor Fan Motor are Working. No Cooling and/or Heating Takes Place.
Overload safety device on compressor is cut out due to high temperature.
Switch off power and try again after one hour.
Compressor run capacitor is burnt. Replace compressor run capacitor. Compressor winding shorted. Replace compressor.
No Air Supply at Indoor Unit (Compressor Operates).
Indoor fan motor is blocked or turns slowly. 1. Check voltage. Repair wiring if necessary.
2. Check indoor fan wheel if tight on motor shaft. Tighten if necessary.
Indoor fan motor capacitor is burnt. Replace indoor fan motor capacitor. Indoor fan motor winding is burnt. Replace indoor fan motor. In Heat mode: Delayed start for indoor fan motor. Normal software delay (maximum of 20 sec). Clogged air filters. Clean filters.
Low Capacity. Lack of refrigerant. Ice formation on the evapora-
tor coil.
Unit must be charged (according to the nameplate) after localizing the gas leak.
Clogged air filters. Clean filters.
In Heat Mode, Only Compressor Runs. Outdoor and Indoor Fan Motors are Stopped.
A/C operating in defrost cycle. Wait 10 minutes (maximum) until the unit resumes
normal operation.
Water Accumulates and Overflows from Evaporator Drain Pan.
Drain pan pipe or hose is clogged or the spout of drain pan is clogged.
Disassemble plastic drain pipe from spout of evapora­tor drain pan. Flush with clean water.
Unit Does Not Operate in Desired Mode.
The unit is in the Auto. (emergency) mode. Push button once to cancel Auto. (emergency) mode. Faulty remote control settings. 1. If remote control symbols respond to the commands
correctly, check the unit ID Code (Standard or Alter­native). Refer to Changing Unit ID Code in the
Owner's Manual.
2. If Cool commands are OK, but Heat symbol is skipped on LCD, refer to setting the remote to cooling only
or heat pump on the Owner's Manual.
3. Replace remote control.
Remote control low battery. Replace remote control batteries.
The Unit Receives Interference from Other Remote Control or the Remote Control Interferes with Other Instruments.
Common Infrared Code. Modify the Remote Control IR transmission code.
Refer to Changing Unit ID Code in the Owners Manual.
Power supply from outdoor unit to indoor unit is not connected.
Printed in Israel Pg 15
Loading...