ICP DFS2A309J1A, DFS2A312J1A, DFS2H312J1A, DFS2H309J1A, DFS2A318K1A Installation, Start-up And Service Instructions Manual

...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc
Printed in Israel Pg 1
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Indoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . .6
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Leak Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
System Checks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
CARE AND MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . .11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Indoor Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
To Clean the Indoor Unit Front Panel . . . . . . . . . . . . . . .11
To Clean Indoor Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
. . . . . . . . . . . . . . . . . . . . . . . . . .11
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .12-15
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
GENERAL
System Requirements
 Consult local building codes and National Electrical
Code (NEC, U.S.A.) for special installation requirements.
 Use only type G or C fuses.  Use single length power cable without extension.  Allow sufficient space for airflow clearance on condens-
ing units for wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2 for minimum required distances between unit and walls or ceilings.
 Indoor and outdoor units should be installed at a
Maximum line length of 50 ft, and vertical separation of 30 ft.
 Do not install indoor units near a direct source of heat
such as direct sunlight, steam or flame.
Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect. There may be more than one disconnect switch. Electrical shock can cause personal injury.
IMPORTANT: The Indoor unit & the inter units cable voltage
is 30 VDC
IMPORTANT: Each refrigerant line must be insulated separately. See line sizing requirements in table 2.
Do not bury more than 36 in. of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refriger­ant slugging and could possibly damage the compressor at start-up.
DFS2A/H 09,12,18
Duct Free Systems
Fig. 1B  Outdoor Unit Clearances
Fig. 1A  Outdoor Unit Clearances
These instructions cover the installation, start-up and servicing of
DFC2A/DFC2H outdoor and DFF2A/DFF2H indoor units
cooling only and heat pump duct free systems. See Table 1 for parts included. See Tables 2 and 3 for Physical Data.
51302618915 0106
TOP (min.)
2 (0.6m)
LEFT (min.)
6 (0.15m)
RIGHT (min.)
2 (0.6m)
FRONT (min.)
2 (0.6m)
REAR (min.)
6 (0.15m)
Max. cable length
. Total voltage drop should not exceed 1V. Therefore max. length: For #18 AWG 24.3 Feet (7.4 m)
For #16 AWG 37.7 Feet (11.5 m) For #14 AWG 50.0 Feet (18 m)
Outdoor Units . . . .
Outdoor Unit Installation . . .
Air Filters for Indoor Units
LEFT(min.)
6 (0.15m)
TOP(min.)
2 (0.6m)
REAR(min.)
6 (0.15m)
RIGHT(min.)
2 (0.6m)
FRONT(min.)
2 (0.6m)
Cooling Model Heat Pump
DFS2A309J1ADFS2H309J1A DFS2A312J1A DFS2H312J1A DFS2A318K1ADFS2H318K1A
421 01 9217 00
2
Table 1  Parts List  High Wall Units
ITEM QTY DIAGRAM
Mounting Bracket 1
DFF2A/DFF2H 09, 12 or DFF2A/DFF2H 18
Long Screws 8
Outdoor Sensor
Connecting Cable
1
Absorption Cushions 4
Electric Terminals 8
Remote Controller Rack 1 rack with 2 screws
Remote Controller
and Batteries
1
1
Owners Manual 1
1
(Available for HEAT PUMP ONLY)
(OPTIONAL)
(Not included)
Insulation for indoor Fittings
Wall mounted Receiver RTX
NADA001TW
TURBO-JET
ECONOMY
3
Table 2  Physical Data  Cooling Only
LEGEND
*Units are shipped with a factory charge based on 25 ft of refrigerant lines.
Table 3  Physical Data  Heat Pump
LEGEND
*Units are shipped with a factory charge based on 25 ft of refrigerant lines. NOTE: Standard Ambient Operating Limitations  55
ºF to 125 ºF (12.7 ºC to 51.6 ºC).
INDOOR UNIT
DFF2AH09J1A DFF2AH12J1A DFF2AH18J1A
COOLING CAPACITY (Btuh)
SEER
SYSTEM CHARGE (lb)* 2.7 3.1 4.1 MOISTURE REMOVAL (pt/hr) AIRFLOW
High Cfm 350 400 670
DIMENSIONS L x H x W (in.) 32 3/32 x 10 15/64 x 7 9/32 32 3/32 x 10 15/64 x 7 9/32 42 1/2 x 11 5/8 x 7 9/32
NET WEIGHT (lb) 19.0 19.0 27.5
OUTDOOR UNIT
DFC2A309J1A DFC2A312J1A DFC2A318K1A
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft)
30/30/50 30/30/50 30/30/50
NOMINAL LINE SIZING
Mixed Phase...Suction (in.)
DIMENSIONS L x H x W (in.) 28 3/4 X 21 1/4 X 10 7/16 35 7/16 X 25 3/16 X 12 9/32 43 5/16 X 25 3/16 X 15 3/4
NET WEIGHT (lb) 73 114 136
SEER  Seasonal Energy Efficiency Ratio
COOLING CAPACITY (Btuh) 9,000 11,600 19,000
SEER 13.0 13.0 13.0
HEATING CAPACITY (Btuh) 8,600 11,800 18,300
HSPF 7.7 7.7 7.7
SYSTEM CHARGE* (lb) 2.7 3.1 4.1
MOISTURE REMOVAL (pt/hr)
AIRFLOW
High Cfm
350 400 670
DIMENSIONS L x H x W (in.)
NET WEIGHT (lb)
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft)
NOMINAL LINE SIZING
Mixed Phase...Suction (in.)
DIMENSIONS L x H x W (in.)
SHIPPING WEIGHT (lb)
HSPF  Heating Seasonal Performance Factor SEER  Seasonal Energy Efficiency Ratio
9,000
11,600
19,000
13 13 13
3
/8...5/
8
1
/4...1/
2
1
/4...1/
2
32 3/32 x 10 15/64 x 7 9/32 32 3/32 x 10 15/64 x 7 9/32 42 1/2 x 11 5/8 x 7 9/32
19.0 19.0 27.5
30/30/50 30/30/50 30/30/50
28 3/4 X 21 1/4 X 10 7/16 35 7/16 X 25 3/16 X 12 9/32 43 5/16 X 25 3/16 X 15 3/4
73 114 136
3
/8...5/
8
1
/4...1/
2
1
/4...1/
2
2.6 4.5 5.3
2.6 4.5 5.3
INDOOR UNIT DFF2HH09J1A DFF2HH12J1A DFF2HH18J1A
OUTDOOR UNIT DFC2H309J1A DFC2H312J1A DFC2H318K1A
4
INSTALLATION
Plan the installation carefully to avoid component failures
and make installation easier.
Indoor Unit Installation
REFRIGERANT LINE ROUTING  The refrigerant lines may be routed in any of the four directions shown in Fig. 3.
INSTALL THE MOUNTING BRACKET
1. Carefully remove the mounting bracket, which is connected to the back of the indoor units base with
screws.
2. Position the mounting bracket on the wall and level it using a spirit level (see Fig. 2 for minimum required clearance distances).
3. Mark the four drilling holes on the wall, as they appear in Fig. 4.
4. Drill the holes, insert the wall plugs and use four long screws to attach the mounting bracket to the wall.
5. Check that the bracket is leveled and securely fastened to the wall.
DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER-UNIT CONNECTIONS  To make the connections between the indoor and outdoor units, drill a 3-in. hole through the wall for the refrigerant lines, drainage hose and control cable passage as shown in Fig. 5.
1. Mark the center of the hole to be drilled according to the re­frigerant line routing used and dimensions shown in Fig. 4.
2. Make sure to drill outwards and downwards, so that the opening in the outside wall is at least
1
/2-in. lower than
the opening on the inside.
3. Make sure the drainage hose is at the bottom side of the hole.
4 . If refrigerant line route no. 1, 2 or 4 are used, use a small
saw blade to carefully remove the corresponding plastic covering on the side panel.
5. Run the outdoor sensor cable, electrical cable, refrigerant lines, and drainage tube through the hole.
6. Fill the remaining wall hole gap with an appropriate sealant material.
Fig. 2  Indoor Unit Clearances
Fig. 4 Mounting Bracket DFF2A/DFF2H 09, 12
Fig. 4 Mounting Bracket DFF2A/DFF2H 18
REFRIGERANT
LINES
DRAINAGE
TUBE
ELECTRICAL
CABLE
1/2.IN. MIN
3-IN.
INDOOR OUTDOOR
Fig. 5  Drill Holes
(Optional for HEAT PUMP SYSTEMS)
OUTDOOR SENSOR CABLE
6" (0.15m)
(1.8-2.5m)
min.
min.
min.
6'-8'3"
8"
(0.2m)
8"
(0.2m)
Fig. 3  Refrigerant Lines
4
2
3
1
35 15
2
2
1
6
18
13¾
10
5
10
3
25
2
2
09, 12
17
9
16
11
32
23
32
5
32
11
4
1
32
19
8
5
8
1
2. Put the control box cover and grille frame back on using the appropriate screws (Steps 3 and 4 of Wire the Indoor Unit section). Put the grille insert back on.
REASSEMBLE
Fig. 8  Indoor Unit Mounting
5
Fig. 9  Outdoor Sensor Connection
123456
ON
HEAT PUMP
Model-12 DIP Switches location
(on the Control Box side)
HEAT PUMP
Models-09,18 DIP Switches location
(on the Control Box side)
Inter unit cable clamp
TH1
TH2
TH3
Display
connection
Inter unit
terminal block
30 VDC
123456
ON
123456
ON
123456
ON
COOLING ONLY
Model-12 DIP Switches location
(on the Control Box side)
COOLING ONLY
Models-09,18 DIP Switches location
(on the Control Box side)
Standard Dip Switches
status from the factory
(Heat pump only)
MAKE DRAINAGE CONNECTIONS
1. Connect the unattached end of the drainage tube to the drainage hose outlet.
2. Seal the drainage connection to prevent leakage.
3. Make sure there are no kinks, U bends or flattened sections in the tube.
4. Check that the drainage functions properly. Fill the pan below the units coil with water and observe that it freely drains out.
5. Make sure the drainage hose is at the bottom side of the wall through-hole (see Fig. 5).
outdoor sensor cable towards the lower right hand corner
of the indoor unit.
WIRE THE INDOOR UNIT
2. Remove the unit's front panel by lifting the lower part
and pulling it gently outward and upward. See Fig. 6.
5. Pull downwards and outwardston the bottom of the grille and gently raise the frame of
the top of the unit.
3. Remove the two screws from the control box cover
and take off the cover. See Fig.
7. Save the screws to reassemble.
6 . Once all covers are off, mount the unit onto the wall
mounting bracket. See Fig. 8.
NOTE: Leave covers off until after the Making Drainage Connections section.
7 . Route the interconnecting units electric cable and the
Make sure that all wires and screws are firmly fastened. Loose wires or connections can cause damage and present a fire hazard.
1.Strip the cables back1/4 inch.
8. Make sure that the wires are connected in accordance with the wiring diagram on the inside of the unit front
cover or within this instruction manual.
9. Secure the control cables to the strain relief.
10. For heat pump systems only, connect the outdoor sensor
TH3 to its mating black terminal. See Fig.
9.
NOTE: In general wiring the indoor unit does not require the removal of the grille frame but in case of need do as follow:
4. Remove the two screws from the air discharge opening. Save the screws to reassemble. See Fig. 7A.
1. Connect the display connector to the display panel printed circuit board.
Fig. 6  Remove Grille Insert
Fig. 7  Remove Control Cover
Mount the indoor unit on the mounting bracket
Gently push with
the arrow direction
1
2
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
FILTER
IR
RECEIVER
POWER/AIRCOND
TIMER
Fig. 7A---Remove the screws from the air discharge opening.
Loading...
+ 10 hidden pages