ICP CSA618GKA100, CSA624GKA100, CSA630GKA100, CSA636GKA100, CSA642GKA100 Installation Guide

...
Theseinstructionsmustbereadand understoodcompletelybeforeattemptinginstallation.
IMPORTANT:Effective January 1,2015, all split system and packaged air conditioners must be installed pursuant to
applicable regional efficiency standards issued by the Department of Energy.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and
throughout this manual and other manuals that may apply to the product.
DANGER - Immediate hazards which will result in severe personal injury or death.
WARNING - Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which may result in minor personal injury or product or
property damage. NOTE - Used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
Signal Words in Manuals The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this manual in the following manner:
Signal Words on Product Labeling Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Safety Considerations ........................... 2
Installation Requirements ........................ 2
Installation ..................................... 2
Start-up Procedure ............................. 7
General Sequence of Operation .................. 8
Control Functions & Sequence of Operation ........ 8
Troubleshooting ................................ 9
Status Codes ................................. 10
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in per-
sonal injury and/or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the
OFF position. There may be more than 1 discon-
nect switch. Lock out and tag switch with a suit-
able warning label.
CUT HAZARD
Failure to follow this caution may result in per-
sonal injury Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing
and gloves when handling parts.
421 01 5104 03 02/11/15
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal
injury, or property damage. Consult a qualified installer,
service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with
the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical
Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety-alert symbol /_ When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING
signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which
would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
INSTALLATION RECOMMENDATIONS
Figure 1 _ Connecting Tube Installation
NOTE: Avoid contact between tubing and structure
THROUGH THE WALL
SUSPENSION
Outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57
m) of field-supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging
information located on control box cover and/or in the Check Charge section of this instruction.
IMPORTANT: Maximum liquid-line size is 3/8-in. OD for all residential applications including long line.
IMPORTANT: Always install the factory-supplied liquid-line filter drier. Obtain replacement filter driers from your
distributor or branch.
INSTALLATION
NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5.
When passing refrigerant tubes through the wall, seal
opening with RTV or other pliable silicon-based caulk. (See Fig. 1.)
6.
Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7.
Do not suspend refrigerant tubing from joists and studs
with a rigid wire or strap which comes in direct contact with tubing.(See Fig. 1.)
8.
Ensure that tubing insulation is pliable and completely
surrounds vapor tube.
9.
When necessary, use hanger straps which are 1 in.
(25.4 mm) wide and conform to shape of tubing insulation. (See Fig. 1.)
10.
Isolate hanger straps from insulation by using metal
sleeves bent to conform to shape of insulation.
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could result in personal
injury or equipment damage. R-410A refrigerant systems operate at higher pressures
than standard R-22 systems. Do not use R-22 service
equipment or components on R-410A refrigerant equipment.
Specifications for this unit in residential new construction market require the outdoor unit, indoor unit, refrigerant tubing
sets, metering device, and filter drier listed in presate literature. There can be no deviation.
Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate
on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit
matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through
knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout
hole location.
2 specificationssubjecttochangewithout notice. 421 01 5104 03
Forhurricanetiedowns- contactyourlocaldistributorfor
detailsandPE(ProfessionalCertification),ifrequiredbylocal authorities.
Make Piping Connections
Onrooftopapplications,mountonlevelplatformorframe.
Placeunitabovea load-bearingwallandisolateunitand
tubingsetfromstructure.Arrangesupportingmembersto adequatelysupportunitandminimizetransmissionof vibrationtobuilding.Consultlocalcodesgoverningrooftop
applications.
Roofmountedunitsexposedtowindsmayrequirewind
baffles.ConsulttheLow-Ambientpressureswitchinstallation
instructionsforwindbaffleconstruction.
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Use all service ports and open all flow-control devices, including solenoid valves.
NOTE:Unitmustbe levelto within+2° (+3/8 in./ft..) per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30 in. (762 mm)
clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance
on one side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in.
(609.6 mm) between units. Position so water, snow, or ice
from roof or eaves cannot fall directly on unit.
Figure 2 J Tie Down Knockouts
3/8-in. (9.53 mm) Dia. Tiedown Knockouts in
Basepan(2) Places
1
View From Top
UNIT BASE PAN
Dimension
31-1/2 X 31-1/2
35 X 35
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
9-1/8 (231.8) 6-9/16 (166,7) 24-11/16 (627.1) 9-1/8 (231.8) 6-9/16 (166,7) 28-7/16 (722,3)
Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55°F (12.78°C) without low ambient cooling enabled, and the
maximum outdoor operating ambient in cooling mode is
125°F (51.67°C).
Table 1 - Accessory Usage
REQUIRED FOR LOW-AMBIENT
COOLING APPLICATIONS
Accessory APPLICATIONS* (Over 80 ft. / 24.38 m)
Crankcase Heater Yes Compressor Start Assist Capacitor and Relay Yes
Evaporator Freeze Thermostat No Liquid Line Solenoid Valve See Long Line Applications Guideline
Low-ambient Pressure Switch No
Support Feet No Thermal Expansion Valve (TXV) Yes
Hard Shutoff
Winter Start Control No
For tubing line sets between 80 and 200 ft, (24.38 and 60,96 m) and/or 20 ft, (6.09 m) vertical differential, refer to Long Line Applications Guideline.
(Below 55°F / 12,8°C)
Recommended
421 01 5104 03 Specifications subject to change without notice. 3
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without
further special consideration. Do not bury lines more than
36 in. (914.4 mm).
Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade
tubing of correct size and condition. For tubing requirements beyond 80 ft/24.38 m, substantial capacity and performance
losses can occur. Following the recommendations in the Long Line Applications Guideline for Split-System Air
Conditioners and Heat Pumps will reduce these losses. Refer to Table 1 for accessory requirements. Refer to Table 2 for
field tubing diameters. There are no buried-line applications greater than 36 in.
(914.4 mm). If refrigerant tubes or indoor coil are exposed to atmosphere,
they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Outdoor Unit Connected to Factory Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier.
Check refrigerant charge for maximum efficiency.
REQUIRED FOR LONG LINE
Yes Yes
Yes
No
Yes
Yes Yes
Table 2 - Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
RATED VAPOR
up to 80 ft. (24,38 m)*LIQUID
UNIT SIZE Diameter Diameter Diameter
18, 24, 30, 3/8 3/4 3/4 36, 42, 48 3/8 7/8 7/8
60 3/8 7/8 1- 1/8
Units are rated with 25 ft. (7.6 m) of lineset. See Specification sheet for performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Long Line Applications Guideline.
Install Liquid Line Filter Drier Indoor Evacuate Refrigerant Tubing and Indoor Coil
Connection and Tube Connection Rated Tube
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Installation of filter drier in liquid line is required. Filter drier must be wrapped in a heat-sinking material such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5 in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
Figure 3 J Liquid Line Filter Drier
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. An alternate triple evacuation method may be used. See triple evacuation method in Service Manual.
IMPORTANT: Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage
capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a
system is free of air and liquid water. (See Fig. 4)
Figure 4
Deep Vacuum Graph
IN
SYSTEM
Refrigerant Tubing Connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service valves (see Table 2.) Connect and braze the 3/8" coupling
(provided with the filter drier) to the liquid service valve and
connect and braze the liquid tubing to the other end of this coupling. Use refrigerant grade tubing.
Sweat Connection
0 1 2 3 4 5 6 7
MINUTES
Final Tubing Check
VACUUM TIGHT
TOO WET TIGHT
DRY SYSTEM
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Make Electrical Connections
Service valves must be wrapped in a heat-sinking material such as a wet cloth.
Service valves are closed from factory and ready for brazing. ELECTRICAL SHOCK HAZARD After wrapping service valve with a wet cloth, braze sweat Failure to follow this warning could result in personal
connections using industry accepted methods and materials, injury or death. Consult local code requirements. Refrigerant tubing and
indoor coil are now ready for leak testing. This check should
Do not supply power to unit with compressor terminal box
include atl field and factory joints, cover removed.
4 Specifications subject to change without notice. 421 01 5104 03
Be sure field wiring complies with local and national fire,
safety, and electrical codes, and voltage to system is within
limits shown on unit rating plate. Contact local power
company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate.
Do not install unit in system where voltage may fluctuate
above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and
unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within
sight from and readily accessible from unit, per Section 440-14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend
wires from disconnect through power wiring hole provided and into unit control box.
ELECTRICALSHOCKHAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in accordance with existing electrical codes.
Connect Ground and Power Wires
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24-v/40-va minimum.
NOTE: Use of available 24-v accessories may exceed the minimum 40-va power requirement. Determine total
transformer load and increase the transformer capacity or split the load with an accessory transformer as required.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire
connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish
power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required for low-ambient cooling or if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the
Long Line Applications Guideline - Residential Split-System Air Conditioners and Heat Pumps Using R-410A Refrigerant.
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when installing.
Check OAT Thermistor and OCT Thermistor Attachments
Outdoor Air Temperature (OAT) Thermistor is factory installed by inserting the nibs on either sides of the thermistor body
through a keyhole in the bottom shelf of the control box and locking it in place by turning it 90 degrees, such that the
spherical end of a nib faces the front of the control box.
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.
Figure 5 J Line Power Connections
DISCONNECT PERN. E. C.AND/OR
LOCALCODES
FIELD POWER O
CONTACTOR
OO
FIELD GROUND
WIRING j GROUND
Connect Control Wiring
Route 24-v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 10 & Fig. 11)
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use
No. 16 AWG color-coded, insulated wire to avoid excessive voltage drop.
421 01 5104 03
®
LUG
Specifications subject to change without notice. 5
Check to make sure the OAT is locked in place. See Fig. 6.
Figure 6 J Outdoor Air Thermistor (OAT) Attachment
OAT Thermistor must be locked in place with spherical nib end facing towards
the front of the control box .................... \\\
/
/
\
\\
The Outdoor Coil Temperature (OCT) Thermistor is factory installed on the liquid tube between the coil assembly and the
liquid service valve. See Fig. 7. Check to make sure the thermistor is securely attached on
the liquid tube with the clip as shown in Fig. 7.
Loading...
+ 9 hidden pages