ICP CHS180 Installation, Start-up And Service Instructions Manual

Installation, Start--Up, and
Service Instructions
Split System Heat Pump
Save This Manual for Future Reference
Models
CHS180
506 01 2002 01
5/07/07
Split System Heat PumpsInstallation Instructions
Installation/ Startup Information
!
FIRE, AND ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Before performing service or maintenance operations on unit, turn off unit main power switch and install lockout tag.
These instructions must be read and understood completely before attempting installation.
WARNING
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the the National Electrical Code NFPA 70/ANSI C1-1999 or current edition and Canadian Electrical Code Part 1 CSA C.22.1.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instruc­tions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
After uncrating unit,inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
!
REDUCED EQUIPMENT LIFE AND PERSONAL INJURY HAZARD
mproper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
CAUTION
Safety Precautions
1. Always wear safety eye wear and work gloves when installing equipment.
2. Never assume electrical power is disconnected. Check with meter and disconnect.
3. Keep hands out of fan areas when power is connected to equipment.
4. R--22 causes frost--bite burns.
5. R--22 is toxic when burned.
Locating The Outdoor Unit:
Check local codes covering zoning, noise, platforms.
If practical, avoid locating next to fresh air intakes, vent or windows. Noise may carry into the openings and disturb people inside.
Placement of the unit should be in a well drained area or unit must be supported high enough so runoff will not enter the unit.
Do not locate where heat, lint or exhaust fumes will be discharged on unit (as from dryer vents).
Roof top installations are acceptable providing the roof will support the unit and provisions are made for water drainage and the noise or vibration through the structure.
Do not install the unit in a recessed or confined area where recirculation of discharge air may occur.
Top skid assembly should be left in place until after the unit is rigged into its final location.
2
Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit.
Split System Heat Pumps Installation Instructions
Figure 1
CHS180 UNIT DIMENSIONS and CLEARANCES
39--1/2”
76--1/2”
Unit Total Weight 1 2 3 4 CHS180 803 158 243 244 158
(365) (72) (110) (111 ) (72)
NOTE: Recommended service clearances are as follows (local codes or jurisdictions may prevail): Side (compressor) -- 3--1/2 ft. (1067 mm) Side (opposidte compressor) -- 3 ft. (914 mm) Ends -- 2 ft. (616 mm) Top -- 5 ft. (1524 mm)
Support Point
28--13/16”
18”
74--1/4”
43”
39--7/8”
36--1/16”
27--15/16”
3
Split System Heat PumpsInstallation Instructions
Rig and Mount the Unit:
!
REDUCED EQUIPMENT LIFE HAZARD
Failure to follow these precautions could result in damage to the unit being installed.
Be sure unit panels are securely in place prior to rigging.
RIGGING -- See Figure 2. These units are designed for overhead rigging. Refer to rigging label for preferred rigging method. Spreader bars are not required if top crating is left on unit. All panels must be in place when rigging. As further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal is not less than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll the unit into position, mount the unit on field--supplied rails placed lengthwise under the unit using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit. Raise from above to lift unit from the rails or pad when unit is in final position. After unit in position, remove all shipping materials and top crating.
NOTE: Before mounting unit, remove holddown brackets and release skid. If conditions or local c odes require unit to be fastened to pad, use the mounting holes in the base rails.
CAUTION
Clearances:
Locate unit so that outdoor coil (condenser) airflow is unrestricted on all sides and above. See Figure 1 for unit clearances, weight, and clearance data.
Unit Support:
The unit must be level, and supported above grade by beams, platform or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel or pressure treated timbers approved for ground contact. Refer to Unit Clearances and weights to help determine size of supports etc. Soil conditions should be considered so the platform or pad does not shift or settle excessively and leave the unit only partially supported.
!
REDUCED EQUIPMENT LIFE HAZARD
Failure to follow these precautions could result in damage to the unit being installed.
Inadequate support could cause excessive vibration and noise or binding and stress on refrigerant lines resulting in equipment failure.
To minimize vibration or noise transmission, it is recommended that supports not be in contact with the building structure. However, slabs on grade construc­tions with an extended pad are normally acceptable.
A. Ground Level Installation:
If beams or an open platform are used for support it is recommended that the soil be treated or area be graveled to retard the growth of grasses and weeds.
B. Roof Top Installation:
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof the unit should be 4 inches (10cm.) above roof level. Four by four posts placed over a load bearing wall make a suitable mounting platform.
If possible, place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are self--supporting and span load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure.
CAUTION
4
Split System Heat Pumps Installation Instructions
Figure 2
NOTICE TO RIGGERS
All Panels Must Be In Place When
Rigging
3’ 7”
1092mm
10’ 0”
3048mm
Spreader Bars
10’ 0”
3048mm
NOTICE TO RIGGERS: Rig by inseting hooks into unit base rails as shown. Maintain a distance of 120 inch­es (3048mm) from top of unit to eyehook. Use corner post or top board from packaging to protect coil of unit from damage by rigging cable. Use bumper boards for spreader bars.
CHECK VERTICAL SEPARATION -- If there is any vertical separation between the indoor and outdoor units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary. See Table 2.
SIZE REFRIGERANT LINES -- Consider the length of the piping required between the outdoor and indoor units. The maximum allowable line length is 100 ft (30.5 m). See Table
1. Refrigerant suction piping should be insulated.
Carefully evaluate any vapor risers at minimum load conditions to ensure proper compressor oil return. If the indoor unit is above the outdoor unit, the riser will function as a hot gas riser. If the outdoor unit is above the indoor unit, the riser is a suction riser. Use a reduced diameter riser design and construct a double riser if necessary.
Table 1 - Refrigerant Piping Sizes
Linear Length of Interconnecting Piping -- Ft. (mm)
0--25
(0 -- 7.5)
Unit
CHS180 5/8 1--5/8 3/4 1--5/8 3/4 1--5/8
L S L S L S 3/4
25 -- 60
(7.5 -- 18)
Line Size (in. OD)
61 -- 100
(18.3 -- 30 )
Maximum
Liquid Line
LEGEND L -- Liquid Line, S -- Suction Line *Maximum length of interconnecting pipe is 100 ft (30.5 m).
NOTES:
1. Pipe sizes are based on a 2° F(1° C) loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for each column, plus a 50% allowance for fittings.
Installing Refrigerant Lines
Complete Refrigerant Piping Connections
Refrigerant lines must be carefully designed and constructed to ensure equipment reliability and efficiency.
Line length, pressure drop, compressor oil return, and vertical separation are several of the design criteria that must be evaluated. See Table 1.
IMPORTANT: Piping must be properly sized and installed for the system to operate efficiently.
3. Charge units with R--22 in accordance with unit installation instructions.
4. Maximum line length must not exceed 100 ft (30.5 m).
Table 2 - Max. Vertical Separation Between Indoor & Outdoor Units
Unit Evap. Distance ft (m)
Unit
CHS180 BHC180 80 (24.4)
Above Unit Evap.
INSTALL FILTER DRIER(S) AND MOISTURE INDICATOR(S) -- Every unit should have a filter drier and liquid--moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses. One filter drier and sight glass may be installed at A locations in Fig. 3. Or, 2 filter driers and sight glasses may be installed at B locations.
Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping from indoor unit to outdoor unit before opening the liquid and suction lines at the outdoor unit.
5
Split System Heat PumpsInstallation Instructions
WARNING
Recover R--22 holding charge before removing runaround liquid piping loop. Failure to recover holding charge before removing piping loop could result in equipment damage and severe injury.
MAKE PIPING CONNECTIONS
1. Open service valves in sequence:
a. Discharge service valve on compressor.
b. Suction service valve on compressor.
c. Liquid line valve.
2. Remove 1/4 --in. flare cap from liquid valve Schrader port.
3. Attach refrigerant recovery device and recover holding charge.
4. Remove runaround loop.
Table 3 -- Insulation for Vapor Line Exposed to Outdoor Conditions
Length of Exposed Vapor Line* Insulation Thickness
feet meter inches mm
10 3 3/8 10 25 8 1/2 13 35 11 3/4 19 50 15 3/4 19
5. Connect system liquid line from liquid connection of outdoor unit(CHS) to indoor unit liquid line connections. Select proper field-- supplied bi--flow filter driers and install in the liquid line. See Fig. 2. Install a field--supplied liquid moisture indicator between the filter drier(s) and the liquid c onnections on the indoor unit. Braze or silver alloy solder all connections.
Pass nitrogen or other inert gas through piping while making connections to prevent formation of copper oxide. (Copper oxides are extremely active under high temperature and pressure. Failure to prevent collection of copper oxides may result in system component failures.)
VAPOR LINE PIPING PROCEDURE -- Connect system vapor line to the vapor line stub on the outdoor unit and the vapor stubs on the indoor unit. At the indoor unit, construct vapor piping branches as shown in Fig. 3 for good mixing of the refrigerant leaving the indoor coil during cooling. This will ensure proper TXV (thermostatic expansion valve) bulb sensing. Where vapor line is exposed to outdoor air, line must be insulated. See Table 3 for insulation requirements.
*Recommended vapor line insulation for piping exposed to outdoor conditions to prevent loss of heating during heating cycle. When vapor line goes through interior spaces, insulation should be selected to prevent condensation on cooling cycle. Heating capacity should be reduced 1000 Btuh (295 W) if over 35 ft (11m) of vapor line with 3/4 in. (19 mm) insulation is exposed to outdoor conditions. +Closed cell foam insulation with a thermal conductivity of: 0.28 Btu in./ft 2 • h •°F (0.04W/m •°C).
Fig. 3 — Location of Sight Glass(es) and Filter Driers (Typical)
6
LEGEND TXV -- Thermostatic Expansion Valve
Loading...
+ 11 hidden pages