ICP C4H418GKD100, C4H424GKD100, C4H430GKD100, C4H436GKD100, C4H442GKD100 Installation Guide

...
INSTALLATION INSTRUCTIONS
R410A Split System Heat Pump
N4H3, C4H3, H4H3, T4H3,
N4H4, NXH5, CXH5, HXH5, TXH5
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Inspect New Unit 2...............................
Safety Considerations 2...........................
Location 2.......................................
Clearances 2....................................
Unit Support 2...................................
Refrigeration System 3...........................
Electrical Wiring 7................................
Defrost System 9................................
Startup Procedure 11............................
Refrigerant Charge 11............................
Sequence of Operation 12.........................
Troubleshooting 16...............................
Maintenance 16..................................
Comfort Alertt Diagnostics Codes 17..............
R410A Quick Reference Guide 18.................
Specifications subject to change without notice.
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per­sons could result in equipment malfunction, prop­erty damage, personal injury and/or death.
The information contained in this manual is in­tended for use by a qualified service technician fa­miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
428 01 5106 02 5/14/14
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the dealer/distributor for information and assistance. The qualified installer must use factory authorized kits and accessories when modifying this product. Refer to the individual instructions packaged with the kit or accessory when installing.
The weight of the product requires careful and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use a heat sinking material such as a wet rag − during brazing operations. Keep a fire extinguisher available. Consult local codes and the National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
!
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis­connect device could result in personal injury or death.
Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device. There may be more than one disconnect device. Lock out and tag switch with a suitable warning label.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage
R410A systems operate at higher pressures than R22 systems. When working with R410A sys­tems, use only service equipment and replace­ment components specifically rated or approved for R−410A service.
WARNING
CAUTION
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEARANCES section of this document).
Rooftop installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional information.
CLEARANCES
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (610 mm) clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance on one side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66m). Position so water, snow, or ice from roof or eaves cannot fall directly on unit. On rooftop applications, locate unit at least 6 in. (152.4mm) above roof surface.
UNIT SUPPORT
NOTE: Unit must be level " 2 degrees [3/8 inch rise or fall
per foot of run (10mm rise or fall per 305 mm of run)] or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure treated timbers approved for ground contact. Soil conditions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Figure 1.
If beams or an open platform are used for support, it is recommended that the soil be treated or area be graveled to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is recommended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
!
CAUTION
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bedroom windows. Noise may carry into the openings and disturb people inside.
2 428 01 5106 02
Specifications subject to change without notice.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Top surface of platform must be above estimated snow­fall level to prevent snow blocking coil and to allow water melt to drain from unit.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Figure 1 Tie Down Knockouts
a” (10mm) dia. Tie Down Knockouts In Base Pan (2 places)
A
Base Pan Width
View From Top
Base
Pan
Depth
C
B
Inches (mm)
Base Pan
Width x Depth
23 x 23
(584 x 584)
2511/16 x
2511/16
(652 x 652)
311/8 x 311/8
(791 x 791) 3415/16 x
3415/16
(887 x 887)
Tie Down
Knockouts
A B C
7−3/4
4−7/16
(197)
9−1/16
(230)
9−1/16
(230)
9−1/16
(230)
(113)18(457)
4−7/16
(113)
6−1/2 (165)
6−1/2 (165)
211/4
(540)
245/8
(625)
287/16
(722)
Minimum
Mounting Pad
Dimensions
23 x 23
(584 x 584)
26 x 26
(660 x 660)
311/2 x 311/2
(800 x 800)
35 x 35
(889 x 889)
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof, locate unit minimum 6 inches (152mm) above roof level.
Place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are selfsupporting and span several load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid locating the unit over bedrooms or study.
NOTE: When unit is to be installed on a bonded guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install tie down bolts through the holes (refer to Figure 1).
Contact local distributor for hurricane holddown details and the P.E. (Professional Engineer) certification, when required.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Inadequate unit support may cause excessive vibration, noise, and/or stress on the refrigerant lines, leading to re­frigerant line failure.
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in place, especially the indoor coil.
R410A outdoor units can only be used with R410A specific indoor coils. If there is a refrigerant mis−match, consult the indoor coil manufacturer to determine if a refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed to achieve maximum efficiency when used with indoor coils that utilize a TXV refrigerant metering device or Piston with Teflon ring metering device. If any other type of metering device is installed on the indoor coil, consult the indoor coil manufacturer to determine if a conversion kit is available.
Installing with TXV.
When installing a TXV on an indoor coil, follow the instructions provided with the new TXV.
A typical TXV installation is shown in Figure 2.
Figure 2 Typical TXV Installation
INDOOR
EQUALIZER TUBE
SENSING BULB
TXV
10 O’Clock
7/8
2 O’Clock
SUCTION TUBE
IN. OD & SMALLER
COIL
SUCTION TUBE
LIQUID TUBE
SENSING BULB
STRAP
428 01 5106 02 3
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Installing with Indoor Piston cooling operation. (Heat pumps also use an outdoor piston for heating
operation, refer to section F.)
Check piston size shipped with indoor unit to see if it matches required indoor piston size shown on outdoor unit rating plate.
If it does not piston, according to size marked on outdoor unit rating plate. (Some outdoor models include a cooling piston in the accessory bag.)
Heating piston is shipped in the service valve refer to section F.
Example fan coils with piston: FEM4P, FSM4P, FSU4P, FMA4P, FMC4P, FMU4P.
See Figure 3. When changing indoor piston, use a back−up wrench.
Finger tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ftlbs (40.7 Nm).The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body, and must be installed properly to ensure proper seating in the direction for cooling operation.
Figure 3 Indoor (cooling) Piston
match, replace indoor piston with cooling
Refer to Product Specifications and Long Line Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet
(61m). NOTE: A crankcase heater must be used when the
refrigerant line length exceeds 80 feet (24.4m). If outdoor unit is more than 10 feet (3m) higher than the
indoor coil, refer to the Long Line Applications Guideline for instructions.
NOTE: When the outdoor unit is higher than the indoor coil, the vertical separation must not exceed 100 feet (30m).
NOTE: When the outdoor unit is lower than the indoor coil, the vertical separation must not exceed 50 feet (15.2m).
If it is necessary to add refrigerant line in the field, use dehydrated or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can “kink” easily, and if this occurs, the entire length of tubing must be replaced.
BRASS
HEX NUT
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation. If using a TXV in conjunction with a singlephase reciprocat­ing compressor, a compressor start capacitor and relay are required. Consult outdoor unit presale literature for start as­sist kit part number.
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation.
4 428 01 5106 02
TEFLON SEAL
TEFLON RING
PISTON
FLOW IN COOLING
PISTON RETAINER
STRAINER
CAUTION
DISTRIBUTOR
BRASS HEX BODY
!
PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all flow control devices, including solenoid valves.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp­er product operation.
Do not leave system open to atmosphere any lon-
L10S017
Specifications subject to change without notice.
ger than absolutely required for installation. Inter­nal system components especially refrigerant oils are extremely susceptible to moisture con­tamination. Keep ends of tubing sealed during installation until the last possible moment.
C. ROUTING AND SUSPENDING REFRIGERANT
LINES
Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when routed through an attic or when routed through an underground raceway.
When routing refrigerant lines through a foundation or wall, do not allow refrigerant lines to come in direct contact with the building structure. Make openings large enough so that lines can be wrapped with extra insulation. Fill all gaps with RTV caulk. This will prevent noise
WARNING
CAUTION
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
transmission between the tubing and the foundation or wall.
Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water
Figure 4
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL SUSPENSION
Routing and Suspending Refrigerant Lines
LIQUID TUBE
SUCTION TUBE
pipes, or ductwork. Use insulated or suspension type hangers. Metal straps must be at least 1” (25mm)wide to avoid cutting into the tube insulation. Keep the liquid and suction lines separate. Refer to Figure 4.
JOIST
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1” (25mm) MIN
INSULATION
SUCTION TUBE
LIQUID TUBE
D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT
!
UNIT OPERATION HAZARD Failure to follow this caution may result in improp-
er product operation. Do not bury more than 36” (1m) of line set under-
ground. Refrigerant may migrate to cooler buried section during extended periods of unit shut down, causing refrigerant slugging and possible compressor damage at start−up. If ANY section of the line set is buried under­ground, provide a minimum 6” (152mm) vertical rise at the service valve.
Figure 5
CAUTION
Liquid Line Filter−Drier
Installed at Indoor Coil
Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below 1500 fpm (feet per minute), oil return will be decreased. To maintain suction gas velocity, do not upsize vertical suction risers.
E. LIQUID LINE FILTER−DRIER
Outdoor units are shipped with an appropriate filterdrier for installation in the liquid line. Leave the plugs in the tube ends until the filterdrier is installed. The optimal location for the filterdrier is close to the indoor coil. Heat pump filterdriers are “biflow” type. Either end can be pointed towards indoor coil. Refer to Figure 5.
F. SERVICE VALVES
Service valves are closed and plugged from the factory. Outdoor units are shipped with a refrigerant charge sealed in the unit. Leave the service valves closed until all other refrigerant system work is complete or the charge will be lost. Leave the plugs in place until line set tubing is ready to be inserted.
Heat pumps require a piston metering device in the liquid service valve for proper heating operation. Piston is shipped in the piston body of the liquid service valve, temporarily held in place with a plastic cap. Do not remove the plastic cap until line set tubing is ready to be installed.
Refer to Figure 6 and follow these steps for piston installation:
1. Remove plastic cap holding piston in piston body of liquid service valve.
2. Check that piston size (stamped on side of piston) matches with number listed on unit rating plate. Return piston to piston body of liquid service valve (either direction).
3. Find plastic bag taped to unit containing copper adapter tube, brass nut, and plastic washer.
4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install tube onto liquid service valve. Tighten nut finger tight, then wrench additional ½ turn only [15ft lbs (20.3
FilterDrier
428 01 5106 02 5
3811 84
Specifications subject to change without notice.
Nm)]. Over tightening may damage the plastic washer.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Service valve bodies are brass and suction tube stub is copper.
Figure 6
LIQUID SERVICE VALVE
VALVE CORE
Liquid Service Valve with Heating
Piston and Adapter Tube
BRASS NUT
ADAPTER TUBE
PLASTIC WASHER
PISTON
PISTON BODY
Vapor Service Valve
SERVICE VALVE
Apply heat absorbing paste or heat sink product between service valve and joint. Wrap service valves with a heat sinking material such as a wet cloth.
Braze joints using a SilFos or Phoscopper alloy.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Braze with SilFos or Phoscopper alloy on cop­pertocopper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV.
H. EVACUATING LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The liquid line and suction line service valves have been closed after final testing at the factory. Do not disturb these valves until the line set and indoor coil have been evacuated and leak checked, or the charge in the unit may be lost.
NOTE: Do not use any portion of the factory charge for purging or leak testing. The factory charge is for filling the system only after a complete evacuation and leak check has been performed.
CAUTION
G. BRAZING CONNECTIONS NOTE:
For Liquid Service Valve − Braze lineset to adapter tube BEFORE bolting adapter to valve. This helps prevent overheating and damage to plastic washer or o−ring.
For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing. This helps prevent overheating and damage to valve seals (refer to Figure 6). Replace valve core when brazing is completed.
!
FIRE HAZARD
Failure to remove refrigerant and oil charge before brazing could result in personal injury, death, and/ or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and contacts brazing torch. Make sure the refrigerant charge is properly removed from both the high and low sides of the system be­fore brazing any component or lines.
WARNING
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Never use the outdoor unit compressor as a vacu­um pump. Doing so may damage the compressor.
Line set and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. If deep vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure.
If vacuum must be interrupted during the evacuation procedure, always break vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum to 500 microns and a vacuum gauge capable of accurately measuring this vacuum level. The deep vacuum method is the most positive way of assuring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down. The response of the gauge is an indicator of the condition of the system (refer to Figure 7).
With no leaks in the system, allow the vacuum pump to run for 30 minutes minimum at the deep vacuum level.
CAUTION
Clean line set tube ends with emery cloth or steel brush. Remove any grit or debris.
Insert line set tube ends into service valve tube stubs.
6 428 01 5106 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Triple Evacuation Method
The triple evacuation method should only be used when system does not contain any water in liquid form and vacuum pump is only capable of pulling down to 28 inches of mercury (711mm Hg). Refer to Figure 8 and proceed is as follows:
Figure 7
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
Deep Vacuum Gauge Response
and System Conditions
01
246
375
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
Figure 8 Triple Evacuation Sequence
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
5. Repeat this procedure as indicated in Figure 8.
6. After the final evacuate sequence, confirm there are no leaks in the system. If a leak is found, repeat the entire process after repair is made.
I. OPENING SERVICE VALVES
Outdoor units are shipped with a refrigerant charge sealed in the unit. Opening the service valves releases this charge into the system.
NOTE: Open the Suction service valve first. If the Liquid service valve is opened first, oil from the compressor may be drawn into the indoor coil TXV, restricting refrigerant flow and affecting operation of the system.
Remove Suction service valve cap and insert a hex wrench into the valve stem. Hold the valve body steady with an end−wrench and back out the stem by turning the hex wrench counterclockwise. Turn the stem until it just contacts the rolled lip of the valve body.
After the refrigerant charge has bled into the system, open the Liquid service valve.
NOTE: These are not back−seating valves. It is not necessary to force the stem tightly against the rolled lip.
The service valve cap is a primary seal for the valve and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap.
Tighten cap finger tight and then tighten additional 6 of a turn (1 wrench flat) to properly seat the sealing surfaces.
J. GAUGE PORTS
Check for leaks at the schrader ports and tighten valve cores if necessary. Install plastic caps finger tight.
ELECTRICAL WIRING
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
CHARGE SYSTEM
1. Pull system down to 28 inches of mercury (711mm Hg) and allow pump to continue operating for an additional 15 minutes.
2. Close manifold valves or valve at vacuum pump and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and fill with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the system absorbing moisture.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis­connect device could result in personal injury or death.
Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device. There may be more than one disconnect device.
Supply voltage must be 208/230 volts (197 volt minimum to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper conductors only. Do not use aluminum wire.
Refer to unit rating plate for minimum circuit ampacity and circuit protection requirements.
Grounding
Permanently ground unit in accordance with the National Electrical Code and local codes or ordinances. Use a copper conductor of the correct size from the grounding lug in control box to a grounded connection in the service panel or a properly driven and electrically grounded ground rod.
428 01 5106 02 7
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Wiring Connections
Make all outdoor electrical supply (Line Voltage)
16 AWG colorcoded wires to avoid excessive voltage
drop. connections with raintight conduit and fittings. Most codes require a disconnect switch outdoors within sight of the unit. Consult local codes for special requirements. Route electrical supply (Line Voltage) wiring through knockout hole in bottom of Control Box. Connect wires to Contactor and Ground Lug according to Wiring Diagram
Figure 9
DISCONNECT
PER NEC AND/OR
LOCAL CODES
Electrical Supply (Line Voltage)
on unit. Refer to Figure 9. Route thermostat wiring through rubber grommet in
bottom of Control Box. Low voltage lead wires are provided in the control box for connection to thermostat
FIELD POWER
WIRING
wires (use wire nuts). Refer to Wiring Diagram on unit and Figure 10 for low voltage wiring examples.
NOTE: Use No. 18 AWG (American Wire Gage) colorcoded, insulated (35 ° C minimum) wire. If
FIELD GROUND
WIRING
thermostat is located more than 100 feet (30.5 m) from unit as measured along the control voltage wires, use No.
Figure 10 Typical Thermostat (Control Circuit) Connections
THERMOSTAT SUBBASE
NOTE: WHEN USING OUTDOOR THERMOSTATS, W
SYSTEMS WITH ONE OUTDOOR THERMOSTAT
INDOOR SPLICE CONNECTION
W
3
OUTDOOR SPLICE CONNECTION
MUST BE ENERGIZED WHEN REQUESTING SUPPLEMENTAL HEAT.
2
SYSTEMS WITH TWO OUTDOOR THERMOSTATS
DEFROST BOARD
THERMOSTAT
SUBBASE
INDOOR SPLICE CONNECTION
W
3
Connections
L1
L2
GROUND
OUTDOOR SPLICE CONNECTION
LUG
CONTACTOR
11
23 or 13
DEFROST BOARD
ODT
SHR
SHR
C
W
2
Y
ODT
O
R
C
W
2
L
G
Y
E
O
R
C
W2E
G
R
C
W
2
ODT
Y
O
R
C
W
2
L
G
Y
EHR
E
O
R
C
W
2
G
E
R
REMOVE WIRES FROM CRIMP NUT IN INDOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS.
SYSTEMS WITHOUT OUTDOOR THERMOSTATS
THERMOSTAT SUBBASE
C
W
2
L
G
Y
E
O
R
INDOOR
SPLICE
CONNECTION
C
W
2
G
R
OUTDOOR SPLICE CONNECTION
C
W
2
Y
O
R
DEFROST
BOARD
LEGEND
24V FACTORY WIRING
24V FIELD WIRING
FIELD SPLICE CONNECTION
OUTDOOR THERMOSTAT
EMERGENCY HEAT RELAY
EHR
SHR
SUPPLEMENTAL HEAT RELAY
8 428 01 5106 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
DEFROST SYSTEM
A. DEFROST THERMOSTAT
The defrost thermostat is factory installed on a short tube stub extending from the coil end plate. Refer to Figure 11 and confirm that the thermostat is securely fastened in place on the tube stub.
Figure 11 Defrost Thermostat
FEEDER TUBE
TUBE STUB
COIL
DEFROST THERMOSTAT
B. DEFROST CONTROL BOARD
The defrost board is a time/temperature control which includes a fieldselectable time period between defrost cycles of 30, 60, or 90 minutes (quickconnects located at board edge, factory set at 60 or 90 minutes).
Defrost mode is identical to cooling mode except that outdoorfan motor stops and secondstage heat is turned on to continue warming conditioned space.
Initially, the defrost cycle timer starts when the contactor is energized and a 24 VAC signal is present on the T1 terminal. Then the defrost cycle begins when the defrost thermostat is closed and the cycle timer times out (30, 60, 90 or minutes).
There are two timers involved in the defrost sequence: Interval Timer – 30, 60, or 90 minutes, selected by
setting the jumper on the defrost board. Timer is only active during calls for heating. Timer starts when the defrost thermostat closes 32° F (0°C ). Timer stops when a defrost is initiated by the defrost board or when the defrost thermostat opens 65° F (18° C). Defrost Timer – 10 minutes, not adjustable. Timer is only active while the coil is defrosting. Timer starts when the defrost board initiates a defrost. Timer stops when the defrost thermostat opens 65° F (18° C) or after timing out at 10 minutes (whichever comes first). SPEEDUP pins are provided on the defrost board to help in troubleshooting without waiting for timers to expire. Jumpering the SPEEDUP pins causes any active timer to run very fast (256 times normal speed). Jumpering the SPEEDUP pins does not by itself initiate any timers, it only affects timers that are already running or are already part of the sequence.
To initiate a forced defrost cycle (test cycle), the defrost thermostat (Figure 11) must be closed.
There are two ways to verify that the defrost thermostat is closed:
1. Jumper across the DFT terminals on the defrost board (Figure 12). With this method, the defrost thermostat is removed from the circuit, and operation of the defrost thermostat itself will not be observed. Skip to #3.
2. Use a volt-meter to confirm there is no voltage across the DFT leads. 24 volts across the SFT terminals indicates an OPEN defrost thermostat. Zero volts across the DFT terminals indicates a CLOSED defrost thermostat. With this method, the operation of the defrost thermostat can be observed during the test. If the defrost thermostat is confirmed closed, skip to #3. If the defrost thermostat is open (24 volts across DFT leads) it may be possible to close the defrost thermostat by forcing a frost buildup on the outdoor coil. Follow these steps:
S Turn off power to unit. S Disconnect outdoor fan-motor lead from OF2 on
control board (Figure 12). Tape lead to prevent grounding.
S Restart unit in heating mode; wait for
accumulation of frost on outdoor coil. Use volt-meter to confirm there are zero volts across the DFT leads (thermostat closed).
S Turn off power to unit. Replace outdoor fan-motor
lead to OF2 on control board (Figure 12). Restart the unit in heating mode.
3. With unit running in heating mode and the defrost thermostat closed, the entire defrost sequence can be sped up for testing by shorting together the SPEEDUP pins on the defrost board. Use a flat-headed screwdriver to short the pins together.
4. Hold the SPEEDUP pins shorted together until the reversing valve shifts. SPEEDUP reduces whatever time was left on the interval timer (30/60/90 minutes). In normal operation the reversing valve will always shift with the SPEEDUP pins shorted for between 1 and 21 seconds.
5. After shorting the SPEEDUP pins together as described in #4, the reversing valve will energize (shift to AC mode), the outdoor fan will stop, the strip heat will energize, and the coil will begin to defrost. There are two options for the defrost test: a. Remove the short from between the SPEEDUP
pins immediately after the reversing valve shifts, and the unit will defrost for a shortened period of time (something less than 10 minutes). The defrost will stop when the defrost thermostat opens (reaches 65° F)(18° C) or when the defrost timer times out (something less than 10 minutes).
b. Leave the SPEEDUP pins shorted together for
more than 2 seconds after the reversing valve shifts, and the unit will immediately return to heating operation (#6 below). Continue to leave the pins shorted together and the sequence starts over at #4 above.
6. Unit returns to heating mode after defrost sequence. Reversing valve shifts back, outdoor fan starts up, and strip heat de-energizes.
428 01 5106 02 9
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Figure 12 Defrost Control Board
H9C1
OF1
C US
K1
O1
R21
C2
R6
R14
R13
D13
C19
D10
CEBD43052401A 5501A
T1 C C O
D1
OF2
C9
D2
R26
C1
A29
R9
D4
D3
D6
JW1
C16
R28
C10
JW2
1
C7
1
R20
U1
C17
R1R2R3
C4
JW3
R8
C13
R7
R4
U3
R11
R5
HK32EA001
1
Y
P2
DFT
P3
1
P1 1
SPEEDUP
J2
W1
30 60 90
J1
1
O R
W
2
Y
C
10 428 01 5106 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
STARTUP PROCEDURE
1. Set indoor thermostat selector switch to OFF.
2. Turn ON all electrical disconnect devices.
3. If unit has a crankcase heater, energize the heater and wait 24 hours before proceeding.
4. Set indoor thermostat at desired temperature. Be sure setpoint is below indoor ambient temperature to call for cooling, or above indoor ambient to call for heating.
5. Set indoor thermostat selector switch to COOL or HEAT. Operate unit for minimum 15 minutes, then check the system refrigerant charge.
REFRIGERANT CHARGE
Factory charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on information plate inside unit. Additional subcooling may be required to achieve optimal heating performance based on installed indoor unit. (see figure 17)
For TXV, use subcooling method. For Piston, use superheat method. To properly check or adjust charge, conditions must be
favorable for subcooling or superheat charging. Favorable conditions exist when the outdoor temperature is between 70_F and 100_F (21_C and 38_C), and the indoor temperature is between 70_F and 80_F (21_C and 27_C). Follow the procedure below.
Unit is factory charged for 15 feet (4.6m) of lineset. Adjust charge by adding or removing 0.6 oz/ft (17 g/mm) of 3/8 liquid line above or below 15 feet (4.6 m) respectively.
For standard refrigerant line lengths 80 feet (24.4m) or less, allow system to operate in cooling mode at least 15 minutes. If conditions are favorable, check system charge by super heat method for fixed metering device and subcooling method for TXV. If any adjustment is necessary, adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system.
If the indoor temperature is above 80_F (27_C), and the outdoor temperature is in the favorable range, adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F (27_C) before attempting to check system charge by subcooling method as described above.
If the indoor temperature is below 70_F (21_C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15 feet (4.6m) only. Charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range.
NOTE: If line length is beyond 80 feet (24.4m) or greater than 20 feet (6.1m) vertical separation, See Long Line Guideline for special charging requirements.
A. UNITS WITH COOLING MODE TXV
Units installed with cooling mode TXV require charging by the subcooling method.
1. Operate unit a minimum of 15 minutes before checking charge.
NOTE: If outdoor unit has a 2−speed fan motor, motor will operate in low speed when outdoor ambient temperature is below 82_F (28_C). Pull the BRN/YEL low voltage wire off the fan control and the unit will default to high speed fan for servicing. Reconnect wire after servicing.
2. Measure liquid service valve pressure by attaching an accurate gage to service port.
3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Figure 15. Find the point where required subcooling temperature intersects measured liquid service valve pressure.
6. To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of "3_F (|1.7_C).
B. UNITS WITH INDOOR PISTON
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within "21 percent of its rated CFM.
1. Operate unit a minimum of 15 minutes before checking charge.
2. Measure suction pressure by attaching an accurate gage to suction valve service port.
3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service valve.
4. Measure outdoor air dry−bulb temperature with thermometer.
5. Measure indoor air (entering indoor coil) wetbulb temperature with a sling psychrometer.
6. Find outdoor temperature and evaporator entering air wetbulb temperature. At this intersection, note superheat. Where a dash (−−) appears on the table, do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighted in, adding or removing
0.6 oz/ft of 3/8 liquid line above or below 15 feet (4.6m) respectively.
7. Find superheat temperature (from #6 above) and suction pressure. At this intersection, note suction line temperature.
8. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
9. If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached.
10. When adding refrigerant, charge in liquid form into suction service port using a flow−restricting device.
428 01 5106 02 11
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on chart.
12. Optimum performance will be achieved when the operating charge produces 5_ to 6_F suction superheat at suction service valve with 82_F (28_C) outdoor ambient and 80_F (27_C) dry bulb (67_F / 19_C) wet bulb) indoor temperature (DOE “B” test conditions) at rated airflow.
C. HEATING MODE
To check system operation during heating cycle, refer to the Tech Label on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust refrigerant charge.
NOTE: When charging is necessary during heating season, charge must be weighed in accordance with unit rating plate 0.6 ounces per foot of a inch liquid line above or below 15 feet respectively (17g per 305mm of 10mm liquid line above or below 4.6m respectively).
SEQUENCE OF OPERATION
A. COOLING MODE
On a call for cooling, the thermostat makes circuits R−O, RY, and RG. Circuit RO energizes reversing valve, switching it to cooling position. Circuit RY energizes contactor, starting outdoor fan motor and compressor. Circuit R−G energizes indoor unit blower relay, starting indoor blower motor.
When thermostat is satisfied, its contacts open, deenergizing contactor and blower relay. Compressor and motors stop.
NOTE: If indoor unit is equipped with a time−delay relay circuit, the blower runs an additional length of time to increase system efficiency. (Applies to both cooling and heating modes.)
B. HEATING MODE
On a call for heating, the thermostat makes circuits R−Y and RG (circuit RO is NOT made, and the reversing valve stays in the deenergized, heating position). Circuit RY energizes contactor, starting outdoor fan motor and compressor. Circuit RG energizes indoor blower relay, starting blower motor. If the room temperature continues to fall, circuit RW2 is made through the second−stage room thermostat bulb. Circuit R−W2 energizes a sequencer, bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer (if used). If outdoor temperature falls below the setting of the outdoor thermostat (fieldinstalled option), contacts close to complete the circuit and bring on the second bank of supplemental electric heat.
When the thermostat is satisfied, its contacts open, deenergizing contactor, blower relay, and sequencer. Compressor, motors, and heaters stop.
12 428 01 5106 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
SUPERHEAT CHARGING TABLE ˚F SUPERHEAT CHARGING TABLE ˚C
Figure 13
EVAPORATOR ENTEREING AIR ˚F AT WB EVAPORATOR ENTEREING AIR ˚C AT WB
˚F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 ˚C 10 11 12 13 14 16 17 18 19 20 21 22 23 24
Outdoor
Temp
SUPERHEAT ˚F AT LOWSIDE SERVICE PORT 55 9 12 14 17 20 23 26 29 32 35 37 40 42 45 13 5 7 8 9 11 13 14 16 18 19 21 22 23 25 60 7 10 12 15 18 21 24 27 30 33 35 38 40 43 16 4 6 7 8 10 12 13 15 17 18 19 21 22 24 65 6 10 13 16 19 21 24 27 30 33 36 38 41 18 3 6 7 9 11 12 13 15 17 18 20 21 23 70 7 10 13 16 19 21 24 27 30 33 36 39 21 4 6 7 9 11 12 13 15 17 18 20 22 75 6 9 12 15 18 21 24 28 31 34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6 10 14 18 22 25 29 35 3 6 8 10 12 14 16
100 8 12 15 20 23 27 38 4 7 8 11 13 15 105 5 9 13 17 22 26 41 3 5 7 9 12 14 110 6 11 15 20 25 43 3 6 8 11 14 115 8 14 18 23 46 4 8 10 13
*Optimum performance point, 95°F (35°C) outdoor ambient and (80°F / 27°C dry bulb), (67°F / 19°C wet bulb) indoor conditions. (DOE A Test Conditions) Where a dash (-) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.
Note: Superheat °F is at low-side service port, Allow a tolerance of ± 3°F (± 1.7°C) Note: Indoor dry bulb between 70°F and 80°F (21°C and 27°C)
Figure 14 SUCTION PRESSURE AT SERVICE PORT PSIG SUCTION PRESSURE AT SERVICE PORT kPa
SUPER-
HEAT
TEMP ˚F
108 112 117 121 126 131 139 141 146
REQUIRED SUCTION TUBE TEMPERATURE ˚F
(MEASURED AT LOW-SIDE SERVICE PORT)
0 35 37 39 41 43 45 47 49 51 0 2 3 4 5 6 7 8 9 11 2 37 39 41 43 45 47 49 51 53 1 3 4 5 6 7 8 9 11 12 4 39 41 43 45 47 49 51 53 55 2 4 5 6 7 8 9 11 12 13 6 41 43 45 47 49 51 53 55 57 3 5 6 7 8 9 11 12 13 14
8 43 45 47 49 51 53 55 57 59 4 6 7 8 9 11 12 13 14 15 10 45 47 49 51 53 55 57 59 61 6 7 8 9 11 12 13 14 15 16 12 47 49 51 53 55 57 59 61 63 7 8 9 11 12 13 14 15 16 17 14 49 51 53 55 57 59 61 63 65 8 9 11 12 13 14 15 16 17 18 16 51 53 55 57 59 61 63 65 67 9 11 12 13 14 15 16 17 18 19 18 53 55 57 59 61 63 65 67 69 10 12 13 14 15 16 17 18 19 21 20 55 57 59 61 63 65 67 69 71 11 13 14 15 16 17 18 19 21 22 22 57 59 61 63 65 67 69 71 73 12 14 15 16 17 18 19 21 22 23 24 59 61 63 65 67 69 71 73 75 13 15 16 17 18 19 21 22 23 24 26 61 63 65 67 69 71 73 75 77 14 16 17 18 19 21 22 23 24 25 28 63 65 67 69 71 73 75 77 79 16 17 18 19 21 22 23 24 25 26 30 65 67 69 71 73 75 77 79 81 17 18 19 21 22 23 24 25 26 27
Outdoor
Temp
SUPER-
HEAT
TEMP ˚C
SUPERHEAT ˚C AT LOWSIDE SERVICE PORT
743 774 805 836 869 902 957 971 1005
REQUIRED SUCTION TUBE TEMPERATURE ˚C
(MEASURED AT LOW-SIDE SERVICE PORT)
428 01 5106 02 13
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Figure 15 Rating Plate (required) Subcooling Temperature ° F (° C)
° F (° C) ° F (° C) ° F (° C) ° F (° C) F (° C) F (° C)
Measured Liquid
6 3 8 4 10 6 12 7 14 8 16 9
Pressure (psig)
R410A Required Liquid Line Temperature ° F (° C)
251 78 26 76 24 74 23 72 22 70 21 68 20 259 80 27 78 26 76 24 74 23 72 22 70 21 266 82 28 80 27 78 26 76 24 74 23 72 22 274 84 29 82 28 80 27 78 26 76 24 74 23 283 86 30 84 29 82 28 80 27 78 26 76 24 291 88 31 86 30 84 29 82 28 80 27 78 26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 42 106 41 104 40 102 39 100 38 98 37 395 110 43 108 42 106 41 104 40 102 39 100 38 406 112 44 110 43 108 42 106 41 104 40 102 39 416 114 46 112 44 11 0 43 108 42 106 41 104 40 427 116 47 114 46 11 2 44 110 43 108 42 106 41 439 118 48 116 47 11 4 46 112 44 110 43 108 42 450 120 49 118 48 11 6 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 11 6 47 114 46
14 428 01 5106 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Figure 16 - Additional Subcooling
15 SEER 13 & 14 SEER
Subcooling Delta from Rating Plate
Value
OUTDOOR UNIT TONNAGE OUTDOOR UNIT TONNAGE
Indoor Models 18 24 30 36 42 48 60 18 24 30 36 42 48 60
ED*4X18B**/EA*4X18*14A*   EN(A,D)4X18*14**   FEM4(P,X)18**A*+TXV   F(E,S)A4X18**A*   FXM4X18**A*  +3 FS(M,U)4P18**A*+TXV   ED*4X24***/EA*4X24*(14,17)A*   +3 +3 EN*4X24*****   +3 +3 EHD4X24A**   +5 +5 FEM4P24**A*+TXV     F(E,S)A4X24**A*   +5 +3 (FVM/FCM)4X24**** +3   +5 +3 +3 FXM4X24**A*   +5 +3 FEM4X24**A*   +3 +3 FS(M,U)4P24**A*+TXV   +5 +3 ED*4X30***/EA*4X30*(14,17)A*  +3  EN*4X30*****  +3 +3 EHD4X30A**  +3 +3 FEM4(P,X)30**A*+TXV  +3  FSA4X30**A*  +3  FEA4X30**A*  +3  FXM4X30**A* +3 +5 +5 FS(M,U)4P30**A*+TXV +3 +5 +5 (FVM/FCM)4X36****   +5 +3 ED*4X36***/EA*4X36*(14,17,21)A*   +5 +3 EN*4X36*****   +3  EHD4X36A**   +5 +3 FEM4P36**A*+TXV     FSA4X36**A*   +5 +3 FEA4X36**A*   +5 +3 F(E,X)M4X36**A* +5  +5 +5 FS(M,U)4P36**A*+TXV   +5 +3 ED*4X42***/EA*4X42*(21,24)A*   +3  EN*4X42*21**   +3  END4X42*17**   +3  EHD4X42A**   +5  FEM4(P,X)42**A*+TXV   +5  FXM4X42**A*   +5  FS(M,U)4P42**A*+TXV   +5  ED*4X48F**/EA*4X48*17A* +5  +5 +3 ED*4X48(J,L)**/EA*4X48*(21,24)A* +3  +3  EN*4X48*****     EHD4X48A**   +3  FEM4P48**A*+TXV     (FVM/FCM)4X48**** +3 +3 +3  +5 +5 +3   F(E,X)M4X48**A* +3  +3  FS(M,U)4P48**A*+TXV +3  +3  ED*4X60***/EA*4X60*(21,24)A* +5  +5 +3
Subcooling Delta from Rating Plate
Value
428 01 5106 02 15
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Figure 17 - Additional Subcooling Tables
15 SEER 13 & 14 SEER
Subcooling Delta from Rating Plate
Value
OUTDOOR UNIT TONNAGE OUTDOOR UNIT TONNAGE
Indoor Models 18 24 30 36 42 48 60 18 24 30 36 42 48 60
EN*4X60*24**   +3  EHD4X60A** +3 +5 +3 FEM4X60**B*  +5  (FVM/FCM)4X60**** +5 +5 +3 +5 +5 +5 +3 FXM4X60**A* +3  +5 +3 FS(M,U)4X60**A* +3  +5 +3
Subcooling Delta from Rating Plate
Value
TROUBLESHOOTING
Some models are factory equipped with the Comfort Alertt Diagnostics device in the control box (refer to Figure 17). Comfort Alert provides around−the−clock monitoring for common electrical problems, compressor defects, and broad system faults. If trouble is detected, an alert code is displayed with a flashing LED indicator. Alert codes are listed in Figure 18.
The device is factory wired and requires no modification. Low voltage lead wires are provided in the
control box for connection to thermostat wires (use wire nuts).
The Comfort Alert device operates by monitoring the compressor power leads and the thermostat demand signal (Y terminal). It draws constant 24 VAC power at the R and C terminals.
Figure 17
R
Comfort Alertt Diagnostics
(some models)
Compressor Wires Pass Through Holes (3)
“Power” LED
MAINTENANCE
Condensate Drain
During the cooling season, check monthly for free flow of drainage and clean if necessary.
Cleanliness
These tips will help keep the heat pump looking better and working more efficiently:
1. Free flow of air is essential. Keep fences, shrubs, trash cans, and other obstructions at least 18 inches (457mm) from all coil inlets.
2. Keep the coil free of grass clippings, leaves, weeds, and other debris. NOTE: Coil may occasionally require cleaning with a liquid solution. The coil must be cold when cleaning. Use an alkaline based cleaner only. Cleaning a hot coil or using an acid based cleaner will remove the paint from the fins and may clog the coil.
3. Never use a weather cover over the outdoor unit unless it is a ventilated type or made of breathable fabric that will allow moisture to evaporate rapidly. A cover that holds moisture in the unit will cause more rust build−up and damage than normal exposure to weather.
C
Y
C
S
R
Thermostat Demand
24 VAC Common
“Alert” LED “Trip” LED
24 VAC Hot
16 428 01 5106 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
Figure 18 Comfort Alertt Diagnostics (some models)
Status LED Status LED Description Status LED Troubleshooting Information
Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal
Y1 is present, but the com­pressor is not running
1. Compressor protector is open
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. Low pressure switch open if present in system
6. Compressor contactor has failed open
Yellow “ALERT” Flash Code 1
Long Run Time
Compressor is running ex­tremely long run cycles
1. Low refrigerant charge
2. Evaporator blower is not running
3. Evaporator coil is frozen
4. Faulty metering device
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in system)
7. Thermostat is malfunctioning
Yellow “ALERT” Flash Code 2
System Pressure Trip
Discharge or suction pres­sure out of limits or com­pressor overloaded
1. High head pressure
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3. Condenser fan is not running
4. Return air duct has substantial leakage
5. If low pressure switch present in system, check Flash Code 1 information
Yellow “ALERT” Flash Code 3
Short Cycling
Compressor is running only briefly
1. Thermostat demand signal is intermittent
2. Time delay relay or control board defective
3. If high pressure switch present go to Flash Code 2 informa­tion
4. If low pressure switch present go to Flash Code 1 informa­tion
Yellow “ALERT” Flash Code 4
Locked Rotor
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Yellow “ALERT” Flash Code 5
Open Circuit
1. Outdoor unit power disconnect is open
2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
4. High pressure switch is open and requires manual reset
5. Open circuit in compressor supply wiring or connections
6. Unusually long compressor protector reset time due to ex­treme ambient temperature
7. Compressor windings are damaged
Yellow “ALERT” Flash Code 6
Open Start Circuit
Current only in run circuit
1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
3. Compressor start winding is damaged
Yellow “ALERT” Flash Code 7 Yellow “ALERT” Flash Code 8 Yellow “ALERT” Flash Code 9
Open Run Circuit
Current only in start circuit
Welded Contactor
Compressor always runs
Low Voltage
Control circuit < 17VAC
1. Open circuit in compressor run wiring or connections
2. Compressor run winding is damaged
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
1. Control circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
S Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. S TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation. S Reset ALERT Flash code by removing 24VAC power from module. S Last ALERT Flash code is displayed for 1 minute after module is powered on.
428 01 5106 02 17
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
R410A QUICK REFERENCE GUIDE
R410A refrigerant operates at 50% 70% higher pressures than R22. Be sure that servicing equipment and
replacement components are designed to operate with R410A.
R410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
Manifold sets should be 750 psig highside and 200 psig lowside with 520 psig lowside retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
R410A, as with other HFC refrigerants, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Do not use liquid line filterdriers with rated working pressures less than 600 psig.
Do not install a suction line filterdrier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filterdriers and service valves with wet cloth when brazing.
A liquid line filterdrier is required on every unit.
Do not use with an R22 TXV.
If indoor unit is equipped with an R22 TXV, it must be changed to an R410A TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace all filterdriers.
Do not vent R410A into the atmosphere.
Do not use capillary tube indoor coils.
Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
18 428 01 5106 02
Specifications subject to change without notice.
Copyright 2014 International Comfort Products
Lewisburg, TN 37091 USA
Loading...