ICP AHX32400A1, AHX33600A1, AHX34800A1, AHX36000A1 Installation Guide

Page 1
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only
used on product labels to signify an immediate haz-
NOTE will be used on product labels and through-
out this manual and other manuals that may apply to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death. WARNING - Hazards or unsafe practices which
could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or opera-
tion.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Introduction .................................... 2
Location ....................................... 2
Position Unit ................................... 4
Air Ducts ...................................... 5
Electrical Connections .......................... 5
Refrigerant Tubing .............................. 6
Refrigerant Metering Device ..................... 6
Condensate Drains ............................. 6
Wiring Schematic ............................... 8
Sequence of Operation ......................... 10
Care and Maintenance ......................... 10
Parts ........................................ 11
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning
could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per- sons could result in equipment malfunction, prop- erty damage, personal injury and/or death.
The information contained in this manual is in- tended for use by a qualified service technician fa-
miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code
NFPA70 current edition.
Distributed by ICP under the Freedom Air brand name spe_ific,tio°s_,e._bj_ttoch,,gewitho.t°otice 496 01 2100 03 June 2006
Page 2
Figure 1 Clearances and Unit Dimensions
,s .,_
- -_ -_ ,,.," J "
REQUIRED CLEARANCES (inches)
All Sides 0
All
Models Serviceability from the front 30
From Supply Duct 0
_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!i_!
Model
AHX32400 2 171/2 21 AHX33600 3 171/2 21
AHX34800 4 211/2 25 AHX36000 5 211/2 25
Size
(tons) A B
C D E F G Liquid Suct. Type fibs)
15 171/2 16 12b/8 403/4 3/8 3/4 "A" 144 15 17_/2 16 12_/8 403/4 3/8 3/4 "A" 144
191/4 221/4 19b/8 171/4 493/4 3/8 //8 "A" 192 191/4 221/4 19b/8 171/4 493/4 3/8 //8 "A" 192
INTRODUCTION
Models AHX3 are designed for an upflow vertical applica- tions.
All models are available for system sizes 2 - 5 tons
(24,000 - 60,000 BTUH) nominal cooling capacity.
All models have a factory installed 15% bleed port TXV
designed for use with R-22 refrigerant. AHX3 are for
all dimensions inches Coil Ship.
Weight
R-22 refrigerant ONLY. Use only with outdoor units de-
signed for R-22 An accessory R410A TXV kit is available through the dis-
tributor. AHTXV153 (2 - 3 ton) or AHTXV355 (4 - 5 ton)
LOCATION
Select the best position which suits the installation site conditions. The location should provide adequate struc-
tural support, space in the front of the unit for service ac- cess, clearance for return air and supply duct
connections, space for refrigerant piping connections and
2 Specilic.ti........ bjectto_h.ng_.itho.t.oti_ 496 01 2100 03
condensate drain line connections. See Clearances in
Figure 1. If the unit is located in an area of high humidity, nuisance
sweating of casing may occur. On these installations a
Page 3
wrap of 2" fiberglass insulation with a vapor barrier is rec-
ommended. NOTE: Internal filter can be accessed from separate filter
door. If the filter can NOT be easily accessed, a remote
filter is recommended. Refer to ACCA Manual D for re-
mote filter sizing.
FIRE HAZARD Failure to maintain proper clearances could result
in personal injury, death, and/or property damage. When heaters are installed, maintain clearances
from combustible materials as specified on unit rating plate. Do not use plastic lined or combus-
tible flexible ducting within 36 inches of the supply
end of the fan coil.
Figure 2
Airflow Motor @ 240V DD
Model No
Tonnage 1 Ph 60 Hz Blower Motor
Range HP FLA Wheel
AHX32400 1.5-2.0 1/4 2.2 10x6 M
AHX33600 2.5-3.0 1/3 3.1 10x7 M
AHX34800 3.0-4.0 1/3 3.1 10x8 M
AHX36000 4.0-5.0 3/4 6.0 11x9 M
Notes:
(1) Based upon unit with nominal tonnage dry coil and filter installed.
Blower Data
3-Spd
H
L
H
L
H
L
H
L
Duty
SCFM vs. ESP (1) (2)
0.10 0.20 0.30 0.40 0.50
Cool 950 900 850 790 720 Cool 950 900 850 790 720 Heat 950 900 850 790 720
Cool 1250 1200 1120 1060 1000 Cool 1070 1020 970 920 860
Heat 900 870 840 790 720 Cool 1850 1700 1650 1500 1410 Cool 1750 1650 1450 1330 1180
Heat 1150 1060 1000 920 810 Cool 2160 2100 2000 1940 1880
Cool 2110 1980 1810 1750 1650 Heat 2000 1860 1670 1340 1200
(2) Use .96 as approximate SCFM correction factor for wet coil.
Figure 3
Air Handler
Model
2400 to to 8 6 33.3 29.2 44 39
Heater
Model No.
None
HTR05*S1 HTR08*S1 HTR10*S1
HTR15*S1
Nominal Cooling
SCFM BTUH 240V I 208V 240V 208V
800 18,000 5 3.8 20.8 18.2 30 27
900 24,000 10 7.5 41.6 36.5 56 49
Nominal Electric Heater Amps
Electric Heat Performance Data
KW
240V 208V
10/5 7.5/3.8 41.6/20.8 36.5/18.2 56/26 49/23
Min
Circuit
AMP
Max. Fuse
240V 208V
15 15 30 30
45 40
60 50
60/30 50/30
None 15 15
3600 HTR08*S1 to to 8 6 33.3 29.2 46 40 50 40
4800 HTR10*L1 to to 10 7.5 41.6 36.5 57 50 60 50
6000 HTR10*L1 to to 10 7.5 41.6 36.5 59 52 60 60
HTR05*S1 1020 30,000 5 3.8 20.8 18.2 30 28 30 30
HTR10*S1 1200 36,000 10 7.5 41.6 36.5 57 50 60 50 HTR15*S1 10/5 7.5/3.8 41.6/20.8 36.5/18.2 57/26 50/23 60/30 50/30
None 15 15 HTR05*L1 5 3.8 20.8 18.2 30 27 30 30 HTR08*L1 1250 42,000 8 6 33.3 29.2 46 40 50 40
HTR15*L1 1750 48,000 7.5/3.8 7.5/3.5 41.6/20.8 36.5/18.2 57/27 50/24 60/30 50/30 HTR20*L1 10/5 7.5/7.5 41.6/41.6 36.5/36.5 57/53 50/46 60/60 50/50
None 15 15 HTR08*L1 1980 48,000 8 6 33.3 29.2 48 42 50 45
HTR15*L1 2100 60,000 7.5/7.5 7.5/3.8 41.6/20.8 36.5/18.2 59/27 52/24 60/30 60/30 HTR20*L1 10/10 7.5/7.5 41.6/41.6 36.5/36.5 59/53 52/46 60/60 60/50
* = (B) breaker or (N) non-breaker models
496 01 2100 03 Specilic.ti........ bjecztochangewithoutnotice 3
Page 4
POSITION UNIT
Unit is designed to be installed in a closet or flush mounted. Can be serviced entirely from the front, includ-
ing replacing the filter. Allow space for wiring, piping, and servicing unit.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper- ty damage
A field fabricated auxiliary drain pan, with a sepa- rate drain is REQUIRED for all installations over a
finished living space or in any area that may be
damaged by overflow from a restricted main drain pan. In some localities, local codes require an aux- iliary drain pan for ANY horizontal installation.
A. UPFLOW INSTALLATION If return air isto be ducted through a floor, set unit on floor
over opening and use ]/8 to ]/4 inch thick fireproof resil- ient gasket between duct, unit, and floor.
Exterior surface may sweat when unit is installed in non- conditioned space. Installer must provide protection such
as full size auxiliary drain pan on all units installed in non-
conditioned space to prevent damage from condensation
runoff. It is recommended that units be insulated with 1"
thick fiberglass with the vapor barrier on the outside.
B. HORIZONTAL APPLICATION Units are shipped in right to left configuration. Horizontal
applications require a return air duct be attached to the furnace inlet. The opposite end of the return air duct is at- tached to a return air filter grill through the ceiling or wall.
For left to right applications:
1. Remove and set aside front panels.
2. Remove the coil support bracket (4 screws).
3. Remove horizontal drain pan retaining clip (1 screw).
4. Carefully remove coil assembly and bottom drain pan.
5. Move Horizontal drain pan from left hand side of coil to right.
6. Install modified coil assembly back into unit.
7. Reinstall coil support bracket and horizontal drain pan retaining clip.
8. Determine drain holes being used and reposition knockout caps.
9. Reinstall doors.
AIR DUCTS
Connect supply-air duct over the outside of 3A"flanges provided on supply-air opening. Secure duct to flange us- ing proper fasteners for type of duct used, and seal duct-
to-unit joint. If return-air flanges are required, install
factory authorized accessory kit.
Use flexible connectors between duct work and unit to prevent transmission of vibration. Duct work passing
through unconditioned space must be insulated and cov- ered with vapor barrier to prevent formation of conden-
sate to prevent formation of condensate.
ELECTRICAL CONNECTIONS
Refer to the unit's nameplate for specific electrical data. Before proceeding with electrical connections, make cer-
tain that supply voltage, frequency, phase, and circuit am- pacity are as specified on the unit rating plate. Make all
electrical connections in accordance with the NEC and any local codes or ordinances that may apply. Use cop-
per wire rated for 75 degrees C minimum wire in the unit
wiring compartment only. A single power supply may be
connected directly to terminal block provided in the unit.
Duct work Acoustical Treatment Metal duct systems that do not have a 90 degree elbow
and 10 feet of main duct before first branch takeoff may
require internal acoustical insulation lining. As an alterna-
tive, fibrous duct work may be used if constructed and
installed in accordance with the latest edition of SMACNA
construction standard on fibrous glass ducts. Both acous- tical lining and fibrous duct work shall comply with Nation-
al Fire Protection Association as tested by UL Standard
181 for Class 1 air ducts.
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD Failure to follow this warning could result in per-
sonal injury, death, and/or unit damage. Ifa disconnect switch isto be mounted on unit, se-
lect a location where drill and fasteners will not contact electrical or refrigeration components.
4 5pecilic,ti........ bj_ttoch,ngewitho.t.otice 496 01 2100 03
Page 5
Figure 4 [ Transformer Connections
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in per-
sonal injury or death. Turn off the main (remote) disconnect device be-
fore working on incoming (field) wiring. Incoming (field) wires on the line side of the dis-
connect found in the fan coil unit remain live, even when the pull-out is removed. Service and main-
tenance to incoming (field) wiring cannot be per- formed until the main disconnect switch (remote to the unit) is turned off.
A. LINE VOLTAGE CONNECTIONS This Fan Coil is not electric heat compatable.
1. Connect 208/240V power leads from field discon- nect to units high voltage terminal block.
2. Connect ground wire to unit ground lug.
B. 24V CONTROL SYSTEM Connection to Unit Wire low voltage in accordance with wiring label on the
unit. Use 18 AWG color-coded, insulated (35 degrees C minimum) wire to make the low-voltage connections be-
tween the thermostat, the unit, and the outdoor equip- ment. If the thermostat is located more than 100 feet from
the unit (as measured along the low voltage wire), use 16
AWG color-coded, insulated (35 degrees C minimum) wire. All wiring must be NEC Class 2 and must be sepa-
rated from incoming power leads. Refer to outdoor unit
wiring instructions for additional wiring recommenda-
tions. NOTE: Before proceeding with electrical connections,
make certain that supply voltage, frequency, phase, and circuit ampacity are as specified on the unit rating plate. See unit wiring label for proper field high and low voltage
wiring. Make all electrical connections in accordance with
the NEC and any local codes or ordinances that may ap- ply. Use copper wire only. The unit must have a separate
branch electric circuit with a field-supplied disconnect switch located within sight from, and readily accessible
from the unit.
Transformer Information Transformer is factory wired for 208/240V operation.
BLUE
24VAC
t 1TRANSFOR_R
L 20g'240',/AC J
_ O;RANGE
WHITE
C. GROUND CONNECTIONS
ELECTRICAL SHOCK HAZARD Failure to establish uninterrupted or unbroken
ground could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground in order to minimize potential for personal injury or death if an electrical fault should occur. The ground may consist of electri-
cal wire or metal conduit when installed in accor- dance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground wire must be used.
NOTE: Use UL listed conduit and conduit connectors for
connecting supply wire(s) to unit to obtain proper ground-
ing. Grounding may also be accomplished by using
grounding lugs provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION Units require a minimum CFM. Refer to the unit wiring la-
bel to ensure that the fan speed selected is not lower than
the minimum fan speed indicated.
Fan speed selection is done at the fan relay. To change motor speeds, disconnect fan lead used on relay terminal
(FR) and replace with motor speed lead desired (refer to Figure 8). Save insulating cap and place on motor lead
removed from relay.
496 01 2100 03 Specilicati........ bjecl tochangewithoutnotice 5
Page 6
NOTE: In low static applications, lower motor speed tap should be used to reduce possibility of water being blown
off coil.
All units have three (3) motor speed taps. Low speed (red
or 4) is designed for mismatch outdoor unit applications.
REFRIGERANT TUBING
Medium speed (blue or 3) is designed for straight matched operations. High speed (black or 2) is used with
high external static duct situations on straight matched
systems.
Size and install refrigerant lines according to information provided with outdoor unit. Route refrigerant lines to the
fan coil in a manner that will not obstruct service access to
the unit or removal of the filter.
1. Find the liquid tube grommet in the small-parts bag and slide it onto the liquid refrigerant line (field line- set).
2. Remove the lower door. Remove the tubing plate (with suction tube grommet) and slide the plate with
grommet onto the refrigerant lines (field line-set), away from braze joints.
3. Using a tubing cutter, carefully cut approximately 1/2_ off of the suction and liquid line stubs. These coils are pressurized with a nitrogen holding charge. Cut the first stub, either the suction or liquid
line slowly to allow the pressure to escape before cutting all the way through the entire stub.
REFRIGERANT METERING DEVICE
These Fan Coils have a factory installed 15% bleed port TXV designed for use with R-22 refrigerant. Use only with
outdoor units designed for R-22. TXV is factory set and not field adjustable.
4. Wrap TXV and nearby tubing with a heat-sinking material such as a wet cloth.
5. Fit refrigerant lines into coil stubs. Wrap a heat sink- ing material such as a wet cloth behind braze joints.
6. Braze using a SiI-Fos or Phos-copper alloy.
7. After brazing, allow joints to cool. Slide tubing plate back into place and position grommets around suc-
tion and liquid tubes to ensure air seal.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Braze with SiI-Fos or Phos-copper alloy on cop- per-to-copper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV.
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product
damage. This Fan Coil has a hard shut-offTXV metering de-
vice. A compressor Hard Start Kit is REQUIRED in all applications where the matching outdoor unit has a single-phase reciprocating compressor.
CONDENSATE DRAINS
Unit is provided with primary and secondary 3A"NPT drain connections. Refer to Figure 7 to identify the primary and
secondary locations. To prevent property damage and achieve optimum drainage performance, BOTH primary
and secondary drain lines should be installed and include properly sized condensate traps. Factory approved con-
densate traps are available (accessory part number EBAC01CTK).
Install traps in the condensate lines as close to the coil as possible (refer to Figure 7), but avoid blocking filter ac-
cess panel. Install drain lines below the bottom of the drain pan and
pitch the drain lines down from the coil at least 1Ainch per
foot of run. Horizontal runs over 15 feet long must also
have an anti-siphon air vents (stand pipes), installed ahead of the horizontal runs. Extremely long horizontal
runs may require oversized drain lines to eliminate air trapping.
6 Specilicati........ bj_ttochangewithout.otice 496 01 2100 03
Route primary drain line to the outside or to a floor drain. Check local codes before connecting to a waste (sewer)
line. Route the secondary drain line to a place in compliance
with local installation codes where it will be noticed when
unit is operational. Condensate flowing from secondary (overflow) drain indicates a plugged primary drain - unit
requires service or water damage will occur.
PRODUCT or PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Use only full size P-traps in the condensate line (refer to Figure 5). Shallow, running traps are inad- equate and DO NOT allow proper condensate drainage (refer to Figure 6).
Page 7
Prime all traps, test for leaks, and insulate drain lines
where sweating could cause water damage. Consult local
codes for additional requirements or precautions. If a gravity drain cannot be used, install a condensate
pump. Install the pump as close to the indoor section as possible.
Be sure to install plastic push-in plugs in unused conden- sate drain holes.
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor
unit performance and/or product damage.
Never operate unit without a filter. Factory autho-
rized filter kits must be used when locating the fil- ter inside the unit. For those applications where access to an internal filter is impractical, a field- supplied filter must be installed inthe return duct system.
Figure 6 [ Insufficient Condensate Trap
DO NOT USE SHALLOW RUNNING TRAPS!
Figure 7
[
Condensate Drain
Figure 5
I Recommended Condensate Trap
2" MIN
O
O
-FILTER ACCESS
._ PANEL
SECONDARY DRAIN WITH APPROPIATE TRAP REQUIRED
(USE FACTORY KIT OR FIELD - SUPPLIED TRAP)
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR FIELD - SUPPLIED TRAP OF PROPER DEPTH.
STANDARD P - TRAPSARE NOT SUFFICENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
496 01 2100 03 Specilic.Ii........ bjecttochangewithoutnotice 7
Page 8
Figure 8 I
Wiring Layout - Cooling
£
_7! ",1
GROUNDLUG
£0
'_'_ T- "_- T'- _-=
h- mm mmm
Z O[IZ_Od n_
w k-l- l-l-l-
o0 n-l-zzT
3
co
L_
_3
Z
W
_<
oo
r_
LU
8 Sp_ilb_li........ bjectto_ng__it_o._.oti_ 496 01 21 O0 03
Page 9
Figure 9 I Wiring Layout - Electric Heating
O_
s_
!
o
/ o.......o \
S
<
8 Z
<
496 01 2100 03 Sp_i{i_mi........ _je_ltod_ange_ithoul.oti¢e 9
Page 10
SEQUENCE OF OPERATION
A. CONTINUOUS FAN
Thermostat closes R to G. G energizes Time Delay Relay (TDR).
Time Delay Relay (TDR) energizes Fan Relay (FR) within 30 seconds.
When Fan Relay (FR) is energized, circuit is com- plete to Indoor Blower Motor.
When G isde-energized, there is a 3 second delay before Fan Relay (FR) opens.
B. COOLING MODE
Thermostat closes R to G, R to Y, and R to O (heat pump only).
G energizes Time Delay Relay (TDR). Y energizes Condense contactor, and O energizes the reversing valve (heat pump only)
Time Delay Relay (TDR) energizes Fan Relay (FR) within 30 seconds.
When Fan Relay (FR) is energized, circuit is com- plete to Indoor Blower Motor.
When G isde-energized, there is a 3 second delay before Fan Relay (FR) opens.
CARE AND MAINTENANCE
SAFE TY SWITCHES
Unit is equipped with a limit switch for each sepa- rate heating element.
These switches are normally closed and are set to open at 170 F.
Blower continues running until unit has cooled enough (below set point) for switches to automati- cally reset.
C. HEATING MODE
Thermostat closes R to W and R to G. W closes the Heat Sequencer(s) to switch line volt-
age from Terminals 1 and 4 to Terminals 3 and 5,
which energizes the Heating Elements.
G energizes the Time Delay Relay (TDR). Time Delay Relay (TDR) energizes Fan Relay (FR)
within 30 seconds.
When Fan Relay (FR) is energized, circuit is com- plete to Indoor Blower motor.
When G is de-energized there is a 3 second delay.
The system should be regularly inspected by a qualified service technician. Consult the servicing dealer for rec-
ommended frequency. Between visits, the only consumer service recommended
or required is air filter maintenance and condensate drain operation.
Air Filter
Air handlers are factory equipped with an air filter, tf the
return grille has its own filter, it is not recommended to install a filter in the Air handler.
Inspect air filters at least monthly and replace or clean as required. Disposable type filters should be replaced. Re-
usable type filters may be cleaned by soaking in mild de-
tergent and rinsing with cold water. Install filters with the arrows on the side pointing in the direction of air flow.
Condensate Drain During the cooling season check at least monthly for free
flow of drainage and clean if necessary.
10 Specilicali........ bjecltochangewithoulnotice 496 01 2100 03
Page 11
AHX3 Series
NOTE: This illustration is for reference only. Your unit may differ in appearance or may not
include all components shown
o
L
>
e
r-(
@
38-11-87a
496 01 2100 03 specilic.ti........ bj_ttoch.°gewitho.t.otic_ 11
Page 12
KEY
NO.
1
BOARD TERMINAL LINE VOLT
2
BOARD TERMINAL LO VOLT
3
GROUND LUG
4
TRANS 208/240 24 40VA
5
RELAY BLOWER DPDT
8
RELAY TIME DELAY
10
CAPACITOR 370 V 10 MFD
10
CAPACITOR 370 V 15 MFD
10
CAPACITOR 370 V 5 MFD
11
MOTOR BLR 1/230 1/3
11
MOTOR BLR 1/230 3/4
11
MOTOR BLR 1/230 1/4
12
WHEELDD10X6
12
WHEEL DD 10 X 7
12
WHEEL DD 10 X 8
12
WHEEL DD 11 X 9
13
BLOWER ASSY 13 13 13 14
VALVE TXV 1.5-3.0 1 1 -
14
VALVE TXV 3.0- 5.0 - 1 1
15
PAN DRAIN VERTICAL - 1 15 15
16
PAN DRAIN HORIZONTAL 1 1 - 16
16 19
EVAR COIL 1 - 19 19
19
GASKET/WASHER TEFLON 1 1 1 1 STUB KIT 3/8" 1 1 1 1
A
TOP PANEL 1 1 -
A
B
BLOWER/CONT. BOX DOOR 1 1 -
B C
CLOSURE DOOR 1 1 - C D
ACCESS DOOR 1 1 - D
E
CAPACITOR CLAMP 1 1 1 1 F
FILTER DOOR 1 1 - F G
THUMBSCREW 2 2 2 2
DESCRIPTION
PART NO. R68DC0018 R68DC0017
R68DC0001
R68AA0003 R68AB0001 R68AC0003
R68DE0001 R68DE0002 R68DE0003 R65BP0014 R65BP0006
R65BP0016 R69AC0001 R69AC0002 R69AB0001 R69AC0003
BRA3441 BRA4541 BRA5515
BRA5115
R72DB0005 R72DB0006
R71AA0015 R71AA0026 R71AA0028
R71AA0029 R71AA0031
R71AA0045
CA024A862T41A CA036A8E2T41A CA048A6E5X 15A
CA060A6E5X 15A
R72BA0003
R86FJ0202 R871AE017
R871X0013
R871FC001 R871XB001 R871FBX07 R871XA004 R871FBX08
R871XA005
R87NBK001
R871BA012
R871Z0010
R66AB0022
O O C, C_
X X X X
-r "r -r "r
1111 1111
1111 1111 1111 1111
-11
- - 1
1
-11
- - 1
1 1
- 1 -
- 1
- - 1
- 1 -
1
- 1
- - 1
1 1 -
- - 1
- 1
- - 1
- 1 -
- 1
- - 1
- 1 1
- 1 1
- 1 1
- 1 1
- 1 1
* Part not shown, available through FAST
12 Specifications are subject to change without notice 496 01 2100 03
Loading...