ICP *9MPT050F12, *9MPT100J16, *9MPT075F14, *9MPT125L20, *9MPV050F12 Installation Instruction

...
*9MPT & *9MPV
FAN ASSISTED,
DIRECT OR NON--DIRECT VENT
GAS FURNACE
* Denotes Brands (C, H, T)
SAFETY REQUIREMENTS
Recognize safety information. This is the safety-- alert symbol!. When you see this symbol on the furnace and in instructions manuals be alert to the potential for personal injury.
Understand the signal words DANGER,WARNING,or CAUTION. These words are used with the safety--alertsymbol. DANGER identifies the most serious hazards, those that willresult in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or death. CAUTION is used to identify unsafe practices that may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions that will result in enhanced installation, reliability, or operation.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas Code (NFGC) ANSI Z223.1--2002/NFPA No. 54--2002. In Canada, refer to the current edition of the National Standard of Canada Natural Gas and Propane Installation Code (NSCNGPIC) CSA B149.1--05. Wear safety glasses and work gloves. Have fire extinguisher available during start --up and adjustment procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Ò
International Comfort Products, LLC
Lewisburg, TN 37091
1. Safe Installation Requirements 3...................
2. Installation 4..................................
3. Combustion & VentilationAir 8....................
4. Vent & Combustion Air Piping 11...................
5. Concentric VentTermination 29....................
6. Gas Supply and Piping 32........................
!
WARNING
ELECTRIC SHOCK HAZARD Failure to follow safety
warnings exactly could result in serious injury and/or death.
Turn Off All Power Before Servicing.
Ò
Table of Contents
INSTALLER: Affix these instructions on or adjacent to the furnace.
CONSUMER: Retain these instructions for future reference.
7. ElectricalWiring 35............................
8. Ductworkand Filter 37.........................
9. Checksand Adjustments 40.....................
10. Furnace Maintenance 43........................
11. Sequenceof Operation & Diagnostics *9MPV 44......
12. Sequence of Operation & Diagnostics *9MPT 46......
TechSupport and Parts 49.........................
!
CARBON MONOXIDE POISONING AND FIRE HAZARD.
Failuretofollowsafetywarnings exactly could result in serious injury,death,and/or property damage.
This furnace is not designed for use in mobile homes, trailers or recreational vehicles.
WARNING
PrintedinU.S.A. 07/18/2005 440 01 2021 (01)
START--UP CHECK SHEET
For 90+ Furnace
(Keep this page for future reference)
Dealer Name: Address: Business Card Here City, State(Province), Zip or Postal Code:
Phone: Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Type of Gas: Natural: LP:
Which blower speed tap is used?
High Fire
For variable speed models (*9MPV), What dip switches are
selected?
High Fire
Temperature of Supply Air: High Fire (°F) or (°C)
Temperature of Return Air: (°F) or (°C)
Temp. Rise Hi Fire (Supply -- Return ): (°F) or (°C)
Lo Fire (Supply -- Return ): (°F) or (°C)
Low Fire or (Cooling)
Low Fire or (Cooling)
Low Fire (°F) or (°C)
Manual Gas Shut--Off Upstream
of Furnace/Drip--Leg? YES
Condensate Drain Connected? YES NO
Condensate Drain Trapped? YES NO
Transition Pressure switch hose relocated for U/D/H
Application? YES
Blower Speed Checked? YES NO
All Electrical Connections Tight? YES NO
Gas Valve turned ON? YES NO
Measured Line Pressure When Firing Unit:
Calculated Firing Rate:(See Checks and Adjustments Sec-
tion). (Lo)
Temperature Rise (supply--return temperature):(°F)
Measured Manifold Gas Pressure: (Lo) &(Hi)
Static Pressure (Ducts): Supply Air Return
NO
&(Hi)
NO
Filter Type and Size:
Fan “Time ON” Setting:
Fan “Time OFF” Setting:
Dealer Comments:
2
Date of Start--Up:
CO ?
CO2 ?
440 01 2021 01
1. Safe Installation Requirements
!
WARNING
FIRE, EXPLOSION, AND ASPHIXIATION HAZARD Improper adjustment, alteration, service,
maintanence or installation could cause death, personal injury and/or property damage.
Installation or repairs made by unqualified persons could result in hazards to you and others. Installation MUST conform with local codes or, in the absence of local codes, with codes of all governmental authorities having jurisdiction.
The information contained in this manual is intended for use by a qualified service agency that is experienced in such work, is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools and test instruments.
NOTE: This furnace is design--certified by the CSA International
(formerly AGA and CGA) for installation in the United States and Canada. Refer to the appropriate codes, along with this manual, for proper installation.
· Use only the Type of gas approved for this furnace (see
RatingPla te on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation. (Furnaces can be converted to L.P. gas with approved kit.)
· Install this furnace only in a location and position as speci-
fied in “2. Installation” of these instructions.
· Provide adequate combustion and ventilation air to the fur-
nace as specified in “4. Combustionand VentilationAir” of
these instructions.
· Combustion products must be discharged outdoors. Con-
nect this furnace to an approved vent system only, as spe-
cified in “5. Combustion and Ventilation Air, 6. Horizontal Venting and 7. Masonry Chimney Venting” of these in-
structions.
· Never test for gas leaks with an open flame. Use a com-
mercially available soap solution made specifically for the detection of leaks to check all connections, as specified in
“8. Gas Supply and Piping, Final Check” of these instruc-
tions.
· Always install furnace to operate within the furnace’s in-
tended temperature--rise range with a duct system which has an external static pressure within the allowable range,
as specified in “Technical Support Manual” of these in-
structions. See furnace rating plate.
· When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con­taining the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating out­side the space containing the furnace.
· A gas--fired furnace for installation in a residential garage
must be installed as specified in “2. Installation Require­ments” of these instructions.
· This furnace is not to be used for temporary heating of
buildings or structures under construction.
· This furnace is NOT approved for installation in mo-
bile homes, trailers or recreation vehicles.
· Seal around supply and return air ducts.
· Install correct filter type and size.
· Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
Safety Rules
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission encourages
installation of carbon monoxide alarms. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas--fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas--fired fireplaces, wood fireplaces.
Carbon monoxide can cause serious bodily injury and/or death. Carbon monoxide or “CO” is a colorless and odorless gas produced when fuel is not burned completely or when the flame does not receive sufficient oxygen.
Therefore, to helpalert people of potentially dangerous carbon monoxide levels, you should have a commercially available carbon monoxide alarm that is listed by a nationally recog­nized testing agency in accordance with UnderwritersLabora­tories Inc. Standard for Single and Multiple Station Carbon Monoxide Alarms, ANSI/UL 2034 or the CSA 6.19--01 Resi­dential Carbon Alarming Devices installed and maintained in the building ordwelling concurrently with the gas--firedfurnace installation (see Note below). The alarm should be installed as recommended by the alarm manufacturer’s installation in­structions.
B. There can be numerous sources of fire or smoke in a building
or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert people of potentiallydangerous fire orsmoke, you should have fire extinguisher andsmoke alarms listedby Underwriters Lab­oratories installed and maintained in the building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type of alarms.
C. To ensure safe and efficient operation of your unit, you should
do the following:
1. Thoroughly read this manual and labels on the unit. This
will help you understand how your unit operates and the haz­ards involved with gas and electricity.
2. Do not use this unit if any part has been under water. Im-
mediately call a qualified service technician to inspect the unit and to replace anypart of the control system and any gas con­trol which has been under water.
3. Never obstruct the vent grilles,or any ducts that provide air to the unit. Air must be provided for proper combustion and ventilation of flue gases.
440 01 2021 01
3
Frozen Water Pipe Hazard
!
WATER DAMAGE TO PROPERTY HAZARD FaiIure to protect against the risk of freezing may
result in property damage. Do not leave your home unattended for long periods
during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage.
Your furnace is designed solely to provide a safe and comfortable living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety de­vices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.
If your furnace remains off for an extended time, the pipes in your home could freeze and burst, resulting in serious water damage.
If the structure will be unattended during cold weather you should take these precautions.
1. Turn off the water supply to the structure and drain the water lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate areas.
CAUTION
-- o r --
2. Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.
-- o r --
3. Install a reliable remote sensing device that will notify some­body of freezing conditions within the home.
Winter Shutdown
If you go away during the winter months and do not leave the heat on in your home,the plastic transition box and the condensatetrap on the furnace must be protected from freeze damage.(See Figure 9 trough Figure 18)
1. Disconnect the5/8² OD rubber hose from the vent drain fit­ting that is located downstream of the combustion blower. Insert a funnel into the hose and pour four(4) ounces of sani­tary type (RV) antifreeze into the condensate trap. Recon­nect the fitting. Secure with the hose clamp.
2. Disconnect the3/4² OD rubber hose from the condensate trap. Insert a funnel into the hose and and pour four(4) ounces of sanitary type (RV) antifreeze into the plastic Tran­sition box. Squeeze the hose together near the end and quickly reconnect the condensate trap. Secure with the hose c lamp.
When you return home, your furnace will be ready to start, as it is not necessary to drain the antifreeze from the furnace.
5
/8² OD rubber hose to the stub on the vent drain
3
/4² ODrubber hose to the stub on the
2. Installation
!
CARBON MONOXIDE POISONING HAZARD Failure to properly vent this furnace or other
appliances could result in death or personal injury. This furnace can NOT be common vented or
connected to any type B, BW or L vent or vent connector, nor to any portion of a factory--built or masonry chimney. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See Venting and Combus- tionAirCheckin the 5.Combusion&VentilationAir section. This furnace MUST be vented to the outside.
Installation Positions
This furnace can be installed in an upflow, horizontal (either left or right) or downflow airflow position. DO NOT install this furnace on its back. For the upflow position, the return air ductwork can be at­tached to either the left or right side panel and/or the bottom. For horizontal and downflow positions, the return air ductwork must be attached to the bottom. The return air ductwork must never be at­tached to the back of the furnace.
WARNING
Location and Clearances
1. Refer to Figure 1 or Figure 2 for typical installation and basic connecting parts required. Refer to Figure 3 for typi­cal horizontal direct vent installation and basic connecting parts required. Supply and return air plenums and duct are also required.
2. If furnace is a replacement, it is usually best to install the fur­nace where the old one was. Choose the location or evalu­ate the existinglocation based uponthe minimum clearance and furnace dimensions (Figure 4 ).
!
FROZEN AND BURST WATER PIPE HAZARD FaiIure to protect against the risk of freezing may
result in property damage. Special precautions MUST be made if installing
furnace in an area which may drop below freezing. This can cause improper operation or damage to equipment. If furnace environment hasthe potential of freezing, the drain trap and drainline must be protected. The use of electric heat tape or RV antifreeze is recommended for these installations. (See“Condensate Trap Freeze Protection Section”)
CAUTION
4
440 01 2021 01
Figure 1
*8² Min. 20¢ Max. in same atmospheric zone
VentPipes MUST be supported Horizontallyand
Vertically
*Increaseminimumfrom8²
below 0 °°°° F).
T y pical Upflow Installation
Aluminumornon--rustingshield recommended. (SeeVentTermination Shielding fordimensions).
InletPipe (notusedon SinglePipe model)
DISCHARGEAIR
² to18²²²² forcoldclimates(sustainedtemperatures
²²
Couplingon endsof exhaust pipe. Total pipe & coupling out­side structure = 8²
*8² Min. 20¢ Max. insameatmosphericzone
25--23--33
Figure 2 Typical Downflow Installation
InletPipe (notusedon SinglePipe model)
VentPipes MUST besupportedHorizon­tally and Vertically
* Increaseminimum from8 ²
below 0°°°°F).
See VentTermination Shielding in VentSection.
*8² Min. 20¢ Max.insame atmosphericzone
² to18²²²² forcold climates(sustained temperatures
²²
Coupling on inside andoutsideofwallto restrainvent pipe
8² Min.
*8² Min. 20¢ Max. in same atmosphericzone
25--23--33a
Installation Requirements
1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of build-
ings or structures under construction.
3. Install furnace as centralized as practical with respect to the heat distribution system.
4. Install the vent pipes as short as practical, and in accor-
dance to these instructions. (See Vent and Combustion Air Piping section).
5. Maintain clearance for fire safety and servicing. A front clearance of 24² is required for access to the burner, con­trols and filter. See clearance requirements in Figure 4.
6. Use a raised base for upflow furnace if the floor is damp or wetattimes.
7. For downflow installations, non combustible subbase must be used under the furnace unless installation is on a non combustible floor surface. This requirement applies even when a coil box or cabinet is used.
8. For horizontal installations, line contact is permissible only between lines formed by intersection of back and two sides of furnace jacket, and building joists, studs or framing.
9. Residential garage installations require:
· Burners and ignition sources installed at least 18² above
the floor.
· Located or physically protected from possible damage by
a vehicle.
10. Local codes may require a drain pan under the entire fur­nace and condensate trap when the furnace is installed in attic application.
This furnace may be used for construction heat provided that all the following conditions are met:
· The furnace is permanently installed with all electrical wir-
ing, piping, venting and ducting installed according to these installation instructions. A return air duct is provided,sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
· The furnace is controlled by a thermostat. It may not be “hot
wired” to provide heat continuously to the structure without thermostatic control.
· Clean outside air is provided for combustion. This is to mini-
mize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
· The temperature of the return air to the furnace is main-
tained between 55° F(13° C) and 80° F(27° C) , with no eve- ning setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
· The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the rating plate value.
· The filters used to clean the circulating air during the
construction process must be either changed or thoroughly cleaned prior to occupancy.
· The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all HVAC system components after construction is completed.
· Afterconstruction is complete, verify furnace operating con-
ditions including ignition, input rate, temperature rise and venting according to these instructions.
440 01 2021 01
5
!
WARNING
CARBON MONOXIDE POISONING HAZARD. FaiIuretofollow this warning could resultindeathor
personal injury. Do NOT operate furnace in a corrosive atmosphere
containing chlorine, f luorine or any other damaging chemicals, which could shorten furnace life.
Refer to 3. Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air evaluation and remedy.
Furnace Installation Considerations
The installation ofthe furnace for a given application will dictate the position of thefurnace, the airflow, ductwork connections, vent and combustion air piping. Consideration must be given to the follow ­ing:
Horizontal Furnace Installation
Figure 3
Vent Pipe
T ypical Horizontal Installation
Inlet Pipe (not used on SinglePipe model)
Condensate Trap
Condensate Trap and Drain Lines
The supplied condensate trap must be attached to the furnace side panel on either the left or right side. For horizontal installa­tions, the drain trap is vertically attached to the side panel below the furnace. A minimum clearance of 6² below the furnace is re­quired for the condensate trap. Downward slope of the conden­sate drain line from the condensate trap to the drain location must be provided. Adequate freeze protection of the drain trap and the
drain line must be provided. See “CondensateDrainTrap”section
for further details.
Leveling
Proper leveling of the furnace must be provided to insure proper drainage of the condensate from the furnace. The furnace must be level to within and downflow installations or top to bottom for horizontal installa­tions.
1
/4² from front to back and fromside to side for upflow
Ventand Combustion Air Connections
On the Dual Certified furnace, the vent and combustion air pipes attach to the furnace through the top panel for the upflow and hori­zontal installations. For the downflow installation, the vent and combustion air pipes attach to the furnace through the alternate locations on the furnace side panels.
Note: On the Direct Vent furnace, the vent pipe attaches to the fur­nace through the side panels. The combustion air pipe attaches to the top panel or to the alternate location on the side panel. On the Single Pipe furnace, the vent pipe attaches to the furnace through the furnace side panels.
Note: Repositioning of the combustion blower is required for the vent pipe connection to the furnace through the “right side” panel.
See “Vent and Combustion Air Piping” section for further details.
25--23--34
NOTE: 5² bottom clearance required for condensate trap.
This furnace can be installed horizontally in an attic, basement, crawl s pace, alcove, or suspended from a ceiling in a basement or utility room (See Figure 3). Do notinstall furnace on its back or in the reverse airflow positions as safety control operation will be ad­versely affected.
If the furnace is to be suspended from the floor joists in a crawl space or the rafters in an attic, it is necessary to use steel pipe straps or an angle iron frame to rigidly attachthe furnace to prevent movement. These straps should be attached to the furnace with sheet metal screws and to the rafters or joists with bolts. The pre­ferred method is to use an angle iron frame bolted to the rafters or joists. (Takecaution to allowdoor panels to be removedfor mainte­nance)
If the furnace is to be installed in a crawl s pace, consult local codes. A suitable concrete pad or blocks are recommended for crawl space installation on the ground.
NOTE: 6² bottom clearance required for condensate trap.
Twenty four (24) inches between the front of the furnace and adja ­cent construction orother appliances MUSTbe maintainedfor ser ­vice clearance. (Thirty (30) inches is required to remove furnace).
Keep all insulating materials clear from louvered door. Insulating materials may be combustible.
The horizontal furnaces may be installed directly on combustible wood flooring or supports as long as all required furnace clear­ances are met. See Figure 3 .
This furnace MUST NOTbe installed directly on carpeting or tile or other combustible material other than wood flooring or supports.
For horizontal installation over a finished living space. A field fabri­cated auxiliary drain pan with drain pipe is required to prevent damage by overflow due to blocked condensate drain.
6
440 01 2021 01
Figure 4
Uni
t
Dimensions and Clearances
F
AIR INTAKE
VENT
TOP
H
G
E
LEFT SIDE
TRAP (COUNTERFLOW)
GAS
VENT
AIR INTAKE (ALTERNATE)
TRAP UPFLOW/HORIZONTAL
1
2
/
4
1
/
13
4
7
1
/
8
THERMOSTAT
215/
8
24
413/
611/
16
ELECTRICAL
11/
4
11/
16
11
13
/
16
3111/
283/
16
297/
16
8
4
1913/
16
16
13/
8
7
241/
175/
16
111/
16
47/
8
Drawing is representative, but some models may vary
D
C
BOTTOM
1
23
/
8
37/
8
ALL DIMENSIONS IN INCHES
Unit
Capacity
Cabinet Bottom Top
A B C D E F G H
*9MPT050F12 191/8175/821/8143/443/841/221/291/ *9MPT075F14 191/8175/821/8143/443/841/221/291/ *9MPT100J16 223/4211/4115/16183/443/841/225/8113/ *9MPT125L20 241/223
7
/
23 43/841/221/4121/
16
*9MPV050F12 191/8175/821/8143/443/841/221/291/ *9MPV075F12 191/8175/821/8143/443/841/221/291/
*9MPV100J20 223/4211/4115/16183/443/841/225/8113/ *9MPV125L20 241/223
7
/
23 43/841/221/4121/
16
* Dentoes Brand
A B
FRONT
2 2
8
4 2 2
8
4
COMBUSTIBLE MATERIALS FOR ALL UNITS
MINIMUM CLEARANCES TO
REAR 0
FRONT (combustion air openings in furnace and in structure)
Required For Service
ALL SIDES Of SUPPLY PLENUM 1²
SIDES 0
VENT 0
TOP OF FURNACE 1²
*30² clearance recommended forfurnaceremoval.
Horizontalposition: Line contactis permissibleonlybetween linesformedby intersectionsof top and two sides of furnace jacket,and building joists,studsor framing.
NOTE: Evaporator “A” coil drain pan dimensions may vary from furnace duct opening size. Always consult evaporator specifications for duct size requirements.
Furnace is designed for bottom return or side return.
Return air through back of furnace is NOT allowed.
1
1
/
4
7
2
913/
/
8
45/
16
3
/
2
8
11/
16
GAS
3
/
1
16
16
3311/
16
297/
273/
413/
16
11/
16
8
16
215/
8
175/
111/
7
16
16
7
4
/
8
281/
2
1
18
/
RIGHT SIDE
TRAP (COUNTERFLOW)
ELECTRICAL
AIR INTAKE(ALTERNATE)
VENT
TRAP UPFLOW/HORIZONTAL
215/
21/
131/
8
THERMOSTAT
24
2
3²
*24²
3
/
4
TYPE
40
4
4
17/
8
25--23--36b
440 01 2021 01
7
3. Combustion & Ventilation Air
For Single Pipe Installation
(Non--Direct Vent)
!
CARBON MONOXIDE POISONING HAZARD Failure to provide adequate combustion and
ventilation air could result in death or personal injury.
Use methods described here to provide combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open­ings for supplying combustion and ventilation air must comply with National Fuel Gas Code, NFPA54/ANSI Z223.1, 2002 (or current edition) and applicable provisions of local building codes.
1. Section 8.3, Air for Combustion and Ventilation, of the Nation ­al Fuel Gas Code, National Fuel Gas Code (NFGC), ANSI Z223.1--2002/NFPA 54--2002 in the U.S.,
2. Sections 7.2, 7.3, 7.5, 7.6, 7.7, and 7.8 of National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1--05 in Canada,
3. Applicable provisions of the local building code.
This furnace can NOT be c ommon vented or connected to any type B, BW or L vent or vent connector,nor to any portion ofa facto­ry--built or masonry chimney. Multistory venting i s NOT permitted. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing v ent and chimney to pre­vent oversizing problems for the other remaining appliance(s).
See “VentingandCombustionAir Check” in this section. This fur-
nace MUST be vented to the outside.
When the installation is complete, check that all appliances have
adequate combustion air and are v enting properly. See Venting AndCombustionAirCheckin “5. GasVentInstallation” Section in
this manual.
WARNING
Outdoor Combustion Air Method
A space having less than 50 cubic feet per1,000 BTUH input rating for all gas appliances installed in the space requires outdoor air for combustion and ventilation.
Air Openings and Connecting Ducts
1. Total input rating for all non direct vent gas appliances
MUST be considered when determining free area of open­ings.
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, they MUST be
no less than1/4² mesh.
4. The minimum dimension of rectangular air ducts MUST NOT be less than 3².
5. When sizing grille or louver, use the free area of opening. If free area is NOT stamped or marked on grill or louver, as­sume a 20% free area for wood and 60% for metal.
Confined Space Installation
NOTE: A confined space is defined as an area with less than 50 cubic feet per 1,000 BTUH input rating for all gas appliances installed in the area.
Requirements
1. Provide confined space with sufficient air for proper com­bustion and ventilation of flue gases using horizontal or ver­tical ducts or openings.
2. Figure 5 illustrate how to provide combustion and ventila­tion air. A minimum of two permanent openings, one inlet and one outlet, are required.
a. One opening MUST commencewithin12² of the floor
and the second opening MUST commence within 12² of the ceiling.
b. Size openings and ducts per Table 1.
Figure 5
Outside Air (This is O NLY a guide. Subject to codes of country having jurisdiction.)
This installation NOT approved in Canada
Gable Vent
Gas Vent
VentilatedAttic
TopAbove Insulation
Outlet Air (1)
VentilatedCrawl Space
Alternate Inlet Air (1)
Alternate Inlet Air (1)
Soffit Vent
Inlet Air (1)
Gas Vent
c. Horizontal duct openings require 1 square inch of free
area per 2,000 BTUH (1,100 mm2/kW) of combined input for all gas appliances in the space (see Table 1).
8
Gable Vent
VentilatedAttic
TopAbove Insulation
OutletAir (1)
Gas Vent
Outlet
Soffit Vent
Inlet Air (2)
Outlet Air (1)
Inlet Air (1)
Minimum OneInlet and One OutletAir Supply is Required May bein any Combination Shown
Inlet Air Opening Must be Within12² of floor Outlet Air Opening Must be Within12² of ceiling (1) 1 Square Inch per 4000 BTUH (2) 1 Square Inch per 2000 BTUH
Inlet Air (2)
Air (2)
d. Vertical duct openings or openings directly communicat-
ing with the outdoors require 1 square inch of free area per 4,000 BTUH (550 mm
2
/kW) for combined input of all
gas appliances in the space (see Table 1).
440 01 2021 01
3. One opening MUST be within 12² of the floor and the sec-
BTU
H
ond opening within 12² of the ceiling.
a. 1 sq. in of free area per 3,000 BTUH (700 mm
2
/kW) for
combined input of all gas appliances in the space (see Table 1) and
b. not less than the sum of the areas of allvent connectors in
the space.
The opening shall commence within 12² of the top of the enclo­sure. Appliances shallhave clearances ofat least 1² from the sides and back and 6² from the front. The opening shall directly commu­nicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
4. Size openings and ducts per Table 1. a. Indoor openings that comply with the Indoor Combus-
tion Air Method below and
b. Outdoor openings located as required in the Outdoor
Combustion Air Method above and
c. Outdoor openings sized as follows.
1) Calculate the Ratio of all Indoor Space volume divided by required volume for IndoorCombustion Air Method.
2) Outdoor opening size reduction Factor is 1 minus the Ratio in 1) above.
3) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor.
5. Horizontal duct openings require 1 square inch of free area per 2,000 BTUH of combined input for all gas appliances in area (see Table 1).
6. Vertical duct openings or openings directly to outside re­quire 1 square inch of free area per 4,000 BTUH for com­bined input of all gas appliances in area (see Table 1).
Table 1
Input
Rating
50,000 25sq.in. 16.7 sq. in. 12.5 sq. in. 4²
75,000 37.5 sq. in. 25sq. in. 18.75 sq. in. 5² 100,000 50sq.in. 33.3 sq. in. 25 sq. in. 6² 125,000 62.50 sq. in. 41.7 sq. in. 31.25 sq. in. 7²
EXAMPLE: Determining Free Area
Furnace 100,000 Furnace 100,000
Unconfined Space Installation
!
Free Area
TwoHorizontal Ducts
(sq. in./2,000 BTUH)
Water Heater
+
+
30,000
Water Heater
30,000
=
=
WARNING
Minimum FreeAreaRequired for Each Opening or Duct to Outdoors
TwoVerticalDuctsor
(sq. in./4,000BTUH)
(sq. in./3,000 BTUH)
Total Input
(130,000 ¸ 4,000)
Total Input
(130,000 ¸ 2,000)
Single Opening
==32.5 Sq. In. Vertical
65 Sq. In. Horizontal
An unconfined space is defined as an area having a minimum vol­ume of 50 cubic feet per 1,000 Btuh total input rating for all gas ap­pliances in area. Refer to Table 2 for minimum area required.
Openings
CARBON MONOXIDE POISONING HAZARD Failure to supply additional air by means of
ventilation grilles or ducts could result in death or personal injury.
An unconfined space or homes with tight construction may not have adequate air infiltration for proper combustion and ventilationofflue gases.
Most homes will require additional air.
Rd Duct
(sq. in./4,000 BTUH)
MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATIONAIR FROM INDOORS (ft3)
Table 2
ACH
0.60 1,050 1,400 1,750 1,250 1,875 2,500 3,125
0.50 1,260 1,680 2,100 1,500 2,250 3,000 3,750
0.40 1,575 2,100 2,625 1,875 2,813 3,750 4,688
0.30 2,100 2,800 3,500 2,500 3,750 5,000 6,250
0.20 3,150 4,200 5,250 3,750 5,625 7,500 9,375
0.10 6,300 8,400 10,500 7,500 11,250 15,000 18,750
0.00 NP NP NP NP NP NP NP
NP = Not Permitted Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54--2002, 8.3.3.2:
440 01 2021 01
30 40 50 50 75 100 125
Other Than Fan-Assisted Total
(1,000’sBtuh)
Fan-assisted Total
(1,000’sBtuh)
1. For other than fan--assisted appliances such as a draft hood--equipped water heater,
9
(
1000 Btu / hr
(
1000 Btu / hr
I
I
other
fan
)
)
3
Volume
2. For fan--assisted appliances such as this furnace,
Volume
If:
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
other
fan
= combined input of all other than fan--assisted
I
other
appliances in Btu/hr
I
= combined input of all fan--assisted appliancesin Btu/hr
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
21 ft
=
ACH
3
15 ft
=
ACH
· Adjoining rooms can be considered part of a space, if there
are no closable doors between rooms.
· An attic or crawl space may be considered a space that freely
communicateswith the outdoors provided there are adequate ventilation openings directly to outdoors. Openings MUSTre­main open and NOT have any means of being closed off. Ven­tilation openings to outdoors MUST be at least 1 square inch of free area per 4,000 BTUH of total input rating for all gas ap­pliances in the space.
· Combining s paces on the same floor level. Each opening
shall have a free area of at least 1² 2/1,000 BTUH (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in2 (0.06 m2). Once opening shall commence within 12² (300 mm) of the ceiling and the second opening shall commence within 12² (300 mm) of the floor. The minimumdimension of air openings shall be atleast 3² (80 mm).
· Combining spaces on different floor levels. The volumes of
spaces on different floor levels shall be considered communi­cating spaces if connected by one or more permanent open­ings in doors or floors having a free area of at least 2² 2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas ap­pliances.
· In spaces that use the Indoor Combustion Air Method, in-
filtration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be pro­vided using the methods described in section titled Outdoor Combustion Air Method:
· Unusually tight construction is defined as Construction with
1. Walls and ceilings exposed to the outdoors have a con­tinuous, sealed vapor barrier. Openings are gasketed or sealed and
2. Doors and openable windows are weather stripped and
3. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Ventilation Air
Some provincial codes and local municipalities require ventilation or make--up air be brought into the conditioned space as replace­ment air. Whichever method is used, the mixed return air tempera­ture across the heat exchanger MUST not fall below 60° so that flue gases will not condense excessively in the heat exchanger. Excessive condensation will shorten the life of the heat exchanger and possibly void your warranty.
Venting and Combustion Air Check
The following information is s upplied to allow the installer to make adjustments to the setup of existing appliances, IF REQUIRED, based on good trade practices, local codes, and good judgement of the installer. Manufacturer does NOT take responsibility for modifications made to existing equipment.
NOTE: If this installation replaces an existing furnace from a commonly vented system, the original venting system may no lon­ger be sized to properly vent the attached appliances. An improp­erly sized venting system may cause the formation of condensate in the vent and the leakage or spillage of vent gases. To make sure there is adequate combustion air for all appliances, MAKE THE
FOLLOWING CHECK.
!
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each
applianceconnected totheventing systembeingplaced into operation, could result in carbon monoxide poisoning or death:
Thefollowingstepsshall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or CSA B149.1, Natural Gas and Pro­paneInstallationCodeand these instructions. Determine
that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe con­dition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operat­ing at maximum speed. Do not operate a summerexhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so ap­pliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hoodrelief opening after5 minutesof main burner operation. Use the flame of a match or candle. (Figure 6)
8. If improper venting is observed, during any of the above tests, the venting system must be corrected in accor-
dance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning ap­pliance to their previous conditions of use.
WARNING
10
440 01 2021 01
Figure 6
Vent Check
For Two Pipe Installation
(Direct Vent)
Vent Pipe
Typical Gas Water Heater
If flame pulls towards draft hood, this indicates sufficient venting.
Draft Hood
Match
This furnace can NOT be c ommon vented or connected to any type B, BW or L vent or vent connector,nor to any portion ofa facto ­ry--built or masonry chimney. If this furnace is replacing aprevious­ly common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the
other remaining appliance(s). See “Venting and Combustion Air Check” in this section. This furnace MUST be v ented to the out-
side.
4. Vent and Combustion Air Piping
!
WARNING
CARBON MONOXIDE POISONING HAZARD. Failure to properly vent this furnace could result in
death or personal injury. Use methods described here to provide combustion
and ventilation air.
Dual Certified (*9MPT & *9MPV Models) Direct or Non-Direct Vent
This furnace is certified as a CategoryIVfurnace. This furnace can
be installed as a direct vent furnace using outside air for combus­tion or the furnace can use air from inside the s tructure for combus­tion. The INLET air pipe is optional. If combustion air comes from inside the structure, adequate make up air MUST be provided to compensate for oxygen burned. See Confined Space Installa- tion in the Combustion and Ventilation Air chapter. If c ombus ­tion air is drawn from outside the structure, it MUST be taken from the same atmospheric pressure zone as the vent pipe.
Contaminated Combustion Air
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the furnace.
The following areas or types of structures may contain or have ex­posure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion.
· Commercial buildings.
· Buildings with indoor pools.
· Furnaces installed in laundry rooms.
· Furnaces installed i n hobby or craft rooms.
· Furnaces installed near chemical storage areas.
· Permanent wave solutions for hair.
· Chlorinated waxes and cleaners.
· Chlorine based swimming pool chemicals.
· Water softening chemicals.
· De--icing salts or chemicals.
· Carbon tetrachloride.
· Halogen type refrigerants.
· Cleaning solvents (such as perchloroethylene).
· Printing inks, paint removers, varnishes, etc.
· Hydrochloric acid.
· Sulfuric Acid.
· Solvent cements and glues.
·
· Masonry acid washing materials.
Vent and Combustion Air Piping Guidelines
This furnace is approved for venting with Schedule 40 PVC, CPVC, ABS, Cellular Core pipe fittings and SDR--26 PVC.
Materials
ABS D1527 __ F628
PVC D1785 D2241 F891
CPVC F441 F442 -- -- F438 -- -- F493
ABS to
PVC
NOTE: 1) In Canada, all pipe, fittings & cements must conform to
applicable CSA standards or to local codes having jurisdiction.
the specific venting material.
vent cement that meets the requirements of ASTM D3138.
cementing plastic pipe and fittings.
NOTE: In order to create a seal that allows future removal of pipe, RTVsealant MUSTbe usedonthe inletpipewhere it joins to the
furnace. NOTE: All vent piping MUSTbeinstalledincompliancewithlocal
codes or ordinances, these instructions, good trade practices, and codes of country having jurisdiction.
1. Determine the best routing and termination for the vent pipe
2. Determine the size required for the vent pipe and air inlet
3. Loosely assemble all venting parts without adhesive (pipe
4. Furnace shall be installed so as to prevent the accumulation
Antistatic fabric softeners for clothes dryers.
Applicable ASTM Standards for Vent Materials
Sch. 40
Pipe
-- -- -- -- -- -- -- -- -- -- D3138
2) Only use solvent cements that are marked for use with
3) ABS to PVC transition joints REQUIRE a special sol-
4) Refer to ASTM D2855 for general procedure to use for
and air inlet pipe by referring to all of the instructions and guidelines in this Section.
pipe.
joint cement) for correct fit before final assembly.
of condensate.
SDR Pipe
Cell Core Pipe
Fittings Primer
D2468
&
D2661
D2466
&
D2665
-- -- D2235
F656 D2564
Solv.
Cement
440 01 2021 01
11
5. Use of vertical piping is preferred because there will be some moisture in the flue gases that may condense as it leaves the vent pipe.
6. The vertical vent pipe MUSTbe supported so that no weight is allowed to rest on the combustion blower.
7. Exhaust vent piping or air inlet piping diameter MUST NOT be reduced.
8. All exhaust vent piping from the furnace to termination MUST slope upwards. A minimum of required to properly return condensate to the furnace drain system.
9. Use DWV type long radius elbows whenever possible, as they provide for the minimum slope on horizontal runs and they provide less resistance in the vent system. If DWV el­bows cannot be used, use two, 45° elbows when possible. On horizontal runs the elbows can be slightly misaligned to provide the correct slope.
10. All horizontal pipe runs MUST be supported at least every five feet with galvanized strap or other rust resistant materi­al. NO sags or dips are permitted.
11. All vertical pipe runs MUST be supported every six feet where accessible.
12. The maximum pipe length is 40¢ total in the inlet or outlet side of the system. Up to five,90° elbows can be used on the inlet or the outlet. With the Concentric Vent TerminationKits (NAHA001CV or NAHA002CV), the maximum pipe length is 35¢ with490° elbows. If more elbows are required, reduce the length of both the inlet and exhaust pipes 5¢ for each additional elbow used. (See Table 3 or Table 4).
13. The minimum pipe run length is 2¢.
14. The piping can be run in the same chase or adjacent to sup­ply or vent pipe for water supply or waste plumbing. It can also be run in the same chase with a vent from another 90+ furnace.
NOTE:InNO case can the piping be run in a chase where temperatures can exceed 140° F. or where radiated heat from adjacent surfaces would exceed 140° F.
15. The vent outlet MUST be installed to terminate in the same atmospheric pressure zone as the combustion air inlet.
16. The vent system can be installed in an existing unused chimney provided that:
1
/4² per foot of run is
· Both the exhaust vent and air intake run the length of the
chimney.
· No other gas fired appliance or fireplace (solid fuel) is
vented into the chimney.
· The top of the chimney MUST be sealed flush or crowned
up to seal against rain or melting snow so ONLYthe piping protrudes.
· The termination clearances shown in Figure 7 are main-
tained.
17. Furnace applications with vertical vents requiring vent di­ameter increaser fittings must have increaser fittings installed in vertical portion of the vent. Condensate will be trapped in the vent if the vent diameter is increased prior to having an elbow turned upward. This could cause nuisance tripping of the pressure switch.
Combustion Air and VentPiping Insulation Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. If Fiber­glass or equivalent insulation is used it must have a vapor barrier. UseRvaluesof7upto10¢, R--11if exposure exceeds 10¢. If Fiber-
glass insulation is used, exterior to the structure, the pipe MUST be boxed in and sealed against moisture.
1. When the vent or combustion air pipe height above the roof exceeds 30², or if an exterior vertical riser is used on a hori­zontal vent to get above snow levels, the exterior portion MUST be insulated.
2. When combustion air inlet piping is installed above a sus­pended ceiling, the pipe MUST be insulated with moisture resistant insulation such as Armaflex or other equivalent type of insulation.
3. Insulate combustion air inlet piping when run in warm, hu­mid spaces.
Sizing Combustion Air and Vent Pipe
Consult Table 3 or Table 4 to select the proper diameter exhaust and combustion air piping. Exhaust and combustion air piping is sized for each furnace Btuh size based on total lineal vent length (on inlet or outlet side), and number of 90° elbows required.
1. Double Pipe Installation--If installing as a direct--vent ap- pliance, consult Table 4 to select the proper diameter ex­haust and combustion air piping. Exhaust and combustion air piping is sized for each furnace Btuh size based on total lineal vent length (on inlet oroutlet side), and number of 90° elbows required.
2. Single Pipe Installation--If installing as a non--direct vent appliance, (single outlet pipe and no inlet pipe) refer to Table 3. The table shows the maximum number of elbows allowed with any given pipe diameter and length of run.
3. Use of Elbows--Two 45° elbows can be substituted for one 90° elbow. The elbow or elbows used for vent termination outside the structure AREcounted, including elbows need­ed to bring termination above expected snow levels.
Table 3
50,000 & 75,000 Btuh Furnaces
40¢¢¢¢ & (5) 90° elbows with 2² PVC pipe
40¢¢¢¢ & (5) 90° elbows with 3² PVC pipe
40¢¢¢¢ & (5) 90° elbows with 3² PVC pipe
Elbows are DWV Long Radius Type for 2² and 3² vents.
If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5¢ foreach additional elbow used.
NOTE: It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters than shown.
Table 4
50,000 & 75,000 Btuh Furnaces
40¢¢¢¢ & (5) 90° elbows with 2² PVC pipe
40¢ & (5) 90° elbows with 3² PVC pipe
40¢ & (5) 90° elbows with 3² PVC pipe
Elbows are DWV Long Radius Type for 2² and 3² vents.
If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5¢ for each additional elbow used.
*Feetof pipe is whichever pipe run is the longest, either inlet or outlet side.
Pipe Diameter Table
Single Piping ONLY
100,000 Btuh Furnace
125,000 Btuh Furnace
Pipe Diameter Table
Dual Piping ONLY
75,000 Btuh Furnaces
100,000 Btuh Furnace
125,000 Btuh Furnace
12
440 01 2021 01
For “Concentric Termination Kit” Venting table, see “Section 11” in this manual.
VentTerminationClearances
!
CARBON MONOXIDE POISONING AND FIRE HAZARD.
Failure to properly vent this furnace could result in death, personal injury and/or property damage.
Inlet and outlet pipes may NOT be vented directly above each other.
WARNING
1. Determine termination locations based on clearances spe­cified in following steps andas shownin Figure 7, Figure 8,
Figure 20, through Figure 27.
For “Concentric Termination Kit” clearances, see Figure 30, Figure 31, Figure 32, Figure 33 and Figure 3 4 in “Section 10” in this manual.
2. This furnace is Dual Certified and can be installed as a single pipe appliance (all combustion from inside the struc­ture) or asa directvent appliance where all combustionair is taken from outside the s tructure.
3. For Single Pipe installation refer to Figure 8 for vent ter­mination c learances.
4. For Direct Vent installation, refer to Figure 7 for vent ter­mination.
440 01 2021 01
13
Figure 7
Direct Vent Te rmination Clearance
X
N
Y
Y
D
E
V
B
V
O
C
F
V
VENT TERMINAL
Item Clearance Description Canadian Installation (1)
A Clearance abovegrade, veranda, porch, deck, balcony, or
anticipated snow level
B Clearance toa window or door that may be opened 6² (15cm) forappliances £ 10,000 BTUH (3kW), 12² (30
C Clearance to a permanently closed window D Vertical clearance to a ventilated soffit locatedabovethe
terminal within a horizontal distance of 2¢ (61cm) from the centerline of the terminal
E Clearance to an unventilated soffit F Clearance toan outside corner G Clearance to an inside corner H Clearance to each side of thecenterline extendedabove
electrical meter or gas service regulator assembly
I Clearance to service regulator vent outlet 3¢ (91 cm)
J Clearance to non--mechanical air supply inlet tobuilding or
the combustion air inlet toany other appliance
K Clearance toa mechanical air supply inlet 6¢ (1.83 m) 3¢ (91cm) aboveifwithin 10¢ (3m horizontally) L Clearance under a veranda, porch,deck, orbalcony 12² (30cm) +
M Clearance to each sideof the centerline extended above or
below vent terminal of the furnace to a dryer or water heater
vent, or other appliance’s direct ventintake or exhaust. N Clearance from a plumbing vent stack 3¢ (91 cm) 3¢ (91 cm) O Clearance above a pavedsidewalk or paveddriveway located
on public property.
(1.) In accordance with thecurrentCSA B149.1, Natural Gas and Propane Installation Code (2.) In accordance with thecurrent ANSI Z223.1/NFPA 54, National Fuel GasCode #18² (46cm) aboveroof surface + Permittedonly if veranda, porch, deck, or balcony is fully open ona minimum oftwo sides beneath the floor.
B
B
V
B
B
X
AIR SUPPLYINLET
12² (30cm) # 12² (30 cm)
cm) for appliances > 10,000Btuh(3 kW) and £ 100,000 Btuh (30kW), 36² (91 cm) forappliances > 100,000Btuh (30 kW)
* * * *
* * * * * *
3¢ (91 cm) within15¢ (4.5 m) abovethe meter/regulator assembly
6² (15 cm) for appliances £ 10,000 BTUH (3kW), 9² (23 cm) for appliances > 10,000Btuh (3 kW) and £ 100,000 Btuh (30 kW) and £ 50,000 Btuh (15 kW), 12² (30 cm) forappliances > 50,000Btuh(15 kW)
12² (30cm) 12² (30cm)
7¢ (2.13 m) 7¢ (2.13 m)
B
X
J
A
H
I
L
AREA WHERE TERMINAL IS NOT PERMITED
X
G
V
K
6² (15cm) forappliances £ 10,000 BTUH (3kW), 9² (23cm) for appliances > 10,000Btuh (3 kW) and £ 50,000Btuh (15 kW), 12² (30 cm) for appliances > 50,000 Btuh(15 kW)
3¢ (91 cm) within15¢ (4.5 m) above themeter/regulator assembly
A
U.S. Installation (2)
*
6² (15 cm) for appliances £ 10,000 BTUH (3kW), 9² (23 cm) for appliances > 10,000Btuh (3 kW) and £ 50,000 Btuh (15 kW), 12² (30 cm) for appliances > 50,000Btuh(15 kW)
*
M
V
25--24--65--2
* Forclearancesnot specifiedin ANSIZ223.1/NFPA 54orCSAB149.1, clearancesshallbe inaccordance withlocal installation codesand therequirements ofthe gassupplier andthemanufacture’sinstallation
instructions.
** A vent shall not terminate directly above a sidewalk or paved driveway thatislocated between two single family dwellingsand serves both dwellings.
Notes:
1. The vent forthis appliance shall notterminate a. Over public walkways; or b. Nearsoffitvents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard orproperty damage;or c. Where condensate vapor could cause damageor could be detrimental to the operation ofregulators, relief valves, or otherequipment.
2. Whenlocatingvent terminations,considerationmustbe given to prevailingwinds, location,andother conditions which may cause recirculation of the combustion products ofadjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
14
440 01 2021 01
Figure 8
Other than Direct Vent Termination Clearance
N
Y
Y
D
E
V
B
O
V
C
F
B
V
VENT TERMINAL
Item Clearance Descriptions Canadian Installation (1)
A Clearance abovegrade, veranda, porch, deck, balcony, or
anticipated snow level
B Clearance toa window or door that may be opened 6² (15cm) forappliances £ 10,000 BTUH (3kW), 12² (30
C Clearance to a permanently closed window D Vertical clearance to a ventilated soffit locatedabovethe
terminal within a horizontal distance of 2¢ (61cm) from the centerline of the terminal
E Clearance to an unventilated soffit F Clearance toan outside corner G Clearance to an inside corner H Clearance to each side of thecenterline extendedabove
electrical meter or gas service regulator assembly
I Clearance to service regulator vent outlet 3¢ (91 cm)
J Clearance to non--mechanical air supply inlet tobuilding or
the combustion air inlet toany other appliance
K Clearance toa mechanical air supply inlet 6¢ (1.83 m) 3¢ (91cm) aboveifwithin 10¢ (3m horizontally) L Clearance under a veranda, porch,deck, orbalcony 12² (30cm) +
M Clearance to each sideof the centerline extended above or
below vent terminal of the furnace to a dryer or water heater
vent, or other appliance’s direct ventintake or exhaust. N Clearance from a plumbing vent stack 3¢ (91 cm) 3¢ (91 cm) O Clearance above a pavedsidewalk or paveddriveway located
on public property.
(1.) In accordance with thecurrentCSA B149.1, Natural Gas and Propane Installation Code (2.) In accordance with thecurrent ANSI Z223.1/NFPA 54, National Fuel GasCode #18² (46cm) aboveroof surface + Permittedonly if veranda, porch, deck, or balcony is fully open ona minimum oftwo sides beneath the floor.
B
V
B
B
X
AIR SUPPLYINLET
12² (30cm) # 12² (30 cm)
cm) for appliances > 10,000Btuh(3 kW) and £ 100,000 Btuh (30kW), 36² (91 cm) forappliances > 100,000Btuh (30 kW)
* * * *
* * * * * *
3¢ (91 cm) within15¢ (4.5 m) abovethe meter/regulator assembly
6² (15 cm) for appliances £ 10,000 BTUH (3kW), 12² (30 cm) for appliances > 10,000Btuh(3 kW) and £ 100,000 Btuh (30kW), 36² (91 cm) forappliances > 100,000Btuh (30 kW)
* *
7¢ (2.13 m) 7¢ (2.13 m)
B
X
J
A
H
I
L
X
G
V
K
AREA WHERE TERMINAL IS NOT PERMITED
4¢ (1.2m)belowor to the side of the opening. 1¢ (30 cm) above theopening.
3¢ (91 cm) within15¢ (4.5 m) above themeter/regulator assembly
A
*
4¢ (1.2m)belowor to the side ofopening:1¢ (30 cm) above opening.
*
M
V
25--24--65--2
U.S. Installation (2)
* For clearances not specifiedin ANSI Z223.1/NFPA 54 orCSA B149.1, clearances shall be inaccordance with local installation codes and therequirements ofthe gas supplier and the manufacture’s
installation instructions.
** A vent shall not terminate directly above a sidewalk or paved driveway thatislocated between two single family dwellingsand serves both dwellings.
Notes:
1. The vent forthis appliance shall notterminate a. Over public walkways; or b. Nearsoffitvents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard orproperty damage;or c. Where condensate vapor could cause damageor could be detrimental to the operation ofregulators, relief valves, or otherequipment.
2. Whenlocatingvent terminations,considerationmustbe given to prevailingwinds, location,andother conditions which may cause recirculation of the combustion products ofadjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
440 01 2021 01
15
CondensateDrain Trap
This furnace removes both sensible and latent heat from the prod­ucts of combustion. Removal of the latent heat results in con­densation of the water vapor. The condensate is removed from the furnace through the drains in the plastic transition and the vent fit­ting. The drains connect to the factory installed internally mounted condensate drain trap on the left or right side of the furnace.
The startup of a new furnace will involve a cycle or two of the fur­nace to properly prime the condensate trap with water. Until the trap is fully primed, some condensate will be pulled into the com­bustion blower. The furnace may cycleon the pressure switch con­nected to the plastic transition box due to condensate buildup. After the trap is primed, the condensate will start draining from the furnace. The combustion blower will clear out any remaining con­densate in the blower housing through the vent fitting downstream of the blower. Note that the condensate trap can also be primed by pouring water into the hose from either the gutter or the white PVC Tee Trap.Using a fun ­nel pour eight (8) ounces of water into flow through the drain hose and into the condensate drain trap. This will prime both the vent and the transition sides of the trap.Re­connect the gutter or the PVC Tee Trap.
The condensate drain trap supplied with the furnace MUST be used. The drain connection on the condensate drain trap is sized
3
/4² PVC or CPVC pipe, however alternate1/2² CPVC (nominal
for
5
/8² O.D.) or vinyl tubing with a minimum inner diameter (I.D.) of
5
/8² may also be used, as allowed by local codes. Alternate drain
pipes and hoses may be used as allowed by local codes.
The drain line must maintain a the drain.1/4² per foot is recommended. Installation of an overflow line is recommended when the1/4² per foot slope to the conden­sate drain cannot be maintained. See Figure 18 for proper routing and installation of the overflow.
DO NOT trap the drain line in any other location than at the con­densate drain trap supplied with the furnace.
If possible, DO NOT route the drain line where it may freeze. The drain line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.
1
/2² ID drain hose to the original component, either the
1
/2² drain hose. Remove the1/2² ID drain
1
/2² ID drain hose.Water will
1
/4² per footdownward slope toward
1. A condensate sump pump MUST be used if required by lo-
cal codes, or if no indoor floor drain is available. The con­densate pump must be approved for use with acidic condensate.
2. A plugged condensate drain line or a failed condensate pump will allow condensate to spill. If thefurnace is installed where a condensate spill could cause damage, it is recom­mended that an auxiliary safety switch be installed to pre­vent operation of the equipment in the event of pump failure or plugged drain line. If used, an auxiliary safety switch should be installed in the R c ircuit (low voltage) ONLY.
3. If the auxiliary switch in the condensate pump is used, the furnace may shut down due to a blocked condensate line or failed pump. To prevent frozen water pipes see the “Frozen Water Pipe Hazard” section on Page 4 of this manual.
!
CAUTION
FROZEN AND BURST WATER PIPE HAZARD Failure to do so may result in burst water pipes,
serious property damage. If a condensate pump is installed, a plugged
condensate drain or a failed pump may cause the furnace to shut down. Do not leave the home unattended during freezing weather without turning off water supply and draining water pipes or otherwiseprotectingagainsttheriskof frozenpipes.
Condensate Drain Trap Freeze Protection
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper opera­tion or damage to the equipment. If the the furnace environment has the potential of freezing, the drain trap and drain line must be protected. Use 3 to 6 watt per foot at 115volt, 40° F self--regulating shielded and waterproof heat tape. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow the heat tape manufacturer’s recommendations. Prime the trap before fur­nace operation.
16
440 01 2021 01
Figure 9
Upflow Installations Top Vent
Vent Drain &Clamps
Dual Pressure Switch Detail
FLOW
AIR
Casing Grommet Black Rubber
5
/
²
² ID
²²
8
(Loose partsbag)
Plastic Caps (2) Yellowor black
Coupling & Clamps (Optional)
DrainTee
Drain Tube Black Rubber
1
/
²
² ID&Clamps
²²
2
Drain Tube Corrugated
5
Drain ConnectorBlack PVC
3
/
²
² PVC X1/
²²
4
(Loose partsbag)
²
² CPVC
²²
2
/
²
² ID&Clamps
²²
8
EXHAUST
ON
On Some Models ONLY
Single Pressure Switch
ReliefTube Black Rubber
StreetElbow
1
/
²
² CPVC
²²
2
(Loose partsbag)
3
/
²
² ID
²²
16
INLET
V
E
N
T
IN
OFF
Drain LineVent Tee
1
/
²
² CPVC (Field supplied)
²²
2
3
/
²
² PVC or
²²
4
Drain TubeBlack Rubber5/ Cut lengthtofit (Loose parts bag)
²
² ID & Clamps,
²²
8
25--24--67
Upflow Installations Top Vent (See Figure 9)
Remove plug from the sideof the furnace casing where Drain Tube will exit.
5
Install casing grommet (black rubber
/8² ID grommet -- in loose
parts bag)
1
Install the
Install the black PVC tube connector (
/2² CPVC street elbow on discharge of Trap
3
/4² PVC x1/2² CPVC from
loose parts bag) as shown in the illustration above.
5
Cut the black Drain Tube (
/8² ID -- in loose parts bag) to length to
fit between Trap and tube connector through grommet.
Clamp both ends of the Drain Tube using clamps provided.
NOTE: “PVC” is used as a generic term. Pipe and fitting materials used must be acceptable to the local code officials having jurisdiction.
Glue the CPVC street elbow to the Trap using appropriate cleaner and solvent cement.
Connect the Tee trap and the main drain line exiting the casing as shown Figure 18.
Note: It is recommended that all PVC piping and fitting connec­tions be fit up and inspected before final cementing. Trapmustbe primed before operation. Verify all condensate drain connec­tions are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent sys­tem.
440 01 2021 01
17
Figure 10
Vent Drain &Clamps
Upflow Installations Vent thru Left Side
Dual Pressure Switch Detail
AIR FLOWAIR FLOW
Drain ConnectorBlack PVC
3
/
²
² PVC X1/
²²
4
(Loose partsbag)
Plastic Cap Yellowor black
Coupling & Clamps (Optional)
Either:The PVC Drain Teeor a field supplied 2²²²² PVC Tee
Drain Tube Black Rubber
1
/
²
² ID&Clamps
²²
2
²
² CPVC
²²
2
EXHAUST
TeeTrap White PVC (loose partsbag)
Drain Tube Corrugated
5
/
²
² ID&Clamps
²²
8
2²²²² PVC Coupling
INLET
On Some Models ONLY
V
E
N
T
IN
ON
OFF
Single Pressure Switch
ReliefTube Black Rubber
3
/
²
² ID
²²
16
SIDE VIEW
Rotate downward 5°°°° to 10°
°
°°
Casing Grommet Black Rubber
5
/
²
² ID
²²
8
(Loose partsbag)
Drain LineVentTee
3
/
²
² PVC or1/
²²
4
²
² CPVC (Fieldsupplied)
²²
2
Upflow Installations Vent thru Left Side (See Figure 10)
Remove Drain Tee from inducer discharge and remove black Drain Tube (1/2² ID) from bottom of Drain Tee. (*9MPT or V models only)
Install Vent Pipe grommet in side of casing.
Cut an appropriate length of 2² PVC pipe long enough to exit the cabinet and connect the vent drain to either:
· A2² PVC coupling fastened onto the Drain Tee (*9MPT or V models)
Install Tee trap into bottom of tee.
Install the
Install the black PVC drain connector (
1
/2² CPVC street elbow on discharge of Trap
3
/4² PVC x1/2² CPVC from
loose parts bag) as shown in the illustration above.
Cut the black Drain Tube (5/8² ID -- in loose parts bag) to length to fit between Trap and tube connector through grommet.
Clamp both ends of the Drain Tube using clamps provided.
Glue the CPVC street elbow to the Trap using appropriate cleaner and solvent cement.
Connect the Tee trap and the main drain line exiting the casing as shown in Figure 18.
Note: It is recommended that all PVC piping and fitting connec­tions be fit up and inspected before final cementing. Both the in-
ternal Trap and the external Tee Trap must be primed before operation. Verify all condensate drain connections are securely
clamped. A c oupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
NOTE: Built- -inchannel will be angled5° to 10° also.
25--24--67a
18
440 01 2021 01
Figure 11
All Models Vent thru Right Side
Plastic Cap Yellowor black
INLET
Dual Pressure Switch
On Some Models ONLY
Vent Drain &Clamps
Drain Tube Corrugated
5
/
²
² ID&Clamps
²²
8
SIDE VIEW
Rotate downward 5°°°° to 10°
Relief Tube Black Rubber
3
/
²
² ID
²²
V
E
N
T
IN
ON
OFF
16
Either:The PVC Drain Teeor a field supplied 2²²²² PVC Tee
Single Pressure Switch Details
2²²²² PVC Coupling
EXHAUST
AIR FLOW
TeeTrap White PVC (loose partsbag)
Elbow Tubes(2) Black Rubber
1
/
²
² ID&Clamps
²²
2
(loose partsbag)
Barbed Coupling,1/ (loose partsbag)
°
°°
²
² OD
²²
2
²
² CPVC
²²
2
3
/
4
Drain LineVentTee
1
/
²
² CPVC (Field supplied)
or
²²
2
Drain ConnectorBlack PVC
3
/
²
² PVC X1/
²²
4
(Loose partsbag)
²
² PVC
²²
NOTE: Built- -inchannel will be angled5° to 10° also.
All Models Vent thru Right Side (See Figure 11)
Disconnect the black Drain Tube between the drain vent and the Trap.
Rotate the inducer 180° for a right side vent after loosening the 4 inducer attachment screws. Reinstall and retighten the inducer screws to 20² pounds torque.
Using the1/2² OD barbed coupling in the loose parts bag connect together with the 2 short1/2² ID elbow tubes and connect the lower discharge port of the vent drain to the Trap. Secure allconnections with clamps.
Install the vent pipe grommet into the casing
Cut an appropriate length of 2² PVC pipe long enough to exit the cabinet and connect the vent drain to either:
· A2² PVC coupling fastened onto the Drain Tee
Install Tee Trap into bottom section of Tee.
Remove plug from the sideof the furnace casing where Drain Tube will exit.
Casing Grommet Black Rubber (Loose partsbag)
Install casing grommet (black rubber
5
/
²
² CPVC
²²
8
5
/8² ID grommet -- in loose
25--24--68
parts bag)
1
Install the
Install the black PVC tube connector (
/2² CPVC street elbow on discharge of Trap
3
/4² PVC x1/2² CPVC from
loose parts bag) as shown in the illustration above
5
Cut the black Drain Tube (
/8² ID -- in loose parts bag) to length to
fit between Trap and tube connector through grommet.
Clamp both ends of the Drain Tube using clamps provided.
Glue the CPVC street elbow to the Trap using appropriate cleaner and solvent cement.
Connect the Tee trap and the main drain line exiting the casing as shown in Figure 18.
Note: It is recommended that all PVC piping and fitting connec­tions be fit up and inspected before final cementing. Both the in-
ternal Trap and the external Tee Trap must be primed before operation. Verify all condensate drain connections are securely
clamped. A c oupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
440 01 2021 01
19
Loading...
+ 44 hidden pages