Amber LED On Solid............................................................................10
Improper Cooling Air Flow...................................................................11
Minimum and/or Maximum Heat Temperature Rise Too Low............13
Secondary Voltage Fuse Open ..............................................................14
Status Code 2 - Pressure Switch Did Not Open....................................16
Status Code 3 - Low Pressure Switch Did Not Close or Reopened ..... 17
Status Code 4 - Limit Circuit Fault.......................................................19
Status Code 5 - Abnormal Flame-Proving Signal.................................21
Status Code 6 - Ignition-Proving Fault .................................................21
Status Code 7 - Limit Circuit Lockout..................................................23
Status Code 8 - Gas Heating Lockout ...................................................24
Status Code 9 - Medium Pressure Switch, High Pressure Switch, or
PSR Relay did not Close or Reopened.........................................24
Status Code 10 - Polarity....................................................................... 27
Status Code 1 + 2 - Blower On After Power Up...................................28
Status Code 1 + 5 - Blower Motor Lockout..........................................28
Status Code 2 + 5 - Model Selection or Setup Error ............................29
Status Code 3 + 5 - Gas Valve Fault.....................................................30
Status Code 4 + 1 - Blower Motor Fault...............................................32
Status Code 4 + 2 - Inducer Motor Fault .............................................. 34
Status Code 4 + 3 - Low or Medium Pressure Switch Open While
Medium or High Pressure Switch Is Closed................................. 36
Status Code 6 + 1 - Ignition Lockout....................................................37
Cleanup and Start-Up Instructions........................................................37
APPENDIX A - Board Layout & Wiring Schematic........................... 38
APPENDIX B - ECM Blower Motor Description & Operation..........40
APPENDIX C - Pressure Check Diagram............................................ 42
APPENDIX D - Static Pressure Reading Location Diagrams..............43
APPENDIX E - Quick Reference Information..................................... 45
APPENDIX F - Furnace Staging Algorithm ........................................ 46
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified personnel
should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils, or cleaning and replacing filters. All other
operations should be performed by trained service personnel. When
working on heating equipment, observe precautions in literature, on
tags, and on labels attached to or shipped with the unit, and other
safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes
including the National Fuel Gas Code (NFGC) NFPA 54-2006/ANSI
Z223.1-2006. In Canada, refer to the National Standard of Canada
Natural Gas and Propane Installation Codes (NSCNGPIC), CSA
B149.1-05.
Wear safety glasses and work gloves. Have a fire extinguisher
available during start-up, adjustment procedures, and service calls.
Recognize safety information. This is the safety-alert symbol.
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION, and NOTE. The words DANGER, WARNING, and
CAUTION are used with the safety-alert symbol.DANGER
identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal injury, or
product and property damage.NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
INSTRUCTIONS
This guide uses your expertise and observations to lead you to the
trouble spot as efficiently as possible. This is only intended as a
guide and should not be used blindly. Your experience and expertise
are of high value when troubleshooting this unit. Do not disregard
all of your instincts.
The modulating furnace control was designed with diagnostic
capabilities built in. A AMBER LED is used to flash a status code
which will lead you to one of the sections as listed in the Index.
-1-Replaces: NewForm: ICP Eng
3-12
You should ALWAYS begin in the START HERE section (see
440 08 4001 00
Index for page number) which will guide you to the appropriate
to the step indicated in the YES column. If the answer is NO, go to
the step indicated in the NO column.
section where a minimal number of steps will be used to correct the
problem. Once in a section, read the ACTION. An ACTION may
have a number in the GO TO column. Do whatever the ACTION
says, then proceed to the step indicated in the GO TO column.
Let’s try our guide out using the EXAMPLE section below, and see
how it works. Suppose that the problem is a defective low pressure
switch (for example the contacts will not open). This is an internal
problem and cannot simply be seen. We go to the START HERE
If the ACTION is a question (a question will have a number in the
section to Step 1.
YES or NO column), answer it YES or NO. If the answer is YES, go
EXAMPLE
Start Here Section
STEPACTIONYESNOGO TO
1.Step 1 tells us NOT TO REMOVE THE BLOWER DOOR. It then asks the question, “Is
219
AMBER LED status light ON SOLID, alternately flashing bright-dim-bright-dim like a
heartbeat, or flashing ON and OFF?”. If the low pressure switch was defective, a pressure
switch did not open status code would be flashing, so the answer is YES. We go to Step 2.
2.Step 2 asks the question, “Is the AMBER LED status light ON SOLID?”. If the low pressure
34
switch was defective, a pressure switch did not open status code would be flashing, so the
answer is NO. We go to Step 4.
4.Step 4 asks the question, “Is the AMBER LED status light alternately flashing bright-dim-
75
bright-dim like a heartbeat?”. If the low pressure switch was defective, a pressure switch did
not open status code would be flashing, so the answer is NO. We go to Step 5.
5.Step 5 tells us to determine the status code. The status code is a single or two digit number
with the first number determined by the number of short flashes and the second number after
the (+) sign is the number of long flashes. So we count the short flashes and long flashes if
available and see that status code 2 is flashing and go to Step 6.
6.Step 6 tells us to go to status code 2 section.INDEX
6
GENERAL
The furnace must have a 115-vac power supply properly connected
and grounded. Correct polarity must be maintained to enable gas
heating operation.
The gas service pressure must not exceed 0.5 psig (14-in.wc), and no
less than 0.16 psig (4.5-in.wc).
Thermostat wire connections to the furnace at R and W/W1 are the
minimum required for gas heating operation. W2 must be connected
for 2-stage heating thermostats. Y/Y2 and G are required to be
connected to the furnace for single-stage cooling and heat pumps.
Y1, Y/Y2, and G are required for two-stage cooling and heat pumps.
G is required for continuous-fan. COM-24V is required for some
clock thermostats. These connections must be made at the 24-vac
terminal block on the furnace control. (See Appendix A)
This furnace can be installed with either a single-stage heat/cool or a
two-stage heat/cool thermostat.
!
CAUTION: This furnace is equipped with a manual
reset switch in the gas control area. The switch will open
and shut off power to the gas valve, if a flame rollout or
overheating condition occurs in the gas control area. DO
NOT bypass the switch. Correct inadequate combustionair supply, or component failure before resetting the
switch.
Before operating the furnace, check each manual reset switch for
continuity. If necessary, press and release the button to reset the
switch.
SEQUENCE OF OPERATION
Using the schematic diagram in Appendix A, follow the sequence of
operation through the different modes. Read and follow the wiring
diagram very carefully!!
Note: If a power interruption occurs during a call for heat (W/W1
or W/W1-and-W2), the control will start a 90-second blower-only
ON period two seconds after power is restored, if the thermostat is
still calling for gas heating. The amber LED light will flash code 12
during the 90-second period, after which the LED will be ON
continuous, as long as no faults are detected. After the 90-second
period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through
the blower door interlock switch ILK to the furnace control CPU,
transformer TRAN, inducer motor IDM, blower motor BLWM, hotsurface igniter HSI, and gas valve GV.
COMMUNICATING CONTROL ANDMODULATING
HEATING
Best comfort will be attained when a Communicating Wall Control is
used with this product. Wiring and set-up instructions are provided
with the communicating control. See the furnace data sheet accessory
section for help in selecting the appropriate communicating control
for this furnace.
When a communicating control is used, the furnace will modulate
through its full operation range, or can be limited via the minimum
and maximum cfm configurations.
Operation of the furnace at the beginning and end of each heating
cycle, will be the same as detailed below in the Single-Stage
- 2 -
Thermostat section, EXCEPT that the communicating control will
440 08 4001 00
send modulating rate command signals through the communication
bus rather than energizing the 24-v thermostat terminals.
SINGLE-STAGE THERMOSTAT AND MODULATING
HEATING (ADAPTIVEMODE)
Note: Minimum-heat only switch SW1-2 selects the minimum-heat
only operation mode when ON. Intermediate-heat only switch SW42 selects intermediate-heat only operation mode when ON. If both
switches are ON the furnace control will default to intermediate-heat.
If either or both switches are ON the furnace control will operate at
two-stages only as referenced in the Two Stage Thermostat section
below. If both switches are OFF the furnace control will operate in
the adaptive heating mode in response to a call for heat. When the
W2 thermostat terminal is energized it will always cause maximumheat operation as long as the R to W circuit is closed, regardless of
the setting of the minimum-heat or intermediate-heat only switches.
This furnace can operate as a modulating furnace with a single-stage
thermostat because the furnace control CPU includes a programmed
adaptive sequence of controlled operation, which selects a modulated
rate between minimum- and maximum-heat. This selection is based
upon the stored history of the length of previous gas-heating periods
of the single-stage thermostat.
The furnace will start up in either intermediate-, or maximum-heat.
The furnace will transition and operate at minimum-heat or the
calculated modulating rate after starting and operating for 45 seconds
at intermediate-heat. The furnace control CPU defaults to minimumheat on the first thermostat cycle and calculates the modulating rate
that the furnace should run at for 19 minutes on subsequent heat
cycles.
If the power is interrupted, the stored modulating rate is erased and
the furnace control will select intermediate-heat for 45 seconds,
minimum-heat for 19 minutes and then switch to maximum-heat, as
long as the thermostat continues to call for heat. The furnace control
CPU then uses this information to calculate the modulating rate the
furnace will operate at on the next heating cycle. If the calculated
modulating rate is between 40% - 99% then the furnace control CPU
will operate for 45 seconds at intermediate-heat, and then operate at
the calculated modulating rate for up to 19 minutes and then switch
to maximum-heat as long as the thermostat continues to call for heat.
If the calculated modulating rate is 100% then the furnace control
will only operate at maximum-heat until the thermostat is satisfied.
The wall thermostat ”calls for heat”, closing the R to W circuit. The
furnace control CPU performs a self-check, verifies the low, medium,
and high pressure switch contacts LPS, MPS, and HPS are open,
then de-energizes the PSR relay to close the NC contact.
Note: The heat cycle can start in either intermediate- or maximum-
heat. If a maximum-heat cycle is initiated, the furnace control CPU
will continue to increase the inducer motor speed after the medium
pressure switch MPS closes. When the medium pressure switch
closes, inducer motor RPM is noted by the furnace control CPU, and
a 25-second prepurge period begins. The RPM is used to evaluate
vent system resistance. This evaluation is then used to determine the
required RPM necessary to operate the inducer motor in maximumheat pre-purge, and maximum-heat mode. The high pressure switch
HPS should be closed before ignition but the furnace control ignores
this input until after ignition occurs.
2.Igniter Warm-Up - At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second igniter
warm-up period.
3.Trial-For-Ignition Sequence - When the igniter warm-up
period is completed the main gas valve relay contact GVR
closes to energize the gas valve solenoid GV (pin PL17-5). The
gas valve solenoid GV permits gas flow to the burners where it
is ignited. Five seconds after the GVR closes, a 2-second
Flame-Proving period begins. The HSI igniter will remain
energized until flame is sensed or until the 2-second flame
proving period begins.
4.Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control CPU
begins the blower-ON delay period and continues to hold the
gas valve GV open. If the burner flame is not proved within
two seconds, the furnace control CPU will close the gas valve
GV, and the furnace control CPU will repeat the ignition
sequence for up to three more Trials-For-Ignition before going
to Ignition-Lockout. Lockout will be reset automatically after
three hours, by momentarily interrupting 115 vac power to the
furnace, or by interrupting 24 vac power at SEC1 or SEC2 to
the furnace control CPU (not at W/W1, G, R, etc.).
If flame is proved when flame should not be present, the furnace
control CPU will lock out of Gas-Heating mode and operate the
inducer motor IDM at full speed until flame is no longer
proved.
5.Inducer Speed Change – If the cycle starts in intermediate-
heat, the furnace control CPU reduces the inducer speed slightly
after flame sense. If the cycle starts in maximum-heat, the
furnace control CPU increases the inducer speed after flame
sense.
6.Blower-On delay – If the burner flame is proven the blower-
ON delay for intermediate-heat and maximum-heat are as
follows:
1.Inducer Prepurge Period - The furnace control CPU turns on
inducer motor IDM and slowly increases the inducer motor
speed. After the low pressure switch LPS closes the furnace
control CPU continues to increase the inducer motor speed until
the medium pressure switch MPS closes. When the medium
pressure switch MPS closes, inducer motor RPM is noted by
the furnace control CPU, and a 25-second prepurge period
begins. The RPM is used to evaluate vent system resistance.
This evaluation is then used to determine the required RPM
necessary to operate the inducer motor during prepurge, the first
45 seconds of intermediate-heat mode, or any modulating rate
that the furnace will transition to after the blower on-delay is
completed.
Intermediate-heat – 45 seconds after the gas valve GV is
opened the blower motor BLWM is turned ON at the
modulating heat airflow.
Maximum-heat – 25 seconds after the gas valve GV is opened
the BLWM is turned ON at maximum-heat airflow.
Simultaneously, the humidifier terminal HUM and electronic air
cleaner terminal EAC-1 are energized and remain energized
throughout the heating cycle.
7.Switching fromIntermediate-Heat to a Low Range Input- If
the furnace control switches from intermediate-heat to a low
- 3 -
range input (low range input is an input rate less than or equal
440 08 4001 00
to 51% of full rate, 45% of full rate on the 5T-060 model), the
furnace control will turn the blower ON or switch to the
modulating heat airflow, energize the PSR relay to open the NC
contact, and slowly decrease the inducer motor speed to the
desired inducer RPM.
Switching from Intermediate-Heat to a Medium Range
Input - If the furnace control CPU switches from intermediate-
heat to a different medium range input (medium range input is
an input rate between 52% and 71% of full rate, 46% and 71%
of full rate on the 5T-060 model), the furnace control CPU will
turn the blower ON or switch to the modulating heat airflow,
and continue to maintain the inducer motor speed or change it
further if required.
Switching from Intermediate-Heat to a High Range Input -
If the furnace control CPU switches from Intermediate-heat to a
high range input (high range input is an input rate greater than
or equal to 72% of full rate), the furnace control CPU will turn
the blower ON or switch to the modulating heat airflow, and
increase the inducer motor speed to the desired inducer motor
RPM.
Switching fromLow Range Input to Maximum-Heat - If the
furnace control CPU switches from a low range input to
maximum-heat, the furnace control CPU de-energize the PSR
relay to close the NC contact and slowly increase the inducer
motor speed until the medium pressure switch MPS closes.
When the medium pressure switch MPS closes the inducer
motor RPM is noted by the furnace control CPU. The RPM is
used to evaluate vent system resistance. This evaluation is then
used to determine the required RPM necessary to operate the
inducer motor at maximum-heat. The blower motor BLWM
will transition to maximum-heat airflow five seconds after the
furnace control CPU switches from a low range input to
maximum-heat.As the inducer RPM increases the high
pressure switch HPS should close.
Switching from Medium Range Input to Maximum-Heat -
If the furnace control CPU switches from a medium range input
to maximum-heat, the furnace control CPU will increase the
inducer motor speed to the maximum-heat inducer motor RPM.
The blower motor BLWM will transition to maximum-heat
airflow five seconds after the furnace control CPU switches
from a medium range input to maximum-heat. As the inducer
RPM increases the high pressure switch HPS should close.
W1-and-W2 circuits always causes maximum-heat operation,
regardless of the setting of the minimum-heat only switch.
The furnace will start up in either intermediate-, or maximum-heat.
The furnace will operate in minimum-heat after starting and
operating for 45 seconds at intermediate-heat before transitioning to
minimum-heat.
The wall thermostat "calls for heat", closing the R to W1 circuit for
minimum-heat or closing the R to W1-and-W2 circuits for
maximum-heat. The furnace control performs a self-check, and
verifies the low, medium, and high pressure switch contacts LPS,
MPS, and HPS are open, then de-energizes the PSR relay to close the
NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage minimum/maximum heating mode as well,
except for switching from maximum- to minimum-heat.
1.Switching from Maximum- to Minimum-Heat - If the
thermostat R to W2 circuit opens, and the R to W1 circuit
remains closed, the furnace control CPU will gradually decrease
the inducer motor speed to the required intermediate-heat RPM.
When the inducer motor IDM reduces pressure sufficiently, the
high pressure switch HPS will open and the gas rate will be
changed to intermediate-heat. The gas valve solenoid GV (pin
PL17-5) will remain energized as long as the low pressure
switch LPS remains closed. When the inducer motor speed gets
within 15% of the required intermediate-heat RPM the furnace
control CPU will start a 5 second blower airflow change delay.
After the 5 second blower airflow change delay is completed the
blower airflow will transition to minimum-heat airflow. At this
point the furnace control CPU will energize the PSR relay to
open the NC contact and slowly decrease the inducer motor
speed to the required minimum-heat RPM. When the PSR
relay is energized and the NC contact opens the furnace control
CPU will reduce the gas rate to minimum-heat.
TWO-STAGE THERMOSTAT AND TWO-STAGE
INTERMEDIATE/MAXIMUM HEATING
Note: In this mode the intermediate-heat only switch SW4-2 must
be ON to select the intermediate-heat only operation mode in
response to closing the thermostat R to W1 circuit. Closing the
thermostat R to W1-and-W2 circuits always causes maximum-heat
operation, regardless of the setting of the intermediate-heat only
switch.
8.Blower-Off Delay - When the thermostat is satisfied, the
R to W circuit is opened, de-energizing the gas valve GV,
stopping gas flow to the burners, and de-energizing the
humidifier terminal HUM. The inducer motor IDM will remain
energized for a 15-second post-purge period. The blower motor
BLWM and air cleaner terminal EAC-1 will remain energized
at minimum-heat airflow or transition to minimum-heat airflow
for 90, 120, 150, or 180 seconds (depending on selection at
blower-OFF delay switches). The furnace control CPU is
factory-set for a 120-second blower-OFF delay.
TWO-STAGE THERMOSTAT AND TWO-STAGE
MINIMUM/MAXIMUM HEATING
Note: In this mode the minimum-heat only switch SW1-2 must be
ON to select the minimum-heat only operation mode in response to
closing the thermostat R to W1 circuit. Closing the thermostat R to
The wall thermostat "calls for heat", closing the R to W1 circuit for
intermediate-heat or closing the R to W1-and-W2 circuits for
maximum-heat. The furnace control performs a self-check, and
verifies the low, medium, and high pressure switch contacts LPS,
MPS, and HPS are open, then de-energizes the PSR relay to close the
NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage intermediate/maximum heating mode as well,
except for switching from maximum- to intermediate-heat.
1.Switching from Maximum- to Intermediate-Heat – If the
thermostat R to W2 circuit opens, and the R to W1 circuit
remains closed, the furnace control CPU will gradually decrease
the inducer motor speed to the required intermediate-heat RPM.
When the inducer motor IDM reduces pressure sufficiently, the
high pressure switch HPS will open and the gas rate will be
changed to intermediate-heat. When the inducer motor speed
- 4 -
gets within 15% of the required intermediate-heat RPM the
440 08 4001 00
furnace control CPU will start a 5 second blower airflow change
delay. After the 5 second blower airflow change delay is
completed the blower airflow will transition to intermediateheat airflow.
COOLING MODE
The thermostat "calls for cooling".
1.Single-SpeedCooling
The thermostat closes the R to G-and-Y circuits. The R to Y
circuit starts the outdoor unit, and the R to G-and-Y/Y2 circuits
start the furnace blower motor BLWM on cooling airflow.
Cooling airflow is based on the A/C selection shown in Table 1.
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuits are
opened. The outdoor unit will stop, and the furnace blower
motor BLWM will continue operating at cooling airflow for an
additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the
cooling off-delay to 5 seconds. (See Fig. 1.)
2.Two-StageThermostat and Two-SpeedCooling
The thermostat closes the R to G-and-Y1 circuits for lowcooling or closes the R to G-and-Y1-and-Y2 circuits for highcooling. The R to Y1 circuit starts the outdoor unit on lowcooling speed, and the R to G-and-Y1 circuit starts the furnace
blower motor BLWM at low-cooling airflow which is the true
on-board CF selection as shown in Table 1.The R to
Y1-and-Y2 circuits start the outdoor unit on high-cooling
speed, and the R to G-and-Y/Y2 circuits start the furnace
blower motor BLWM at high-cooling airflow. High-cooling
airflow is based on the A/C selection shown in Table 1.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y1 or
R to G-and-Y1-and-Y2 circuits are opened. The outdoor unit
stops, and the furnace blower BLWM and electronic air cleaner
terminal EAC-1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling off-delay
to 5 seconds. (See Fig. 1.)
DEHUMIDIFICATION MODE
The dehumidification output, D or DHUM on a Thermostat should
be connected to the furnace control thermostat terminal DHUM.
When there is a dehumidify demand, the DHUM input is activated,
which means 24 vac signal is removed from the DHUM input
terminal. In other words, the DHUM input logic is reversed. The
DHUM input is turned ON when no dehumidify demand exists.
Once 24 vac is detected by the furnace control on the DHUM input,
dehumidification capability is activated. If the DHUM input is low
for more than 48 hours, the furnace control reverts back to nondehumidification mode.
The cooling operation described above in the Cooling Mode section
also applies to Dehumidification Mode. The exceptions are listed
below:
1.Low Cooling - When the R to G-and-Y1 circuit is closed and
there is a demand for dehumidification, the furnace blower
motor BLWM will drop the blower airflow to 86% of lowcooling airflow which is the true on-board CF selection as
shown in Table 1.
2.High Cooling - When the R to G-and Y/Y2 circuit is closed
and there is a demand for dehumidification, the furnace blower
motor BLWM will drop the blower airflow to 86% of highcooling airflow. High-cooling airflow is based on the A/C
selection shown in Table 1.
- 5 -
3.Cooling Off-Delay - When the “call for cooling” is satisfied
440 08 4001 00
and there is a demand for dehumidification, the cooling bloweroff delay is decreased from 90 seconds to 5 seconds.
SUPER-DEHUMIDIFY MODE
Super-Dehumidify mode can only be entered if the furnace control is
in the Dehumidification mode and there is a demand for
dehumidification. The cooling operation described in the Cooling
Mode section above also applies to Super Dehumidify Mode. The
exceptions are listed below:
1.Low Cooling – When the R to Y1 circuit is closed, R to G
circuit is open, and there is a demand for dehumidification, the
furnace blower motor BLWM will drop the blower airflow to
65% of low-cooling airflow for a maximum of 10 minutes each
cooling cycle or until the R to G circuit closes or the demand for
dehumidification is satisfied. Low-cooling airflow is the true
on-board CF selection as shown in Table 1.
2.High Cooling – When the R to Y/Y2 circuit is closed, R to G
circuit is open, and there is a demand for dehumidification, the
furnace blower motor BLWM will drop the blower airflow to
65% of high-cooling airflow for a maximum of 10 minutes each
cooling cycle or until the R to G circuit closes or the demand for
dehumidification is satisfied. High-cooling airflow is based on
the A/C selection shown in Table 1.
3.Cooling Off-Delay – When the “call for cooling” is satisfied
and there is a demand for dehumidification, the cooling bloweroff delay is decreased from 90 seconds to 5 seconds.
seconds at high-cooling airflow before transitioning back to
continuous-blower airflow.
When the R to G circuit is opened, the blower motor BLWM will
continue operating for an additional 5 seconds, if no other function
requires blower motor BLWM operation.
HEATPUMP DEFROST
When installed with a heat pump, the furnace control automatically
changes the timing sequence to avoid long blower off times during
demand defrost cycles. Whenever W/W1 is energized along with Y1
or Y/Y2, the furnace control CPU will transition to or bring on the
blower motor BLWM at cooling airflow, minimum-heat airflow, or
the midrange airflow, whichever is lowest. The blower motor
BLWM will remain on until the main burners ignite then shut OFF
and remain OFF for 25 seconds before coming back on at
modulating heat airflow. When the W/W1 input signal disappears,
the furnace control begins a normal inducer post-purge period while
changing the blower airflow. If Y/Y2 input is still energized the
furnace control CPU will transition the blower motor BLWM airflow
to cooling airflow. If Y/Y2 input signal disappears and the Y1 input
is still energized the furnace control CPU will transition the blower
motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM will
remain on at minimum-heat airflow for the selected blower-OFF
delay period. At the end of the blower-OFF delay, the blower motor
BLWM will shut OFF unless G is still energized, in which case the
blower motor BLWM will operate at continuous blower airflow.
COMPONENT TEST
CONTINUOUS BLOWER MODE
When the R to G circuit is closed by the thermostat, the blower motor
BLWM will operate at continuous blower airflow. Continuous
blower airflow selection is initially based on the CF selection shown
in Table 1. Factory default is shown in Table 1. Terminal EAC-1 is
energized as long as the blower motor BLWM is energized.
During a call for heat, the furnace control CPU will transition the
blower motor BLWM to continuous blower airflow, minimum-heat
airflow, or the midrange airflow, whichever is lowest. The blower
motor BLWM will remain ON until the main burners ignite then shut
OFF and remain OFF for the blower-ON delay (45 seconds in
intermediate-heat, and 25 seconds in maximum-heat), allowing the
furnace heat exchangers to heat up more quickly, then restarts at the
end of the blower-ON delay period at modulating or maximum-heat
airflow respectively.
The blower motor BLWM will revert to continuous-blower airflow
after the heating cycle is completed. When the thermostat satisfies,
the furnace control CPU will drop the blower motor BLWM to
minimum-heat airflow during the selected blower-OFF delay period
before transitioning to continuous-blower airflow.
When the thermostat "calls for low-cooling", the blower motor
BLWM will switch to low-cooling airflow. When the thermostat is
satisfied, the blower motor BLWM will operate an additional 90
seconds at low-cooling airflow before transitioning back to
continuous-blower airflow.
The furnace features a component test system to help diagnose a
system problem in the case of a component failure. To initiate the
component test procedure, ensure that there are no thermostat inputs
to the control and all time delays have expired. Turn on setup switch
SW1-6. (See Appendix A)
Note: The component test feature will not operate if the control is
receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows:
1.The furnace control CPU turns the inducer motor IDM ON at
medium speed and keeps it ON through step 4.
2.The furnace control CPU will test communication with the
modulating gas valve GV.
3.After waiting 15 seconds the furnace control CPU turns the hot
surface igniter ON for 15 seconds, then OFF.
4.The furnace control CPU then turns the blower motor BLWM
on at midrange airflow for 15 seconds, then OFF.
5.After shutting the blower motor OFF the furnace control CPU
shuts the inducer motor IDM OFF.
Note: The EAC terminals are energized when the blower is
operating.
After the component test is completed, 1 or more status codes
(Heartbeat, 2 + 5, 3 + 5, 4 + 1, or 4 + 2) will flash. See Service Label
on control door or Service/Status Code Instructions for explanation
of status codes.
When the thermostat "calls for high-cooling", the blower motor
BLWM will switch to high cooling airflow. When the thermostat is
satisfied, the blower motor BLWM will operate an additional 90
Note: To repeat component test, turn setup switch SW1-6 to OFF
and then back ON.
- 6 -
SERVICE/STATUS CODE INSTRUCTIONS
440 08 4001 00
If status code recall is needed disconnect the “R” thermostat lead, reset power, and put setup switch “SW1-1” in the ON position. To clear the status
code history put setup switch “SW1-1” in the ON position and jumper thermostat terminals “R”, “W/W1”, and “Y/Y2” simultaneously until the
Heartbeat flashes.
LED CODESTATUS
CONTINUOUSOFF -Check 115 VAC at L1 and L2, 24 VAC at SEC-1 and SEC-2, and 24V fuse.
HEARTBEAT -(bright-dim-bright-dim) Control has 24 VAC power.
ON SOLID -The control is locked out and will auto reset after 1 hour. Lockout could be due to any of the following:
-Flame sense circuit failure.
-Gas valve relay stuck open.
-Software check error.
Reset power to clear lockout. Replace control if status code repeats.
EACHOF THE FOLLOWING STATUS CODES IS A SINGLE OR TWO DIGIT NUMBERWITH THE FIRST NUMBERDETERMINED
BY THE NUMBER OF SHORT FLASHES AND THE SECOND NUMBER AFTER THE (+) SIGN IS THE NUMBER OF LONG
FLASHES.
2PRESSURE SWITCH DID NOTOPEN – Check for:
-Obstructed pressure tubing.
-Pressure switch stuck closed.
3LOW PRESSURESWITCHDID NOT CLOSE OR REOPENED – Indicates the low pressure switch input failed to close on a call for
heat, or opened during minimum-heat. If opens during blower on-delay period, blower will come on for the selected blower off-delay. If
opens within 5 minutes after ignition the next heating cycle will be restricted to maximum-heat. Check for:
-Proper vent sizing.
-Air leak between vestibule and blower compartment.
-Restricted vent.
-Plugged condensate drain.
-Low inlet gas pressure (if LGPS used).
-Excessive wind. If problem persists turn setup switch “SW1-3” ON to boost inducer speed.
-Improper pressure switch wiring.
-Failed or “Out-of-Calibration” pressure switches.
-Water in vent piping, possible sagging pipe.
-Disconnected or obstructed pressure tubing.
4LIMIT CIRCUITFAULT – Indicates the limit, or flame rollout is open or the furnace is operating in maximum-heat only mode due to 2
successive limit trips while operating at any rate less than or equal to 71% of maximum rate. Blower will run at intermediate heat airflow
for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #7. If open less
than 3 minutes status code #4 continues to flash until blower shuts off. Flame rollout switch requires manual reset. Check for:
-Loose blower wheel.
-Defective switch or connections.
-Improper minimum- or maximum-heat gas input adjustment.
-Dirty filter or restricted duct system.
-Improper limit switch or no limit gasket.
5ABNORMAL FLAME-PROVING SIGNAL – Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared.
Check for:
-Leaky gas valve.
-Stuck-open gas valve.
6IGNITION PROVINGFAILURE– Control will try three more times before lockout #6 + 1 occurs. If flame signal is lost during blower
on-delay period, blower will come on for the selected blower off-delay. Check for:
-Low inlet gas pressure.
-Control ground continuity.
-Gas valve defective or turned off.
-Defective Hot Surface Igniter.
-Manual valve shut off.
-Oxide buildup on flame sensor (clean with fine steel wool).
-Proper flame sense micro amps (.5 micro amps DC min., 4.0 – 6.0 nominal).
-Green/Yellow wire MUST be connected to furnace sheet metal.
-Inadequate flame carryover or rough ignition.
-Flame sensor must not be grounded.
7LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, or flame rollout switch is open longer than 3 minutes or 10 successive limit
trips occurred during maximum-heat. Control will auto reset after 3 hours. Refer to status code #4.
- 7 -
8GAS HEATINGLOCKOUT – Control will NOT auto reset. Check for:
440 08 4001 00
-Stuck closed gas valve relay on control.
-Miswire or short to gas valve BLUE wire.
9MEDIUM PRESSURE SWITCH, HIGH PRESSURE SWITCH, OR PSR RELAY DID NOT CLOSE OR REOPENED –
Indicates the medium or high pressure switch input failed to close on a call for intermediate- or maximum-heat, or opened during a heat
cycle. PSR relay may be defective. Refer to status code #3.
10POLARITY– Check for correct line voltage polarity. If units are twinned, check for proper low-voltage (24V) transformer phasing.
1 + 2BLOWER ON AFTER POWER UP – (115 VAC or 24 VAC) – Normal operation. Blower runs for 90 seconds, if unit is powered up
during a call for heat (R-W/W1 closed) or (R-W/W1 opens) during the blower on-delay period.
1 + 5BLOWERMOTOR LOCKOUT – Indicates the blower failed to reach 250 RPM or the blower failed to communicate within 30 seconds
after being turned ON in two successive heating cycles. Control will auto reset after 3 hours. Refer to status code #4 + 1.
2 + 5MODEL SELECTION OR SETUP ERROR – If status code 2 + 5 only flashes 4 times on power-up the control is missing its model
plug PL4 and is defaulting to the model selection stored in memory. If status codes 2 + 5 flashes continuously it could indicate the
following:
-Model plug PL4 is missing and there is no valid model stored in permanent memory. This will happen if you forget to install the
model plug PL4 on a service replacement control.
-Thermostat call with setup switch “SW1-1” ON.
-Thermostat call with setup switch “SW1-6” ON.
-Setup switch “SW1-1” and “SW1-6” both ON together.
-Two different furnace models twinned.
-Service replacement control is incorrect. Need modulating board with software version V17 or later.
-See rating plate for model plug number and resistance values if code flashes continuously.
3 + 5GAS VALVE FAULT– Indicates the modulating gas valve failed to respond to a command from the furnace control or power to the gas
valve electronics was interrupted. Check for:
-Intermittent RED, YELLOW, or ORANGE wire at gas valve or PL8 connections.
4 + 1BLOWER MOTOR FAULT – Indicates the blower failed to reach 250 RPM or the blower failed to communicate within the prescribed
time limits. Thirty seconds after being turned ON or ten seconds during steady-state operation.
4 + 2INDUCER MOTOR FAULT – Indicates the inducer has not started within 20 seconds after a call for heat, the inducer motor RPM is
outside its valid range of operation, or the inducer RPM signal was lost for 5 seconds during operation. Check for:
-Proper vent sizing.
-Restricted vent.
-Failed inducer motor.
-Improper motor wiring.
-Blockage in the tubing to the pressure switch assembly or blockage in the pressure tap at the collector box.
4 + 3LOW OR MEDIUM PRESSURE SWITCH OPEN WHILE MEDIUM OR HIGH PRESSURE SWITCH IS CLOSED – Check
for:
-Low inlet gas pressure (if LGPS used).
-Plugged condensate drain.
-Improper pressure switch wiring.
-Water in vent piping, possible sagging pipe.
-Low or Medium pressure switch stuck open.
-Disconnected or obstructed pressure tubing.
6 + 1IGNITION LOCKOUT – Control will auto reset after 3 hours. Refer to status code #6.
To initiate the component test sequence, shut “OFF” the room thermostat or disconnect the “R” thermostat lead. Reset power and then put setup
switch “SW1-6” in the ON position to start the component test sequence. Once initiated the furnace control will turn the inducer ON at medium
speed. The inducer motor will run for the entire test. The hot surface igniter and blower motor will be turned ON for 15 seconds each. When the
blower is turned OFF the inducer will be turned OFF. When the component test is completed one or more of the following codes will flash.
LED CODEDESCRIPTION
HEARTBEATIndicates the inducer motor, gas valve, & blower motor tested OK. Visual check of the hot surface igniter required.
2 + 5SETUPERROR– Same as code 2 + 5 above.
3 + 5GAS VALVEFAULT– Same as code 3 + 5 above.
4 + 1BLOWERMOTORFAULT– Indicates blower motor failed test. Check blower, wiring, and furnace control.
4 + 2INDUCER MOTOR FAULT– Indicates inducer motor failed test. Check inducer, wiring, and furnace control.
To repeat component test turn setup switch “SW1-6” OFF and then back ON. After component test is completed put setup switch “SW1-6” in the
OFF position and reconnect the “R” thermostat lead.
COMPONENT TEST
- 8 -
START HERE- Ifaproblemexists, theservice technician should always begin
440 08 4001 00
troubleshooting here.
Special Note: All voltmeters are not the same - your voltage readings will vary. This applies to the entire content of this troubleshooting manual.
They are not absolute values.Correct 115-VAC VOLTAGE, CURRENT, and power MEASUREMENTS CANNOT BE TAKEN ON
MODULATING FURNACES UNLESS USING A TRUE rms METER.
STEPACTIONYESNOGO TO
1.DO NOT REMOVE THE BLOWER DOOR! Record status of AMBER LED. See
Service/Status Code Instructions.
Is AMBER LED status light ON SOLID, alternately flashing bright-dim-bright-dim like a
heartbeat, or flashing ON and OFF?
2.Is AMBER LED status light ON SOLID?34
3.Go to page number indicated in the Index for the section covering AMBER LED ON SOLID.INDEX
4.Is the AMBER LED status light alternately flashing bright-dim-bright-dim like a heartbeat?75
5.Determine status code. The status code is a single or two digit number with the first number
determined by the number of short flashes and the second number after the (+) sign is the
number of long flashes.
6.Go to page number indicated in the Index for the section covering the status code.INDEX
7.Remove blower door and depress door switch. Use a piece of tape to hold it closed. To
retrieve previous codes, disconnect the communication connector PL7 (if used) or the R
thermostat lead (if used) from the furnace control board and wait for the blower to turn off if
it is running. Put setup switch SW1-1 in the ON position and record the status codes listed in
the status code history. The status codes will flash in the order of occurrence. Read status
codes until the heartbeat flashes. After the heartbeat flashes several times the status codes
will repeat.
8.Was there a previous status code other than the heartbeat?
219
6
8
910
Note: Status codes are erased after 72 hours or can be manually erased by putting setup
switch SW1-1 in the ON position and jumpering R, W/W1, and Y/Y2 simultaneously until
the heartbeat flashes.
9.Go to page number indicated in the Index for the section covering the first previous status
code.
10.Does the problem appear to be low cooling airflow?1112
11.Go to page number indicated in Index for the section covering IMPROPER COOLING
AIRFLOW.
12.Set thermostat to call for heat and set the thermostat fan control to AUTO position if
equipped.
13.Does the furnace respond to the call for heat?1428
14.Observe operation of furnace for 20 minutes or until AMBER LED status light starts
blinking.
15.Does the AMBER LED status light blink ON/OFF slowly with short flashes or a combination
of short and long flashes?
16.Is the temperature rise below the range specified on the rating plate when the unit is operating
in minimum, and/or maximum heat?
Note:If the temperature rise is above the range specified on the rating plate refer to the Start-
Up and Adjustment section in the Installation, Start-Up, and Operating Instructions.
17.Go to page number indicated in Index for the section covering MINIMUM AND/OR
MAXIMUM HEAT TEMPERATURE RISE TOO LOW (COLD BLOW).
18.Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.INDEX
19.Make sure power is being supplied to the furnace.20
20.Check fuses, breakers, or manual disconnects to be sure they are correctly set. If not, reset
them and go back to step 1.
21.Remove blower door and depress door switch. Use a piece of tape to hold switch closed.22
22.Is 115-vac across L1 and L2?2423
23.Turn power off. Check continuity of power leads and door switch. If necessary repair power
leads and/or replace door switch.
24.Is 24-vac across SEC-1 and SEC-2?3226
25.Replace the modulating furnace control.18
516
1718
INDEX
INDEX
13
15
INDEX
21
18
- 9 -
STEPACTIONYESNOGO TO
440 08 4001 00
26.Is 115-vac across the transformer leads?2725
27.Replace the transformer.18
28.Is 24-vac across W/W1 and on the modulating furnace control?
You will not be able to check for voltage across W/W1 and COM-24V if the furnace is
connected to a Communicating Wall Control at communication connector PL7. Go to step
29.
29.You have a defective thermostat, or a break in wiring between thermostat and furnace. Fix
problem.
30.Disconnect all thermostat leads from the thermostat terminal block and jumper R to W/W1.
Does the furnace respond to the call for heat?
31.You have an incompatible thermostat. Do any of the following:
- Wire the thermostat C terminal to COM-24V.
- Isolate the W/W1 input with a relay.
- Install ballast resistor across W/W1 and COM-24V.
- Replace the thermostat with a compatible model.
32.Turn power off. Remove secondary voltage fuse from the modulating furnace control and
check the continuity of the fuse.
33.Is the secondary voltage fuse open?3425
34.Go to page number indicated in Index for the section covering SECONDARY VOLTAGE
FUSE IS OPEN.
3029
18
3125
18
33
INDEX
AMBER LED ON SOLID – Check to make sure the correct model plug PL4 is installed. The
rating plate shows the correct model plug for this furnace.If the correct model plug is
installed then the control is locked out and will auto reset after 1 hour. Lockout could be due
to any of the following:
-Flame sense circuit failure.
-Gas valve relay stuck open.
-Software check error.
Reset power to clear lockout. Replace control if status code repeats.
- 10 -
IMPROPER COOLING AIR FLOW - Generally, this indicates the Y/Y2 thermostat lead is not
440 08 4001 00
properly connected.If a Communicating Wall Control is connected to communication
connector PL7 then the wrong size outdoor unit could be configured in the Communicating
Wall Control.
STEPACTIONYESNOGO TO
1.Remove blower door and depress door switch. Use a piece of tape to hold switch closed.27
2.Set thermostat to call for cooling. If thermostat does not have G connection jumper across
thermostat terminals R and G.
3.Make sure thermostat fan control is in the AUTO position if equipped.4
4.Do you have 24-vac across Y/Y2 and COM-24V on the modulating furnace control?85
5.You have a defective thermostat, or a break in the wiring between the thermostat and the
furnace, or the Y/Y2 thermostat terminal is not wired to the thermostat.
6.Fix the problem.7
7.Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.INDEX
8.Are the air conditioning airflow select switches A/C set to the proper airflow as required by
the condensing unit? Typical airflow is based on 350 CFM/TON (See Table 2.)
9.Set the air conditioning airflow select switches A/C to the proper airflow as required by the
condensing unit. (See Table 2.)
10.Disconnect the G thermostat lead or jumper if used.11
11.Does the blower motor turn off in 5 seconds when the G thermostat lead is disconnected?
Note:When using a humidity sensing thermostat the blower may change airflow when the G
thermostat lead is disconnected and a call to dehumidify is active.
12.Replace the modulating furnace control.7
13.Reconnect the G thermostat lead or jumper and observe operation of furnace in cooling mode
for 10 minutes.
14.Does the furnace operate properly in cooling mode?1516
15.- Check outdoor unit for correct suction pressure and verify charge.
- Check filter(s) and ductwork for restrictions.
- Check furnace coil.
16.Does the AMBER LED abruptly shut off as the blower comes up to speed?1724
17.Do you have less than 17-vac between R and COM-24V on the modulating furnace control?1824
18.Do you have less than 90-vac between L1 and L2 on the modulating furnace control?1920
19.Make sure the wire gage between main fuse box and furnace complies with wire size
specification in Installation, Start-Up, and Operating Instructions.
20.Disconnect the R thermostat lead.21
21.Do you have less than 17-vac between R and COM-24V on the modulating furnace control?2223
22.Replace transformer.7
23.Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor
unit. It is recommended that AWG No. 18 color-coded copper thermostat wire be used for
lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.
24.Is Status Code 4 + 1 flashing?2526
25.Go to the page number indicated in the Index for Status Code 4 + 1.INDEX
26.- Check outdoor unit for correct suction pressure and verify charge.
- Check furnace coil.
27.Is a Communicating Wall Control connected to communication connector PL7?282
28.The wrong size outdoor unit may have been selected in the Communicating Wall Control.
You will need to set the proper size of the outdoor unit in the Communicating Wall Control.
If set properly then the Communicating Wall Control may be reducing the airflow for
dehumidification.
109
1213
3
6
7
14
INDEX
6
6
7
7
- 11 -
Table2 – CoolingTonnage vs. Airflow (CFM)
440 08 4001 00
AIR CONDITIONINGTONS
(12,000BTU/HR)
1-1/2
2
2-1/2
3
3-1/2
4
5
6
AIRFLOW
(CFM)
3.5T-060&
3.5T-080MODEL
5T-060MODEL5T-080 MODEL100 & 120
525XX
700XXXX
875XXXX
1050XXXX
1225XXXX
1400XXX
1750XXX
2100X
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF)
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF, SW4-3 OFF)
MODEL
SIZE
3.5T-60, -80
5T-80
100
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON, SW4-3 OFF)
MODEL
SIZE
AIRFLOW SELECTION CHART
SETUP SWITCH SW2 OR SW3 POSITIONS
525
700
875
1050
1225
1225
1225
1
1400
1400
DEF.
DEF.5T-60
DEF.
DEF.
2
52527008751050 1225 1400 1750
700
8751050
2
70028751050
70087521050 1225 1400 175012100DEF.120
SETUP SWITCH SW2 OR SW3 POSITIONS
1225
1750
1750
1225
1
1750
1
2100
1
MODEL
60028001000 120011400 1400 1400DEF.3.5T-60, -80
60028001000 1200 1400 1600 2000
DEF.5T-60
5T-80
100
80021000 1200
DEF.
80021000 1200
DEF.
1400
1400
1600
1600
2000
2000
1
1
800 100021200 1400 1600 200012100DEF.120
BASED ON 325 CFM/TON (SETUP SWITCH SW1-5 OFF, SW4-3 ON)
SETUP SWITCH SW2 OR SW3 POSITIONS
MODEL
SIZE
488
651
814
976
1139
1302
1302
1139
1627
1627
1
1
3.5T-60, -80
5T-80
100
DEF.
DEF.5T-60
DEF.
DEF.
2
1
48826518149761139 1302 1627
651
814976
2
6512814976
1139
1139
65181429761139 1302 162711953DEF.120
BASED ON 370 CFM/TON (SETUP SWITCH SW1-5 ON, SW4-3 ON)
SETUP SWITCH SW2 OR SW3 POSITIONS
MODEL
SIZE
558
744
930
1116
1302
1488
1488
1302
1860
1860
1
1
3.5T-60, -80
5T-80
100
DEF.
DEF.5T-60
DEF.
DEF.
2
1
55827449301116 1302 1488 1860
744
9301116
2
74429301116
1302
1302
74493021116 1302 1488 186012100DEF.120
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
1
2000
2100
1139
1
1627
1953
1302
1
1860
2100
- 12 -
MINIMUM AND/OR MAXIMUM HEAT TEMPERATURE RISE TOO LOW - Generally, this
440 08 4001 00
indicates the furnace is extremely underfired.
STEPACTIONYESNOGO TO
1.Remove the blower door. Disconnect the communication connector PL7 (if used) or the R
thermostat lead (if used) from the furnace control board. If setup switch SW4-2 is ON then
turn it OFF.
2.Depress the door switch. Use piece of tape to hold it closed.3
3.Put setup switch SW1-2 into the ON position.4
4.Jumper R, W/W1, and W2 thermostat terminals.5
5.Once the blower motor turns ON and the furnace is running in maximum heat, clock the
maximum heat gas rate. On propane installations check the manifold pressure.
6.Is the maximum heat rate within 2% of that specified on the rating plate?97
7.Ensure the gas inlet pressure and burner orifices are correct. Reference the Installation, StartUp, and Operating Instructions. Then adjust maximum heat on the gas valve to the proper
manifold pressure. If maximum heat cannot be adjusted to the proper manifold pressure,
replace the gas valve GV.
Note: The modulating furnace manifold pressure is set at two points. The first point is
maximum heat. The second point is minimum heat. Both adjustments are independent and
are done with the same rotary adjustment switch on the modulating gas valve. When
adjusting do not apply excessive force as you may damage the rotary adjustment switch. To
adjust, slowly turn the rotary adjustment switch counterclockwise to decrease manifold
pressure or clockwise to increase manifold pressure. Turn the rotary adjustment switch one
click per second until you obtain the desired manifold pressure. If you turn the rotary
adjustment switch too quickly the manifold pressure will not change.
8.Fix problem.11
9.Check maximum heat temperature rise and external static pressure with blower door in place.
Temperature rise should be mid range or higher than midpoint of range stated on furnace
rating plate. External static pressure in maximum heat should be less then .7 in.w.c. If
return temperature is below 60 deg. F condensation may form on heat exchangers. If left
uncorrected failure will result.
10.Remove the jumper from the R and W2 thermostat terminals. When the furnace is running in
minimum heat, clock the minimum heat gas rate. On propane installations check the
manifold pressure.
11.Go to the page number indicated in Index for the CLEANUP AND STARTUP
INSTRUCTIONS.
12.Is the minimum heat rate within 2% of that specified on the rating plate?1413
13.Ensure the gas inlet pressure and burner orifices are correct. Reference the Installation, StartUp, and Operating Instructions. Then adjust minimum heat on the gas valve to the proper
manifold pressure. If minimum heat cannot be adjusted to the proper manifold pressure,
replace the gas valve GV.
2
6
11
10
12
INDEX
11
Note: The modulating furnace manifold pressure is set at two points. The first point is
maximum heat. The second point is minimum heat. Both adjustments are independent and
are done with the same rotary adjustment switch on the modulating gas valve. When
adjusting do not apply excessive force as you may damage the rotary adjustment switch. To
adjust, slowly turn the rotary adjustment switch counterclockwise to decrease manifold
pressure or clockwise to increase manifold pressure. Turn the rotary adjustment switch one
click per second until you obtain the desired manifold pressure. If you turn the rotary
adjustment switch too quickly the manifold pressure will not change.
14.Is outdoor condensing unit operating during heating cycle?815
15.Check minimum heat temperature rise and external static pressure with blower door in place.
Temperature rise should be mid range or higher than midpoint of range stated on furnace
rating plate. External static pressure in minimum heat should be less then .25 in.w.c. If
return temperature is below 60 deg. F condensation may form on heat exchangers. If left
uncorrected failure will result.
16.Check return air ducts in unheated spaces for leaks.11
16
- 13 -
SECONDARY VOLTAGE FUSE IS OPEN
440 08 4001 00
STEPACTIONYESNOGO TO
1.Turn power off and remove the blower door.2
2.Is secondary voltage fuse blown? Check continuity to make sure.53
3.Replace modulating furnace control.4
4.Replace secondary voltage fuse if necessary then go to page number indicated in Index for
CLEANUP AND START-UP INSTRUCTIONS.
5.Disconnect the communication connector PL7 (if used), or all thermostat leads (if used) from
the modulating furnace control (including all wires connected to the HUM terminal) and
replace secondary voltage fuse.
6.Turn power on and depress door switch. Use a piece of tape to hold switch closed.7
7.Does the AMBER LED alternately flash bright-dim-bright-dim like a heartbeat?128
8.Turn power off and disconnect PL1 from modulating furnace control.9
9.Do you have continuity between either RED wire connected to the limit circuit and chassis
ground?
10.You have a short circuit in the limit switch circuit. This includes limit switch LS, and both
flame roll-out switches FRS.
11.Fix problem.4
12.Disconnect the pressure tube from the collector box and jumper R and W/W1 thermostat
terminals.
13.Does the AMBER LED turn off when W/W1 is energized?1420
14.Turn power off and disconnect PL1 from modulating furnace control.15
15.Do you have continuity between the YELLOW wire connected to the low pressure switch
LPS and chassis ground?
16.You have a short circuit in the YELLOW wire to the low pressure switch LPS.11
17.Does the AMBER LED turn off when the HUM terminal is energized?
1041
1639
318
INDEX
11
13
6
Note: On the modulating furnace control the HUM terminal is energized when the blower
turns ON.
18.Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower
stops.
19.Jumper R, W/W1, and W2 thermostat terminals.44
20.Disconnect jumper wire across R and W/W1 thermostat terminals and wait until inducer
stops.
21.Reconnect the pressure tube from the pressure switch assembly back to the collector box.22
22.Jumper R and W/W1 thermostat terminals.23
23.Does the AMBER LED turn off before the hot surface igniter HSI is energized?2433
24.Turn power off and disconnect PL1 from modulating furnace control.25
25.Do you have continuity between the ORANGE wire connected to the low pressure switch
LPS and chassis ground?
26.The ORANGE wire from low pressure switch LPS is shorting to ground. Replace or repair
it.
27.Do you have continuity between the VIOLET wire connected to the medium pressure switch
MPS and chassis ground?
28.The VIOLET wire from medium pressure switch MPS is shorting to ground. Replace or
repair it.
29.Disconnect jumper wire across R and W/W1 thermostat terminals, reconnect PL1 to the
modulating furnace control, disconnect PL17 from modulating gas valve, and replace
secondary voltage fuse.
30.Turn power on and depress door switch. Use a piece of tape to hold switch closed.31
31.Jumper R and W/W1 thermostat terminals.32
32.Does status code 3 + 5 flash?603
33.Does the AMBER LED turn off when the gas valve GV is energized?3417
34.Disconnect jumper wire across R and W/W1 thermostat terminals and replace secondary
voltage fuse.
35.Put gas valve manual ON/OFF switch in the OFF position and jumper R and W/W1
thermostat terminals.
2627
2829
19
21
11
11
30
35
36
- 14 -
STEPACTIONYESNOGO TO
440 08 4001 00
36.Does status code 6 flash? If not, the AMBER LED should turn off when BLUE wire is
6037
energized.
37.Turn power off and disconnect PL1 from modulating furnace control.38
38.Do you have continuity between the BLUE wire and chassis ground?593
39.Do you have continuity between the GRAY wire connected to both the medium and high
403
pressure switches and chassis ground?
40.You have a short circuit in the GRAY wire to the medium and high pressure switches.11
41.Disconnect PL8 from modulating furnace control.42
42.Do you have continuity between RED wire on PL8 and chassis ground?
613
Note: The terminals can be permanently damaged if the continuity probe is jammed into the
terminal end of the connector. Use caution when checking continuity.
43.The RED wire to the modulating gas valve is shorting to ground. Replace or repair it.11
44.Does the AMBER LED turn off when the high pressure switch HPS is energized?4548
45.Turn power off and disconnect PL8 from modulating furnace control.46
46.Do you have continuity between the BROWN wire on PL8 and chassis ground?
473
Note: The terminals can be permanently damaged if the continuity probe is jammed into the
terminal end of the connector. Use caution when checking continuity.
47.The BROWN wire to the high pressure switch HPS is shorting to ground. Replace or repair
11
it.
48.Disconnect jumper wire across R, W/W1, and W2 thermostat terminals and wait until blower
49
stops.
49.Jumper R, G, and Y/Y2 thermostat terminals.50
50.Does the AMBER LED turn off when G and Y/Y2 are energized?351
51.Reconnect communication connector PL7 (if used) or all thermostat leads (if used) to the
52
modulating furnace control. Do not reconnect the humidifier lead to HUM terminal. Operate
the furnace in heating and cooling mode from thermostat.
52.Does the AMBER LED turn off during the heating cycle?5354
53.You have a defective thermostat or a short circuit in the wiring between thermostat and
11
furnace. If the furnace is twinned, also check the twinning kit relay TKR.
54.Does the AMBER LED turn off during the cooling cycle?5556
55.You have a defective thermostat or a short circuit in the wiring between thermostat and
11
outdoor unit, or a short circuit in the outdoor unit contactor or reversing valve(heat pump
only).
56.Does the problem usually occur in cooling mode?5758
57.Check outdoor unit contactor. Failure to pull in can cause excessive current draw on low-
11
voltage circuit. This can be an intermittent problem.
58.Reconnect humidifier and check for excessive current draw when the blower turns ON. If
11
current draw is excessive check wiring to humidifier solenoid, diode bridge(if used), and
humidifier solenoid.
59.The BLUE wire to gas valve GV is shorting to ground. Replace or repair it.11
60.Replace gas valve GV.4
61.Disconnect PL17 from modulating gas valve.62
62.Do you have continuity between RED wire on PL8 and chassis ground?
4360
Note: The terminals can be permanently damaged if the continuity probe is jammed into the
terminal end of the connector. Use caution when checking continuity.
- 15 -
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.