
BIA-DPC1 rev 4 Page 1
Installation and Operation Manual
DPC1

BIA-DPC1 rev 4 Page 2
Conventions used in this manual.
In the manual the following symbols will be used:
Generic danger. Failure to comply with the safety regulations that follow can irreparably
damage the controller or equipment.
Electric shock risk. Failure to comply with the safety regulations that follow can cause death
or serious injury.
WARNINGS
Read this manual carefully before any operation.
Please keep this manual for future use.
WARNING!!
1. Installation must be carried out by a suitably qualified electrician.
2. Before carrying out any installation or maintenance operation, controller must be
disconnected from the power supply.
3. Do not open the cover during running the controller.
4. Do not splash water or other liquid over the controller.
5. Do not allow children or infirm persons to operate the control.
6. Qualified electrician is to correctly size and install circuit breakers to protect power supply.
CAUTION!!
1. The electrical and hydraulic connections must be carried out by competent, skilled, qualified
personnel.
2. Never connect AC power to the output terminals.
3. Ensure the pump and controller characteristics match.
4. Do not install the controller in the following conditions:
a. Vibration and mechanical shock.
b. Corrosive gasses and liquids.
c. Extreme heat and cold, operating range -25
o
C - +55oC.
d. Salt mist corrosion.
e. Rain and moisture.
f. Flammable materials, solvents.

BIA-DPC1 rev 4 Page 3
TABLE OF CONTENTS
Page
1.0 INTRODUCTION
1.1 Applications 5
1.2 Technical parameters and features 5
1.3 Meanings of the icons shown on the LCD 7
2.0 INSTALLATION – DRAINAGE
2.1 Electrical connection to the power supply and pump 8
2.2 Function switch setting 9
2.3 Connections for pump over temperature protection (where supplied) 10
2.4 Installing float switches and probes 10
2.5 Diagrams for drainage by liquid level through float switches or probes 11
2.0a INSTALLATION – DRAINAGE
WITH AUTOMATIC PUMPS
2.1a Electrical connection to the power supply and pump 15
2.2a Function switch setting 16
2.3a Connections for pump over temperature protection (where supplied) 17
2.4a Installing float switches and probes 17
2.5a Diagram for drainage by liquid level 18
3.0 INSTALLATION – BOOSTING
3.1 Electrical connection to the power supply and pump 20
3.2 Function switch setting 21
3.3 Connections for pump over temperature protection (where supplied) 22
3.4 Installing float switches and probes 22
3.5 Diagrams for boosting by liquid level through float switches or probes 23

BIA-DPC1 rev 4 Page 4
Cont....
TABLE OF CONTENTS cont.
4.0 INSTALLATION – TRANSFER
4.1 Electrical connection to the power supply and pump 27
4.2 Function switch setting 28
4.3 Connections for pump over temperature protection (where supplied) 29
4.4 Installing float switches and probes 29
4.5 Diagrams for transfer by liquid level through float switches or probes 30
4.0a INSTALLATION – TRANSFER
HOT WATER CIRCULATION
4.1a Electrical connection to the power supply and pump 33
4.2a Function switch setting 34
4.3a Connections for pump over temperature protection (where supplied) 35
4.4a Installing float switches and probes 35
4.5a Diagrams for transfer by liquid level through float switches or probes 36
5.0 OPERATION
5.1 BEFORE YOU START – Parameter calibration and erasing 37
5.2 Switching to AUTO mode 38
5.3 Switching to MANUAL mode 38
5.4 Alarm Test and MUTE 38
5.5 Pump protection 38
5.6 Last five failure record 39
5.7 Pump accumulated running time 39
5.8 Pump disable 39
6.0 COMMUNICATION LINK 40
6.1 Basic Function 41
6.2 Special application 41
6.3 Technical parameters 41
7.0 TROUBLE SHOOTING GUIDE 42

BIA-DPC1 rev 4 Page 5
1.0 Introduction
Thank you for choosing a Bianco Icon Series Intelligent Pump Controller.
The Intelligent Pump Controller model is an easy to use, programmable controlling and protection
device for direct start, single phase pumps with output power from 0.37kW – 2.2kW.
The Controller has many operation modes by adopting different electrical installations. Important
features that distinguish the Bianco Icon Series Intelligent Pump Controllers from some other
controllers are the push button calibration of overload and ability for dry run protection without
float switches or probes.
1.1 Applications
The Controller is useful in all cases where there is the need to control and protect single pump
installations managing the automatic operation by a variety of switching methods.
Typical usage scenarios include:
• Stormwater
• Sewage
• Booster sets
• Rainwater reuse
• Irrigation
• Water supply
1.2 Technical parameters and features
• Built in function switch for
o Drainage by liquid level control through float switches or probes
o Boosting water supply by pressure control through pressure switch and tank
o Transfer water by liquid level control through float switches and probes
• Dry run protection without float switches or probes
• Auto/Manual switch
• Dynamic LCD displaying pump running state
• Protect the pump against many faults
• Push button calibration
• Pump accumulative running time
• Last five fault record
• RS485 communication
• Starts and stops the pump in accordance with liquid levels and pressure settings

BIA-DPC1 rev 4 Page 6
The following chart shows main technical parameters for the Controller DPC1
Main technical characteristic
Double liquid level control
Liquid level control characteristic
pulse electrode probe and float switch
Pressure control characteristic
pressure switch and pressure tank
0.37 – 2.2 kW (0.5 – 3.0 hp)
Trip response time of overload
Trip response time of open phase
Trip response time of short circuit
Trip response time of under/over voltage
Trip response time of dry run
Recovery time of over load
Recovery time of under/over voltage
Trip voltage of over voltage
115% of rated input voltage
Trip voltage of under voltage
80% of rated input voltage
Liquid level transfer distance maximum
20% to 90% Relative Humidity, non-condensing
Unit dimensions (L x W x H)
RS485 Bus Interface: asynchronous semi duplex
1200,2400,4800,9600 bps (default 9600bps)

BIA-DPC1 rev 4 Page 7
1.3 Meanings of the icons shown on the LCD.
Icon Meaning / Description
pump parameter configuration icon, when this icon appears, pump control box
is parameter setting
time displaying icon, when this icon appears, it means pump control box is
displaying some parameter of time, eg: pump accumulated running time (unit:
hour); counting down etc
pump fault icon, when this icon appears, it means pump control box is displaying
some fault information
network connection error icon, when this icon appears, it means there is no
network connections or network connection error between pump control box
and SC(slave controller) or computer
network normal connection icon, when this icon appears, it means the network
connection between pump control box and SC (slave controller) or computer is
normal
V voltage
M minute
S second
H hour
% percent
A ampere
pump running
pump stopped
low pressure or lack of pressure in the pipeline or pressure tank
high pressure or full of pressure in the pipeline or pressure tank
pump A
pump B (for dual pump controllers)

BIA-DPC1 rev 4 Page 8
2.0 Installation – DRAINAGE
2.1 Electrical connection to the power supply and pump
DANGER. Electric shock risk.
Before carrying out any installation or maintenance operation, the control panel should be
disconnected from the power supply and one should wait at least 2 minutes before opening the
control panel.
Never connect AC power to output L and N terminals.
Ensure the motor, controller and power specifications match.
The electrical and hydraulic connections must be carried out by competent, skilled, qualified
personnel.

BIA-DPC1 rev 4 Page 9
2.2 Function switch setting - DRAINAGE
Installers can set the function switch to meet different applications. Before setting the function
switch, the control panel should be disconnected from the power supply.
After completing the setting, apply power to the control panel and observe the application sign
displayed on the LCD conforming to the DRAINAGE symbol.
DRAINAGE SETTING DRAINAGE SYMBOL
SWITCHES DOWN

BIA-DPC1 rev 4 Page 10
2.3 Connections for pump over temperature protection (where supplied with pump).
Note: to realize the pump motor winding over temperature protection, it requires that there must be overtemperature switches embedded in the pump motor winding (microtherms as fitted to Zenit 3ph pumps 2.2
kW or greater). To utilise the pump’s over temperature protection connect the pump’s microtherm leads to
terminals 9 and 11, 10 and 12 and remove the jumper.
Note: if the pump is without over temperature switch, please use jumper to connect terminals 9 and 11, 10
and 12.
2.4 Installing float switches and probes.
Float switch installation.
Do not encase sensor leads, float switches or signal cables in metal pipes. Use PVC or PE tubing.
Liquid probe installation.

BIA-DPC1 rev 4 Page 11
In event of high risk of electrical storms (lightning) or when liquid medium in sump, well or tank is very
dirty, it is recommended to use float switches.
2.5 Electrical connections for DRAINAGE applications
2.5.1 Drainage by liquid level control through float switches or probes
Note: for 4 float switch installation connect float switch A (pump off) to terminals 1 and 3, float switch B (1st
pump on) to terminals 1 and 5, float switch C (2nd pump on) to terminals 2 and 4 and float switch D (alarm) to
terminals 2 and 6.

BIA-DPC1 rev 4 Page 12
2.5.1 Drainage by liquid level control through float switches or probes (cont)
Note: for 4 float switch installation connect float switch A (pump off) to terminals 1 and 3, float switch B (1st
pump on) to terminals 1 and 5, float switch C (2nd pump on) to terminals 2 and 4 and float switch D (alarm) to
terminals 2 and 6.

BIA-DPC1 rev 4 Page 13
2.5.1 Drainage by liquid level control through float switches or probes (cont)

BIA-DPC1 rev 4 Page 14
Stop condition
Liquid level in the sump is reaches probe 2, (float switch A down) the control panel will stop the pump.
Start condition
Liquid level in the sump reaches probe 3, (float switch A up) the control panel will run a pump. Control panel
will alternate the pumps when the liquid level varies between probe 2 and probe 3 (float switch A up and
down).
2nd pump start condition
Liquid level in the sump reaches probe 4, (float switch B up) the control panel will run the second pump.
Pumps run simultaneously until liquid level reaches probe 2, (float switches A and B down).
Alarm condition
While pumping, if the liquid level rises in the sump to probe 5, (float switch C up), the control panel will sound
the alarm to warn the user to take further action.
Meanings of the messages & graphic shown on the LCD screen

BIA-DPC1 rev 4 Page 15
2.0a Installation – DRAINAGE WITH AUTOMATIC PUMPS
2.1a Electrical connection to the power supply and pump
DANGER. Electric shock risk.
Before carrying out any installation or maintenance operation, the control panel should be
disconnected from the power supply and one should wait at least 2 minutes before opening the
control panel.
Never connect AC power to output L and N terminals.
Ensure the motor, controller and power specifications match.
The electrical and hydraulic connections must be carried out by competent, skilled, qualified
personnel.

BIA-DPC1 rev 4 Page 16
2.2a Function switch setting – DRAINAGE WITH AUTOMATIC PUMPS
Installers can set the function switch to meet different applications. Before setting the function
switch, the control panel should be disconnected from the power supply.
After completing the setting, apply power to the control panel and observe the application sign
displayed on the LCD conforming to the DRAINAGE symbol.
DRAINAGE SETTING DRAINAGE SYMBOL
FOR AUTOMATIC PUMPS

BIA-DPC1 rev 4 Page 17
2.3a Connections for pump over temperature protection (where supplied with pump).
Note: to realize the pump motor winding over temperature protection, it requires that there must be overtemperature switches embedded in the pump motor winding (microtherms as fitted to Zenit 3ph pumps 2.2
kW or greater). To utilise the pump’s over temperature protection connect the pump’s microtherm leads to
terminals 9 and 11, 10 and 12 and remove the jumper.
Note: if the pump is without over temperature switch, please use jumper to connect terminals 9 and 11, 10
and 12.
2.4a Installing float switches and probes.
Float switch installation.
Do not encase sensor leads, float switches or signal cables in metal pipes. Use PVC or PE tubing.
Liquid probe installation.

BIA-DPC1 rev 4 Page 18
In event of high risk of electrical storms (lightning) or when liquid medium in sump, well or tank is very
dirty, it is recommended to use float switches.
2.5a Electrical connections for DRAINAGE applications WITH AUTOMATIC PUMPS
2.5.1a Drainage by liquid level control.
Note: for “3 wire” floats use black and brown wires. Terminate blue wire with closed end connector.
Alarm float C connected to terminals 2 and 6.
If the system activates the high level alarm connected to the control panel the second pump will start
and the alarm will activate until the high level float deactivates.
If a pump fail situation is detected then the pump will switch to the second pump.
Warning – DRY RUN Protection not active in Drainage with Automatic Pump Mode.
High Level Alarm Delay
High Level Alarm delayed by 15 minutes after activation of High Level Float to allow 2nd Pump to turn on
and assist with pump out.
Note, For 30 minutes after High level Alarm activated, both pumps work concurrently.
Note: for drainage
with automatic
pumps, floats A & B
are not used and
terminals 1, 3, 5 and
2,4 are bridged.

BIA-DPC1 rev 4 Page 19
2.5.1a Drainage by liquid level control WITH AUTOMATIC PUMPS
Stop condition
Liquid level in the sump is below automatic pump float switch off position which will stop both pumps.
Start condition
The control panel alternates power supply between pumps every 240 hours. When liquid level in the sump is
above the automatic pump float switch on position, the pump that is being supplied power will run.
Alarm condition
While pumping, if the liquid level rises in the sump to float switch C up, the control panel will sound the alarm
to warn the user to take further action.
Meanings of the messages & graphic shown on the LCD screen

BIA-DPC1 rev 4 Page 20
3.0 Installation – BOOSTING
3.1 Electrical connection to the power supply and pump
DANGER. Electric shock risk.
Before carrying out any installation or maintenance operation, the control panel should be disconnected from
the power supply and one should wait at least 2 minutes before opening the control panel.
Never connect AC power to output L and N terminals.
Ensure the motor, controller and power specifications match.
The electrical and hydraulic connections must be carried out by competent, skilled, qualified personnel.

BIA-DPC1 rev 4 Page 21
3.2 Function switch setting - BOOSTING
Installers can set the function switch to meet different applications. Before setting the function switch, the
control panel should be disconnected from the power supply.
After completing the setting, apply power to the control panel and observe the application sign displayed on
the LCD conforming to the BOOSTING symbol.
BOOSTING SETTING BOOSTING SYMBOL
SWITCHES UP

BIA-DPC1 rev 4 Page 22
3.3 Connections for pump over temperature protection (where supplied with pump).
Note: to realize the pump motor winding over temperature protection, it requires that there must be overtemperature switches embedded in the pump motor winding (microtherms as fitted to Zenit 3ph pumps 2.2
kW or greater). To utilise the pump’s over temperature protection connect the pump’s microtherm leads to
terminals 9 and 11, 10 and 12 and remove the jumper.
Note: if the pump is without over temperature switch, please use jumper to connect terminals 9 and 11, 10
and 12.
3.4 Installing float switches and probes.
Float switch installation.
Do not encase sensor leads, float switches or signal cables in metal pipes. Use PVC or PE tubing.
Liquid probe installation.
In event of high risk of electrical storms (lightning) or when liquid medium in sump, well or tank is very
dirty, it is recommended to use float switches.

BIA-DPC1 rev 4 Page 23
3.5 Electrical connections for BOOSTING applications.
3.5.1 Water supply by pressure control through pressure switch and tank.

BIA-DPC1 rev 4 Page 24
3.5.1 Water supply by pressure control through pressure switch and tank (cont)

BIA-DPC1 rev 4 Page 25
3.5.1 Water supply by pressure control through pressure switch and tank (cont)

BIA-DPC1 rev 4 Page 26
3.5.1 Water supply by pressure control through pressure switch and tank (cont)
Normal demand
Pressure in the pipeline is lower than the setting of pressure switch B, control box will order single pump to
run; pressure in the pipeline reaches the setting of pressure switch B, single pump stops running; control box
will alternate double pumps running automatically when pressure in the pipeline varies in the range of
pressure switch B
Extra demand
Single pump is running, pressure in the pipeline still decrease to the setting of pressure switch A, control box
will order another pump to run simultaneously, till pressure in the pipeline reaches the setting of pressure
switch B, double pumps will not stop running; Note: pressure switch should be N/C, close on pressure drop.
Note: Pressure switch A = Low Pressure Switch, Pressure switch B = High Pressure Switch
Meanings of the messages & graphic shown on the LCD screen

BIA-DPC1 rev 4 Page 27
4.0 Installation – TRANSFER
4.1 Electrical connection to the power supply and pump
DANGER. Electric shock risk.
Before carrying out any installation or maintenance operation, the control panel should be disconnected from
the power supply and one should wait at least 2 minutes before opening the control panel.
Never connect AC power to output L and N terminals.
Ensure the motor, controller and power specifications match.
The electrical and hydraulic connections must be carried out by competent, skilled, qualified personnel.

BIA-DPC1 rev 4 Page 28
4.2 Function switch setting - TRANSFER
Installers can set the function switch to meet different applications. Before setting the function switch, the
control panel should be disconnected from the power supply.
After completing the setting, apply power to the control panel and observe the application sign displayed on
the LCD conforming to the TRANSFER symbol.
TRANSFER SETTING TRANSFER SYMBOL

BIA-DPC1 rev 4 Page 29
4.3 Connections for pump over temperature protection (where supplied with pump).
Note: to realize the pump motor winding over temperature protection, it requires that there must be overtemperature switches embedded in the pump motor winding (microtherms as fitted to Zenit 3ph pumps 2.2
kW or greater). To utilise the pump’s over temperature protection connect the pump’s microtherm leads to
terminals 9 and 11, 10 and 12 and remove the jumper.
Note: if the pump is without over temperature switch, please use jumper to connect terminals 9 and 11, 10
and 12.
4.4 Installing float switches and probes.
Float switch installation.
Do not encase sensor leads, float switches or signal cables in metal pipes. Use PVC or PE tubing.
Liquid probe installation.
In event of high risk of electrical storms (lightning) or when liquid medium in sump, well or tank is very
dirty, it is recommended to use float switches.

BIA-DPC1 rev 4 Page 30
4.5 Electrical connections for TRANSFER applications.
4.5.1 Water supply by liquid level control through float switches or probes.

BIA-DPC1 rev 4 Page 31
4.5.1 Water supply by liquid level control through float switches or probes (cont)

BIA-DPC1 rev 4 Page 32
4.5.1 Water supply by liquid level control through float switches or probes (cont)
Normal demand
Liquid level in the water storage tank is lower than Probe 1 # (float switch A: Down level), control box will
order single pump to run; Liquid level reaches probe 4 # (float switch A: Up level), single pump stops running;
control box will alternate double pumps running automatically when liquid level varies from Probe 1# & Probe
4#, (Float Switch A: Down level Up level Down level)
Extra demand
when single pump is running, liquid level is still decreasing to Probe 2# (Float Switch B: Down level), control
box will order another pump to run simultaneously, until liquid level reaches Probe 4# (Float Switch A & B: Up
level), double pumps will not stop running;
Meanings of the messages & graphic shown on the LCD screen

BIA-DPC1 rev 4 Page 33
4.0a Installation – TRANSFER HOT WATER CIRCULATION
4.1a Electrical connection to the power supply and pump
DANGER. Electric shock risk.
Before carrying out any installation or maintenance operation, the control panel should be disconnected from
the power supply and one should wait at least 2 minutes before opening the control panel.
Never connect AC power to output L and N terminals.
Ensure the motor, controller and power specifications match.
The electrical and hydraulic connections must be carried out by competent, skilled, qualified personnel.

BIA-DPC1 rev 4 Page 34
4.2a Function switch setting – TRANSFER HOT WATER CIRCULATION
Installers can set the function switch to meet different applications. Before setting the function switch, the
control panel should be disconnected from the power supply.
After completing the setting, apply power to the control panel and observe the application sign displayed on
the LCD conforming to the TRANSFER symbol.
TRANSFER SETTING FOR TRANSFER SYMBOL
HOT WATER CIRCULATION

BIA-DPC1 rev 4 Page 35
4.3a Connections for pump over temperature protection (where supplied with pump).
Note: to realize the pump motor winding over temperature protection, it requires that there must be overtemperature switches embedded in the pump motor winding (microtherms as fitted to Zenit 3ph pumps 2.2
kW or greater). To utilise the pump’s over temperature protection connect the pump’s microtherm leads to
terminals 9 and 11, 10 and 12 and remove the jumper.
Note: if the pump is without over temperature switch, please use jumper to connect terminals 9 and 11, 10
and 12.
4.4a Installing float switches and probes.
Float switch installation.
Do not encase sensor leads, float switches or signal cables in metal pipes. Use PVC or PE tubing.
Liquid probe installation.

BIA-DPC1 rev 4 Page 36
In event of high risk of electrical storms (lightning) or when liquid medium in sump, well or tank is very
dirty, it is recommended to use float switches.
4.5a Electrical connections for TRANSFER HOT WATER CIRCULATION applications.
4.5.1a Hot Water Circulation with or without thermostat.
The control panel alternates power supply between pumps every 240 hours. A thermostat can be wired to
terminals 2 and 4 for automatic operation on temperature.

BIA-DPC1 rev 4 Page 37
5.0 OPERATION
5.1 BEFORE YOU START – Parameter calibration and erasing.
To achieve best level of protection of the pump, it is essential that parameter calibration be done immediately
after successful pump installation or pump maintenance.
Setting the parameter calibration.
Pump/s must be able to pump water to enable correct calibration. If pumps are calibrated without water,
overload and pump stalled errors may occur later.
If calibration is required without water, please contact White International for advice.
Press the MODE key to switch to manual state. If the control panel is locked press MODE and STORE keys at
the same time to unlock and go into manual mode. Make sure that the pump is not running and LCD screen is
displaying:
Press the A START key to run pump A, confirm the pump and all pipe network is in normal working state
(including voltage, amps etc) with LCD screen displaying:
Press the STORE button. The control panel makes a “beep” and a countdown starts with the LCD displaying:
Control now counts down from 5 seconds.
The pump stops running and parameter calibration is completed with LCD displaying:
Press the B START key to repeat calibration for pump B.

BIA-DPC1 rev 4 Page 38
Erasing former parameter. When pump is reinstalled after maintenance or a new pump is installed, user must
erase the former calibration and a new calibration must be done.
Erasing the parameter calibration.
Press the MODE key to switch to manual state. If the control panel is locked press MODE and STORE keys at
the same time to unlock and go into manual mode. Make sure the pump is not running and LCD is displaying:
Press the A STOP key for 30 seconds; the control panel makes a “beep” sound, and the control panel recovers
the default factory setting and the LCD displays: with Pump No Calibration
flashing.
Repeat for pump B by using the B STOP key for 30 seconds.
5.2 Switching to AUTO mode.
To switch between MANUAL and AUTO mode press MODE. AUTO mode automatically locks control panel.
Under auto state the control panel will run or stop the pump according to the signal from the liquid level probe
or float switch.
Note: under auto state, if the pump is running and user wants to stop the pump, press the MODE key to switch
to manual state and the pump stops.
Note: under auto state, if the input power is cut off and the recovers, the control panel will enter operating
state after 10 seconds countdown
Note: no matter if the control panels is under auto or manual state, if the input power is cut of and recovers
again, the control panel will resume its operation in the same state as before the power being cut off.
5.3 Switching to MANUAL mode.
To switch between AUTO and MANUAL model press MODE and STORE keys at the same time to unlock and go
into MANUAL mode. Press the START key to start the pump and the STOP to stop the pump.
5.4 Alarm Test and Mute.
Under MANUAL mode and pump/s not operating press STORE for 3 seconds to test the alarm.
At any time press ASTOP to mute the alarm.
5.5 Pump Protection

BIA-DPC1 rev 4 Page 39
During pump running, if dry run, overload, over voltage, etc failures occur, the control panel will immediately
shut down the pump running and automatically execute a check for restarting conditions after a built in time
delay has elapsed. The control panel will not recover automatically until all the abnormal situations have been
cleared.
If pump stalled, open phase or other serious failure has occurred, pump user must immediately check pump
and motor.
5.6 Last five failure record
The control panel can memorize the last five failures of pump, so it is very convenient for the users to analyse
the pump running conditions.
Displaying the last five failure record.
Press the MODE key to switch to manual state, make sure the pump is not running and the LCD screen is
displaying:
Hold pressing A STOP key and press MODE key, the control panel makes a “beep” sound and displays pump A
failure record.
Press the A STOP key to quit the failure record display;
Note: the failure displayed above is PUMP STALLED.
Repeat for pump B by using B STOP key.
5.7 Pump accumulative running time
The control panel can memorise how many hours of pump running, so it is very convenient for the pump user
to analyse the pump running conditions and do maintenance.
Displaying the pump accumulative running time.
Press the MODE key to switch to manual state, make sure that the pump is not running and the LCD screen is
displaying:

BIA-DPC1 rev 4 Page 40
Hold pressing the STORE key and press the A STOP key. The control panel makes a “beep” sound and displays
the accumulative run time.
The pump has run for 23 hours.
Press the A STOP key to quit the accumulative running time display.
Repeat for pump B by using B STOP key.
5.8 Pump disable.
To disable a pump independently press A STOP or B STOP and MODE at the same time.
6.0 Communication link.
The control panel has communication interface, that along with the optional Slave Controller, users can realise
a long distance monitoring function.
This function applies to where the control panel is installed in the basement or pumping room, but users
require to monitor and control the pump on the ground or in a control room.

BIA-DPC1 rev 4 Page 41
6.1 Basic function.
Slave Controller (SC) with communication interface can realize long distance monitoring. In the control room,
users can realize all the functions of the master control panel through the SC, except parameter calibration
and adjusting.
6.2 Special application.
As adopting communication interface, the wire communication distance is less than 1200 metres. For those
installation environments which require a longer distance communication, i.e., mine, water tower, across
railway road and bridge etc., users can adopt RS485 extender, wireless communication or GSM. Please contact
the manufacturer for more information.
6.3 Technical parameters.
The following chart shows main technical parameters of communication between the control panel and the
slave controller.
RS485 Bus Interface: asynchronous semi duplex
1 start bit, 8 data bit, 1 stop bit, no verify
1 start bit, 8 data bit, 2 stop bit, no verify
Default: 1 start bit, 8 data bit, 1 stop bit, no verify
1200,2400,4800,9600 bps (default 9600bps)
Setting range of controller address: 1-126
127: broadcast address, host computer broadcasting,
slave machine response forbidden
Rated input voltage for SC
AC 240V/50Hz, single phase
Wire communication distance
1200 metres max by shield twisted pair cable (STP)
5000 metres max by STP and RS485 extender
STP-120U one pair 20AWG for RS485 & CAN

BIA-DPC1 rev 4 Page 42
7.0 Trouble shooting guide
the real running voltage is lower than the
report low line voltage to the power
calibrated voltage, pump is in under
voltage
Control will attempt to restart the pump
every
5 min until line voltage is restored to normal
the real running voltage is higher than the
report low line voltage to the power
calibrated voltage, pump is in over voltage
Control will attempt to restart the pump
every
5 min until line voltage is restored to normal
the real running ampere is higher than the
Control will attempt to restart the pump
every
calibrated running ampere, pump is in
30 min until running ampere is restored to
over load protection state
parameter calibration not completed
refer to parameter calibration setting
liquid level in the well / sump is below the
Control will attempt to restart the pump
every
pump intake, pump stops running
30 min until liquid level is above the pump
pump running amps exceeded
cut off power supply and repair or
normal rum amps by more than 200%
pump starts more than 5 times per
Check pressure tank precharge
Check pressure tank bladder
Check pressure switch settings
Check pressure switch for defects
no communication link between
connect the Control to SC / computer
SC / computer and Control
to realize long distance monitoring