I.C.E. HTDM Food Process Unit User Manual

Page 1
Industrial 51 Aikins Street
EXTINGUISH ANY OPEN
FOR YOUR SAFETY THE USE
MAINTAINACE CAN CAUSE PROPERTY DAMAGE OR DEATH. PLEASE READ THIS
ON, OPERATION AND MAINTAINANCE MANUAL THOUROUGHLY BEFORE
Commercial Winnipeg, MB Equipment Canada, R2W 4E3 Manufacturing LTD.
HTDM
INSTALLATION, OPERATION AND MAINTAINANCE MANUAL
the unit carefully before attempting to install, operate or service these units! Check unit data plates for type of gas, model number and serial numbers. Retain this document for future reference.
FOR YOU SAFTEY IF YOU SMELL GAS FOLLOW THESE INSTRUCTIONS,
1) OPEN WINDOWS
2) DO NOT TOUCH ELECTRICAL SWITCHES
3) FLAMES
4) CALL THE GAS SUPPLIER IMMEDIATLY
Model:______________________ Serial Number:___________________
Job:________________________ Date of Installation:____________
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR
OF GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN OPEN CONTAINERS IN THE VICINITY OF THIS APPLIANCE IS HAZARDOUS
WARNING
INSTALLATI
INSTALLING OR SERVICING THIS EQUIPMENT
INSTALLERS RESPONSIBILITY
Installer please note: This equipment has been test fired and inspected. It has
been shipped free from defects from our factory. However, during shipment and
installation, problems such as loose wires, leaks or loose fasteners may occur.
It is the installer’s responsibility to inspect and correct any problems that
may be found.
INSTALLER/SERVICE CONTRACTOR
NAME:____________________________ ADDRESS:_________________________ TELEPHONE:_______________________ CONTACT:_________________________
Page 2
2
Table of Contents
Receiving and Warehousing 3 General Handling instructions 3 General Installation Notes 3 Clearance to Combustables 4 Connecting the Flue 5 Electrical Connections 6 Gas Piping 6
Gas Vent 7
Duct Furnaces 7 Cooling 8 High Altitude 8 Indoor Units 8 General Operating Instructions 8 Start Up Procedures 8 Precautions 8 Gas Units 9 Start Up 9 Shut Down 10 Emergency Shut Down 10 Service Shut Down 10 Recommended Quarterly Maintenance 10 Recommended Yearly Maintenance 11 ICECON II Operators Manual 12 ICECON II Controller 13 Normal Start Up Sequence 14 Heat Modes 14 External Modulation Control 15 How the ICECON II Controller Responds to External Control 15 Switching From mA to VDC control 16 Available Options (Software Control) 17 Error Signals 19 Trouble Shooting 21 Tachometer Test Procedure 23 Discharge Sensor/RSP Test 24 Wiring 25 Appendix A 26 Programming the ICECON II Controller 27 Setting Up the Software 27 The Main Interface 28 The System Tune Interface 29 I/O View 30 Set Points 31 Altering Combustion Set Points 32 Calibrating the Tachometer 32 Adjusting combustion Points 33 Saving an ICECON II Program 34 Uploading an ICECON File 34 Appendix 36 ICECON I to ICECON II Upgrade 37
Page 3
3
RECEIVING AND WAREHOUSING
Inspect the unit upon arrival for any shipping damage. If any part is missing or damaged, Mark bill of lading as to damage and notify the carrier at once.
If the unit cannot be installed immediately, store it and its accessories in a clean and dry place.
GENERAL HANDLING INSTRUCTIONS
A qualified and experienced crane operator must do all rigging. General rigging methods should be followed in all cases:
a) Spreader bars must be used when lifting equipment. b) Equipment must be lifted simultaneously by all “eye” bolts or
channel slots provided on each section at the same time to distribute the loading properly. Damage or injury may result if all provisions for lifting are not utilized at time of lift. When multiple lifting eyes are furnished they are to share the weight of the lift evenly via spreader bar(s).
c) Lifting eyes and channel slots are designed to be lifted
vertically. The MAXIMUM angle from a vertical lift, which is permitted, is 30 degrees. Single sections only are to be lifted at one time and stacked from the lowest section upward. Sections are designed to be self-supporting in compression only. Do not attempt to hang multiple sections from any structure. The total perimeter base and all frame structure must be supported, and levelled, on high-density concrete or sufficient I-beam steel.
d) For some models the heating and blower sections may be
shipped separately. Assemble the sections by aligning the base frames and/or the pre-drilled flanges and secure the assembly with the fasteners provided. Use gasketing material to prevent infiltration at the joints.
WARNING
FAILURE TO COMPLY WITH THE GENERAL REQUIREMENTS MAY RESULT IN
EXTENSIVE PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
GENERAL INSTALLATION NOTES
a) In Canada the installation must conform with local building
codes or, in the absence of local building codes, with the current CAN/CGA -BI49.1 or B149.2 “Installation Codes for Gas Burning Appliances and Equipment”. Indoor duct furnaces
Page 4
4
have been designed for, and certified to comply with, CAN/CGA2.8.
b) Installation must be made in accordance with local codes or
in absence of local codes with ANSI Standard Z223.1-1992 (N.F.P.A. No.54) “National fuel Gas Code” or the latest edition of all ANSI and NFPA standards. Standards referred to in these installation instructions are in effect at the time of certification. ANSI Standards are available from the American Gas Association 1515 Wilson Boulevard, Arlington, Virgina 22209. NFPA standards are available from the National Fire Protection Association, Batterymarch Par, Quincy, Massachusetts 02269. Heaters referred to in this manual are designed for use in airplane hangers when installed in accordance with ANSI/NFPA No.409 and in public garages when installed in accordance with the NFPA No. 88a
and NFPA No.88b. c) No alterations are to be made on this equipment. d) For suspended appliances which are installed in air craft
hangers, parking structures, and repair garages must be
installed in accordance with the standard on air craft
hangers, ANSl/NFPA 409, the standard for parking structures.
ANSI/NFPA 88a, the standard for repair garages, ANSI/NFPA
88b, and with the CAN I-B149 codes,
CLEARANCE TO COMBUSTIBLE MATERIALS in inches (mm)
MODEL TOP FRONT BACK FLOOR SIDES FLUE
HTDM 200 0 (0) 0 (0) 0 (0) 3(76) 0 (0) 18(457) HTDM 400 6(152) 6(152) 4(102) 3(76) 4(102) 18(457)
HTDM 600 6(152) 6(152) 4(102) 3(76) 4(102) 18(457) HTDM 1000 6(152) 6(152) 6(152) 3(76) 6(152) 18(457) HTDM 1500 6(152) 6(152) 6(152) 3(76) 6(152) 18(457)
All units installed on the floor has a minimum clearance of 3" (76mm) provided by the base frames of each individual unit.
For service it is advisable to maintain a minimum 24' clearance on the side opposite the controls side (note: not valid for the HTDM
200), and 42" clearance on the control side. If this unit is to be operated within a confined space or within a building of unusually tight construction, air for combustion and ventilation must be obtained from outdoors or other spaces freely communicating with the outdoors. Refer to current United States and Canadian Fuel Codes.
Page 5
5
Ducts connected to the furnace shall have removable access panels on both the upstream and downstream sides of the furnace. These openings shall be accessible when the furnace is installed and shall be sized to allow the observation of smoke or reflected light inside the casing to indicate the presence of leaks in the heat exchanger. The covers for the openings shall be attached in such manner as to prevent leaks.
The furnace must not be operated in the presence of chlorinated vapours. When such vapours mix with products of combustion, highly corrosive compounds result, which will result in the premature failure of the heat exchanger and other components. In such an event the warranty is void.
CONNECTING THE FLUE (VENTING)
When making flue connection to the unit, observe the following general recommendations. In addition, the HTDM series ofunits are approved and must use recognized type "8" vent and/or vent connector. All connections must conform to the requirements of current United States and Canadian codes (gas fires units), and be in accordance with local authorities, which include but are not limited to:
a) The flue must be securely attached to the unit with tight
joints.
b) The pipe from the unit to the flue should rise at least If.."
per foot, (76.2 mm).
c) The flue must be sized to have a cross-sectional area not
less than that of the flue collar at the unit.
d) Other appliances must not be connected so as to vent through
the flue of this unit.
e) Do not support the weight of the stack on the flue connection
of the heating section.
f) Minimize connecting pip length and the number of bends by
locating the unit as close to the flue pipe as possible.
g) Maintain clearances between the flue pipe and combustible
material that are acceptable to the local authorities having jurisdiction.
h) For indoor/outdoor application the flues condensate deposal
pipe, located on the unit, shall be piped to prevent accumulation of condensate on or around the unit.
The HTDM series are approved for use with type “B” venting. The venting must be of recognized type. For type “B” vent use with the HTDM 1000 and HTDM 1500 models a draft hood must be connected in series with the type “B” vent. The Drafthood must
Page 6
6
be installed between the unit’s flue connection and the type “B” vent.
NOTE: For venting diagram see Appendix C.
ELECTRICAL CONNECTIONS
a) This unit has been examined and tested for compliance with
CSA C22.2 no.0, CSA C22.2 no.3 and the NED code.
b) All electrical work must conform to the requirements of the
current NEC and CSA standard C22.1, Canadian Electric Code
part I, and local ordinances. c) Control voltage is as indicted on the rating plate. d) Follow the wiring diagram supplied with the unit. e) If a space thermostat is used with the furnace, locate the
thermostat so the cold drafts and hot discharge air streams
do not affect the performance of the unit. Do no mount the
thermostat on the casing of the unit, as it will be affected
by radiated and conducted heat. Refer to the instruction
furnished with the thermostat for further details. f) If any of the original wires as supplied with the unit must
be replaced, it must be replaced with type TEW 105 degrees or
its equivalent except where noted. g) Temperature controllers, limit controllers, remote selector
switches, door switches or any other auxiliary electrical
items must be connected to the terminals provided as shown on
the wiring diagram. h) For units shipped in multiple sections, electrical
connections between sections are to be made by the installer
in the field. i) Field wiring to be done by the installer is denoted by doted
lines on the wiring diagram. Solid lines on the wiring
diagram indicate factory wiring by the manufacturer. j) The unit must be electrically grounded in accordance with
local codes, or in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70, and/or the CSA.C22.1
Canadian Electrical code.
NOTE: Due to the nature of transport check all bolts and fasteners for tightness.
GAS PIPING
All gas piping should be in accordance with NFPA, National Gas Code, and CAN 1-B149 with the regulation of local authorities having jurisdiction. An emergency manual shut down valve shall
Page 7
7
be provided upstream of the piping to unit and should be labelled for quick identification. Colour coding of gas piping is also recommended.
In addition:
a) Carefully check the unit rating plate for fuel type and
supply pressure. b) If required, locate the high-pressure regulator at least five
feet from the unit. c) Gas lines must not be located in such a way as to hinder
access to the unit. d) A minimum 1/8" NPT plugged tapping, accessible for test gauge
connection, must be installed immediately upstream of the gas
supply connection to the appliance.
GAS VENT
High gas pressure regulator (if required), low pressure regulator, pilot pressure regulator, gas pressure switch (if supplied), and normally open vent valve (if supplied) must be vented outside of building for an indoor unit (check with authorities having jurisdiction).
DUCT FURNACES
a) A duct furnace shall be installed with an inlet duct, which
will provide air distribution equivalent to a straight run of
duct having the same cross-section area as the inlet
connection and not less than two equivalent diameters in
length. b) The ducts connected to the duct furnace must have removable
access panels on both upstream and downstream sides of the
duct. The opening must be accessible, and shall be of such
size, that smoke or reflected light may be observed inside
the casing to indicate the presence of leaks in the heating
element. The cover for the opening shall be attached in such
a manner as to prevent leaks. c) The installation of the duct furnace must be adjusted to
obtain an air throughout within the range specified on the
appliance rating plate. d) If a duct furnace is connected to a return air duct or any
other inlet air restoration; the duct furnace shall be
installed on the positive pressure side of the air-
circulating blower.
Page 8
8
COOLING
When installed downstream from a refrigeration system. Condensation will form and provisions shall be made to dispose of condensate.
HIGH ALTITUDE
As per June I, 1998 all HTDM units are derated four percent of maximum input of each 1OOOft(305m) elevation above sea level.
INDOOR UNITS
Install an indoor unit in such that the gas ignition control system is not directly exposed to water spray, rain or dripping water.
GENERAL OPERATING INSTRUCTION
a) Refer to the rating plate for fuel input and supply
pressures. b) Do not attempt to start the burner if the unit is full of
vapour gas, or if the combustion chamber is very hot. c) Do not leave combustible material near the unit. d) Shut off the manual fuel supply valve if the burner has been
shut down for an extended period of time. e) Ensure clean-out doors are in place before starting the
burner. f) Do not start the burner unless the blower access doors are
securely in place. g) Refer to literature regarding controls, gas valves and other
components.
START-UP PROCEDURES
1. PRECAUTIONS
a) Ensure the main disconnect switch is in the “off”
position. b) Ensure the burner on-off switch is in the “off” position. c) Check all electrical and gas connections and tighten if
necessary d) Check main fans (by rotating fan shaft by hand), bearing
set screws, and pulley set screws. Ensure blowers are free
to turn, vibration isolation shipping blocks are removed
(if equipped), shipped loose items (if supplied), are
removed from inside blower sections.
Page 9
9
e) Lubricate (if necessary) the burner and main fan motors.
The specification on the motors for grease and oil shall
be adhered to. f) Check heater outlets for obstruction. g) Check all fuse blocks to determine that all fusing is
insta11ed. h) Set the operating controls (e.g. thermostat, remote panel
switches) so as to allow heating operation of the unit. i) Reset the motor starter by pushing the reset button, if so
equipped. Ensure all blowers are rotating in the correct
rotation. j) Check building system gas supplies and be sure all lines
are purged of air. k) Check building system gas supply pressure.
2. CAUTION-GAS UNITS
At maximum input the supply gas pressure must fall within the range specified on the unit rating plate.
a) Check all piping for tightness and correct any signs of
leaks.
b) Ensure purge timer is set to 70 seconds.
3. START-UP
a) Refer to start-up check list and field report for correct
settings that are to be checked on the unit.
b) Check the supply fan motor thermal overload setting against
the rating plate figure. c) Ensure burner on-off switch is in the “off” d) Verify units sequence of operation corresponds to sequence
provided in the supplied literature. e) Check supply fan motor amps against rating plate figure. If
actual figure varies by +/-20% from rating plate value, take
corrective actions with respect to duct work and accessories
external to the unit or blower/motor drive adjustments making
sure to follow manufactures rating for blower rotational
speeds. f) The thermal overloads must be set to appropriate motor
performance after all adjustments have been make. g) Follow sequence and perform necessary steps to intiate burner
activation. h) Once flame is detected the controller goes into "Power" and
“Heat” mode. i) Check unit performance as described on the factory test
report, (include items such as stack temperature. CO-2 level,
Page 10
10
flame signals etc.) Readings obtained in the field should not
deviate significantly from those obtained at the factory.
SHUT DOWN
1. EMERGENCY SHUT DOWN
a) Set disconnect switch to "off' position. b) Close the manual main fuel valve. c) Set the burner on-off switch to "off'.
2. SERVICE SHUT DOWN
a) Set the burner toggle switch to "off' position. b) Close the manual main fuel valve. c) Set the operating controls, (e.g. thermostat, remote panel
switches), so as to prevent heating operation.
MAINTENANCE
Regular maintenance is necessary to ensure the efficient operation and long life of this unit. This maintenance should be preformed by or supervised by qualified service personnel. A maintenance schedule should be prepared for the unit based on its application and location.
1. RECOMMENDED OUARTERLY MAINTENANCE
a) Check for loose connections in the wiring. b) Check the voltage at the unit while it is in operation. c) Check motor amperage draws against rating plate values. d) Inspect all contractors to ensure that they are clean and
making good contact. e) Check all fittings valves and lines for leaks. f) Check for proper combustion. Adjust if necessary. g) Check the flame sensor signal (1.5-6.0 mA), clean if
necessary. h) Check the fuel supply pressure to the unit. i) On gas fired units check the manifold pressure. j) Clean or replace air filters if necessary. Replace filters
only with type equivalent to those supplied with the unit by
the factory. k) Check all dampers, linkages and damper actuators; adjust and
tighten as required. l) Check all belts. Adjust or replace as necessary. m) Check all bearings and lubricate if necessary. n) Check operation of all safety controls.
Page 11
11
o) Oil burner fan. p) Check all bearing to ensure tightness on shaft and lubricate
if necessary. q) Check ignition spark and adjust gap if necessary.
2. RECOMMENDED YEARLY MAINIENANCE
a) Perform the monthly quarterly maintenance recommended. b) Inspect blower wheels and housing, clean if necessary. c) Inspect all set screw on blower wheels and pulleys to ensure
that they are secured to their respective shafts d) Check flame supervisor controller. e) Inspect all operating and safety controls. clean and replace
if necessary. f) Inspect and clean the collection and disposal systems to
ensure proper drainage.
NOTE: If ignition controller is replaced ensure the control system is not exposed to water spray, rain or dripping water. Refer to individual manufacturer’s literature provided for maintenance requirements of optional equipment.
Power Venter Installation
The HTDM series may be equipped with a power vent system. Whnre installing ensure that the factory supplied diverter box is install on the unit, in series with the power venter.
a) Diverter box relief opening must be installed 10” from walls
and restrictions.
b) Mount power venter in desired location. NOTE: Refer to
manufactures installation instructions for vent length and
sizing. c) Power venter must operate for the individual unit only. d) Wire power venter and safeties according to supplied diagram. e) Verify all safeties. In the event of venter failure the
burner must become in active.
NOTE: For venting diagram see Appendix C.
Page 12
12
ICECON II
OPERATORS MANUAL
Page 13
13
I. ICECON2 CONTROLLER
Figure 1
Page 14
14
II. NORMAL START-UP SEQUENCE
1) Call For Heat
The ICECON 2 controller will indicate power by illuminating the power LED (light emitting diode). The combustion blower is ramped to full speed. Upon proof of closer of the modulating gas valve the auto heating light is energized. 24VAC power is sent to the purge timer coil. Upon the timing out of the purge timer the combustion blower will ramp to minimum speed for trial for ignition.
2) Trial for Ignition
Upon timing out the combustion blower drops to low speed and the ignition controller is powered. The pilot line solenoid is powered opening the pilot gas flow to the burner. Simultaneously the ignition controller initiates spark. . Upon proof of flame ignition controller opens the main gas valves allowing gas to flow to the modulating gas valve, simultaneously sending a 24VAC signal to the ICECON2 controller. Upon receiving the 24VAC signal the board will enter System Preheat.
3) System Preheat
System preheat is indicated by a flashing Heat Mode LED. During this stage the ICECON2 controller will ramp the firing valve and combustion blower to midrange without energizing the main supply fan. Preheat lasts approximately 60 seconds. Upon completion of the system pre-heat the main supply fan energizes and the unit will begin to operate in one of the following modulation modes
III. HEAT MODES
1) Factory Set Discharge Temperature, no field adjustment.
The unit will adjust the firing rate to maintain the factory set discharge temperature. The Power, Heat Mode and Auto LEDs are illuminated to indicate this condition.
2) RTS (Remote Temperature Selector)
There are two temperature ranges for the RTS’, 40-90F and 90-120F. The unit will modulate to maintain the temperature selected on the RTS.
Page 15
15
3) External Modulation Control
The ICECON II controller is capable of responding to a 0-10Vdc or 4-20mA signals. To configure the ICECON II controller to respond to an external signal the RSP and Mod/std check boxes (In the software interface) must not be checked. The control signal connects to terminals J3-25 and J3-26. The ICECON II controller will remain in control of errors and will lock out if any error condition occurs. The BMS has complete control over the discharge temperature.
The BMS supplier must supply the ICECON controller with either 0­10 VDC or 4-20 ma signal. The signal is to be supplied to terminals J25 and J26. After normal startup sequence is finished the auto led will remain de-energized. The unit will now only respond to the BMS signal and is unable to self adjust to changes in conditions.
The ICECON II controller will respond to the incoming signals and modulate to a corresponding firing rate. The firing curve is composed of discrete steps. Each step is controlled by a trigger voltage or current that once reached the combustion will move to the next combustion step. When tuning a the BMS system the following points must be consider:
How the ICECON II Controller Responds to External Modulation Control
The ICECON II controller automatically scales the incoming signal to the internal combustion curve that has been programmed at the factory. The curve is made of discrete steps. There are dead­bands in the signal in which the unit will not modulate with an increase or decrease in the control signal.
Once a signal is received the controller will modulate to the corresponding firing point. During this transition the ICECON II controller will not respond to changes in the control signal. As a result the Control system must be tuned for a very slow response. Poor temperature control will result if the system is not tuned correctly.
Page 16
16
Switching From a mA control signal to VDC
Remove the ICECON II control cover plate. In the lower right hand area of the circuit board there is a small black jumper label ed “4-20mA enable”. This jumper is left in place when receiving a 4­20mA control signal and is removed when using a 0-10Vdc signal.
Page 17
17
III. AVAILABLE OPTIONS (Software controlled)
1) Space Override
Units equipped with this option will modulate normally in one of the above heat modes until continuity is sensed between terminals J19 and J21. Upon sensing continuity unit will de-energize the auto indicator LED and ramp to full fire until the contacts are opened. Regular heat mode operation will be resumed once the contacts between J19 and J21 are opened.
2) Low Limit
The unit will shut down the supply fan if the duct temperature falls below the factory set point.
3) System Preheat
The unit can use a built in time delay before the contacts to the main supply fan are energized. This will allow a preheating of the heat exchanger to insure that only warm air will be supplied to the space.
Preheat operation begins with a normal trial for ignition. Once flame has proven the unit will modulate to the midpoint of the firing range. The heat mode led will indicate the preheat cycle by flashing. The unit will remain at the midpoint until the preheat cycle is ended. Once ended the main supply fan contacts will energize and normal heat mode operation will begin.
4) Standby mode
Standby mode is to be used in conjunction with an on/off thermostat or when periodic heating is required. In Standby mode the ICECON2 is continually powered. The unit will indicate standby mode by flashing the power LED. In this mode the heat cycle will remain powered down until there is a call for heat from indicated by a 24VAC signal on terminal J22. Upon a call for heat a normal start up sequence is ran and the unit will then enter heat mode. Once the call for heat is satisfied and the 24VAC signal is lost on terminal J22 the ICECON2 controller will exit heat. The unit will enter a post heat purge. During this time the combustion blower and firing valve are ramped to full fire. Upon completion of the post heat purge the burner and combustion blower are shut down. The main supply fan will remain in
Page 18
18
operation for a period of time to allow for cooling of the heat exchanger.
5) Fan on in Standby Mode
With this option the main supply fan will remain in operation regardless of the call for heat when the Standby option is selected. During transition between heat and standby operation the supply fan may cycle on and off for a short duration.
Page 19
19
IV. ERROR SIGNALS
1) High Limit Error
This condition will occur when the ICECON2 controller has a duct temperature greater than the factory set point or the discharge sensor contacts are in the open condition. This condition is indicated by the illumination of LED numbers 5 and 8. The unit will indicate the high limit error and will lock until reset.
Led numbers 5 and 8 will illuminate. The main supply blower will remain energized until the duct temperature falls below the factory set safe shut down temperature. The combustion blower will remain at max RPM until the unit is reset.
2) Low Limit Error
The low limit lock out condition occurs when the air temperature in the duct work has fallen below a factory set position. This condition is indicated by the illumination of LED numbers 5, 6 and
7. Upon a drop in duct air temperature the unit will lock out and shut down the burner. The main supply fan will be de-energized to stop the flow of unheated air form entering the space. The combustion blower will run at the max RPM setting.
3) Air Proving Error
Air proving error occurs when the tachometer stops sending a signal to the ICECON2 controller. This condition is indicated by the illumination of LED numbers 5 and 6. The fan operation must be checked as well as the function of the tachometer sensor itself. Improper operation will cause poor and irregular combustion. The unit must be reset to reinitiate.
4) Flame Error
Flame error occurs when the flame signal is lost to the ICECON2 controller. Lock occurs after the fourth attempt during trial for ignition and in any instance in which flame is lost after heat mode has been achieved. The unit must be reset to reinitiate.
5) Valve Error
Valve error occurs when the ICECON2 controller looses communication with the modulating gas valve or abnormal operation of the modulating gas valve has been detected. This condition is
Page 20
20
indicated by the illumination of LED numbers 5, 6 and 8. The unit will lock out and will require resetting to reinitiate.
Page 21
21
V. Trouble Shooting
reading above the factory set
Check main blower and dampers
• The ICECON2 controller has
AIR PROVING ERROR
FLAME ERROR
HIGH LIMIT ERROR
The ICECON2 controller has
lost the Tachometer signal.
Check combustion blower
operation.
Check tachometer sensor
operation (see section ******).
Check ICECON2 fuses
The ICECON2 controller has
lost the 24 VAC on terminal J22.
Check gas supply
Check ignition module for
proper operation
Check all fail safes for
proper operation
Check valves, manual and
solenoid, for proper operation
Check ICECON2 fuses
The ICECON2 controller has
received a temperature
LOW LIMIT ERROR
VALVE ERROR
value.
for proper operation.
Check discharge sensor for
correct attachment. Open contacts on the Discharge sensor terminals will cause indication of a high limit condition.
Check ICECON2 fuses
The ICECON2 controller has
detected a temperature below that set by the as the low limit.
Check unit for proper
operation.
Check discharge sensor.
Continuity between the white and black terminals will return a –51 degree F signal.
Check ICECON2 fuses
Page 22
22
10VDC) on
ICECON2 requires 24VAC on terminal J12
ICECON2 controller. If power is trace
NO DISPLAY ON ICECON2 CONTROLER
BOARD WILL NOT ENTER HEAT MODE
UNIT WILL NOT MODULATE
SUPPLY FAN DOES NOT INGAGE
lost communication with the modulating gas valve.
Check that valve is powered
and operating correctly.
Check for signal (0-
terminal J11. The unit will not fire until valve has proven closed (<=2.0 VDC signal on terminal J11)
Check ICECON2 fuses
Board requires 24VAC on terminal J2
for operation. Check fuses on both the control panel and Circuit board and replace as necessary.
Verify correct wiring, wiring
connections and grounding of the electrical components.
to enter heat mode.
Board requires a 2.0 VDC signal on
terminal J11 before initiating trial for ignition.
Flame has not proven. ICECON2
requires a 24VAC signal on terminal J22 before entering heat mode. The controller will use 4 trials for ignition before indicating “flame error”.
Check for free rotation of the
modulating valve
Check for correct feedback signal
Check for power on terminal J5 on the
unit wiring as per diagram to determine fault.
Check for power on terminal J6. If
power is not present trace wiring as per diagram to determine fault.
If power is present on J6 but not J5
the system is not calling for the supply air.
Page 23
23
VI. Tachometer Test Procedure
Old Style Tachometer Test (Pre 2000 units)
1. Insure that the sensor will be no further than ¼ “ from the magnet when aligned
2. With magnet NOT aligned with the tachometer verify 5VDC between red and black wires.
3. With magnet NOT aligned with the tachometer verify 5VDC between white and black wires.
4. Rotate blower wheel until magnet is aligned with Tachometer sensor.
5. Verify 5VDC between red and black wires.
6. Verify 0VDC between white and black wires.
The tachometer sensor is polarity sensitive. Improper operation can be caused from improper orientation of the magnet. If problems continue remove and reverse the magnet and repeat the above procedure
New Style Tachometer Test (Equipped on unit built in 2000-present)
Disconnect power to the combustion blower. Engage a heat cycle so that the board locks out on an air proving error.
Verify approximately 5 VDC between terminals J2-17 and J2-18.
If voltage is not present disconnect all tachometer leads from the board and recheck. If power is now present replace the tachometer and verify wiring is correct. If power is still absent replace the ICECON II controller and verify wiring.
Ensure that the magnet is not aligned with the end of the
tachometer. Approximately 5Vdc should be between J2-18 and J2-16.
Rotate the combustion blower wheel until the magnet is
aligned with the tachometer. The voltage between J2-18 and J2-16 should now be zero. If this is not the case check the distance from the tachometer and the magnet. This space should not exceed 1/8th of an inch. If required adjust to the correct spacing. If the systems remain the same the magnet will have to be remove and reversed as the tachometer is polarity sensitive.
Page 24
24
VII. Discharge Sensor and RSP (Remote Set Point) Test
Once the combustion curve has been set up and the board configured for stand alone the operation of the discharge sensor and RSP must be verified. To accomplish this the computer must be connected to an active ICECON II controller. With the system in heat mode activate the “Tools” pull down menu and select “I/O view”.
A new screen is no displayed. On the lower right there are three buttons, “Read”, “5 second read” and “Exit”. “Read” performs a one-time read of the variables. “5 second read” performs a read function every 5 seconds. “Exit” closes the I/O screen. Click the “5 second read” button.
Compare the value of the discharge sensor reading with a know temperature. At this time if a discharge reading of 281°F is displayed there is an open circuit in the discharge sensor circuit
and the unit will lock out on “High Limit Error”. The discharge sensor reading should be stable with less than 1-2° fluctuations at steady state conditions.
Turn the RSP counter clockwise until the physical stop is reached. A value of 40 when a 40-90°F RSP is being used and 90 when a 90­120°F RSP is used should be displayed in the RSP value (This may take up to 30 seconds).
Turn RSP clockwise until the physical stop is reached. The upper limit of the RSP should be displayed. Verify a mid point and align the pot to the correct temperature scale position. To do this, use a small screwdriver to loosen the knob and reposition such that the arrow points to the correct temperature. Retighten the knob.
The low temperature scale should have an ohm range of 0-5000 resistance range. The High temperature range RSP should have 100k-200k resistance range.
Page 25
25
VII. Wiring
Modulating gas valve ground (24VAC
J1 24VAC Neutral J2 24 VAC J3 Normally open contact to purge
timer coil J4 24VAC for purge timer common J5 Normally open contact to supply
fan J6 24VAC for supply fan common J7 Solid State Relay (+ VDC) J8 Solid State Relay (-VDC) J9 Modulating gas valve control
signal (2-10 VDC) 10
common) J11 Modulating gas valve feedback
signal (2-10 VDC) J12 Heat mode/Standby (Switched 24VAC) J13 Temperature sensor ground (-VDC) J14 Temperature sensor supply (+5VDC) J15 Temperature sensor signal (+VDC) J16 Tachometer sensor signal (+VDC) J17 Tachometer sensor supply (+5VDC) J18 Tachometer sensor ground (-VDC) 1J9 Space Override contact J20 System ground J21 Space Override contact J22 Flame detect in (24VAC) J23 Remote Temperature Selector
Contact J24 Remote Temperature Selector
Contact J25 Building Management in J26 Building Management in
Page 26
26
Appendix A
Page 27
27
I. Programming the HTDM ICECON II controller.
To correctly configure the ICECON series of controllers the ICECON software must be used to communicate with the controller. Factory training is required. Changes to the control program can cause poor combustion, improper or undesired operation.
Software identification
For the ICECON II controllers the icecon1.7b version of the software must be used. This software can be identified by the seven configuration check boxes in the top right hand corner of the main screen. The original software only had 3 configuration boxes.
Setting up the Software
To establish communication ensure that the ICECON II controller is in either “Stand-By” mode (indicated by flashing power led), in “Heat Mode”(indicated by both “Power” and “Heat Mode” leds illuminated) or locked in an error condition
When first installed the program will not be configure to your system. To properly configure the software you must chose the correct COM port for the serial cable connection on your computer. To begin activate the “Settings” pull down menu and select “ComPort”. Select the COM port if known.
If the COM port configuration on you computer is not known you must connect to an active ICECON II controller. Once this is accomplished activate the “Settings” pull down menu and select “ComPort”. Begin by selecting the initial COM port “COM 1”. Allow 30-45 seconds for the software to communicate. If the board continues to indicate “Board not communicating” then try another COM port.
If communication cannot be established ensure that only one application of the ICECON software is running. Check that the correct communication cable is being used (9-pin, straight through cable with gender changer) and is connected to both the computer and ICECON II controller.
Once configured the software will store the correct COM port. This procedure will only be necessary upon initial installation of the software.
Page 28
28
points from which the firing
the combustion curve.
programmed. Changing these will effect
the required inputs and outputs of the
unit.
values that effect the system
response time and accuracy.
The Main Interface
This screen provides a view of the current settings contained in the ICECON2 controller. Various control values such as the high and low limits can be adjusted in this environment. The options that the controller is currently configured with are displayed in the upper right corner and are indicated by a check mark in the corresponding box. The combustion curve settings, six in total, located at the bottom of the screen cannot be adjusted in this environment.
Check boxes control which factory set
Kp and Ki are factory set control
options have been selected and
Factory Set Discharge Temperature
Factory Set High Limit
Factory Set Sae Shut Down
Factory Set Low Limit
Displays all six combustion
curve is calculated.
Displays the corresponding RPM value for each point of
Figure 2
Page 29
29
System Tune Interface
When highlighted this
will proceed to the
To access the combustion settings activate the tools pull down menu and select the system tune option. The screen displayed in figure 2 is now visible. Adjustments to the combustion curve can be made to any of the six points. The previous screen will not be updated until the user has left system tune mode.
The Fan box allows the adjustment of the combustion blower set point at one of the 6 set points. By adjusting this value up or down the fan speed can be increased or decreased. Each point must increase in value or the system will lock out in set up error.
previous point.
The valve box allows for the adjustment of the valve/gas flow at the set point in question. The value indicated in this box will be the output voltage to the modulating gas valve.
When selected the program will move to the next point.
Sends displayed values to the ICECON controller.
Figure 3
Page 30
30
I/O View
detect provide information
indicates normal operation
while OFF
loss of signal.
High Limit, Low Limit and
The READ option will do a one
5 SEC READ
will perform a real time
The bottom four values
The I/O view option located in the tools menu is used as a real time diagnostic tool. The system will communicate a provide status of system safeties and operating points.
Ini Error indicate improper
Air proving and flame
on the combustion blower and flame signal. ON
will confirm a
display the current values of fan speed, valve voltage, discharge temperature and RSP.
Figure 4
operation of the unit. Off will indicate normal operation will ON signal a lock out condition has occured.
time real time read of the sytem operation at that time.
read every five seconds after it is initiated.
ICECON II Configuration
The main configuration for the board is contained in the seven check boxes located in the top right corner of the main screen.
1. ByPass System Preheat. Once checked the preheat cycle will
by eliminated. The preheat cycle will take place once main flame has been established. The burner will be ramped to a mid point in the firing range and remain there for approximately 45 seconds. Once complete the output on J1­5(usually used to energize the supply fan) will be energized. The ICECON II controller is now ready for modulation.
2. RSP. Once checked the ICECON II controller will look for a
remote temperature dial for the temperature set point. The remote temperature dials are available in two ranges 40–90°F and 90-120°F. This is only used during standalone operation and cannot be used when a building management system (BMS) or
other source is being used to provide the modulation control. When not checked the ICECON II controller will maintain the temperature indicated in the “Discharge Temperature” set point box.
Page 31
31
3. Mod/std. This when checked activates the internal modulation
control routines. When checked the system will not respond to a BMS signal.
4. Space Override. When checked the ICECON controller will
monitor terminals J3-20 and J3-21 for continuity. When continuity is detected the system will ramp to full fire and remain at this point, regardless of discharge temperature, until continuity is lost.
5. Standby Mode. When checked the ICECON II controller will
operate in both heating and non-heating modes. To enter a heating cycle 24 Vac must be present on terminal J2-12. When not checked board is only to be power during a heating cycle.
6. System Fan on in Standby. Once checked the output on J1-5
will be energized in both “Standby” and “Heat” modes. A delay will be experienced during transitions between the two modes.
7. Low Limit. When checked the low limit sensing routines are
energized. During “Heat Mode” if a temperature is sensed below the low limit set point the J1-5 output will be deenergized. The is a non-adjustable 3-minute delay upon initiation of a heat cycle.
Set Points
Located beneath the ICECON logo are six set points. They are as follows:
1. Discharge Temperature. This box is used to introduce a
positive offset from the RSP set point. It is used for calibration of the discharge sensor and in the event that no RSP is being used will indicate the temperature to be maintained.
2. Upper Limit. This temperature is the set point at which the
ICECON II controller will de-energize J1-3 (Burner on output) to shut off the heat when the discharge sensor detect any temperature above this value. Once this has occurred the unit will indicate “High Limit Error”.
3. Safe Shut Down. Upon tripping on a “High Limit Error” J1-5
(Supply fan output) will remain energized until the discharge sensor detects a temperature below this set point.
4. Kp. This is used for controlling the aggressiveness of the
temperature response. The higher this value the faster the response and greater chance of temperature overshot. The default value is 70.
5. Ki. This is used to control the temperature response and is an error multiplication factor. The default is 2.
Page 32
32
6. Low Limit. When a temperature below this set point is detected, after a 3-minute internal time delay, the ICECON II controller will de-energize J1-5 and J1-3 and lock out on “Low Limit Error”.
Combustion Set Points
Located across the bottom of the main screen of the ICECON application are the six combustion set points. Each point has three parameters that describe each point. The “Fan” box contains a number that controls the cycle time of the solid-state relay and triac control signal. This number will determine the speed at which the combustion fan will rotate when firing at the corresponding firing point.
The fan rotation speed is indicated by the “RPM” box. This value is read in from the tachometer sensor as the combustion points are configured. This value is used by the software as a reference to ensure that the correct fan speed is maintained. Once configured the RPM values must maintain a 200-rpm separation between points and increase as you move from left to right across the screen.
The “Valve” box contains the valve set points. This will represent actual DC voltage being sent to the modulating gas valve. These points must increase as you transition form left to right across the main screen. The valve functioning range is 2 to 10 VDC.
Altering Combustion Set Points
Calibrating the Tachometer
Before altering any points the main firing valve should be switched to the closed position. When adjusting combustion points it is possible to override the internal stepping functions.
To begin setting up the combustion curve access the “Tools” pull down menu and select the “System tune” function. This gives direct access to the combustion curve set points. The first point (low fire) is displayed. To override the system and force the system to low fire press the “Send” button. The combustion fan will adjust to the appropriate speed and the modulation gas valve will track to the correct voltage. It is important to notice that the valve voltage does not correspond to the voltage that was displayed on the main screen, it is in fact double. This is just how it is at this time so live with it. When the main screen is
Page 33
33
displayed the actual voltage to being sent the valve is displayed (1/2 system tune voltage). Once the valve has reached the low fire set point allow 10 seconds for sufficient sampling time of the fan speed.
Click the “Next” button and the system will now display the second combustion point. Press “Send” to drive the system to this combustion point. Allow the actuator to travel and stop at the correct voltage. Allow 10 seconds to achieve an accurate rpm reading. Repeat the process until the high fire set point is reached. Press “Exit” to return to the main screen. After a few second the system will update the combustion points and the updated tachometer readings will be displayed.
Adjusting Combustion Points
The following tachometer and valve set points provide a rough guideline.
Point #1: 1200-1800 rpm, 2.5Vdc (5.0Vdc in system tune) Point #2: 1800-2200 rpm, 3.5Vdc (7.0Vdc in system tune) Point #3: 2200-2500 rpm, 4.5Vdc (9.0Vdc in system tune) Point #4: 2400-2700 rpm, 5.5Vdc (11.0Vdc in system tune) Point #5: 2600-3000 rpm, 6.5Vdc (13.0Vdc in system tune) Point #6: 3000-3400 rpm, 8.0Vdc (16.0Vdc in system tune)
It is very critical to maintain a minimum 200rpm separation between combustion points. Once this rough curve has been established override this system to high fire. Open the firing valve and set the manifold pressure. Shut the firing valve and force the system to low fire. Reopen the firing valve when the system is at low fire. Walk the system through each point in the combustion curve and check combustion making adjustments to the gas valve voltage as necessary. Once complete exit system tune and recheck complete curve. If the curve is satisfactory press the “Write” button. Confirm that the program has been updated by clicking the “Read” button.
High fire should be running between 5-7% oxygen, 7-9% CO2 while at low fire that number will vary from 18-20% oxygen, 0.1-1% CO2. Remember as the dirt accumulates the combustion fan performance will drop off so allow excess oxygen during initial factory set up.
Page 34
34
Saving a ICECON II Program
Once a HTDM has been configure and all the combustion points have been set (these will vary from unit to unit) it is time to save an electronic copy. Activate the file pull down and click “Save as”. A new screen will pop up displaying the directory in which the file will be saved, the type of file being saved (*.ice…..don’t change this) and the name of the file to be saved. Change the name of the file to something meaningful (job number for example). Click the save button and the file has been saved. This should be done whenever working on a unit that has been in operation and should be used as a base line for adjustments.
Uploading a ICECON II File to a Controller
Connect the computer to the ICECON II controller and establish communication. At this time the program that has been stored in the controller will be displayed. To load an existing program open the “File” pull down menu and click the “Open” function. Locate the file to be loaded and select it. At this time the program to be loaded is displayed on the ICECON interface screen. To upload this to the board click the “Write” button. This will overwrite the information stored with the program displayed on the interface. To confirm that the information has been uploaded press the “Read” button and the stored information will be displayed. Some programs may not be compatible and will cause the “Board not communicating” to be displayed. Try an alternate program.
Error Codes of the ICECON II Controller
1. High Limit Error. The high limit error will occur when the discharge sensor detects a temperature above the upper limit
set point. A false high limit trip can occur when the discharge sensor in not connected, as an open circuit in will
default the temperature reading to 281°F. This is characterized by the system entering heat cycle, purging, lighting and approximately 5 seconds after main flame has proven, locking out on high limit.
2. Low Limit Error. This occurs when the discharge sensor detects a temperature below the low limit set point. A false reading can be created if there is continuity (i.e. a dead short) between terminals J2-13 and J2-15. In this case the
Page 35
35
board will be receiving and false temperature reading of ­58°F.
3. Valve Error. This will occur if the ICECON II controller loses communication with the ball valve. To operate the controller must receive the feed back signal form the ball vale whenever the ICECON II controller is powered.
4. Air Proving Error. If the signal from the tachometer is lost the board will lock out on this condition. To check for proper operation of the tachometer perform the Tachometer test located in the following section.
5. Flame Detect Error. If the ICECON II controller has not detected a flame (i.e. receiver a 24Vac signal on terminal J3-22).
6. Setup Error. This error occurs when the Combustion points have been incorrectly configured.
Figure 5
Page 36
36
Appendix B
Page 37
37
ICECON1 to ICECON2 Upgrade
Purple wire from 10 pin
Yellow wire from 10 pin
Orange wire from 10 pin
1. To operate correctly the unit must be equipped with a Belimo NF24-SR US(or factory approved optional actuator) and ball valve combination for gas modulation. The unit will not operate unless equipped with the correct actuator.
2. Uncouple the 6,8 and 10 pin connector from the ICECON1 controller.
3. Remove the ICECON1 controller from the control panel.
4. If necessary rearrange components to accommodate larger size of ICECON2 controller.
5. Remove the end connector of the 10 pin connector and expose the individual wires (approximately 3 inches).
6. Strip ends of individual wires exposing approximately ¼ inch of wire.
7. Attach wires according to the following diagram
Termin al J1-1 24 VAC Neutral on
J1-2 Red wire from 10 pin
J1-3
J1-4 Grey wire from 10 pin
J1-5
J1-6
J1-7 White wire from 10 pin
J1-8 Blue wire from 10 pin
J1-9 Black wire from 10 pin
J1-10 Brown wire from 10 pin
8. Completely remove the 6 pin connector from the control panel. Use the sensor leads to wire into the ICECON2 Controller for the following connections.
Connect to
control panel
connector
connector
connector
connector
connector
connector
connector
connector
connector
Page 38
38
Terminal Connect to J2-1 Feedback from actuator
(0-10VDC) J2-2 Not used J2-3 Black wire from
discharge J2-4 Red wire from discharge J2-5 White wire from
discharge J2-6 *Black wire from
tachometer J2-7 *Brown wire from
tachometer J2-8 *Blue wire from
tachometer
Option 1
*Note: If equipped with a discharge sensor with red, white and black wire leads see option 2.
Terminal Connect to J2-1 Feedback from actuator
(0-10VDC) J2-2 Not used J2-3 Black wire from
discharge J2-4 Red wire from discharge J2-5 White wire from
discharge J2-6 White wire from
tachometer J2-7
Red wire from tachometer
J2-8 Black wire from
tachometer
Option 2
9. Remove the end connector of the 8 pin connector and expose the individual wires(approximately 3 inches).
Page 39
39
10. Strip ends of individual wires exposing approximately ¼ inch of wire.
11. Attach wires according to the following diagram
Termin al J3-1 Not used J3-2 Red from 8 pin
J3-3 Green from 8 pin
J3-4 Yellow from 8 pin
J3-5 Brown from 8 pin
J3-6 Orange from 8 pin
J3-7 Blue from 8 pin
J3-8 Black from 8 pin
Connect to
connector
connector
connector
connector
connector
connector
connector
Page 40
40
J1 Connector
J2 Connector
J3 Connector
Page 41
41
Appendix C
Page 42
42
Loading...