ICC Mirius, ETH-1000 Installation Instructions Manual

INDUSTRIAL CONTROL COMMUNICATION
Communication Node
for EMS/BMS
Installation Instruction Manual
Models
and Modbus TCP
Control
Serials
Mirius (Serial RS-485) for BACnet MS/TP)
and Modbus RTU
Energy Management System
Building Management System
Installation
PRINTED 0419
100318030 2000571701 (Rev. A)
CONTENTS
INTRODUCTION ........................................................................... 3
Warnings ...................................................................................3
Parts ..........................................................................................3
Tools Required ..........................................................................3
General Guidelines ...................................................................3
FEATURES AND COMPONENTS ................................................ 5
DEVICE CONFIGURATIONS ........................................................ 6
ETH-1000 Wiring .......................................................................6
Mirius Wiring .............................................................................6
INSTALLATION CONSIDERATIONS ............................................8
Touch Screen Style Display Installation ....................................8
High Efciency Water Heater Installation – (BTH Or BTX
Models) ................................................................................. 8
Commercial Electric Water Heater (Touch Screen
Installation) ........................................................................... 8
Membrane Switch Style Display Installation ..........................10
High Efciency Water heater Installation ............................ 10
Commercial Electric Water heater Installation .................... 10
Boiler Installation .....................................................................12
XP XWH Boiler Installation ................................................. 12
ECC DEVICE VERSIONS ........................................................... 13
BACnet / Gas Water Heaters ..................................................13
Product Description ............................................................ 13
Protocol Implementation Conformance
Statement (PICS) ............................................................... 14
BACnet Standardized Device Prole (Annex L): ..................... 14
BACnet Interoperability .............................................................14
Segmentation Capability ...........................................................14
Data Link Layer Options ............................................................14
Device Address Binding ............................................................14
Character Sets ..........................................................................15
Data Types ................................................................................15
Object Types and Properties .....................................................16
Device Object Listings ........................................................ 16
Object Min/Max Values .............................................................16
BACnet/Gas Water Heaters Object List ....................................17
Central Control Board Major State Denitions ..........................20
Xi 1.0 Energy Management System (EMS) Control .................. 20
Mxi Energy Management System (EMS) Control .....................21
Fault Codes and Warnings ........................................................22
BACnet / Electric Water Heaters ............................................23
Product Description ............................................................ 23
Protocol Implementation Conformance
Statement (PICS) ............................................................... 23
BACnet Standardized Device Prole (Annex L): ....................... 23
BACnet Interoperability ............................................................23
Data Link Layer Options ............................................................24
Device Address Binding ............................................................24
Networking Options ...................................................................24
Character Sets ..........................................................................24
Data Types ................................................................................25
Object Types and Property Support ..........................................25
Device Object Listings ........................................................ 26
Device Objects Initial Values .....................................................26
Device Objects Minimum/Maximum Values ..............................26
Central Control Board Major State Denitions ..........................30
Energy Management System (EMS) Control ............................ 30
Fault Codes and Warnings ........................................................30
BACnet / Boilers ......................................................................32
Product Description ............................................................ 32
Protocol Implementation Conformance
Statement (PICS) ............................................................... 32
BACnet Standardized Device Prole (Annex L): ...................... 32
BACnet Boiler Interoperability ...................................................32
Segmentation Capability: ..........................................................32
Data Link Layer Options ............................................................33
Device Address Binding ............................................................33
Character Sets ..........................................................................33
Data Types Supported...............................................................33
Boiler Device Object Types/Property Support ..........................34
Object Listings .................................................................... 34
Boiler Device Object Initial Values ............................................34
Boiler Device Object Min/Max Values .......................................35
Boiler Slave States ....................................................................36
Boiler Modbus Register Access ................................................36
Boiler Modulating Sensor Select/DHW Demand Switch ...........37
Lock and Hold Codes ................................................................37
Modbus / Gas Water Heaters .................................................44
Product Description ............................................................ 44
Modbus Gas Water Heater Register Listings ..................... 44
Modbus Gas Water Heater Register Properties ........................44
Central Control Board Major State Denitions ..........................47
Xi 1.0 Energy Management System (EMS) Control .................. 47
Mxi Energy Management System (EMS) Control .....................47
Fault Codes and Warnings ........................................................48
Modbus / Electric Water Heaters .............................................49
Product Description ............................................................ 49
Electric Water Heater Register Listings .............................. 49
Modbus Electric Water Heaters Register Properties .................49
Central Control Board Major State Denitions ..........................52
Energy Management System (EMS) Control ............................ 52
Fault Codes and Warnings ........................................................52
ICC PROGRAM INFORMATION ................................................. 53
2

INTRODUCTION

New building construction and energy saving techniques have driven the need for improved communications between appliances and building environmental systems. There are several different protocols that have developed for accomplishing this task
including BACnet and Modbus. Since appliances come with a
variety of controls, interfacing with the various protocols presents different challenges.
Industrial Control Communications (ICC) has developed the devices to act as a communication gateway allowing appliances to communicate to the different building management protocols. The ICC module translates the appliance codes and commands into the appropriate protocol language giving the end user the ability to monitor and control the appliance. The end user will be able to adjust and monitor the equipment and obtain better levels
of efciency and cost savings.
The ICC module in this kit has been designed to seamlessly integrate with the water heater controls. Once the unit is connected to the control and to the energy management system,
the user will be able to operate the unit with the Building
Management system interface.

WARNINGS

When installing the unit, ensure that all power is off before opening any water heater enclosure. Failure to do so could result
in electrical shock and/or possible damage to the unit.
Do not install in areas of high temperature, in excess of 167° F. Install in areas not subject to water or excess moisture.

PARTS

Table 1. Parts Required
Item Ethernet Serial (RS-485)
ICC Module X X
Communication Cable X X
Power Adapter X X
Jumpers 4 4
Splitter X X
USB Key X X
lists and instructions required to install and congure to your water heater/boiler and BMS system.
Before plugging in the ICC Gateway, install the ICC Conguration Studio from the USB key and run the program. Once running, select File, Open Project and browse to the USB key and select the conguration le whose name matches the gateway,
Because some USB hubs may not supply sufcient current to run
the Gateway, insure that the ICC Gateway is connected to the
power adaptor. Then connect the ICC Gateway using the USB
cable provided. Run the ICC Gateway Studio application from the start menu.
Each conguration has default address and BACnet instance
settings that can be changed. For Mirius gateways, the default
Modbus address is 1 and the default BACnet address is 81. For gas models the default BACnet Instance Number is 520081 and
for electric models the default instance number is 530081. For Ethernet Gateways, the default setting is to acquire an IP address automatically from the router (DHCP). If a static IP address is desired this can also be set. To change these addresses and
communication settings, use the ICC Conguration Studio
application program. The latest version of this application program can be downloaded from:
www.iccdesigns.com/icc-conguration-studio.html
Before making any changes, it is recommended to save the installed conguration project using the disk icon or File -> Save
Project As, then give it a name and select the folder, nally press Save.
To change the Instance number and the Device Name, scroll down and select the Device Object and replace the text in the boxes in the upper right corner.

TOOLS REQUIRED

Wire Cutters
24 AWG Wire Stripper
2.5 mm Flat Blade Screw Driver

GENERAL GUIDELINES

The module should be installed as close as practical to the water heater control.
The ICC module uses a 120 Volt power adapter to supply 9 volts DC for the unit. One 120 VAC outlet is required for each module installed. The power adapter comes with a six foot length of wire. If additional wire is needed, extra wire may be added, in accordance with local ordinances for installation of low voltage wire.
The ICC Gateway kit contains a USB key with the ICC Conguration Studio program, all conguration les, parameter
Figure 1. Changing Instance Number and Device Name
For ETH-1000 (Ethernet interface) the IP settings, including
DHCP/Static, the IP address and authentication can be changed
by selecting Ethernet from the upper left hand window and changing the text and drop down list selection similar to changing the Instance number above.
For Mirius (RS-485 A interface for BACnet MS/TP or ModBus
RTU), the baud rate and other serial communication parameters can be changed by scrolling down to and selecting RS-485 A -> ModBus RTU Slave.
3
Figure 2. Changing ModBus Parameters
The ModBus address can be changed by selecting Node under the RS-485 A -> ModBus RTU item.
Likewise for BACnet, the baud rate and other serial
communication parameters can be changed by scrolling down to
and selecting RS-485 -> BACnet MS/TP Server. The BACnet
MAC Address can be changed by selecting Node under the
RS-485 A->BACnet MS/TP Server.
Warning: Do not change any other values other than these or the
gateway conguration may not function properly. In this case, the le saved above can be reloaded to start over.
When changes are complete press the Download Conguration icon:
Figure 3. Changing BACnet Parameters
4

FEATURES AND COMPONENTS

Figure 4. ICC ETH-1000 (Ethernet) Version
Works with Cyclone (BTH, BTX-100, BTXL-100, DVE, DSE/ DVE/DHE
Use the ICC Control to enable/disable the water heater.
• Change Temperature Set points and differentials.
Two models with four different congurations to connect to
BACnet and Modbus.
• Ethernet and Serial RS-485 versions available.
• Two-wire or four-wire RS-485 versions available.
Table 2. ICC Versions
Kit Connection Part Number
Mirius Serial - RS485 (RTU/MS/TP) 100316044
ETH-1000 Ethernet - RJ-45 100316045
Figure 5. ICC Merius Serial RS-485 Version
Power can be supplied via the USB cable, as a 7-24 VDC input on the main termainal block, or via IEEE 802.3af Power over Ethernet (PoE on ETH-1000 only).
Congure protocols, network characteristics, and client/server
object denitions.
• Graphically interact with the interal database in real-time via
the USB connection.
Automatically discover and congure IP settings Ethernet gateways connected to the current subnet.
Update rmware.
5

DEVICE CONFIGURATIONS

Brown/White Wire*
Jumper
Brown Wire*
Blue/White Wire*
From 9 VDC Power Adapter Cable
Power
Power
Jumper

ETH-1000 WIRING

Figure 6 shows the standard conguration of the Ethernet modules.
The module has connections for 9 VDC power, three wire connections for the communication cable, and a port for the connection of the EMS system through Ethernet RJ-45 cable or serial communications.
Figure 6. Standard Conguration for Ethernet Modules
Connecting of the power adapter and the boiler or water heater communication cable to the module is accomplished on the same end of the unit. Figure 7 is a close up of the connection terminal and Figure 8 shows the appropriate connection to the strip using the power adapter and communication cable.
The provided communication cable has two RJ-45 plugs. Remove one with a wire cutter, then locate and strip the 3 wires
described below and strip 1/2 inch of insulation before connecting.
Figure 7. Connecting the Power Adapter
The connections in Figure 8 are the same regardless of the appliance or the communication protocol.
At the opposite end of the module is the connection location for the EMS LAN connection. The EMS uses an Ethernet connection with an RJ-45 connector. Plug the cable into the RJ-45 receptacle. When connecting the RS-485A connections, please note the following:
For 2-wire systems, jumper terminal A to Y. Also jumper B to Z. Connect the RX/TX+ (plus) wire from your Building Management System to terminal A/Y. Connect the RX/TX– (minus) wire from your Building Management System to terminal B/Z.
AB YZ
*From Communication Cable
Figure 8. Connections from the Communications and Power Adapter Cables
RS 485
Pos
GND
Black Wire
Black/White Wire†
For more information on connecting the ICC Gateway to your
Building Management System, please refer to the User Manual provided on the enclosed USB key in the “Documents” folder. The
two applicable documents will be found in the Manuals.

MIRIUS WIRING

Figure 9 shows the he standard conguration of the module. Port A
of the module has connections for 9 VDC power, three wire connections for the communication (breakout) cable, for Serial
communications to the water heater/boiler.
Figure 10 is a close up of the connection terminal and Figure 11 shows the appropriate connection to the strip using the power adapter and communication cable.
6
Figure 9. Mirius Unit with Communications Terminal
RS485
* From Communicaon Cable
Figure 10. Close-Up View of Connection Terminal
The provided communication cable has two RJ-45 plugs. Remove one with a wire cutter, then locate and strip the 3 wires
described below and strip 1/2 inch of insulation before connecting.
COM
Blue/White Wire*
Brown Wire*
Brown/White Wire*
†From 9VDC Power Adapter Cable
Figure 11. Mirius Wiring Schematic
The connections in Figure 11 are the same regardless of the appliance or the communication protocol.
At the opposite end, Port B of the module is the connection location for the EMS/BMS connection. See Figure 12. For
connections to the terminal use the labeling on the module as a guide.
When connecting the RS-485A connections (BACnet or Modbus)
please note the following:
• Only 2-wire systems are supported
Connect the RX/TX+ (plus) wire from your Building
Management System to terminal RX/D+. Connect the RX/ TX– (minus) wire from your Building Management System to terminal TX/D-.
B
Power
GND
A
Power
POS
Black/White Wire†
Black Wire†
Figure 12. Mirius Port B Terminal
7

INSTALLATION CONSIDERATIONS

There are two types of displays to consider when installing the ICC gateway modules to the water heaters, the older type with membrane switches and the newer style with a touch screen. The new touch screen style display does not need the provided RJ-485 splitter and it can be discarded.

TOUCH SCREEN STYLE DISPLAY INSTALLATION

HIGH EFFICIENCY WATER HEATER INSTALLATION – (BTH OR BTX MODELS)

Follow the directions under general guidelines for connecting the module to the Energy Management System and power. This section will guide the installer on how to mount and connect the module to the water heater. The control box and mounting location on the water heater is on the top of the unit behind the display module. See Figure 13.
Connection of the RJ-45 end of the communication cable to the heater is required to plug into J13 of the control board inside the
“black controls box” (for newer models) requiring removal of two
screws holding the lid on. After plugging in the communications cable, route the cable to the bottom side with the other cables and put the lid back on with the two screws.
If the control board is in a “grey controls box” (for older model),
double check to make sure the display is not one with membrane switches below and to the right of the display. If the display uses membrane switches, please follow directions under the section
“MEMBRANE SWITCH STYLE DISPLAY INSTALLATION”. If it
has a grey box and is a touch screen display (replacement of original) then the communications cable must be plug inside the box to J9 or J10. This will require removal of the two screws holding the lid on. After plugging in the communications cable, route the cable to the right side with the other cables and put the lid back on with the two screws.
Top
Control Location
Figure 13. Controller Location (BTH or BTX models)
Removal of the top is not required, but it may be helpful to remove the control box lid. Use a ladder to access the top of taller water heaters.
Next locate the upper temperature probe and exhaust switch. Position the module between the two about 1 inch from the central
burner opening. For the 500 MBTUH Model this would be next to
the upper temperature probe.
Figure 14. Location of Exhaust Switch and Upper Temperature Probe
Connect the three wires from the end of the communication cable to the module in Accordance with page 4. Once the unit is installed and connected, the building management system can be connected to the appropriate connection point on the module.
Figure 15. Clearance of ICC Unit from Central Burner Opening

COMMERCIAL ELECTRIC WATER HEATER (TOUCH SCREEN INSTALLATION)

Normally the commercial electric heaters have a display with membrane switches, but may have had a replacement touch screen or future models may one day include touch screens. If this heater has membrane switches on the bottom and right of the display, then see the section below COMMERCIAL ELECTRIC WATER HEATER INSTALLATION.
Follow directions under general guidance for connecting module to the Energy Management System and power. This section will guide the installer on how to mount and connect the module to the water heater.
The module should be located where it will not interfere with the door or in a location that is acceptable to the customer. Care should be exercised to avoid drilling the self-tapping screws into electrical or sensitive components. Electrical power should be disconnected before proceeding with ICC installation.
Using a flat blade screwdriver, loosen the screws holding the door of the unit. See Figure B1. Swing the door to the open position
and locate the control board.
Figure 16. Opening the Control Board Compartment Door
Locate the module on the top of the door cabinet approximately 1 inch from the water heater jacket and on the centerline of the unit (See Figure 17 and Figure 18).
8
Figure 17. ICC Location Relative to Water Heater Jacket
Figure 18. ICC Location Relative to Centerline
Remove the hole plug from the 0.875” knockout on the left corner
of the top panel. See Figure 19.
Plug the communications cable into D9 and run the three wire connection up through the knockout and connect the three wires to the module as shown on page 4. Once the unit is installed and connected, the building management system can be connected to the appropriate connection point on the module.
Figure 19. Location of Communications Wiring Knockout
9

MEMBRANE SWITCH STYLE DISPLAY INSTALLATION

HIGH EFFICIENCY WATER HEATER INSTALLATION

Follow the directions under general guidelines for connecting the module to the Energy Management System and power. This section will guide the installer on how to mount and connect the module to the water heater.
The control box and mounting location on the water heater is on the top of the unit behind the display module. See Figure 20.
Figure 20. Locating the Control Box
Removal of the top is not required. Use a ladder to access the top of taller water heaters. Locate the back of the display as shown in Figure 21. Disconnect the RJ45 plug from the display and connect the RJ45 plug from the split communication cord into the display receptacle. Plug the display communication cord back into the receptacle on the split communication cord as shown in Figure 22. Plug the supplied wiring harness with the gateway controller into the remaining open RJ45 port on the Split Communication cord.
Figure 21. Locating the Back of the Display
Figure 23. Locating Upper Temperature Probe and Exhaust Switch
Figure 24. Connecting the Communications Cable to the Module
Connect the three wires from the end of the communication cable to the module in accordance with Figure 24. Once the unit is installed and connected, the building management system can be connected to the appropriate connection point on the module.

COMMERCIAL ELECTRIC WATER HEATER INSTALLATION

Follow directions in Device Congurations (page 6) for connecting the module to the Energy Management System and power. This section will guide the installer on how to mount and connect the module to the water heater.
The module should be located where it will not interfere with the door or in a location that is acceptable to the customer. Care should be exercised to avoid drilling the self tapping screws into electrical or sensitive components. Electrical power should be disconnected before proceeding with ICC installation.
Using a flat blade screwdriver, loosen the screws holding the door
of the unit. See Figure 25.
Swing the door to the open position and locate the back of the display module. See Figure 26.
Figure 22. Reconnecting the Communication cord to the Receptacle
Next locate the upper temperature probe and exhaust switch. See Figure 23. Position the module between the two about 1 inch from the central burner opening. See Figure 24. For the 500 MBTUH model this would be next to the upper temperature probe.
Figure 25. Loosening the Screws to the Door of the Unit
10
Unplug the display communication cable from the display. Plug the RJ45 plug from the split communication cable into the back of the display. See Figure 27.
Plug the display cable into the split cable receptacle as shown in Figure 28. Plug the supplied wiring harness with the gateway controller into the remaining open RJ45 port on the Split Communication cable (Not shown).
Locate the module on the top of the door cabinet approximately 1 inch from the water heater jacket and on the centerline of the unit (See Figure 29 and Figure 30).
Figure 29. Locating the Module
Figure 26. Locating the Communications Cable on Back of the
Display
Figure 27. Reconnecting RJ45 Plug from Split Communication Cable
Figure 30. Module Location Relative to Centerline
Remove the hole plug from the 0.875” knockout on the left corner
of the top panel. See Figure 31.
Run the three wire connection from the split cable up and through the knockout and connect the three wires to the module as shown on page 4. Once the unit is installed and connected, the building management system can be connected to the appropriate connection point on the module.
Figure 28. Connecting the Display Cable to Split Cable Receptacle
Figure 31. Knockout on Left Corner of Top Panel
11

BOILER INSTALLATION

XP XWH BOILER INSTALLATION

Follow directions under general guidance for connecting module to the Energy Management System and power. This section will guide the installer on how to mount and connect the module to the boiler.
Open the door on the low voltage wiring box on the back side of the heater to see the terminal strip where to connect the gateway to the boiler as shown in Figure 32
Figure 32. Boiler Terminal Strip
Inside the cover of the box shows the wiring legend for the terminal strip (see Figure 33).
Figure 33. Terminal Strip Wiring Legend
Place the Gateway on top of the heater or conveniently nearby.
Locate a knock out on the right side of the low voltage box to run the communication cable through to the inside of the low voltage box.
The boiler does not have an RJ-45 connector as do the water heaters to connect Port A of the gateway, so the plug on the other end of
the communications cable must also be cut off with a wire cutter. Locate and strip the insulation ½ inch from the brown, brown/white and blue/white wires. Connect the brown/white wire to COM2_A, the brown wire to COM2_B, and the blue/white wire to COM2_C.
12
Two versions of the ECC are available as follows:

BACnet / Gas Water Heaters

ECC DEVICE VERSIONS

Product:
Product Model Number:
Product Version:
BACnet Protocol Revision:
The following sections describe the ECC communications characteristics available with each of the following types of water heaters:
BACnet/Gas
BACnet/Electric
BACnet/Boilers
ModBus/Gas
ModBus/Electric
ICC Gateway (for use with XiTM and MXiTM Gas Water Heaters)
100316044 (Mirius for BACnet MT/TP)
100316045 (ETH-1000 for BACnet IP)
V3.000 (Mirius) or V4.001 or greater (ETH-1000)
12 (135-2010)
BACNET / GAS WATER HEATERS
Figure 34. Cyclone Xi Gas Water Heaters (Virtual BACnet device via ICC Gateway)

PRODUCT DESCRIPTION

The Mirius is a multiprotocol RS-485 to RS-485 gateway. The ETH-1000 is an Ethernet to RS-485 multiprotocol gateway. These
products supports native BACnet, connecting directly to IP or the MS/TP LAN using baud rates of 4800, 9600, 19200, 38400, 57600, 76800, and 115200. As shipped the devices are congured as a BACnet Server.
All XI™ MXi™ controls provide communications via propriety protocol with the ICC Gateway. The Mirius supports BACnet MS/TP communications and the ETH-1000 supports BACnet/IP to access data available at the display plus control of a limited number of
points such as Operating Setpoint.
13
BACnet / Gas Water Heaters

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)

BACnet Standardized Device Prole (Annex L):
BACnet Application Specic Controller (B-ASC)
BACnet Interoperability
Table 3. BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing - ReadProperty-A (DS-RP-A)
Data Sharing - ReadProperty-B (DS-RP-B)
Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing - WriteProperty-A (DS-WP-A)
Data Sharing - WriteProperty-B (DS-WP-B)
Data Sharing - WritePropertyMultiple-B (DS-WPM-B)
Data Sharing – COV-B (DS-COV-B) (BACnet/IP only)
Device Management-Dynamic Device Binding-A (DM-DDB-A)
Device Management-Dynamic Device Binding-B (DM-DDB-B)
Device Management-Dynamic Object Binding-B (DM-DOB-B)
Device Management-Device Communication Control-B (DM-DCC-B)
Device Management – ReinitializeDevice-B (DM-RD-B)
Segmentation Capability
Segmentation not supported.
Data Link Layer Options
Table 4. Data Link Layer Options
BACnet IP (Annex J) (ETH-1000 only)
BACnet IP (Annex J), Foreign Device (ETH-1000 only)
ANSI/ATA 878.1, 2.5Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485. ARCNET (Clause 8), baud rates() ________
MS/TP master (Clause9) baud rate(s): 4800, 19200, 38400, 57600,
76800, 115200
MS/TP slave (Clause9) baud rate(s): _________
Point-To-Point, EIA 232 (Clause 10), baud rate(s): _________
Point-To-Point, modem (Clause 10), baud rate(s): _________
LonTalk, (Clause 11), medium ________
Other: _________________
Device Address Binding
Is static device binding supported? (This is currently for two-way communications with MS/TP slaves and certain other devices.) YES
14
Networking Options
Character Sets
BACnet / Gas Water Heaters
Table 5. Networking Options
Router, Clause 6 – List all routing congurations
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD). Does the BBMD
support registrations by Foreign Devices? (ETH-1000 only)
Table 6. Character Sets Supported
ANSI X3.4
IBMTM /MicrosoftTM DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (UCS-4)
JIS C 6226
Data Types
The following table summarizes the data types that are accepted (in the case of a write property service) and returned (in the case of a
read property service) when targeting the present value property of each supported object type.
Table 7. Data Types Supported
Service
Object Type
Analog Output
Read Property Write Property
Real Real, Unsigned, Integer, Null
Analog Value
Analog Input Real N/A
Binary Output
Enumerated Enumerated, Boolean, Real, Unsigned, Integer, Null
Binary Value
Binary Input Enumerated N/A
Multi-state Output
Unsigned Real, Enumerated, Unsigned, Integer, Null
Multi-state Value
Multi-state Input Unsigned N/A
15
Object Types and Properties
Property Device
Object Identier
Object Name
Object Type
System Status
Vendor Name
Vendor Identier
Model Name
Firmware Revision
App S/W Revision
Protocol Revision
Services Supported
Object Types Supported
Object List
Max APDU Length
Segmentation Support
APDU Timeout
Number APDU Retries
Max master
Max Info Frames
Device Address Binding
Database Revision
Present Value
Status Flags
Event State
Out-of Service
Units
Priority Array
Relinquish Default
Polarity
Inactive Text
Active Text
R - readable using BACnet services W - readable and writable using BACnet services
BACnet / Gas Water Heaters
Table 8. Object Types/Property Support Table
Binary
Input
R R R R R R R R R R
R R R R R R R R R R
R R R R R R R R R R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R W W R W W R W W
R R R R R R R R R
R R R R R R R R R
R R R R R R R R R
R R R R R R
R R R R R
R R R R R
R R
R R
R R
Binary
Output
Binary
Value
Analog
Input
Analog Output
Analog
Value
Multi Input
Multi
Output
Multi
Value

DEVICE OBJECT LISTINGS

Object Min/Max Values
Note: Point listings have been changed completely from earlier versions of this listing.
Table 9. Device Object
Property Name ID BACnet Data Type RW Initial Value
(Mirius)
Initial Value
(ETH-1000)
Object_Identier 75 Object Identier RW Device, 520081 Device, 520081
Object_Name 77 Character String RW Water Heater-01 Water Heater-01
Object_Type 79 Enumerated R Device Device
System_Status 112 R Operational Operational
16
BACnet / Gas Water Heaters
Table 9. Device Object
Property Name ID BACnet Data Type RW Initial Value
(Mirius)
Vendor_Name 121 R ICC, Inc. ICC, Inc.
Vendor_Identier 120 R 242 242
Model_Name 70 R Mirius ETH-1000
Firmware_Revision 44 Character String R V3.300 V4.002
Application_Software_Version 12 R V3.300 V4.002
Protocol_Version 98 R 1
Protocol_Revision 139 R 2
Protocol_Services_Supported 97 R See PICS
Protocol_Object_Types_Supported 96 R AI, AO, AV, BI,
BO, BV, MSI,
MSO, MSV
Object_List 76 R See Table See Table
Max_APDU_Length_Accepted 62 R 480 1444
Segmentation_Supported 107 R 3 3
APDU_Timeout 10 RW 1000ms 1000ms
Number_Of_APDU_Retries 73 R 3 3
Max_Master 64 RW 127 Unsupported
Device_Address_Binding 30 R {} {}
Local_Date 56 R Unsupported Unsupported
Local_Time 57 R Unsupported Unsupported
Initial Value
(ETH-1000)
AI, AO, AV, BI, BO, BV, MSI,
MSO, MSV
BACnet/Gas Water Heaters Object List
• Not all models support all registers. Also parameter names may be different than shown here on some models.
• This table may be subject to change in the future.
Adjustable objects are in bold and indicated by “W” (writable).
Table 10. BACnet/Gas Water Heaters Object List
BACnet Object Name (Description)
Firmware Ver-Rev (Firmware Version)
Conguration Analog Input 2 Present_Value R
Upper Temperature (Upper or Primary Temperature)
Lower Temperature (Lower or Secondary Temperature)
Tank Temperature (Controlling Tank Temperature algorithmically calculated)
Temper Setpoint (Desired Tank Temperature)
SetPoint Differ (Setpoint Differential)
1. Data is encoded into the 16 bits as major revision (upper 8 bits) and minor revision (lower 8 bits).
2. Not recommended for use currently as UIM does not currently support and warning will come up as “Unknown.”
1
BACnet
Object
Type/Inst.
Analog Input 1 Present_Value R
Analog Input 3 Present_Value R ºC
Analog Input 4 Present_Value R ºC
Analog Input 5 Present_Value R ºC
Analog Value 201 Present_Value R/W ºC
Analog Value 202 Present_Value R/W °C
BACnet
Object
Property R/W Units
(ºF)
(°F)
Min Value (if W)
32.2 (90)
1.1 (2)
Max
Value
(if W) Xi 1.0 Mxi
82.2
(180)
11.1 (20)
17
Loading...
+ 39 hidden pages