ICA ST 531 C, ST 831 C, ST 1231 C, ST 1631 C User Manual

UNINTERRUPTIBLE POWER
SYSTEMS
ICA
ST 531 C ST 831 C ST 1231 C ST 1631 C
481-1180020-131
CONTENT / DAFTAR ISI
Page / Halaman
I. INTRODUCTION / PENDAHULUAN ………………………………………… 1
II. TECHNICAL SPECIFICATION / SPESIFIKASI TEKNIK …………………... 2
III. FRONT PANEL & REAR PANEL VIEW /
TAMPAK PANEL DEPAN & PANEL BELAKANG ………….……………… 3
V. START UP UPS / MENGHIDUPKAN UPS .....……………………………….. 5
VI. OPERATION PROCEDURE / CARA MENGOPERASIKAN …..…………….. 6
VII. TABLE OF INDICATOR STATUS / TABEL STATUS INDIKATOR .............. 7
VIII. TROUBLE SHOOTING / PETUNJUK KETIDAK NORMALAN ……………. 8
I. INTRODUCTION / PENDAHULUAN
The ST Series UPS is an advanced true on­line sinewave Uninterruptible Power Supplies with high voltage PWM (Pulse Width Modulation) technology and static transfer switch. The UPS can provide reliable, regulated, transient free AC power to sensitive equipment ranging from computers and telecommunication systems to computerized instrument. The UPS has high non linear load current capability (crest ratio 3:1) and this is suitable for powering special loads such switching power supplies or high capacitive load.
The static transfer switch (STS) system provides bypass power as its standby source. Upon inverter failure or overload, the STS will switch the output power Bypass (if the power line exists) within 0 ms. The STS can retransfer back to inverter automatically when the system is restored to normal condition within 2 ms.
This UPS is also provided completed by interface for communication with computer, with operating system Windows 95, 98, ME, Unix / Linux and Windows NT4/2000. Information from UPS to Computer is power fail and battery low.
RECITIFIER WITH PFC
INPUT
CHARGER
ISOLATTION CONVER TER
BATTERY
BY PASS
INVERTER
INV
STATIC SWITCH
Supplies jenis tidak terputus dengan output sinusoida yang menggunakan teknologi PWM (Pulse Width Modulation) tegangan tinggi dan dilengkapi dengan static transfer switch. UPS ini menghasilkan sumber daya output yang sangat stabil dan bebas dari tegangan transient, jadi sangat baik untuk digunakan pada peralatan yang sensitif seperti komputer, sistem telekomunikasi, dan peralatan canggih lainnya.
linier yang tinggi (crest ratio 3:1), sehingga memungkinkan untuk digunakan pada beban-beban seperti switching power supply atau beban kapasitif tinggi.
pemintasan daya UPS. Manakala inverter mengalami kegagalan atau mendapat beban lebih, STS akan mengalihkan sumber daya untuk keluaran UPS dari inverter kepada daya dari jala-jala/PLN (apabila daya jala-jala ada) dengan waktu alih 0 ms. STS otomatis akan kembali mengambil daya dari inverter dalam waktu 2 ms apabila sistem kembali ke kondisi normal.
berkomunikasi dengan komputer, baik dengan sistem operasi Windows 95, 98, ME, Unix/Linux maupun Windows NT4/2000. Informasi yang
OUTPUT
diberikan ke komputer adalah saat PLN mati dan pada saat Battery hampir habis
UPS ST Series adalah Uninterruptible Power
UPS ini mempunyai kemampuan beban non
Static transfer switch (STS) adalah sistem
UPS ini dilengkapi juga interface untuk
II. TECHNICAL SPECIFICATION / SPESIFIKASI TEKNIK
ITEM UNIT SPECIFICATION REMARKS
MODEL ST 531 C ST 831 C ST 1231 C ST 1631 C POWER VA/W 1000/500 1600/800 2400/1200 3200/1600
Voltage V 160 – 250
AC IN-
Frequency Hz 50 ± 3
PUT
Protection A 5 7 10 15 Fuse Voltage V 24 48 72 96
DC
Internal Battery
IN-
PUT
Protection Fuse
CHG
Transfer Time If Input Failure ms 0 On Line
Transfer Time S. T. S. ms Back Up Time min 10
Operating Temperature °C 0 – 40 Dimensions mm 395 x 190 x 290 510 x 190 x 330 D x W x H Weights Kg 14,5 19,5 28 33
Topology Floating Voltage V
Waveform
IN-
Distortion
VER
Topology
TER
O
Voltage V
U
Frequency Hz
T
Efficiency % > 85
BUZ ZER
AC Input Low / Fail
Battery Low Every 1 second
2 x 12V : 7AH 4 x 12V : 7AH 6 x 12V : 7AH 8 x 12V : 7AH
27.2 54.4 81.6 108.8
Switching Regulation
Sinewave
< 3% THD
Pulse Width Modulation (PWM)
220 ± 2 %
50 ± 1%
Load 0 -100%
2 ms from Inverter to Bypass
Zero crossing Bypass to Inverter
Every 4 seconds
SLA Battery
At Full Load
At Nominal
Load
III. FRONT PANEL & REAR PANEL VIEW / TAMPAK PANEL DEPAN & PANEL BELAKANG
1
FRONT PANEL VI EW
UPS ST 531 C, ST 831 C
UPS ST 1231 C, ST 1631 C
1. Panel Monitor
2. Main Switch / Tombol Daya : To turn on and off the UPS / Untuk menghidupkan dan mematikan UPS
3. RS232 Connector / Konektor RS232 : For communication between UPS and Computer / Untuk
4. Outlet / Stopkontak Output
5. Input Fuse / Fuse Input
6. External Battery (Optional) / Battere Luar (Tambahan)
7. Inlet / Stopkontak Input
8. Ventilation / Lubang Angin
2
REAR PANEL VIEW
UPS ST 531 C
REAR PANEL VIEW
UPS ST 831 C
komunikasi antara UPS dengan komputer
REAR PANEL VIEW
UPS ST 1231 C - ST 1631 C
IV. INDICATORS STATUS / STATUS INDIKATOR
1
2
1. Line On : Green led, indicate AC power on / Led hijau, menunjukkan PLN ada.
2. Battery Level : 6 leds, indicate status of battery / 6 buah led, menunjukkan keadaan baterai.
3. By Pass : Yellow led, indicate output UPS from AC input / Led kuning, menunjukkan output berasal dari PLN
4. Inverter Output : Green led, indicate output UPS from inverter / Led hijau, menunjukkan output berasal dari inverter
5. Inverter On : Green led, indicate inverter on / Led hijau, menunjukkan inverter bekerja.
6. Over Load : Red led, indicate overload / Led merah, menunjukkan keadaan beban lebih.
7. Fault : Red led, indicate inverter failure / Led merah, menunjukkan adanya gangguan pada inverter
3
OUTPUT
4
5
6 7
V. START UP UPS / MENGHIDUPKAN UPS
1. Make sure main switch is in the off position and
no load is connected to the UPS output.
2. Connect inlet to the mains. The indicator
“INPUT” will light on.
3. Turn on the main switch, the indicator
“INVERTER” light on and the indicator “BYPASS” light on for about 20 seconds, and will go out, at the same time battery level led will light on (depend on the battery condition) and the indicator “INVERTER OUTPUT” will light on.
4. Disconnect inlet from the mains, the indicator
“INPUT” will go out and audible alarm will sound with 4 seconds intervals. Now the output is supplied from the battery source.
5. Connect inlet to the mains again. The indicator
“INPUT” will light on again.
6. Now UPS is ready for operation. Plug the
critical devices such as computer, disk drives, monitor, printer or electronic instrument to the output UPS.
1. Pastikan posisi Main Switch, pada posisi “OFF”
dan tidak ada beban yang terpasang pada terminal output UPS.
2. Hubungkan kabel input PLN, indikator
“INPUT” akan menyala.
3. Hidupkan main switch, indikator “INVERTER”
menyala dan indikator “BYPASS” menyala ± 20 detik kemudian akan mati, bersamaan dengan itu indikator baterai level akan menyala (tergantung kondisi baterai) dan indikator “INVERTER OUTPUT” akan menyala.
4. Lepaskan kabel input PLN, indikator “INPUT”
akan mati dan buzzer akan berbunyi setiap 4 detik, berarti UPS bekerja dengan battery sebagai sumbernya.
5. Hubungkan lagi kabel Input PLN, indikator
“INPUT” akan menyala kembali.
6. Sekarang UPS siap menjalankan fungsinya,
hubungkan peralatan yang sensitif seperti komputer, diskdrive, monitor, printer atau iInstrument elektronik lainnya ke unit output UPS.
VI. OPERATION PROCEDURE / CARA MENGOPERASIKAN
1. Turn on Procedure :
a. Turn on the main switch at front panel. b. Turn on the power switch on your devices.
2. When utility power is interrupted, the UPS can
work without transfer (0 ms) and the audible alarm will sound every 4 seconds. When battery low, the audible alarm will sound every 1 second.
3. Turn off procedure :
a. turn off all the power switch on your
devices.
b. turn off the main switch at front panel.
1. Menghidupkan UPS : a. Hidupkan Main Switch pada panel depan. b. Hidupkan beban yang terpasang pad a
Output.
2. Pada saat tegangan jala-jala mati, UPS akan segera bekerja tanpa waktu transfer (0 ms) dan Buzzer akan berbunyi tiap 4 detik. Pada saat battery akan habis, buzzer akan berbunyi tiap 1 detik.
3. Mematikan UPS :
a. Matikan semua beb a n yang terpasang pada
UPS.
b. Matikan Main switch pada panel depan
VII. TABLE OF INDICATOR STATUS / TABEL STATUS INDIKATOR
LINE
INPUT
ON ON - - - - Normal -
ON ON - - -
ON - ON - ON Continuous
ON - ON ON - Continuous 1. Inverter failure
INVERTER
OUTPUT
- ON - - -
- ON - - -
BY
PASS
FAULT
OVER LOAD
BUZZER
Every 4 seconds
Every 1 second
Every 4 seconds
STATUS
CONDITION
Utility power failure -
Battery will discharge completely
Rectifier failure Call for service
1. UPS not running
2. Overload
RECOMMENDED
SOLUTION
Close your software and files in use
Remove some load from the UPS
Refer to trouble shooting guide
VIII. TROUBLE SHOOTING / PETUNJUK KETIDAK NORMALAN
SYMPTOM PROBABLE CAUSE RECOMMENDED SOLUTION
1. UPS not running 1. Turn on the UPS
“INPUT” and “BYPASS” indicator are “ON”
“INPUT”, “BYPASS” and “FAULT” indicator are “ON” and alarm sounds continuously
“INPUT” indicator is “OFF” and alarm sounds periodically
No Output Voltage when input power fails
“INPUT” and “INVERTER” indicator are “ON” but alarm sounds
2. Overload
Inverter failure
Utility power failure
Batteries discharged completely
Rectifier failure
1. Remove some load from the UPS
2. If it remains the same, call for service
1. Turn off main switch and turn on main
switch again
2. If UPS doesn’t recover, call for service
1. Check utility power is present at wall
outlet
2. Otherwise, call for service
1. Recharging the battery by keep the main switch “ON” for 10 hours
2. Retest the battery discharging again. If it remains the same, call for service
Call for service
SERVICE CENTRE
ICA
Jln. Pinangsia Raya I No: 22BB
Jakarta - Barat
Telphone : 6906020 (Hunting)