IBC Boilers VFC 15-150, VFC 45-225 Installation And Operating Instructions Manual

VFC 15-150, VFC 45-225
MODULATING GAS BOILERS
(Natural Gas or Propane)
WARNING: If the information in this manual is not followed exactly, a re or
explosion may result causing property damage, personal injury, or loss of life.
Do not store or use gasoline or other ammable vapours and liquids or other combustible materials in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Immediately call your gas supplier from a nearby phone. Follow the gas
supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service
agency or the gas supplier.
This Manual is also available in French - contact IBC or visit our web site www.ibcboiler.com
INSTALLATION AND OPERATING INSTRUCTIONS
www.ibcboiler.com
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
SAFETY CONSIDERATIONS
WARNING
If the information in this manual is not followed
exactly, a re or explosion
may result causing property damage, personal injury, or loss of life.
Installation, start-up and servicing of IBC boilers must be done with due care and attention, and should only be performed by competent, qualied,
licensed and trained heating technicians.
Failure to read and comply with all instructions and applicable National and local codes may result in hazardous conditions that could result in property damage and injury to occupants which in extreme cases might result in death.
HAZARDS & PRECAUTIONS
DANGER
Points out an immediately hazardous situation which
must be avoided in order to prevent serious injury or
death.
CAUTION
WARNING
Points out a potentially hazardous situation which
must be avoided to prevent
serious injury or death.
NOTE
Points out a potentially hazardous situation which
must be avoided to prevent
possible moderate injury and/ or property damage
Points out installation, maintenance and operation details that will result in
enhanced efciency, longevity
and proper operation of your boiler.
BEST PRACTICES
Points out recommendations for better installation.
Supplied with the boiler - The IBC boiler is shipped with an accessory parts kit
consisting of the following items:
1 x Vent connection kit
1 x Condensate trap kit
1 x 30 psig pressure relief valve
1 x Outdoor temperature sensor
2
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
SPECIFICATIONS
SPECIFICATION VFC 15-150 VFC 45-225
CSA Input (Natural Gas or Propane) - MBH
CSA Input (Natural Gas or Propane) - kW
CSA Output - MBH
CSA Output - kW
A.F.U.E. 95% 95%
Minimum gas supply pressure (Natural Gas or Propane) - inch w.c.
Maximum gas supply pressure (Natural Gas or Propane) - inch w.c.
Power use (120Vac/60Hz) @ full re - Watts (excluding pumps)
Weight (shipping) - lbs/Kg 165 / 75 168 / 76
Pressure vessel water content - USG/Litres 2.4 / 9 2.4 / 9
Maximum boiler ow rate - USgpm 16 25
Minimum boiler ow rate - USgpm 4 8
Maximum operating water pressure* - psig 80 80
Minimum water pressure - psig 8 8
Normal ue temperature @ 100°F boiler return water temperature - high re
15 - 150
4.4 - 44
14 - 139
4.1 - 41
3
3
14
14
57 167
100 to 105 °F
37.8 to 40.5°C
45 - 225
13 - 66
41 - 206
12 - 60
3
3
14
14
100 to 105 °F
37.8 to 40.5°C
Normal ue temperature @ 160°F boiler return water temperature - high re
Approved installation altitude - ASL 0 - 12,000’ 0 - 12,000’
Ambient temperature - Low (°F-°C) Ambient temperature - High (°F-°C)
Max. relative humidity (non-condensing) 90% 90%
Minimum water temp. 34°F / 1.1°C 34°F / 1.1°C
Maximum water temp. (electronic hi-limit) 190°F / 87.8°C 190°F / 87.8°C
Maximum water temp. (mechanical hi-limit) 200°F / 93.3°C 200°F / 93.3°C
Max. ΔT - supply/return (electronic fence) 40°F 40°F
Maximum equivalent vent length - 2”
Each side (Vent & Air Intake)) - 3”
(Natural Gas or Propane)
Air intake options: either direct vent or indoor
supply
* boilers are shipped with 30 psig pressure relief valve
160 to 165 °F
71.1 to 73.9°C
32°F / 0°C 122°F / 50°C
50’
120’
160 to 165 °F
71.1 to 73.9°C
32°F / 0°C 122°F / 50°C
N/A
240’
INSTALLATION AND OPERATION INSTRUCTIONS
3
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
THIS PAGE INTENTIONALLY LEFT BLANK
4
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
CONTENTS
1.0 INSTALLATION....................................................1-1
1.1 GENERAL ...................................................1-1
1.2 CODE REQUIREMENTS ........................................1-2
1.3 LOCATION ...................................................1-2
1.4 EXHAUST VENTING AND AIR INTAKE.............................1-3
1.5 CONDENSATE REMOVAL......................................1-14
1.6 WATER PIPING ..............................................1-20
1.7 GAS PIPING.................................................1-26
1.8 ELECTRICAL CONNECTIONS ..................................1-27
2.0 IBC BOILER CONTROL.............................................2-1
2.1 GENERAL ...................................................2-1
2.2 CONTROL ...................................................2-1
2.3 CONTROL INTERFACE.........................................2-2
3.0 STARTUP AND COMMISSIONING ....................................3-1
3.1 LIGHTING AND SHUTTING DOWN THE BOILER ....................3-1
3.2 PRIOR TO START-UP ..........................................3-2
3.3 COMMISSIONING .............................................3-2
3.4 FUEL CONVERSION ...........................................3-5
4.0 MAINTENANCE ...................................................4-1
4.1 BOILER MAINTENANCE ........................................4-1
4.2 COMPONENT DESCRIPTION....................................4-4
4.3 GAINING ACCESS TO COMBUSTION CHAMBER, BURNER REMOVAL
INSTRUCTIONS; FAN AND GAS VALVE REMOVAL INSTRUCTIONS ....4-6
5.0 TROUBLESHOOTING ..............................................5-1
5.1 PRELIMINARY CHECKS ........................................5-1
5.2 ELECTRONIC COMPONENTS ...................................5-2
5.3 TROUBLESHOOTING GUIDE....................................5-6
6.0 DIAGRAMS.......................................................6-1
6.1 VFC 15-150 PARTS DIAGRAMS ..................................6-2
6.2 VFC 45-225 PARTS DIAGRAMS ..................................6-4
6.3 ADDITIONAL PARTS DIAGRAMS .................................6-6
6.4 WIRING DIAGRAMS ...........................................6-7
6.5 SEQUENCE OF OPERATIONS ...................................6-9
INSTALLATION AND OPERATION INSTRUCTIONS
5
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
DANGER
Should overheating occur
or the gas supply fails to shut off, do not turn off or disconnect the electrical supply to the pump. Instead shut off the gas supply at a location external to the appliance.
WARNING
Do not use this boiler if any part has been under water.
Immediately call a qualied service technician to inspect
the boiler and to replace any part of the control system and any gas control that has been under water.
CAUTION
Care must be taken to
properly size the boiler for its intended use. Prolonged
full re run time, over-
sizing or under-sizing,
and incorrect ow rates
through the boiler can lead to increased maintenance
costs, equipment stress and
premature failure.
WARNING
If the boiler can become
exposed to uid temperatures below 34°F (1°C), a method of protection to prevent freezing
of condensate should be
employed. Contact the factory
for further information.
The Installer must carefully read this manual to ensure that all installation details can be adhered to. Special attention is to be paid to clearances and access, vent travel and termination, gas supply, condensate removal and combustion air supply.
The Installer should do a pre-installation check the to ensure that the following precautions can be observed:
The boiler should be installed in areas where the combustion air source is
not subject to chemical fouling or agricultural vapours. Exposure to corrosive
chemical fumes such as chlorinated and/or uorinated hydrocarbons can
reduce the life of a boiler. Cleaners, bleaches, air fresheners, refrigerants,
aerosol propellants, dry-cleaning uids, de-greasers and paint-removers all
contain vapours which can form corrosive acid compounds when burned in a
gas ame. Airborne chlorides such as those released with the use of laundry
detergents are also to be avoided. For this reason, the indoor air venting option using air surrounding the boiler should not be used in a laundry room. Similarly, ensure any direct vent air source is not adjacent to a clothes dryer exhaust terminal. Avoid agricultural applications where the boiler and/or the intake air source are affected by ammonia and/or dust.
The boiler should be located where water leakage will not result in damage
to the area. If a location such as this cannot be found, a suitable drain pan should be installed under the appliance. The boiler is not to be installed above carpeting.
At a new construction site, or during renovations, action must be taken to
protect the boiler from drywall dust or other construction related contaminants; combustion air should be drawn from a CLEAN source (e.g. outdoors) and the boiler should be isolated from interior dust sources. Do not seal boiler case
openings directly when ring - allow for air circulation and ventilation in the
immediate area.
When the boiler is in operation, the impact of the steam plume normally
experienced at the exhaust terminal of a condensing boiler should be assessed. Generally, intake and exhaust pipes should terminate at a rooftop or sterile wall location. Boiler condensate is corrosive. Protective measures must be taken to prevent corrosion damage to metal roofs or other metal building components in contact with the condensate. Keep exhaust plumes well away from all building air intakes including those of neighbouring properties.
The exhaust outlet should be placed so as to reach 24” minimum above the
down-turned intake - to avoid exhaust re-ingestion.
For sidewall venting options: Both the inlet and exhaust terminations should
normally be located on the same plane (side) of the building. The elevation of both pipes can be raised in “periscope style” after passing through the wall to gain required clearance above grade and snow level.
If the indoor combustion air option is used, ensure combustion air openings to
the boiler room remain unblocked and free of obstructions.
Examine the condensate outlet to ensure proper disposal of condensate will
occur during operation. If condensate will be discharged into copper or ferrous metal drains, ensure acid neutralization is employed.
Ensure that the pressure relief valve will be installed with no valves or other
means of isolation between its inlet and the boiler. Make sure the relief valve outlet will be piped with unobstructed piping (minimum 3/4” diameter) to a safe discharge location.
6
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
INSTALLATION1.0
1.1
GENERAL
VFC gas-red modulating boilers are low pressure, fully condensing units having
variable input ranges (a) 15 MBH (15,000 Btu/hr) to 150 MBH (15-150 model, 0 to 12,000’) and (b) 45 MBH to 225 MBH (45-225 model, 0 to 12,000’). The boilers are approved as “Category IV” vented appliances using either Direct Vent (sealed combustion) or indoor combustion air, providing a great degree of
installation exibility.
Figure 1 shows outer case dimensions and piping and electrical holes. Use this diagram to nd a suitable location for the boiler. See also Section 1.3 Location.
DESCRIPTION SIZE
A Water Outlet 1-1/4" NPT-M
B Water Inlet 1-1/4" NPT-M
C Gas Inlet 1/2" NPT-F
D Knock-outs (6) 1/2"
E Touch Screen Display 2-1/4” x 4”
F Exhaust Vent 4.0" Hole
G Combustion Air 4.0" Hole
Table 1: Connections
Figure 1a: Dimensions / Connections for VFC 15-150 Figure 1b: Dimensions / Connections for VFC 45-225
INSTALLATION
1-1
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.2
1.3
WARNING
Keep boiler area free and clear
of combustible materials,
gasoline, and other ammable vapours and liquids.
WARNING
Combustion air must not be
drawn from areas containing
corrosive air from swimming
pools or spas, including air directly next to outdoor pools and spas.
WARNING
The boiler shall not be exposed to water leaks from piping or components located overhead. This includes condensation
dropping from un-insulated
cold water lines overhead.
CODE REQUIREMENTS
The VFC 15-150 and VFC 45-225 boiler models were tested to and certied
under CSA 4.9-2014 / ANSI Z21.13-2014.
Installation must conform to local codes, or in the absence of these, with the latest editions of CAN/CGA B149.1 and the Canadian Electrical Code Part 1 CSA C22.2 No. 1.
In the US, installations must conform to the current National Fuel Gas Code ANSI Z223.1 and the National Electrical Code ANSI/NFPA 70. Where required by jurisdiction, installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. If there is any
conict, then the more stringent requirement will apply.
LOCATION
VFC-series boilers are designed and approved for indoor installation (wall or rack
mounting), with signicant exibility of location provided with the available venting
options. The boiler can be placed in an alcove, basement, closet or utility room. Surrounding ambient conditions shall be 0°C to 50°C and less than 90% relative
humidity.
Install the boiler in areas where the combustion air source is not subject to
chemical fouling or agricultural vapours. Exposure to corrosive chemical fumes such as chlorinated and/or uorinated hydrocarbons can reduce
the life of a boiler. Cleaners, bleaches, air fresheners, refrigerants, aerosol
propellants, dry-cleaning uids, de-greasers and paint-removers all contain vapours which can form corrosive acid compounds when burned in a gas ame.
Airborne chlorides such as those released with the use of laundry detergents are also to be avoided. For this reason, the indoor air venting option using air surrounding the boiler should not be used in a laundry room. Similarly, ensure any direct vent air source is not adjacent to a clothes dryer exhaust terminal.
Avoid agricultural applications where the boiler and/or the intake air source
are affected by ammonia and/or dust.
Locate the boiler where water leakage will not result in damage to the area. If a location such as this cannot be found, a suitable drain pan should be installed under the appliance. The boiler is not to be installed above carpeting.
Boiler weight: 150 lbs / 68 kg without water. Use - as a minimum - 4 x #12 size 2" lag screws or 1/4" bolts (with metal mounting systems). Fasteners are to be attached to solid material capable of supporting the combined weight of the boiler and piping assembly components.
WARNING
Ensure the gas ignition system components are
protected from water (dripping, spraying, rain, etc.) during
appliance operation and when
servicing (pump replacement, condensate trap servicing, control replacement, etc.)
1-2
Other factors affecting potential mounting sites:
Ensure minimum clearance requirements for combustible materials (see
Minimum 24" clearance at the front and 10” above is recommended for
At a new construction site, or during renovations, action must be taken
Table 2) are satised.
adequate servicing. Check local codes for additional access and service clearance requirements.
to protect the boiler from drywall dust or other construction related
contaminants; combustion air should be drawn from a CLEAN source (e.g. outdoors) and the boiler should be isolated from interior dust
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
Exposed water piping and associated components
(relief valves, circulators, etc.)
should not be in contact with
combustible materials. Check local codes for required clearances and/or provide adequate insulation.
1.4
sources. Do not seal boiler case openings directly when ring - allow for air circulation and ventilation in the immediate area.
DISTANCE FROM
SURFACE
Front 2" 24"
Rear 0" 0"
Left Side 0" 8" (for vent run)
Right Side 2" 18"
Top 6" 10"
Table 2 - Clearance from boiler cabinet
Distance below the boiler of up to 15" is required to provide clearance for the inlet and exhaust venting together with the required condensation trap. See page 1-15.
COMBUSTIBLE SURFACES
RECOMMENDED DISTANCE FOR SERVICE
EXHAUST VENTING AND AIR INTAKE
DANGER
Do not common vent the VFC
modulating series boilers with any other existing or new appliance.
WARNING
DO NOT MOUNT THIS BOILER TO HOLLOW WALL STRUCTURES - The
combined weight of the boiler, its water contents and associated piping
components can exceed 225
pounds. Fasteners must be rated for this strain, and must
be rmly anchored into solid
material that will support this weight.
Installers are to take all
necessary precautions
to avoid injury during the
installation of this boiler.
It is important to carefully plan the installation to ensure the appropriate
vent materials, travel and termination decisions are incorporated. Specic
attention is warranted to manage the impact of the steam plume normally experienced at the exhaust terminal of a condensing boiler. Generally,
intake and exhaust pipes should terminate at a rooftop or sterile wall location, to maximize customer satisfaction. Keep exhaust plumes well away from all building air intakes including those of neighbouring
properties.
All venting must be installed in accordance with the requirements of the jurisdiction having authority: in Canada, Part 8, Venting Systems of the B149.1­10 Code and any other local building codes are to be followed. In the USA the National Fuel Gas Code, ANSI 223.1, latest edition, prevails. Where there is a discrepancy between the installation instructions below, and the code requirements, the more stringent shall apply.
IMPORTANT
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z223.1 - latest edition. In Canada, use the B149.1-10 Installation Code.
At the time of removal of an existing boiler the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Seal any unused opening in the common venting system.
Visually inspect the venting system for proper size and horizontal pitch and
INSTALLATION
1-3
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
determine there is no blockage or restriction, leakage, corrosion and other
deciencies which could cause an unsafe condition.
Insofar as is practical, close all building doors and windows and all doors
between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer
exhaust fan. Close replace dampers.
Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust thermostat so appliance will operate continuously.
After it has been determined that each appliance remaining connected to the
common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and any other gas-burning
appliance to their previous conditions of use.
Any improper operation of the common venting system should be corrected
so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 ­latest edition. In Canada, all installations must conform with the current CAN/ CGA - B149.1-10 Installation Code and/or local codes.
WARNING
Venting, condensate
drainage, and combustion
air systems for all IBC
boilers must be installed in compliance with all applicable codes and the instructions of
their respective Installation Manuals.
Inspect nished vent and air
piping thoroughly to ensure all are airtight and comply
with the instructions provided and with all requirements of
applicable codes.
Failure to comply will result
in severe personal injury or
death.
WARNING
Covering non-metallic vent pipe and ttings with thermal
insulation shall be prohibited.
1.4.1 Applications
All VFC-series boilers are approved with alternative venting options: either 2-pipe
Direct Vent or single pipe /Indoor Air venting can be used offering exibility to meet the specic requirements of the installation. With the Direct Vent case,
combustion air is piped directly to the boiler’s air intake from outdoors (see Section 1.4 for air intake piping requirements). Using the indoor air alternative, air
for combustion is drawn from the indoor air surrounding the boiler.
Provided the maximum overall vent length limit is not exceeded, the installer may choose to vent the boiler through the wall, directly through the roof or upward using an existing - but otherwise unused - chimney as a vent raceway.
1.4.2 Exhaust Vent Material
EXHAUST VENT MATERIAL – CANADA
Use Polypropylene (PPs) or CPVC vent systems approved under ULC-S636 Standard for Type BH Gas Venting Systems, or stainless steel Type BH venting
systems. Permitted PPs materials comprise Single Wall Rigid pipe and ttings
and Flexible.
ULC-S636 CPVC: 90°C (194°F)
ULC-S636 PPs: 110°C (230°F)
In the standard conguration, VFC series boilers can supply water temperatures
up to 190°F, leaving stack temperatures above the 65°C (149°F) limit for ULC-S636 approved PVC.
For long vent runs with higher initial exhaust temperature, some jurisdictions may allow the use of mixed materials for economy: ULC-S636 approved CPVC for the initial run followed by ULC-S636 approved PVC to the termination (It is the responsibility of the Installer to conrm that local codes will allow this option). Ensure appropriate transition glue is used. The installer is responsible to ensure
1-4
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
Do not mix PPs venting
materials from different
Manufacturers.
These venting materials are
designed to be installed as part of a complete system.
Failure to comply may result
in severe personal injury or
death.
DANGER
Failure to install PPs adaptor with retainer clip could cause release of harmful exhaust gases into the heated space, potentially leading to injury or death.
that sufcient temperature loss is allowed for in the CPVC section to fall below
the limit for PVC, taking into account the highest possible ambient temperature in the area of vent travel (e.g. boiler room, attic and/or chase).
EXHAUST VENT MATERIAL – USA
IBC strongly recommends that only CPVC or PPs vent component systems approved under UL1738 (Standard for Venting Systems for Gas Burning
Appliances, Categories II, III and IV), ULC-S636 Standard for Type BH Gas Venting Systems, or stainless steel Type BH venting systems* are to be used,
but many local jurisdictions in the USA still allow the use of PVC (Sch. 40 ASTM
D1785 or D2665 and ttings) or CPVC (Sch. 40/ASTM F441 with Sch. 80 ttings).
Do not use ABS or any cellular core pipe for exhaust venting.
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in venting systems shall be prohibited.
The boiler offers 2" venting connections. Fittings are to be used to adapt to the appropriate diameter – see Vent Travel below. Exhaust venting is to be
connected directly to the 2" NPT male threaded stainless steel tting on the
bottom of the pressure vessel using:
For CPVC (and in the USA only, PVC) systems a 2" CPVC (USA: 2” PVC
allowed) threaded adaptor or 90° elbow adaptor. A condensate trap formed
using the supplied ttings shall be considered part of the exhaust and installed
near the base of the boiler (see Figure 2).
for PPs, use IBC’s VFC PPs transition kit as appropriate for the chosen PPs
system:
Figure 1c: PP Vent Adaptor Assembly
CENTROTHERM INNOFLUE™ M&G DURAVENT POLYPRO™
KIT# P-166A KIT# P-167A
2” Stainless Coupler (190-044) 2” Stainless Coupler (190-044)
2” Stainless Steel Adaptor (250-419) 2” Stainless Steel Adaptor (250-419)
Retainer Clip (180-050) Retainer Clip (180-051) x 2
PPs Transition Fitting (180-037) PPs Transition Fitting (180-040)
N/A PPs Condensate Trap Adaptor (180-060)
Condensate Trap and Hose (180-013) Condensate Trap and Hose (180-013)
Re-Usable Trap Strap (152-004) Re-Usable Trap Strap (152-004)
Table 3: Polypropylene Venk Kits
Combustion air piping is connected at the base of the boiler using a standard 2" PVC (ABS) coupler or elbow (see Section 1.4.7). For PPs intake piping, use standard PPs : 2”Sch 40 adaptor parts from the respective PPs manufacturers.
Venting shall be supported in accordance with applicable code.
*Manufacturers of stainless steel Type BH venting systems must submit their approved transition tting to IBC for evaluation and written approval.
INSTALLATION
1-5
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.4.3 Vent Travel
CPVC or PPs (Rigid Single Wall) piping is the standard venting option; with this, the VFC 15-150 boiler, for example, can be sited up to 50 equivalent feet from the vent termination using 2” or up to 120’ using 3”. The actual vent travel allowance is reduced for ttings in accordance with Table 4. – e.g. for an VFC 15-150 using 6 x 90º CPVC elbows, the maximum lineal measure of pipe allowed using 3” pipe is 72 feet (120’ – (6 x 8’ = 48) = 72’).
For 3” exible PPs, up to 60 actual lineal feet are allowed in a nominally vertical orientation (>45°). The equivalent length of 3” ex PPs shall be computed using
a multiple of 3:1, eg. 45’ x 3 = 135’ equivalent (for the VFC 45-225). With 45’ of 3”
ex, up to 105’ equivalent of 3” rigid PPs would still be allowed. 2” exible PPs is
not allowed.
EXHAUST PIPE SIZE MAXIMUM EQUIVALENT LENGTH
Sched.40; Rigid PPs
2" (15-150 only) 50' (each side)
3" (15-150) 120'
3" (45-225) 240'
90° vent elbow allow 8' equivalent
45° elbow allow 3’ equivalent
PPs 87-90° elbow allow 8’ equivalent
Flexible PPs
2” Flexible N/A
3” Flexible (VFC 15-150) 60’ (max) actual lineal x 1.5 = equivalent
3” Flexible (VFC 45-225) 60’ (max) actual lineal x 3 = equivalent
Table 4: Maximum exhaust venting length
Note: Unused intake travel cannot be added to the exhaust. Unequal intake
and exhaust piping is allowed (see Section 1.4.8).
Exhaust venting must slope down towards the boiler with a pitch of at least 1/4” per foot (PPs vent: follow PPs manufacturer requirements) so condensate runs back towards the trap. Support should be provided for intake and vent piping, particularly so for horizontal runs (follow local code). Insulate exhaust piping where it passes through unheated spaces or underground, with appropriate pipe insulation to prevent freezing of condensates.
Certain installations of the VFC 15-150 model can employ the 2” vent options. We caution installers when using horizontal runs of 2” pipe. Reason: air friction from the
fast moving exhaust during long burner runs at high-re in a 2” pipe can overcome
gravity on 1/4” / foot vent slope – leaving a pool of condensate at the next upturned
elbow. Pooling can impair the achievement of full high-re rating plate performance
.
If the site requires a horizontal exit immediately below the boiler – bush out to 3" pipe in the downward vertical run immediately below the 2" threaded adaptor,
and elbow to horizontal before splicing in a eld sourced 3" reducing tee for mounting of the condensate trap; this will slow the exhaust velocity sufciently for
good drainage and reduce “spitting” at the vent termination. In this case, the 3" x 3/4" reducing tee would replace the 2" tee and 2" x 3/4" bushing supplied with the VFC 15-150 boiler.
1-6
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
Fill trap with water before
boiler is rst red to prevent
exhaust fumes from entering
room. Never operate the boiler unless the trap is lled
with water.
Fan control harness plug
Exhaust venting must slope down to the trap/drain with a pitch of at least 1/4" per foot (PPs vent: follow PPs manufacturer requirements for slope) so condensate runs towards the trap. Support should be provided for intake and vent piping, particularly so for horizontal runs (follow local code). Insulate exhaust piping where it passes through unheated spaces or underground, with appropriate pipe insulation to prevent freezing of condensates.
Figure 2a: Basic exhaust vent assembly
Figure 2b: Basic exhaust vent assembly
Ensure all venting components are clean of burrs/debris prior to assembly. Care is to be taken to avoid ingestion into the fan of PVC/ABS debris left in the combustion air piping.
Unplugging fan control harness plug will drive the fan into manual high speed operation for vent leak test
BEST PRACTICES
To reduce the possibility of expansion noise, allow a 1/4”
gap around the exhaust and
air intake piping.
All joints must be secured. For CPVC in Canada, use ULC-S636 approved CPVC solvent cement, in accordance with its manufacturer instructions. Follow the cement manufacturer’s instructions closely when joining various components.For PPs, connections shall be secured using approved retainer clips supplied by the respective PPs manufacturer.
All vent connections must be liquid and pressure tight. Prior to ring the boiler,
and before any of the venting run is concealed by the building construction, the installer must test the exhaust joints under fan pressure with the vent blocked,
using a soap/water solution. Installer must ll condensate trap prior to test.
Remove the fan control harness plug as illustrated in the photos, and then block the vent outlet so that the vent run will be under maximum fan pressure. Paint all joints with an approved leak test solution just as you would joints in a gas line, and make sure there are no leaks. Good practice would suggest that the installer attach a tag on the vent line near the condensate drain tee indicating the type of test, the date and the installer’s name.
INSTALLATION
1-7
WARNING
Condensate can cause corrosion of metal roong
components and other
roong materials. Check with the builder or roong
contractor to ensure that materials will be resistant to
acidic condensate. pH levels can be as low as 3.0
CAUTION
Vent termination clearances
in this section are
code minimum, or IBC
recommended minimum
requirements, and may be inadequate for your installation. Building envelope
details must be examined carefully, and ingress of moisture into building
structures is to be avoided.
Serious structural damage
may occur if adequate
precautions and clearances are not allowed for.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.4.4 Venting Passage Through Ceiling and Floor
Conrm material meets local codes including re stopping requirements.
Pipe clearances - no IBC requirements, but best practice allows a minimum 1/4” gap around pipes to prevent binding and expansion noise; follow local codes.
All piping must be liquid and pressure tight.
1.4.5 Rooftop Vent Termination
Rooftop vents must terminate as follows:
The exhaust pipe can terminate in an open vertical orientation without
concern about rain inltration; this will drain away through a properly congured condensate trap.
If used, the intake air pipe is not typically drained, so it must be terminated
with a down-turned elbow (see Figure 3). The intake pipe does not need to penetrate the roof at the same elevation as the exhaust (as shown); lower down roof is OK.
To promote the projection of exhaust away from the building and from the
intake pipe, reduction of 3" pipe to 2" is permitted for a maximum lineal travel
of 3' (e.g. the nal 3') including 2 x 90° elbows on each side.
Optional bird screen may be placed in a termination tting. Leave unglued,
and hold in place with a short nipple. This permits easy access for cleaning.
For roof top venting of multiple boiler sets, group all intake terminals together
for a common penetration through a custom cap. Alternatively, place in the
closest proximity achievable using commonly available pipe ashing. Similarly
group the exhaust pipes and place the 2 separate groups of pipes at least 3' apart (the closest intake and exhaust pipes shall be 36" - or more - apart). Use the same 24" (minimum) vertical separation for all termination options. For alternate group terminations, contact the IBC Factory for written guidance.
DO NOT exhaust vent into a common venting system.
These precautions are to be observed for neighbouring
structures as well as for the
structure the boiler(s) are
installed in.
Figure 3: Rooftop vent terminal congurations
1-8
INSTALLATION AND OPERATION INSTRUCTIONS
WARNING
It is extremely important to maintain at least the minimum
separation of exhaust vent
termination from boiler
intake air as illustrated in
Figures 3, 4 and 5. Failure to do so can result in a dangerous situation where exhaust gasses are re­ingested with combustion air. Damage to the boiler can result from a failure to maintain these separations.
Third party vent termination kits and concentric wall penetration kits that do not
maintain these minimum separations shall NOT be used. Improper installation
will void the warranty. Do
not use proprietary InnoFlue or PolyPro PPs sidewall
terminals without specic written approval from IBC.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.4.6 Sidewall Vent Termination
Sidewall direct vent applications shall be vented as follows:
Both the inlet and exhaust terminations should normally be located on the
same plane (side) of the building.
The exhaust outlet is to be placed so as to reach 24" minimum above the
down-turned intake - to avoid exhaust re-ingestion.
The elevation of both pipes can be raised in “periscope style” after passing
through the wall, then congured as in Figure 4, to gain required clearance.
Use a 45° elbow on the exhaust termination to launch the plume up and off
the sidewall, for protection of wall.
Bird screen of 1/4" stainless steel or plastic mesh is useful to guard against
foreign objects.
To promote the projection of exhaust away from the building and from the intake pipe, reduction of 3" pipe to 2" is permitted for a maximum lineal travel of 3' including
2 x 90° elbows on each side. This allows for smaller wall penetrations, with sufcient travel allowance to achieve the minimum exterior conguration as shown above.
Figure 5: Sidewall vent termination - multiple vent piping conguration
INSTALLATION
Figure 4: Sidewall vent termination - piping conguration
1-9
Figure 6: Vent terminal clearances
Figure 7: Prohibited installation
WARNING
In areas of high snowfall,
Users must be advised to check side wall vent and air intake terminations on
a regular basis to ensure
blockage does not occur.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
For side venting of multiple boiler sets, group all intake terminals together with 4" to 8" lateral spacing, and similarly group the exhaust pipes. Place the 2 groups on the same plane of the building (e.g. north facing wall). Place the 2 groups of pipes at least 3' apart (the closest intake and exhaust pipes shall be 36" - or more – apart. Use same 24" (minimum) vertical separation as displayed above. Alternately, as long as the boilers are identical models - intake and exhaust terminals can maintain a minimum of 12” of separation horizontally from any exhaust or inlet termination of an adjacent boiler. For alternate group terminations, contact the IBC Factory for written guidance.
Vent terminal clearance minimums are as follows:
Clearance above grade, veranda, porch, deck or balcony – 12" (0.3m), but
check local code also (anticipated snow levels may supersede).
Clearance to openable window or door – 36" (0.91m) (USA – 12”)
Vertical clearance to ventilated sot located above the terminal within a
horizontal distance of 2’ (0.61m) from the centreline of the terminal.
Clearance to each side of centreline extended above meter/regulator
assembly: - 3' (0.91m) within a height of 15' (4.6m) above the meter/regulator.
Clearance to service regulator vent outlet: - 3' (0.91m)
Clearance to non-mechanical air supply inlet to building or the combustion air
intake to any other appliance: - 3' (0.91m) (USA – 12" (0.3m))
Clearance to a mechanical air supply inlet: - 6’ (1.82m) (USA - 3’ (0.91m)
above if within 10’ (3.1m) horizontally)
Clearance above paved sidewalk or paved driveway located on public
property: - 7' (2.2m) NOTE: Cannot terminate directly above a paved sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings
Clearance under veranda, porch, deck or balcony: - 12" (0.3m). NOTE:
Prohibited unless fully open on a minimum of two sides below the oor.
Vents must be installed such that ue gas does not discharge towards
neighbor’s windows, or where personal injury or property damage can occur.
It is important to ensure proper condensate management from vent
terminations. Condensate shall not be discharged in a manner that will cause
damage to external building nishes or components, or inltrate the building
envelope.
1-10
Figure 9: Vent terminal clearancesFigure 8: Vent terminal clearances
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
In addition to preventing
ingestion of chemical contaminants, care must
be taken to ensure air intake terminals are not
installed in locations where contamination might occur due to ingestion of particulate
foreign material (dust, dirt and debris).
WARNING
Intake air openings must be congured such that rain
or other forms of moisture
cannot enter the air intake piping system. Otherwise
serious damage to the boiler may result.
1.4.7 “Direct Vent” Combustion Air Intake Piping
There are two basic methods of supplying combustion air to an IBC boiler.
The direct vent option uses piping from the outside to supply combustion air directly to the boiler’s combustion air connection.
NOTE
Care must be taken when installing air intake piping to ensure that a “trap” is not
formed in the piping so as to allow a build-up of water, and
blockage of intake air.
Such blockage will result in a
boiler safety shut-down.
Figure 10: Direct vent - intake, exhaust and condensate removal system
INTAKE PIPE SIZE MAXIMUM EQUIVALENT LENGTH
Sched.40; Rigid PPs
2" (15-150 only) 50' (each side)
3" (15-150) 120'
3" (45-225) 240'
90° vent elbow allow 8' equivalent
45° elbow allow 3’ equivalent
PPs 87-90° elbow use 8’ equivalent
Air Intake Filter (Part #SC100A) allow 8' equivalent
Flexible PPs
2” Flexible N/A
3” Flexible (VFC 15-150) 60’ (max) actual lineal x 1.5 = equivalent
3” Flexible (VFC 45-225) 60’ (max) actual lineal x 3 = equivalent
Table 5: Maximum intake piping length
INSTALLATION
For the inlet air – Schedule 40 PVC, ABS, or PPs piping of any type is permitted. Use same diameter as Vent pipe, allowing for up to 6 ft actual run of 2” before any required transition.
NOTE: It is not permitted to add to the exhaust length by transfer of unused
intake allowance.
1-11
WARNING
When using Indoor
Air options, adequate
combustion air must be supplied to the boiler room
according to the requirements
of all applicable codes.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Combustion air piping is connected at the base of the boiler using a standard 2” PVC (ABS) coupler or elbow and run horizontally or vertically to the outdoors. Screen material can be placed at the inlet as appropriate for the environment (e.g. insects, dust).
For 3” piping, a 3”x 2” bushing is to be used in the inlet piping within 3 feet of the combustion air line clearance hole at the base of the boiler. Such 3’ interval of 2” pipe can be treated as 3” pipe without reference to its smaller diameter in calculation of the maximum allowable vent travel distance. All elbows and tees at the base of the boiler and at the termination must be included in the calculation.
Care must be taken to ensure adequate separation is maintained between the
air intake inlet and the vent terminal. Refer to the vent terminal conguration
drawings in the Vent Termination section above.
Support should be provided for intake piping, particularly so for horizontal runs (follow local code).
1.4.8 “Indoor Air” Combustion Air Intake Piping
An “Indoor Combustion Air installation”, as described herein, is one in which air for combustion is taken from the ambient air around the boiler.
Figure 11: Indoor air - intake, exhaust and condensate removal system
To support combustion, an ample air supply is required. This may require
direct openings in the boiler room to the outside. If the boiler is not in a room adjacent to an outside wall, air may be ducted from outside wall openings.
Provisions for combustion and ventilation air must be made as follows:
in the USA, in accordance with the National Fuel Gas Code, ANSI Z223.1
in Canada, in compliance with B149.1-10.
1-12
(latest edition), or applicable provisions of the local building codes
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.4.9 Combustion Air Filtration
NOTE
Combustion fan blockages can occur when environmental particulate and
foreign matter contaminants
(leaves, dust, dandelion & cottonwood uff, etc) are drawn into the air intake. In
areas where this problem is suspected to be an issue,
our optional air intake lter
should be installed.
Filters should be checked
and cleaned or replaced on a regular schedule based on
the severity of the problem.
If combustion air contamination from ingested particulate matter may be a
concern in any installation, an optional air intake lter may be installed. IBC supplied air intake lters have a known pressure drop and fouling factor and
should be used as a component of the combustion air system according to the allowable intake length in Table 4.
Figure 12: Optional air intake lter IBC Part #SC100A - Filter element alone is IBC Part #180-103
Air intake lter IBC Part #SC100A
INSTALLATION
Figure 13: Direct vent - intake, exhaust and condensate removal system with optional air
intake lter (ltration may also be used on indoor air applications as required)
1.4.10 Closet Installations
For installations in a conned space (such as a closet), ventilation openings may
be needed through a door or wall to prevent excessive heat from building up inside the space.
The boiler shall not be exposed to ambient conditions above 122°F (50°C) or below 32°F (0°C).
1-13
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.5
WARNING
Fill trap with water before
boiler is rst red to prevent
exhaust fumes from entering
room. Never operate the boiler unless the trap is lled
with water.
Failure to comply will result
in severe personal injury or
death.
WARNING
If condensates are to be discharged into building drain piping materials that are subject to corrosion, a
neutralization package must
be used.
CONDENSATE REMOVAL
IBC’s specied vent conguration promotes the safe drainage of moisture from the boiler and exhaust venting without owing liquids back through the heat exchanger
(as done by other condensing boilers). Reliable system operation requires (1) proper design and installation of exhaust venting to allow condensate to run back to the drain/trap; (2) proper trap depth to handle maximum potential pressure within the vent, and (3) acid neutralization as appropriate. To achieve these:
1. Allow for a 1/4” per foot slope back to the trap connection, with appropriate
hangers to maintain that gradient; do not use 2” pipe on horizontal runs - air
friction from the fast moving exhaust at high re in a 2” pipe can overcome gravity even with the specied slope, leaving a pool of condensate at the
next upturned elbow; do not transition between pipe diameters on horizontal vent runs – always place any reducing couplers in the vertical run)
2. Ensure a trap is established as described below.
3. When required, add (and maintain in good condition) a neutralization tank.
1.5.1 Condensate Trap
When installling the condensate trap, please take into account the following:
Must be piped to within 1” of a drain or be connected to a condensate pump.
Drainage line must slope down to the drain at a pitch of 1/4” per foot so
condensate runs towards the trap
If necessary, the drain connection tee can be laid so the main axis is
horizontal; ensure the drain tee is as close as possible to the vent riser to avoid water bypass and pooling.
Most installers prefer to run the combustion air intake pipe alongside the vent,
both to the left side of the boiler to keep the area right of the unit clear for system water piping.
Use the supplied PVC unions for easy access for cleaning. Locate on the
vertical legs as per Figures 15 and 16. Earlier installations may have a single union at base of the trap (as shown in Figure 13).
Condensate traps should be checked every 2 months, and cleaned and
relled as necessary.
CAUTION
When a condensate
neutralization package is installed, the pH of the
condensate discharge must be measured on a regular schedule to ensure the
neutralizing agent is active and effective.
1-14
INSTALLATION AND OPERATION INSTRUCTIONS
Figure 15: Condensate trap
conguration (double union option
shown)
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.5.1.1 WITH SCHEDULE 40 PLASTIC VENTING SYSTEMS (E.G. ULC-S636 CPVC)
A condensate trap must be installed near the base of the boiler as shown in Figure
14. The trap is formed using PVC pipe, elbows and threaded union ttings.
disassembly for cleaning
Figure 14: Condensate trap conguration Figure 16: Condensate trap
NOTE: for CPVC vent systems, the connecting tee and bushing should be
formed using CPVC, transitioning to PVC in the wetted section of the trap, where
non-ULC-S636 materials are allowed as this section is not in contact with ue
products. The trap must be installed as follows:
The trap depth must be 6” min. in height (see Figure 14); with the
conventional vent kit parts supplied with the boiler, approximately 15” clearance below the boiler is required.
Use the supplied vent kit parts to establish the trap in the location shown
below. Do not place the drain connection tee directly at the base of the boiler.
1.5.1.2 WITH PPS VENTING SYSTEMS
For connection to PPS venting systems, an IBC VFC PPs transition kit is required; select the kit corresponding to the brand of PPs venting to be used at the installation site (see page 1-5). Note this kit is needed to make safe connection to the boiler’s 2” NPT-M threaded exhaust outlet and to provide for good drainage from both the boiler and from the external venting run. Ensure metal retaining clips are applied at each PPs joint in the system, including that
between PPs and the stainless steel coupler, immediately below the boiler ue
outlet. The condensate trap itself is to be installed at the drain outlet provided at
the bottom of the PPs transition tting, as shown in Figure 17.
INSTALLATION
1-15
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Figure 17: Condensate trap installation - PPs
Figure 18: IBC Kit #P-166A for Centrotherm PPs (with Centrotherm clips – IBC #180-050)
1-16
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Figure 19: IBC Kit #P-167A for M&G Duravent PPs (with M&G Duravent clips – IBC #180-051)
Each manufacturer of PPs venting systems has its own unique design for their metal retaining clips. While they may look very similar, do not mix any such components between suppliers. IBC supplies these only within the respective parts kits. Installation steps:
1. With sealant material, attach the stainless coupler and adaptor onto the
boiler’s 2” NPT-M exhaust connection. Take care not to disturb the lower 1” of the stainless adaptor with your pipe wrench – that must be smooth for good sealing with the PPs Exhaust Adaptor.
2. Slide a retainer clip (with barb down) up the stainless adaptor, then move the
PPs Exhaust Adaptor into position. Engage the retainer clip.
3.
Build the venting system upward from the PPs Exhaust Adaptor, securing the venting in accordance with that supplier’s installation instructions and local code (e.g. to the wall, and amongst all the system parts using their retaining clips).
4. For the M&G Duravent system, next install their Condensate Trap Adaptor
(IBC #180-060) after sliding on the 2nd retaining clip supplied in kit P-167A (barb down).
5. The transition assembly is now ready for the trap itself:
Undo Drain Spout Compression Nut (E), remove Drain Hose (G) from Trap. Drain Outlet (F). Place Vacuum breaker cap (J) over the Vacuum breaker
opening and push rmly home. Remove Upper Compression Nut and
Washer (C) and slide over PPs Transition Fitting Drain Outlet (A).
Fill Trap with water, and slide Trap Body (D) over PPs Transition Fitting Drain
Outlet (A).
Attach Drain Hose (G) and tighten Drain Spout Compression Nut (E).
INSTALLATION
1-17
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
The Trap Hook reusable retaining strap (IBC #152-
004) must be installed
as instructed and all trap
ttings must be tightened as instructed to prevent leakage of ue gasses.
Failure to comply may result
in severe personal injury or
death.
NOTE
It is the responsibility of
the installing and/or service Contractor to advise and
instruct the end User in how
to perform the Trap cleaning procedure, and to advise that the Trap be checked at least every two months and cleaned as required.
6. Conrm the Drain Spout Compression Nut (E) is secure by applying 10 lbs
of downward force on the trap body (D). Then apply IBC #152-004 Reusable Strap as shown in Figure 17 to prevent blow-off of the trap during any delayed ignition event. Ensure the Strap is seated well in the “V” formed between the main Trap Body (D) and its Trap Drain Outlet (F).
1.5.2 Condensate Trap Assembly - cleaning procedure
1. Turn off the power to the boiler and allow it to cool down.
2. Remove the trap for cleaning:
for Schedule 40 CPVC/PVC systems, see Figure 16
for PPs systems, see Figure 20
3. Flush the debris out.
4. Re-assemble trap components, re-ll trap, and rex trap. Ensure the
Reusable Retaining Strap is applied to secure the trap against blow-off on PPs systems.
1.5.3 Further installation details
Condensate drain must be piped to within 1” of a drain or be connected to a
condensate pump.
Drainage line must slope down to the drain at a pitch of 1/4” per foot so
condensate runs towards the drain.
Condensate traps should be checked every 2 months, and cleaned and
relled as necessary.
Figure 20: Condensate trap disassembly for cleaning
1-18
Figure 21: Condensate trap drainage
INSTALLATION AND OPERATION INSTRUCTIONS
WARNING
If condensates are to be discharged into building drain piping materials that are subject to corrosion, a
neutralization package must
be used.
CAUTION
When a condensate
neutralization package is installed, the pH of the
condensate discharge must be measured on a regular schedule to ensure the
neutralizing agent is active and effective.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
DANGER
The water in the condensate
neutralizer can cause
severe burns to the skin.
Use extreme caution when
servicing the condensate neutralizer. Wear protective gloves and eyewear.
Figure 22: Condensate neutralization tank
INSTALLATION
1-19
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.6
WARNING
During operation, the relief
valve may discharge large
amounts of steam and/or hot
water. Therefore, to reduce
the potential for bodily injury and property damage,
a discharge line MUST be
installed that it:
1. is connected from the valve outlet with no intervening valve and directed downward to a safe point of discharge.
2. allows complete drainage of both the valve and the discharge line.
3. is independently supported and securely anchored so as to avoid applied stress on the valve.
4. is as short and straight as possible
5. terminates freely to atmosphere where any discharge will be clearly visible and is at no risk of freezing.
6. terminates with a plain end which is not threaded.
7. is constructed of a material suitable for exposure to temperatures of 375°F or greater.
8. is, over its entire length, of a pipe size equal to or greater than that of the valve outlet.
WATER PIPING
1.6.1 General Piping Issues
The VFC modulating series boilers are designed for use within a closed loop, forced circulation, low pressure system. A 30 psi pressure relief valve (3/4" NPT)
is supplied for eld installation in the ow supply line – see below. An optional 75
Psig relief valve can be used where required on closed loop systems within multi­level buildings. Relief valve discharge piping must terminate between 6" (15cm)
and 12” (30cm) above the oor using plain un-threaded end, or per local Code.
DO NOT CAP, PLUG OR OTHERWISE OBSTRUCT THE DISCHARGE PIPE OUTLET!
CAUTION
Installers should inquire of local water purveyors as to
the suitability of their supply for use in hydronic heating systems.
If water quality is questionable, a local water
treatment expert must be consulted for testing,
assessment and, if required,
treatment.
Alternatively, water or hydronic uid of known quality can be brought to the
site.
Figure 23: Boiler trim options
System piping is connected to the boiler using the 1-1/4" NPT-M threaded ttings.
Unions and gate or ball valves at the boilers supply and return water connections are recommended to simplify servicing. Un-insulated hot water pipes must be installed with a minimum 1/4" clearance from combustible materials.
Fluid ll is most often accomplished by using a boiler regulator & ll valve set at 12 psig or more, with appropriate backow prevention device as required by
local code. This is acceptable in areas where municipal water or well water has
been treated and ltered to remove excessive minerals and sediment, and water
chemistry is known to be suitable for closed loop hydronic systems. In areas where water quality is in question, or when chemical treatment or glycol is required, other options should be considered. Follow applicable Codes and good piping practice.
There are a number of boiler feed and pressurization devices on the market
today that may be a better choice than a raw water ll from the mains. When
regular maintenance requires relief valve blow-off, the discharge may be directed
back into the pressurization unit for recycling of boiler uid and chemicals
back into the system. In buildings that may be unoccupied for long periods of
time, pressurization units are useful to prevent ood damage should leakage occur from any component in the system. An additional benet is that backow
prevention devices are not required when using these devices.
1-20
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Do not place any water connections overhead the boiler; leaks can damage the fan & controls. If needed, create a shield over the louvered top of the cover,
but allow clearance for airow and service access.
WARNING
Close ll valve after any
addition of water to the
system, to reduce risk of
water escapement.
NOTE
Full sized application drawings can be downloaded from our web site.
www.ibcboiler.com
NOTE
For best results, use a Primary: Secondary piping system, with a pumped boiler loop using 1-1/4" piping for the 15-150 and 1-1/2” for the 45-225. Heat exchanger head for both models is approx. 7' at 14 gpm, and 12’ at 22 gpm so an inexpensive fractional horsepower pump is normally adequate. Primary/
Secondary piping ensures adequate ow and de-couples Δ°T issues (boiler vs. distribution). Aim for a 20° to 30° F Δ°T across the heat exchanger at high re (there is a boiler protection throttle fence limiting the Δ°T to 40°F).
The boiler, when used
in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with
appropriate valves to prevent
the chilled medium from entering the boiler.
NOTE
The boiler piping system of
a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation
must be equipped with ow control valves or other automatic means to prevent gravity circulation of the
boiler water during the cooling cycle.
Figure 24: Basic Primary/Secondary piping concept
INSTALLATION
Figure 25: Important Primary/Secondary piping details
1-21
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
Water quality has a signicant
impact on the lifetime and
performance of an IBC Boiler
heat exchanger.
Improperly prepared water in a heating circuit may cause damage to the heat exchanger through corrosion or fouling. Repeated or uncontrolled water
lls will increase the potential
for damage.
High levels of dissolved solids
or minerals may precipitate
out of the uid onto the hottest
part of the heat exchanger, impairing heat transfer and
resulting in overheating and premature failure. The amount
of solids that may form on the heat exchanger will depend on the degree of hardness and
the total water volume in the system. A high water volume
system with a low hardness count may cause as much damage as a system with less
volume and higher hardness, so
it is recommended to treat water
so as to remove all dissolved solids. Other water chemistry
allowable limits are as follows:
The VFC modulating series boilers are designed to supply up to four different heating loads with temperatures within the range 34°F to 185°F - to meet three separately piped loads. Use closely spaced tees to connect each pumped “load”
(e.g. DHW, baseboards or radiant oor) to the primary loop, or employ the use
of a hydraulic separator to isolate the boiler loop from the system and pipe the system from the secondary side of the separator.
A variety of application drawings showing basic design options are available from the IBC web site at: www.ibcboiler.com
Figure 26: Primary/Secondary piping concept with hydraulic separator
Acidity pH is to be between 6.6
and 8.5
Chloride is to be less than 125
mg/l
Iron is to be less than 0.3 mg/l
Cu less than 0.1 mg/l
Conductivity is to be less than 400μS/cm (at 25°C)
Hardness is to be 7 Grains or
less
IMPORTANT: Ensure that these limits are acceptable for the other water-side components in the system.
1-22
Figure 27: Important Primary/Secondary piping details with hydraulic separator
Always ensure that loads sensitive to high temperatures are protected using means such as an aquastat (wired to the boiler’s auxiliary interlocks) or mixing
valve set for maximum limit (say 140°F) to protect radiant oors.
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
PRESSURE VESSEL HEAD
Flow rate (gpm) 4 8 12 16 20
Head @ ow (ft wc) 0.7 2.5 5.0 8.3 12.3
NOTE
The Primary (boiler) pump
must be under the control of the boiler and wired to the correct yellow and white
wires labelled “Primary” in
the wiring box.
Failure to do so will result in a no heat condition as the boiler will interrupt start-up
with a “No Water Flow” error.
WARNING
Do not use automotive-type
ethylene or other types of
automotive glycol antifreeze,
or undiluted antifreeze of
any kind. This may result in severe boiler damage. It
is the responsibility of the Installer to ensure that glycol solutions are formulated to inhibit corrosion in hydronic heating systems of mixed materials. Improper mixtures
and chemical additives may
cause damage to ferrous and non-ferrous components as well as non-metallic, wetted components, normally found in hydronic systems. Ethylene glycol is toxic, and may be prohibited for use by codes applicable to your installation
location. For environmental and toxicity reasons, IBC
recommends only using non­toxic propylene glycol.
Table 6: Pressure Vessel Head
Ensure the pump is rated for the design circulating water temperatures; some pumps have a minimum water temperature rating above the low temperature potential of the
boiler. Following installation, conrm actual performance by measuring Δ°T (under high and low ow conditions) after establishing the correct ring rate.
We require waterow after burner shutdown to utilize legacy heat – this is signicant due to the mass of the heat exchanger (40 Kg) plus its 9L internal
water volume. Default software values will run the boiler’s primary pump for up to 5 minutes (300 seconds) after burner shutdown. Secondary pumps can be set to run up to 15 minutes after burner shutdown (for the last calling load). As shipped, the default software will run the DHW pump for 5 minutes to place the legacy heat where it is useful – e.g. in the DHW tank. Any secondary pump can be set to run for 0 – 900 seconds in the heat purge mode. Guard against deadheading pumps when all zone valves are closed.
The primary pump must be under the control of the boiler, to allow the boiler’s
ow proving routine to run. The boiler control looks for ow/no ow during a
pump on / off check on each start up. Ensure that temporarily wired primary or
secondary pumps (e.g. wired externally during the system ll/purge phase) are
returned to the boiler’s control terminals. A “No Water Flow” error message will otherwise be experienced on start-up.
There are two water pressure sensors, located on the boiler’s supply and return water piping. These act to provide both low water pressure and low water level
cut-off protection and water ow measurement. Schematics for several piping
layouts are provided, and additional drawings are available at www.ibcboiler.com.
Installers shall conform the piping design to one of the provided congurations to simplify the control application, promote good loads-and- ows management.
The VFC modulating series boilers offer unparalleled matching of heat generation
to radiation. The low minimum ring is better suited to low thermal loads presented
in a typical multi-zoned radiation system. However, where individual zones in a
heating system have loads under 5,000 Btu/hr, the system will still benet through
use of a buffer tank to ensure a controlled supply temperature, and to prevent short cycling. Buffering should be added on the secondary piping of the relevant load, to avoid bulking up the thermal mass of the primary piping circuit (and potentially lengthen the duration of the transition from hot to cool loads).
Propylene glycol solution is commonly used in a closed loop where freeze protection is required. Its density is lower than that of water, resulting in
lower thermal performance at a given ow and pressure. As a rule of thumb,
a 50%:50% solution of propylene glycol and water will require an increased system circulation rate (gpm up 10%), and system head (up 20%) to provide performance equivalent to straight water.
VFC modulating series boilers can be connected directly to a oor of non-oxygen
barrier polybutylene material (PB tubing). For maintenance of warranty on such
systems, we require evidence of a thorough ushing of all loops, plus installation of a dirt separator or side stream lter. A separator/lter maintenance routine shall be carried out after the retrot, with lter clearing after the 1st day, 1st week, month and annually thereafter. Care is to be taken to avoid use of ferrous ttings
and pumps on PB tube systems.
INSTALLATION
1-23
NOTE
This piping drawings in this
manual are simple schematic guides to a successful
installation. There are many
necessary components not shown, and details such as thermal traps are left out so
the drawings have greater clarity. We require that
our boilers be installed by licensed and experienced trades people who are familiar with the applicable local and national codes. System design is to be completed by an experienced hydronic designer or Engineer. It is necessary to carefully read and follow these installation instructions along with the
application drawing that ts
your system.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.6.2 Installation Rules
NOTE: The Boiler Trim element – common to each of the following systems
- includes the pressure relief, ll, expansion tank and air bleed elements. The
primary pump can be located on either the Supply or Return piping sections.
NOTE
VFC boilers are equipped
with a factory installed
pressure sensor-type Low Water Cut Off system. The
minimum operating system pressure allowable with this
is 4 psig. Check local codes if a Low Water Cutoff Device is required. If so, determine if this device meets the local
codes.
Figure 28: Basic Primary/Secondary, 3 load piping concept
Features of the preferred Primary / Secondary piping system:
1. Good circulating water ow through the boiler irrespective of load or radiation
system head
2. Allows exible ΔT° control in secondary loops
3. Adds to the system’s thermal buffering, to assist in handling small loads and
temperature transition.
This piping conguration requires an extra pump. The VFC modulating series
boilers’ controller hosts wiring terminals and integral relays to simplify installation and operation of this preferred layout, offsetting such costs.
For optimal performance, place pumps on the supply side of secondary loops to facilitate air evacuation. Use pumps with internal check valves to avoid ghost
ows and thermal siphoning.
The primary loop temperature may need to transition from a 180°F domestic water
heating load to a 100°F radiant oor requirement. The secondary pumps will swap
off/on simultaneously, provided the pre-set maximum allowable temperature of the new load is not exceeded. In the case of the typical maximum limit for a radiant
oor (most would enter 140°F); the oor pump would remain off, the boiler shut
down, leaving primary circulation on until the primary loop temperature drops into
the acceptable range for the oor. Temperature sensing is done using thermistors
at the boiler supply and return – no further sensors need to be installed.
1-24
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
NOTE
Load Combining is now available to operate 2
compatible water temperature loads at the same time.
When using the sequential load feature of the IBC boiler,
attention must be paid to the operation of system components in order to ensure they are compatible.
Many air handlers (fan coils) for instance have a
thermostat connection that will energize an internal relay to operate the air handler circulator and its fan on
a call for heat. This may
result in operation of these components when other loads are running at a higher priority, resulting in cold air blowing, or robbing heat from another load.
The use of the multi-temperature modulating system is optimized when the need to shutdown the boiler is reduced or eliminated during the transitional period. System design enhancements: (a) keep a relatively low thermal mass in the primary loop, and (b) incorporate a 3-way mixing valve on the “cool” load piping.
If the installation involves small loads, as in typical zoned baseboard heating applications, use of a buffer tank is recommended. To aid in temperature transition from hot to cool loads, a 3-way mixing valve can be placed at the
entrance to the cool load (this will also provide oor protection). This will permit immediate circulation of mixed ow into the cool loop. See separate publication
Application Notes for more detail (available at www.ibcboiler.com or from your IBC Representative).
Always ensure that loads sensitive to high temperatures (e.g. radiant oor)
are protected using appropriate means such as a manual mixing valve, or an aquastat (set to130°F, for example) wired to the boiler’s auxiliary interlocks.
Some wiring alteration may
be required to divorce both
of these functions from
thermostat control in favour of more effective control from the IBC boiler.
NOTE
For information and details
regarding Multiple Boiler
application, consult our
Technical Notes - Multiple Boiler Systems. These notes
provide necessary detail on specic single and multiple boiler applications “Piping”, “Wiring” and “Settings”. (available at www.ibcboiler. com or from your IBC Representative).
Figure 29: Two pump, two load - parallel piping concept
Compared with the Primary/Secondary approach, the above design saves one
pump. Lost is the simplicity of constant head and ow at the boiler, with reduced exibility in the handling of large temperature differentials.
Check valves or thermal traps should be used to isolate both the supply and
return piping for each load - to avoid thermal siphoning and reverse ow.
To ensure adequate water ow through the boiler under high-head / single
zone space heating conditions, a pressure activated bypass or other means of
bypass must be used on any load where the ow rate might drop below minimum
requirements (4 gpm for the 15-150, 8 gpm for the 45-225).
For further information and details, consult our Application Notes – which provide
detail on specic single and multiple boiler applications “Piping”, “Wiring” and “Settings”. (available at www.ibcboiler.com or from your IBC Representative).
INSTALLATION
1-25
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.7
NOTE
Due to the precision of modern modulating boilers it is important to pay special attention to gas pressure regulation.
It is essential to check gas
supply pressure to each boiler with a manometer or
other high-quality precision measuring device. Pressure
should be monitored before
ring the boiler, when the regulator is in a “lock­up” condition and during
operation, throughout the boiler’s full modulation range.
Pay special attention to
retrot situations where existing regulators may have an over-sized orice and/or
worn seats, causing pressure
“creep” and high lock up
pressures.
A high quality regulator will
maintain constant pressure
above the boiler’s minimum specication at all ring
rates, and will not exceed the boiler’s maximum pressure
rating when locked-up with no
load.
GAS PIPING
The boiler requires an inlet gas pressure of at least 3.0" w.c. for natural gas or propane. For either fuel, the inlet pressure shall be no greater than 14.0" w.c.
Conrm this pressure range is available with your local gas supplier.
The inlet gas connection of the boiler’s gas valve is 1/2" NPT (female).
Adequate gas supply piping shall be provided with no smaller than 1/2" Iron Pipe Size (IPS), in accordance with the following chart:
MODEL 1/2" IPS 3/4" IPS 1" IPS
VFC 15-150 (Natural Gas) 10 40 130
VFC 15-150 (Propane) 50 180 620
VFC 45-225 (Natural Gas) 5 20 60
VFC 45-225 (Propane) 25 90 290
Table 7: Maximum Pipe Length (ft)
Gas piping must have a sediment trap ahead of the boiler’s gas valve (see Figure
30). A manual shutoff valve must be located outside the boiler, in accordance with
local codes/standards. All threaded joints in gas piping should be made with an approved piping compound resistant to the action of natural gas/propane. Use proper hangers to support gas supply piping as per applicable codes.
The boiler must be disconnected or otherwise isolated from the gas supply during any pressure testing of the system at test pressures in excess of 1/2 psig. Dissipate test pressure prior to reconnecting. The boiler and its gas piping shall be leak tested before being placed into operation.
The gas valve is provided with pressure taps to measure gas pressure upstream (supply pressure) and downstream (manifold pressure) of the gas valve (see
Figure 32). Note that manifold pressure varies slightly in accordance with ring
rates with the modulating series boilers, but will always be close to 0” w.c.
Figure 30: Typical gas piping
1-26
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Removing wiring box covers
1.8
ELECTRICAL CONNECTIONS
All Electrical wiring to the boiler (including grounding) must conform to local electrical codes and/or National Electrical Code, ANS/NFPA No. 70 – latest edition, or The Canadian Electrical Code, C22.1 - Part 1.
1.8.1 120VAC Line Voltage Hook-up
Line-voltage wiring is done within the eld-wiring box (refer to Figure 31). Connect the boiler to the grid power using a separate, fused circuit and on/ off switch within sight of the boiler. Use 14-gauge wire in BX cable or conduit properly anchored to the boiler case for mains supply and pump circuits.
Connect a 120 VAC / 15 amp supply to the “AC IN” tagged leads in the wiring box. The max. actual draw (with 4 typical residential size pumps) is less than 4 amps.
The 120 VAC power supply to the load pumps (P/V1, P/V2, P/V3, and P/V4) have been factory installed and connected to P/V-L and P/V-N for your convenience. If you are to use the P/V relay connections for zone valves then the 120 VAC connections at P/V-L and P/V-N will have to be removed and properly capped off. 24VAC can then be applied using an external transformer to supply power to zone valves. The upper 4 pairs of contacts on this green connector strip are then powered to manage up to 4 load pumps – the top pair for Load 1, the second pair for #2 etc. Once the controller is programmed for the respective loads, the boiler will manage all the loads without need of further relays (for loads up to 1/3 HP; for more – use a protective relay).
Line voltage leads for power supply, primary pump and VS output
Line voltage load pump terminals
CAUTION
The internal pump relays are
protected with 5 Amp fuses.
The maximum recommended
load on each fuse is 4 Amps
(80% of rating). The maximum combined pump load is 10
Amps. Isolation relays or
contactors MUST be used if the
loads exceed these maximums.
The primary pump is connected to the White/Yellow pair labeled Primary Pump. This lead is factory wired to the controller (and its 120 VAC supply) at the upper right backside of the controller board – do not attempt to connect the primary pump to the Pump/Zone Valve Terminal Block along the controller’s right edge
- this is for the secondary pumps and/or zone valves only. Connect the pump’s Black wire to the Yellow of this pair (switched Hot). The White/ Yellow pair should be individually capped if the primary pump does not obtain its power from this pair (e.g. if a variable speed primary pump is connected to the mains power).
Pumps can be switched on/off using the keypad, so there is no need for temporary pump wiring during system lling / air purging. If pumps are hard-wired to the panel during the system ll/purge phase, re-wire the
boiler pump to the Primary Pump leads inside the wiring box, to enable the
water ow proving routine to run.
In a new construction application- use a construction thermostat – or jumper with in-line on/off switch – for on/off management of the boiler. Do not just pull power from the unit, or its moisture management routine will be interrupted (fan turns at ultra low rpm for 90 minutes after burner shutdown).
Treat it like a computer, where you do not just pull the plug when done. If a “Low
Airow” error signal shows, check for (and remove) any water in the clear vinyl air
reference tubes. This has been seen occasionally at construction sites where the boiler has been repeatedly de-powered wet.
The combined current of all pumps connected through the on-board pump relays should not exceed 10 amps. The control circuit board is protected using on-board
eld replaceable fuses. Each pump is fused with a separate 5 Amp fuse. The
Alarm contact is fused with a 5 Amp fuse and the 24VAC boiler control circuit is protected with a 2 Amp fuse.
INSTALLATION
1-27
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
NOTE
The IBC boiler (like any
modern appliance that contains electronic
equipment), must have a “clean” power supply, and is
susceptible to power surges
and spikes, lightning strikes and other forms of severe electrical “noise”. Power conditioning equipment (surge protectors, APC or UPS devices) may be required in areas where power quality
is suspect.
1.8.2 Power Quality and Electrical Protection
In areas of unreliable power, appropriate surge protectors and or power conditioning equipment should be installed in powers supply wiring circuits.
1.8.3 Zone Valve Hook-up
If zone valves rather than pumps are used to manage multiple heating loads, then 24VAC for the zone valves should be provided to the power contacts on the Pump/ Zone Valve Terminal Block. Disconnect the 120 Vac leads connected to PV-L/PV-N and cap off. Use a separate transformer – the 40VA unit inside the wiring box is for internal systems only. The individual load/zone valves are then to be wired to their associated contacts on the secondary pump/zone valve connector. Do not confuse such “load/zone valves” with similar valves used to segregate a single load type
(e.g. those used on a zoned radiant oor) – see next section.
1.8.4 Thermostat / Sensor Wiring
Dry contacts for thermostats for each of 4 loads are provided as marked on the lower connector strip (e.g. “Therm 1”). Gang lines from a multiple-zoned load (e.g.
off the end-switches for each radiant oor zone) to present a common thermostat signal to the controller. Ensure there are no disturbing inuences on the call-
for-heat lines - e.g. no coils to switch an air handler motor. Most power stealing thermostats can be connected directly to the Therm terminals. See Touch Screen
Controller Manual section 2.1.1 for more detailed instructions.
DANGER
Do not connect thermistor
sensors to “Therm” terminals. An overheating hazard can
result in serious personal injury and/or property damage.
NOTE
The IBC Touch-Screen
controller has the ability to connect to most power stealing thermostats. See the Wiring Diagram for details.
1.8.5 Other Wiring
Other optional low voltage connections to the control board include:
Two auxiliary interlocks - for external safety devices as may be required by
some jurisdictions, such as a low water cut-off or a low gas pressure cut-out
(for off-grid propane). A oor-protecting aquastat can use one of these, to cause a full boiler shutdown in the case of excess oor temperature.
Contacts for indoor and outdoor temperatures sensors associated with Reset
Heating. A 10K ohm thermister for outdoor reset sensing is supplied with the boiler, to encourage use of this temperature compensating space heating
technique for improved comfort and combustion efciency.
One pair for a DHW tank sensor. Connect to “DHW S” (not the respective
Therm. 1,2,3,4 location) and the boiler will automatically notice and go to a smart DHW routine
One pair of contacts for remote secondary loop temperature control.
One pair (marked BoilerNet) for network connection – this is used for
connecting multiple VFC modulating units for autonomous staging. See separate Technical Memo for guidance.
A nal pair of contacts, to receive a 0-10VDC (default) or 4-20 mA signal
from an external boiler controller- for direct throttle control. The boiler’s own sensors act as high limits only. User must enter maximum and minimum boiler supply temperatures.
NOTE: Sensors connected to any sensor input contacts must be of NTC
Thermister - type with a resistance of 10,000 ohms at 25°C and β = 3892. We do
not recommend using 3rd party supplied sensors. Compatible water temperature sensors and outdoor sensors can be supplied by your IBC distributor.
1-28
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
1.8.6 Thermostat Heat Anticipator
IBC “Therm.” contacts draw no power, so an anticipator setting for the thermostat is not applicable with the VFC modulating series boilers. In the case of a single temperature / heat load where zone valves are used to manage individual thermostatically controlled zones, each room thermostat’s heat anticipator should be adjusted to the current draw of its associated zone valve.
INSTALLATION
Figure 31: Electrical Wiring Connections (full page ladder diagram at back of this manual)
1-29
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
THIS PAGE INTENTIONALLY LEFT BLANK
1-30
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
2.0
2.1
IBC BOILER CONTROLLER
GENERAL
This boiler is equipped with the V-10 Touch Screen controller. The controller
simplies the programing of the boiler while providing greater exibility. For more
detailed instructions, reference the Touch Screen Boiler Controller Manual.
The controller is equipped to provide:
Control of up to 5 pumps – 1 boiler pump + 4 separate load pumps
Outdoor Reset control
Set Point temperature regulation
Domestic Hot Water (DHW)
External control via 0-10VDC or 4-20mA signaling
Alarm dry contacts
Load Combining – simultaneous operation of 2 similar water temperature
loads
The control can manage and/or operate in a network of up to 24 IBC VFC or
SL boilers
Some of the new features available in the touch screen control include:
Express Setup Menu for simple, quick programing
Software updatable in the eld with a SD card or a USB stick
Setup conguration back-up and cloning using SD card or USB stick
Superior warning messages while setting up the control
Advanced Error messages with visual display on the Home Screen
Internet/LAN connectivity
BACnet (with activation)
2.2
WARNING
No sharp or metallic object should be used on the touch screen as this will cause damage. Use only a Stylus or a
clean nger.”
BOILER SYSTEMS AND OPERATION
CONTROL
When the boiler is rst energized, the controller will go through a power up
sequence that will take approximately 90 seconds. During this time the controller is completing a self-diagnostic and loading all previous settings. In the event of a power interruption the boiler will automatically resume operation when power is restored with all the previously stored values. The controller provides overall management of the boiler operations including;
Power-up, Self-diagnostics, easy Load parameter adjustments
Burner operation, safety management systems, Call for Heat management
and Load Priority
Real time boiler data
Temperature and throttle operation
Maintenance of operational and error service logs
2-way communication between other IBC boilers and controls
2-1
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Operational and historical data may be accessed at any time using the System
Status and Load Proles sections of the control. Error logs are available in the
Diagnostics section and the controller is capable of recording any or all errors since original power-up complete with the date and time of the error.
2.3
CONTROL INTERFACE
The control interface is provided through a 2-1/4 x 4 inch, color Touch Screen
display. The Touch Screen responds to a light nger touch on the screen. You
can also use a stylus or similar device to operate the touch controls. Do not use a sharp or metallic object such as a screw driver to operate the control as it could damage the touch screen.
The controller display is divided into two areas, the screen active area and the boiler status bar. All screens have an active area consisting of the screen title bar at the top and a boarder surrounding the active area. At the bottom of the display there is space reserved for the boiler status bar.
Prior to any interaction with the touch screen the display will be showing the Home screen that includes details of the current boiler status. If the controller has been left on the Home screen long enough (user adjustable, 10 minutes by default) the display with be dimmed to save power.
The control will automatically return to the home screen if left unattended. The screens will step back one screen at a time in 10 minute increments if the touch screen has not been touched. The pop-up windows will also step back automatically in 2 minute intervals.
The boiler status bar indicates if the boiler is in a normal, warning or alarm state. When no warning or alarm state is present, the bar will be green and the time will be displayed inside the green area. The bar can also be yellow or red corresponding a warning or alarm state. Text inside the bar will indicate the
specic warning or alarm present. If more than one alarm is present the text
display will slowly change, rotating though whatever alarms that are present.
2-2
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
STARTUP AND COMMISSIONING3.0
3.1 LIGHTING AND SHUTTING DOWN THE BOILER
STARTUP AND COMMISSIONING
3-1
3.2 PRIOR TO START-UP
Inlet gas supply pressure test port
WARNING
Fill trap with water before boiler
is rst red to prevent exhaust
fumes from entering room.
Never operate the boiler unless the trap is lled with water.
Failure to comply will result in
severe personal injury or death.
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
3.2.1 Pre-Ignition Checks
1. Ensure venting system is complete and seal tested. Conrm any common
venting system at the installation site is isolated and independent of the VFC boiler, that any holes left from removal of a previous boiler have been sealed,
and that any resizing of the old ue has been done. Fill condensation trap to
full neck height.
2. Check water piping system is fully ushed and charged, and that all air
has been discharged through loosened bleed caps. Note it is possible to switch all pumps on/off from the Touch Screen – without a call for heat. This greatly simplies system lling and air bleeding (go to Installer Setup, System Settings, Site Settings, change Manual Pump Purge to “ON”. When complete, return to Off, or this will automatically occur with a call for heat).
Use a minimum water pressure of 12 psig. And conrm pressure relief valve
is installed and safely drained.
3. Perform a nal check of electrical wiring.
4. Using a manometer, check to see that adequate gas pressure is present
at the inlet gas supply test port. Requirements are minimum 3” w.c and maximum 14” w.c.
3.3
Manifold pressure test port
DANGER
Making adjustments to the IBC gas valve without
a properly calibrated gas combustion analyzer and by persons who are not trained and experienced in its use is forbidden. Failure to use an analyzer can result in an immediate hazard.
3.2.2 Test Ignition Safety Shutoff
With the boiler in operation, test the ignition system safety shutoff device by shutting the gas control valve immediately outside the boiler case. Ensure boiler has shut off and the appropriate Error information is displayed on the Touch Screen. To restart boiler, reset power or press “Clear Errors” in the Advanced Diagnostics section.
COMMISSIONING
The VFC modulating boilers are factory calibrated to operate with natural gas (or propane if so ordered) at sea level. The relevant valve adjustment screws have been factory sealed using Loctite thread-lock compound, which can be broken where required. However, no mixture adjustment shall be performed unless
done by a qualied technician using properly functioning combustion analyzing equipment.
The controller will automatically detect the installations altitude and make the appropriate adjustments to operate the boiler up to 4,500 feet in elevation without de-ration. The boiler will automatically de-rate at altitudes above 4,500 feet. Refer to the IBC Altitude tables for further information.
To verify the proper operation of the gas valve in the eld, the following procedure can be carried out by a qualied technician (see Figure 32).
1. Turn OFF gas supply to the boiler. With a small (1/8" or 3 mm) at
screwdriver, open the manifold pressure test port by turning its centre- screw 1 full turn counterclockwise. Attach a manometer between the manifold pressure test port and the reference line and turn on gas to the appliance. Static manometer reading should be ideally 7” w.c., for Natural Gas and 11” w.c. for Propane. Minimum and maximum static pressure should be between 5” and 14” w.c. Monitor pressure throughout the commissioning
3-2
INSTALLATION AND OPERATION INSTRUCTIONS
Zero-offset adjustment screw
Gas:Air ratio adjustment screw
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
procedure. Pressure may droop up to 1” to 2” w.c. at high re but under no
circumstances should it drop below 3” w.c. at the gas valve inlet test port.
2. Allow the boiler to ignite / run against a large load, to maintain high re
3. With the boiler at maximum output, use a 2 mm hex key to adjust the zero-
offset (see Figure 32, “A”) as required to achieve -0.2 to -0.3” wc. This adjustment should only be necessary if this screw has been tampered with.
4. With a combustion analyzer probe in the ue gas test port, turn the Gas:Air
Ratio Adjustment screw (see Figure 32, “B”) to achieve the appropriate Table
8 mixture target at High Fire. This screw offers very ne adjustment, and
may require several turns. NOTE: This screw has signicant backlash. When changing direction of turn, it may take up to a full turn before any change
is indicated on the analyzer reading. Clock the gas meter to conrm full
maximum rating plate input.
5. To conrm or adjust the minimum re level settings, Re-dene the load as
“Manual Control”. Use Heat Output in “Congure Load x” to control the output
as needed.
6. At the minimum ring rate, adjust the zero-offset screw (see Figure 32, “A”)
to obtain the target CO2 value. It may be necessary to reduce the output in stages if this adjustment has been tampered with.
7. Turn boiler off by removing the call for heat (use the Heat Load Conguration
screen to turn load to off if no other ready means available); turn OFF gas supply to boiler, then remove the manometer connections, and turn the centre-screw in the manifold pressure test port 1 full turn clockwise. Ensure fully closed, but not over-tightened. Restore gas and soap test for leaks.
MODEL HIGH FIRE LOW FIRE CO MAX PPM
RANGE TARGET RANGE TARGET
VFC 15-150 (Natural Gas) 8.9 to 9.5% CO
VFC 15-150 (Propane) 10.4 to 10.7% CO
VFC 45-225 (Natural Gas) 8.9 to 9.5% CO
VFC 45-225 (Propane) 10.4 to 10.7% CO
2
2
2
2
9.2% CO
10.6% CO
9.2% CO
10.6% CO
2
2
2
2
7.9 to 8.6% CO
9.0 to 9.8% CO
7.9 to 8.6% CO
9.0 to 9.8% CO
8.4% CO
2
9.6% CO
2
8.4% CO
2
9.6% CO
2
2
2
2
2
< 100
< 150
< 120
< 180
Table 8: Combustion test target ranges - CO2 / Maximum CO
Insertion of ue gas analyzer probeRemoval of ue gas test port plug
STARTUP AND COMMISSIONING
3-3
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Figure 32: Gas Valve and Pressure Reference System
3-4
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
3.4
WARNING
Check the rating plate of
the boiler to ensure it is
congured for the fuel you
are using. If the fuel is incorrect for the appliance,
a conversion kit must be ordered from IBC and the gas valve adjusted accordingly.
Failure to perform the
required fuel conversion can
result in an immediate hazard.
DANGER
Operating any IBC boiler
using a fuel other than the fuel listed on its rating plate is prohibited. If the information in this section related to
conversion to alternate
fuels is not followed exactly, a dangerous situation can
result, leading to re or
explosion, which may cause property damage, personal injury, or loss of life.
FUEL CONVERSION
The VFC Series modulating boiler is factory re-tested to operate with natural
gas, or propane as ordered. The rating plate will be marked to indicate which fuel the particular boiler has been set up with. Firing a boiler with a fuel other than what is listed on the rating plate is prohibited unless the following conversion
procedure is completed by a qualied technician.
Refer to the details in the boiler’s current Installation and Operation Manual, section 3.3 - “COMMISSIONING”.
The Low Fire (Zero-offset) valve and High Fire (Gas: Air) ratio adjustment will have to be adjusted to attain optimum combustion results whenever fuel conversion is undertaken however, no mixture adjustment shall be performed
unless done by a qualied technician using properly functioning and calibrated combustion analyzing equipment.
The following procedure can be carried out by a qualied technician:
1. Ensure you are installing the correct fuel conversion kit for your boiler.
Compare the boiler model number with the Kit# found in Table #9.
2. Ensure the fuel conversion instructions supplied with the fuel conversion kit
are read, understood and followed carefully.
3. Carefully follow the procedures on page 3 of the relevant Fuel Conversion
Instruction document, Combustion Testing and Adjustment.
4. Place the conversion labels associated with the new fuel onto the boiler at
the positions indicated on page 4 of the applicable FUEL CONVERSION instruction sheet.
5. Carefully follow the “Prior to Start-Up “ - Section 3.2 and “Commissioning” -
Section 3.3 procedures on the preceding pages 3-2 and 3-3.
MODEL NUMBER NATURAL GAS TO
PROPANE
PROPANE TO NATURAL GAS
STARTUP AND COMMISSIONING
VFC 15-150 P-174 P-176
VFC 45-225 P-174 P-176
Table 9: Fuel Conversion Kits
3-5
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
THIS PAGE INTENTIONALLY LEFT BLANK
3-6
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
4.0
4.1
CAUTION
The owner is responsible for
general care of the boiler. Improper maintenance of the boiler may result in a hazardous condition.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
WARNING
Fill trap with water before
boiler is rst red to prevent
exhaust fumes from entering
room. Never operate the boiler unless the trap is lled
with water.
Failure to comply will result
in severe personal injury or
death.
MAINTENANCE
BOILER MAINTENANCE
4.1.1 General Care
Keep combustible materials and ammable liquids and vapours away from the
boiler.
Keep vent terminals clear of obstructions (snow, dirt, etc.).
4.1.2 Inspection
Inspection of the boiler is to be performed annually by a qualied service
technician.
4.1.3 Venting
Check vent terminals for and remove any obstructions (e.g. leaves, dust,
other debris).
Check, and clean or replace intake air lters or screens as required.
Check for holes or leaks in venting. Replace venting as needed.
Examine for any signs of moisture caused by sweating intake air pipes;
insulate as required.
Ensure proper resealing or reinstallation of venting on each servicing.
4.1.4 Condensate Traps
Condensate trap must be examined every two months to see if cleaning is
necessary (refer to trap cleaning instructions, section 1.5.3 of this manual).
Ensure that trap has been re-lled completely before ring boiler.
If condensate neutralization is used, check pH level of condensate discharge.
4.1.5 Burner
WARNING
Whenever the burner is removed for inspection or boiler servicing, the sealing gaskets must be examined
and replaced if damaged. Upon re-assembly, an
approved leak test solution
must be applied around the
burner ange sealing area to ensure there is no leakage of
combustible gas/air premix.
MAINTENANCE
Annually, remove burner to inspect for extent of fouling (refer to burner
removal and reassembly instructions, section 4.3 of this manual). Blow clear
using compressed air. Evaluate the magnitude of clearing required, and establish a reasonable burner inspection schedule. Some boiler / locations may call for annual service, others showing clean burners will only need
attention every 2 – 5 years. Consider adding air ltration if burner requires
cleaning every year. In alternate years, visually inspect burner through sight
glass. Ensure ame is stable and without excessive uttering. Normal ame
pattern is evenly distributed over the burner surface.
If burner is operating improperly, remove and clean or replace. Use a CO
analyzer to determine proper combustion. See Table 8 for correct values.
When re-installing burner, ensure it is inserted so that the seam (that runs
along the length of the metal-bre surface) is placed as far away from the ignitor as possible (180° rotation arc away). Also conrm spark gap is 1/8". Conrm visually by removing viewport, turning gas supply OFF, and allowing
the boiler to run through an ignition cycle. Compare the spark length with the spark rod diameter, which is the same 1/8" (e.g. use the rod as a reference).
2
4-1
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
CAUTION
The heat exchanger has a
small amount of combustion chamber insulation
(refractory), which contains ceramic bers. When
exposed to extremely high temperatures, the ceramic
bers, which contain
crystalline silica, can be
converted into cristobalite
- which is classied as a
possible human carcinogen.
Care should be taken to avoid disturbing or damaging
the refractory. If damage occurs, contact the factory for
directions. Avoid breathing and contact with skin and
eyes and follow these precautions:
1.
For conditions of frequent use or heavy exposure,
respirator protection is
required. Refer to the “NIOSH Guide to the
Selection and Use of Particulate Respirators
Certied under 42 CFR 84” for selection and use of respirators certied by NIOSH. For the most current information, NIOSH can be contacted at 1-800­356-4676 or on the web at www.cdc.gov/niosh.
2. Wear long sleeved, loose
tting clothing, gloves
and eyes protection.
3. Assure adequate
ventilation.
4. Wash with soap and water
after contact.
5. Wash potentially
contaminated clothes separately from other laundry and rinse washing machine thoroughly.
6. Discard used insulation in
an air tight plastic bag.
4.1.6 Heat Exchanger
During burner inspection (with the burner removed), examine the heat exchanger tubes adjacent to the burner’s normal position. In areas of poor gas quality, there may be a buildup of black plaque (typically sulfur). Other fouling agents: airborne dust, debris and volatiles.
Refer to burner removal instructions in Section 4.3 for access to combustion chamber and heat exchanger. Note that the safety warning regarding burner
refractory on this page must be observed.
4.1.7 Pump
Check that the pump is on in normal operation and that the water Δ°T is reasonable for a given ring rate (e.g. 10°F between supply and return when ring at 75,000 Btu/hr. for a VFC 15-150 unit).
4.1.8 Gas Piping
Check for damage or leaks and repair as needed.
4.1.9 Control Module
Check that boiler operation is consistent with the steps in the Touch Screen
Boiler Controller Manual.
Check that water temperature targets and setpoint is satisfactory and have
not been adversely amended.
Check the operating history using the boilers Logs menu and Error Logs
menu. The controller tracks the duty cycle of the boiler in each of the 4 loads separately. This information can be used to adjust the water temperatures of each load.
If a problem exists with the control, consult troubleshooting guide.
4.1.10 Water
Check water pressure and temperature. There should be no noticeable
change if boiler is functioning normally. Check for any noise in the system.
Check water piping for damage or leaks and repair as needed.
Check for 12-15 psig in normal operation, and look to ensure pressure does
not run up toward 30 psig at high temperature. If pressure rises sharply,
consider replacement of expansion tank. Check also for noise at high re,
which may signal water quality problems.
Check water piping for damage or leaks and repair as needed.
Water chemistry shall be of a quality generally accepted as suitable for
hydronic applications. See Section 1.6 for details.
Ensure any direct “city ll” water connections are left in the closed position to
minimize exposure to leaks and ooding.
4.1.11 Freeze Protection
NIOSH stated rst aid:
Eye contact - Irrigate and
wash immediately.
Check freeze protection. Use only antifreeze made specically for hydronic
systems. Inhibited propylene glycol is recommended. Antifreeze volume must be between 25-50% of the total volume of water in the system.
Breathing - Provide fresh
air.
4-2
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
WARNING
Do not use automotive-type
ethylene or other types of
automotive glycol antifreeze,
or undiluted antifreeze of
any kind. This may result in severe boiler damage. It is the
responsibility of the Installer to ensure that glycol solutions are formulated to inhibit corrosion in hydronic heating systems of mixed materials. Improper mixtures and chemical
additives may cause damage
to ferrous and non-ferrous components as well as non­metallic, wetted components, normally found in hydronic systems. Ethylene glycol is toxic, and may be prohibited for use by codes applicable to your installation location.
For environmental and toxicity reasons, IBC recommends
only using non-toxic propylene glycol.
4.1.12 Boiler Treatment
Check consistency of any boiler treatment used (e.g. Furnox™), for
appropriate mixture. Chemical inhibitors are consumed over time, lowering their density.
Verify proper operation after servicing.
4.1.13 Relief Valve - Maintenance and Testing
The relief valve manufacturer requires that under normal operating conditions a “try lever test” must be performed every two months. Under severe service conditions, or if corrosion and/or deposits are noticed within the valve body, testing must be performed more often. A “try lever test” must also be performed at the end of any non-service period.
Test at or near maximum operating pressure by holding the test lever fully open
for at least 5 seconds to ush the valve seat free of sediment and debris. Then
release the lever and permit the valve to snap shut.
If the lever does not activate, or there is not evidence of discharge, discontinue
use of equipment immediately and contact a licensed contractor or qualied
service personnel.
If the relief valve does not completely seal, and uid continues to leak from the discharge pipe - perform the test again to try and ush any debris that may be
lodged in the valve. If repeated tries fail to stop the leakage, contact a licensed
contractor or qualied service personnel to replace the valve.
CAUTION
Installers should inquire of local water purveyors as to
the suitability of their supply for use in hydronic heating
systems. If water quality is questionable, a local water
treatment expert must be consulted for testing,
assessment and, if required, treatment. Alternatively, water or hydronic uid of known quality can be brought to the
site.
CAUTION
Before testing the relief valve, make certain the discharge
pipe is properly connected to
the valve outlet and arranged to
contain and safely dispose of
equipment discharge.
While performing a “try lever test”, a quantity of heat transfer uid will be discharged from the piping system and the system pressure will drop. This uid
must be replaced. It is highly recommended that a system pressurization unit, such as an Axiom Industries model MF200 be employed to rell and pressurize
your system. Capture the discharged uid in a container and recycle it by
returning it to the system feeder unit. This is particularly important when your system contains treatment chemicals or glycol solutions. If the system employs
plain water, the boiler auto ll valve must be turned on in order to recharge the lost uid.
MAINTENANCE
4-3
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
4.2
COMPONENT DESCRIPTION
A diagram of components and their placement can be found at the end of this manual. To obtain service parts, contact your installer, telephone IBC Technologies or visit our website at www.ibcboiler.com. The following list provides a summary description of major components:
4.2.1 Fan/Blower
PART#/TYPE: RG130 – IBC # 240-040 (VFC 15-150)
RG137 – IBC # 240-048 (VFC 45-225)
FUNCTION: Moves combustion air and ue gas products through the boiler
and venting.
INSTALLATION: Fan removal is done at the ange (4 x #10-32 x 7/8” hex head)
and the gas valve (3 x M4 x 30mm Phillips head self tapping screws accessible for the underside of the gas valve; for improved access – mark and remove vinyl air reference tubes and black air pressure sensor.
4.2.2 Gas Valve
TYPE: IBC # 180-022
FUNCTION: zero governor gas valve provides strict gas/air mixture control over
the range — 15 - 150 MBH for VFC 15-150 or 45 – 225 MBH for VFC 45-225.
Air pressure sensor removal showing reference line connections
INSTALLATION: see Section 3.3 - Commissioning, for gas valve adjustments
4.2.3 Direct Spark Ignition Module
TYPE: Fenwal 240-004C
FUNCTION: microprocessor based spark generator and ame proving control
with 15 sec. pre-purge; 3 try before an auto re-setting 1 hour lockout.
INSTALLATION: (see Diagram 6.1-1 for correct position). Use IBC # 180-011
suppression cable as the ignition lead.
4.2.4 Differential Pressure Sensor
TYPE: Air Prove Switch (IBC # 240-003)
FUNCTION: precise measurement of combustion airow for operating control.
INSTALLATION: (see Figure 32 for correct connection of air reference lines).
4-4
INSTALLATION AND OPERATION INSTRUCTIONS
Main combustion components (clockwise from left) Burner, with ignitor and V clamp - Fan coupler
- Fan/Blower - Mixing plates &
housing - Gas valve
Combustion group assembly
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
4.2.5 Water Pressure Sensor
TYPE: Water Pressure (IBC # 240-006)
FUNCTION: water pressure and ow sensing.
INSTALLATION: (see Diagram 6.1-1, and Diagram 6.1-2).
4.2.6 High Limit
PART#/TYPE: IBC # 240-032 High Limit calibrated for 200°F, 15°F differential.
FUNCTION: Shuts boiler off when water temperature exceeds safety limit.
INSTALLATION: (see Diagram 6.1-1 for correct position). Mount with Honeywell
Tradeline #107408 Heat Conductive Compound between the base of the hi-limit switch and the mounting surface.
4.2.7 Transformer
PART#/TYPE: IBC # 240-008 Primary- 120 VAC; Sec.- 24 V AC; 40VA control
transformer.
FUNCTION: Provides 24 VAC for the control board, for (1) the control / safety
circuit, (2) relays for pump and zone valve control, plus (3) input to DC power converters for 5 V and 12 V circuits (NB not for use to power external zone valves).
INSTALLATION: (see Diagram 6.1-1 for correct position).
Control Module removal
4.2.8 Temperature Sensors
PART#/TYPE: IBC # 240-006 Thermistor; 10,000Ω with Beta = 3892
FUNCTION: Senses water temperature. Signals controller to adjust output
according to water temperature.
INSTALLATION: (see Diagram 6.1-1 for correct position).
4.2.9 Control Module
PART#/TYPE: IBC # 500-0044 Touch Screen boiler controller, V10.0
FUNCTION: (see Touch Screen Boiler Controller Manual for an explanation of
controller function).
INSTALLATION: (see Diagram 6.1-1 for correct position). The 4 screws on
the front panel corners secure the cover. To remove the unit from the mounting brackets, ensure all wires are removed from the connectors on the edge and back
of the control module. Place ngers on the board edge only when handling.
There is a 3V lithium battery (IBC # 240-024) for powering the permanent memory if AC power is not connected.
On-board eld replaceable fuses (IBC # 240-023) are 5A, slow blow, 5mm x
20mm, and must be replaced using these same specs.
Disconnecting Control Module plugs
MAINTENANCE
4-5
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
4.3
NOTE
The safety warning regarding
burner refractory on page
4-2 of this manual must be observed.
Burner Arm Bolts
Fan Screws
Gas Valve Bracket Screws
GAINING ACCESS TO COMBUSTION CHAMBER, BURNER REMOVAL INSTRUCTIONS; FAN AND GAS VALVE REMOVAL INSTRUCTIONS
The installer or service technician can select from three separate routes to gain access to the burner and heat exchanger:
1. The base method involves removal of the aluminum Fan Coupler (FC) while
leaving the fan and gas valve in-place:
a. Ensure boiler cools down to ambient temperature. Do not drain the boiler
unless freezing conditions are expected during this procedure.
b. Remove the front cover. No tools are required. A ladder or step may be
required to have a clear vertical view of the work area. Do not attempt to reach from the front without a clear view, as damage to connectors, screws or refractory may occur.
c. Ensuring the power and gas are shut off, disconnect the ignitor cable and
ground wire from the ignitor
d. Remove the two screws that secure the ignitor to the lid using a # 2
Phillips screwdriver. Carefully remove the ignitor by sliding it straight up.
e. Remove the ignitor gasket and place parts on a clean dry area. f.
Release the v-clamp, taking care to preserve its gasket for possible reuse.
g. For the VFC 15-150, remove the 4 x 6mm hex socket bolts at the FC:
Fan interface. Three of the 4 bolts are easily dealt with using a regular
6mm Allen key, while the upper (rear) fastener is in a conned space;
start turning with the wrench then complete the job using needle-nose
pliers and/or ngers. This task is best done using a 9” tee-handle hex
key. For the VFC 45-225, remove the 4 bolts and nuts at the FC:Fan interface using a 5/16” wrench for the bolts and 3/8” wrench for the nuts.
Lift away the Fan Coupler.
h. Remove the burner, noting the alignment of the longitudinal seam of its
metal bre surface relative to the ignitor location (it should be 180° of arc
opposed).
i.
Remove the burner: heat exchanger gasket, and protect for possible reuse.
j. Remove the 4 bolts that attach the heat exchanger lid to the heat
exchanger. A 17 mm open end wrench or socket will be required. Note alignment for reinstallation. Lift off lid.
k. Note alignment of the inner refractory disk, then carefully lift out and
place on a clean, dry disposable material (paper or plastic).
Using this technique leaves the fan, gas valve and associated electrical
connections exposed to water and/or debris from heat exchanger cleaning; take precaution by bagging these components.
2. The preferred option for experienced IBC service personnel – for combined
servicing of the HX and swirl plate – involves removal of the FC and fan together, done as follows:
a. Perform steps 1 (a) to (f) as listed in #1above. Disconnect the 2 power
connections to the fan within step 1(c).
b. Split the fan from the swirl plate/ intake air housing:
i. Remove the 3 Phillips screws which run vertically upwards from the
gas valve into the fan. The rear screw can be challenging - these bolts
can be identied by the spacers under the bolt heads. Best to use an
4-6
INSTALLATION AND OPERATION INSTRUCTIONS
Vellumoid paper gasket VFC15-150 O-Ring, VFC 45-225
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
angle-driver to reach past the gas valve, or a stubby Phillips screwdriver for enhanced working space.
ii. Three vinyl hoses do not need to be disconnected, but if that is chosen
ensure they are marked for reinstallation. Avoid placing pressure on the disk-shaped air pressure sensor, which can damage the sensor.
iii. Lift away the FC/ Fan assembly and stow safely.
c. Perform steps 1(h) to (k) as listed above, and protect the gas valve from
water and dirt.
Use this method if site conditions provide a risk of debris within the
combustion air (dirty environment with no combustion air ltration). This
offers open access for cleaning of the swirl plate, air intake housing and fan inlet. Take care to protect the air intake and gas valve components left in place.
3. A third option available is a variation of #2, but substituting disassembly of
gas inlet piping (e.g. at a union near the drop leg) in place of splitting the fan/ gas valve in situ. This eliminates having to deal blind with the back screw per 2(b)(i) above; rather it can be handled “face-on” on a work bench. For this option, at Step 1(c), also unplug the gas valve electrical connection by removing the 1/4” gas valve harness connector screw, mark and disconnect the vinyl hoses from the intake air housing and gas valve; after Step 1(f) remove the 4 small Phillips screws at the gas valve inlet. Block off the combustion air intake pipe to prevent debris from falling inside.
Figure 33: Gas Valve Detail
With either approach selected, leave undisturbed the outer refractory ring unless
there are signs of damage. If replacement is required, make specic precautions
for silica dust management then pry up the material (likely in several pieces). Bag with care to seal off, and dispose.
RE-ASSEMBLY
1. Inspect the inner refractory disk (replace as appropriate), and reinsert per
noted alignment. If the outer refractory ring requires replacement, rst perform a dry t test (including placement of the HX lid overtop with the HX: lid gasket properly positioned) to conrm positive engagement of lid to
refractory for a good thermal seal. Apply a thin layer of mouldable refractory to the water pipes and header to be covered then insert the new outer ring. Apply gentle pressure until the ring’s upper surface is level and approx 1/16” (1-1.5 mm) proud to the HX rim.
2. Inspect the HX: lid gasket: look for cracks, deterioration or signs of gas
bypass. Replace if necessary. Conrm it is in place and offers a positive
sealing surface.
3. Place the HX lid over the gasket, reconrming that 1/16” (1-1.5 mm) is
available for compression on bolt tightening. Install the 4 Lid-to-HX bolts; with a 17mm wrench or socket, tighten with light force until bolt starts to get tight,
then nal tighten with 1/2 to 1 extra turn.. Over-tightening will cause lid to warp and possible leakage of fumes or ames.
4. Inspect the lower burner-to-HX gasket. Look for cracks, deterioration or signs
of gas bypass. Install original or replace as necessary.
5. Insert the burner, ensuring the metal mesh seam is rotated away from the
ignitor location.
6. Move the Fan Coupler into place, then:
a. Under option 1 – replace the paper gasket after applying silicone to each
side; install the 4 small Phillips bolts at the Fan: FC interface
b. Under option 2 – install the 3 standard Phillips screws to reattach the Fan
and swirl plate to the gas valve
MAINTENANCE
4-7
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
c. For option 3 – install the 4 small Phillips screws through the gas valve
support bracket and into the gas valve adjacent to the gas inlet. The screws are to be loosely attached at this stage to allow easier alignment at step 7. After the v-clamp is tightened at step 7, these 4 screws at support bracket can be tightened. Reinstate all gas piping.
7. With the FC/ Fan / gas valve assembly secure, place a good v-clamp-to-
burner gasket over the top of the burner ange, spread the v-clamp to span
the HX-burner-gasket sandwich then draw the v-clamp nut tight by hand plus 2 turns by wrench. Do not over-tighten. Use a max. 5 ft/lbs torque.
8. Reconnect all fan and gas valve electric leads, vinyl hoses
9. Re-install ignitor, tightening its screws by hand, then an extra 1/2 turn.
10. Re-attach ignitor wire and ground wire to ignitor.
11. Open up the gas supply and check for possible leaks
12. Return electric power to the boiler and perform start up routine
13. If the outer refractory ring has been replaced at Step 1 above, using a Type J
or K thermocouple, check the upper areas of the HX and lid for temperature for good thermal sealing at the refractory-to-lid interface. Allow 20 mins. prior
running at high re before the test; max target is 110°C
14. Check for gas or fume leaks after 10 minutes of continuous operation.
Figure 34: Refactory Detail
FOR REMOVAL OF THE FAN AND/OR GAS VALVE
For removal of the fan and/or gas valve only, follow steps 1(a) to (f) above, then depending on the objective perform the following:
Fan removal: use Option 2, the additional steps within 2(a) (b) and (c) above
Gas valve: use Option 3
For any change-out of the fan: with a permanent marker or equivalent, make an alignment mark between the fan and swirl plate adapter and use a 6 mm hex (Allen) key or driver, remove the 3 screws that attach the gas valve/swirl plate assembly to the fan.
FOR RE-INSTALLATION OF FAN AND/OR GAS VALVE,
1. If the gas valve has been removed, reattach it to the swirl plate.
2. Re-attach gas valve and swirl plate assembly onto fan observing the
alignment marks made during disassembly.
3. Re-plug both upper and lower fan harness connectors.
4. Re-plug gas valve connector and tighten up retaining screw.
5. If a new gas valve is being installed, remove the protective cover from the
gas inlet now.
Vellumoid paper gasket
Aluminium Spacer
Vellumoid paper gasket
Vellumoid paper gasket
Figure 35a: VFC 15-150 Fan Detial Figure 35b: VFC 45-225 Fan Detail
4-8
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.0
TROUBLESHOOTING
The troubleshooting section is divided into 3 sections:
5.1 Preliminary Checks
5.2 Electronic Components
5.3 Troubleshooting Guide
Often, a problem can be identied and solved through simple checks of the basics: conrming the electrical power supply, gas ow and resetting the
thermostat control. To extend the cover of such preliminary checks, the boiler’s control module offers a clear visual display of the status of the various control circuit components.
Should a problem remain unsolved after applying the preliminary checks, proceed to the detailed system review, using the Troubleshooting Guide. The Guide covers potential error conditions as grouped into the following categories:
5.3.1 Using Control Module Errors Displayed
5.3.2 Ignition Problems
5.3.3 Cycling Problems
5.3.4 Temperature Problems
5.3.5 Miscellaneous
5.1
Below each section is a list of Symptoms, Diagnoses, and Remedies.
Also provided with this manual are a number of diagrams (see Section 6.0) for use with troubleshooting including:
Electrical Wiring Diagrams
Sequence of Operations Flowchart
Boiler Component Layout Diagrams
PRELIMINARY CHECKS
The rst step in troubleshooting this system should be a review of the Controller’s
Touch Screen. There are a number of diagnostic features incorporated in the software that evaluate system integrity, display error conditions and provide initial suggested remedial actions.
In addition to checking the display, the following list is a guideline for troubleshooting:
1. Conrm power to the boiler: check that control module display is on (e.g.
display is lit).
2. Check that boiler is not in a safety lockout.
3. Ensure wiring is clean and secure.
4. Check that gas is reaching the unit.
5. Conrm water system is properly charged to 12 psig and pump is
serviceable.
TROUBLESHOOTING
5-1
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.2
Return water temperature sensor
ELECTRONIC COMPONENTS
This section details the method for troubleshooting the non-standard electronic components on the boiler including the electronic differential air pressure sensor and the temperature sensors.
5.2.1 Temperature Sensors
The resistance of the temperature sensors varies inversely with temperature. To test, measure the temperature of the sensed environment and compare with the value derived from the measurement of the resistance (obtained by connecting a
good quality test meter capable of measuring up to 5,000 kΩ (5,000,000Ω) at the
controller end of the sensor lead).
To obtain a resistance reading, remove power to the boiler. Locate the blue
2-wire leads coming from the thermistors, which are afxed to the boiler supply
and return piping to the right of the heat exchanger. Disconnect the Molex connectors located approx. 6" from the sensors. Place multi-meter probes into Molex socket. Do not apply voltage to the sensor as damage may result.
Sensors are sensitive to excess binding force, which can distort the internal
dielectric isolation. Use modest tension only when afxing sensor to pipe.
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE
°F °C Ω °F °C Ω
10KΩ sensors supplied with boiler
2 x Water temperature sensors - (L) 1 x Outdoor sensor - (R)
See Table #10 for resistance values
0 -18 85,362 100 38 5,828
5 -15 72,918 105 41 5,210
10 -12 62,465 11 0 43 4,665
15 -9 53,658 115 46 4,184
20 -7 42,218 120 49 3,760
25 -4 39,913 125 52 3,383
30 -1 34,558 130 54 3,050
35 2 29,996 135 57 2,754
40 4 26,099 140 60 2,490
45 7 22,763 145 63 2,255
50 10 19,900 150 66 2,045
55 13 17,436 155 68 1,857
60 16 15,311 160 71 1,689
65 18 13,474 165 74 1,538
70 21 11,883 170 77 1,403
75 24 10,501 175 79 1,281
80 27 9,299 180 82 1,172
Table 10: Temperature Sensor resistance values
5-2
85 29 8,250 185 85 1,073
90 32 7,334 190 88 983
95 35 6,532 195 91 903
INSTALLATION AND OPERATION INSTRUCTIONS
Control wire plug
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.2.2 Fan/Blower
Operating power is provided by means of a separate 120 VAC connector at the back of the fan (white/black/green). Control of the fan is provided via a four lead connector at the front of the fan. This connector feeds a PWM control signal (black wire) from the controller and provides a tachometer signal (white wire) back from the fan. Unplugging the connector will cause the fan to go to high speed and trigger a “Blocked Vent Error” within 6 seconds if the boiler is operating.
LEAD COLOR FUNCTION TROUBLESHOOTING
Unplug to run fan full speed
Air pressure sensor mounting
Red
Blue
Black Signal from controller
White Fan tach. 2 pulses/rev (freq x 30=rpm)
Table 11: Fan Operation
35 VDC Positive power terminal
35 VDC Negative power terminal
Fan will only operate at max. speed if disconnected.
Fan will only operate at max. speed if disconnected.
Fan will only operate at max. speed if disconnected.
5.2.3 Differential Air Pressure Sensor
Do not blow into the ports of the sensor, this is not a switch and “does not click when closed”. Excessive pressure will damage the sensor thus requiring replacement. The sensor values are located in the advanced diagnostics section of the controller. In general, the Fan Pressure and the Required Pressure should be very close to each other while the boiler is in operation. If the required pressure is higher than the actual pressure there are several possible causes.
Exhaust and/or Air Intake piping installed longer that allowed
Improper grading of the Exhaust and/or Air Intake piping allowing condensate
to be trapped in the piping
Re-Ingestion of ue gasses has caused the Swirlplate and/or Fan Impeller to
erode, becoming ineffective.
Air Pressure Sensor tubing not correctly attached.
TROUBLESHOOTING
If the Differential Air Pressure Sensor replacement is required, ensure the replacement sensor is IBC part# 240-003 (and specically that it is not a similar- looking part marked for use only on the SL 28-160 model boiler). Use of any other differential air pressure sensor is forbidden.
5.2.4 Water Pressure Sensor
The water pressure sensor ensures there is adequate pressure in the heating system for safe operation. The pressure is displayed in PSI as the default. If the
system pressure should drop below 8PSI the ring rate of the boiler is reduced. If the pressure drops to 4PSI or lower, the boiler will not re.
Check operation of the sensor by isolating the boiler from its system piping,
closing the system ll valve then cracking the pressure relief valve; the pressure displayed should reect declining pressure. If it remains “xed”, drain boiler and
replace sensor, or dislodge any blocking debris from sensor inlet channel and reinsert.
5-3
Fenwal ignition module - Microamp
(μA) test points are shown at top
right corner of module (above red L.E.D.)
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.2.5 Hi-Limit Switch (water and vent)
Check resistance between leads. If resistance is very low, temperature should be acceptable. If resistance is very high, temperature should be out of bounds. A simple means of checking whether a high limit switch is open is by measuring the AC voltage across the device. If the reading is 24 VAC the switch is open. If a 0VAC reading is shown, it is closed. NEVER connect an ohm-meter or continuity checker across a live circuit.
5.2.6 Ignition Module
There are two approved ignition modules - Fenwal (grey) and Capable Controls (white). Each have a red LED lamp providing the following signals: Fenwal – 1
rapid ash on 1st entering Pre-purge, 3 rapid ashes upon Failure to Ignite After 3 Attempts; the Capable Controls module provides a single ash at the start of each Purge and Interpurge cycle, continuous rapid ashes during the 4 second spark
interval, solid illumination following successful ignition until burner shutdown, and a slow on/off cycle with a 3-try failure.
Flame current can be monitored on the Fenwal. Connect an electrical test
meter - set to read Microamps (symbol μA) to the two test pins at the top right of
the ignition module. Recycle the boiler so it enters another trial for ignition and
monitor the ame current reading. When the burner ignites, a steady reading of
2-7 Microamps should be measured by your meter. The control will lock out if the reading drops below 0.7 Microamps. (see Section 5.3.1 - “Control Module
- Maximum ignition trials error”, and Section 5.3.2 - “Ignition problems”). For conversion from Fenwal to the Capable Control, specify IBC part# 240-049 – that provides the module plus added wire lead and instructions.
5-4
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.3 TROUBLESHOOTING GUIDE
5.3.1 Using Control Module Errors Displayed
SYMPTOM DIAGNOSIS REMEDY
AIRFLOW ERROR
Touch Screen Message:
Error – Low Air Flow
Low combustion airow; soft error; will retry in 5 minutes
WARNING
Never attempt to repair the control module (circuit board). If the control module is defective, replace it
immediately.
Check fan operation • Check lead is attached at fan.
• Cycle power off/on; listen for fan initialization. If no action, focus your attention on the fan itself.
Check for fouled
reference lines and air sensor
Check achieved fan
power
Water noise in vent.
Excess condensate in
venting.
• Check clear vinyl air reference lines below gas valve for any sign of water. After disconnecting from black sensor, blow clear. Check for exhaust re-ingestion, or repeated power interruptions .
• Ensure condensate trap is not blocked.
• Go to Advanced Diagnostics and check differential air pressure sensor (at rest and with fan on). See Section 5.2.3.
In Diagnostics, Fan Operation, during Pre­purge, Fan Pressure (FP) should move close to Required Pressure (RP); if FP only 480 to 600 vs. RP of 1,000 to 1,200, then check for actual vent system blockage: (a) disconnect intake within boiler case; (b) open burner then fan/gas valve looking for debris.
• Check condensate trap for obstructions.
Remove obstructions and rell condensate
trap with water.
• Check vent length, size and conguration,
particularly re: horizontal 2" piping.
WATERFLOW ERROR
Touch Screen Message:
Error - No Water Flow
Low water ow – soft error; will
retry in 5 minutes
TROUBLESHOOTING
Check pressure
sensors
Check for proper
piping
Check primary pump If there is a valve on the primary loop, close it
Check for restriction
in water pipe
• Check wiring: water pressure sensors to controller.
• Check pressure sensors. See Section 5.2.4 – 2nd paragraph.
Refer to Section 1.6 Water Piping for recommended piping installation.
and listen for cavitation (evidence ow). If not,
go to Installer Setup; select pump purge “on” to run pumps without a heat call - check for heat
buildup at pump body (indicates no ow).
Check temperature differential across heat
exchanger at low –medium ring rate if possible.
Examine air strainer components for scale.
5-5
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
SYMPTOM DIAGNOSIS REMEDY
MAXIMUM IGNITION TRIALS ERROR
Touch Screen Message:
Error – Ignition Failure after 3
tries
Boiler has failed to ignite on 3 successive attempts. Boiler in lockout for 1 hour, then repeats 3-try seq. Consult service technician if error recurs.
No spark when
igniting. Igniter
Check that igniter lead is secure at the control module and at the probe.
probe/ame sensor
disconnected.
Manual gas shutoff is
closed or gas line not
Check for gas ow. Open manual gas shutoff
and reset boiler.
fully purged.
Gap between igniter probe and ground rod is too large or too small.
Adjust gap between igniter probe/ame sensor
and ground rod to a distance of 3/16" (turn off gas supply and remove viewport for best
visibility; use prole of 1/8" diameter ignitor rod
to gauge distance)
Spark, but no ignition. Check spark module is sending power to gas
valve – close gas supply, then disconnect (black) electric housing from face of gas valve, gently spread plastic tabs to open, and look for 24vac voltage between blue and brown wires during an ignition cycle. Replace module if no current detected
Boiler ignites, but
shuts off at the end of the ignition trial. Improperly grounded pressure
vessel/burner or unserviceable ignition
• Ensure pressure vessel is grounded.
• Check the igniter probe/ame sensor is
electrically isolated from the vessel, and its ceramic insulator is intact.
• Replace ignition lead
• Replace spark module
lead or spark module.
HI LIMIT ERROR
Touch Screen Message:
Error – Water High-Limit
Exceeded
Water temperature exceeds hi­limit. Boiler in hard lockout. Will reset in 1 hour. Consult service technician.
VENT HI-LIMIT ERROR
Touch Screen Message:
Error - Vent High-Limit Exceeded *** Call for service!
Vent temperature has exceeded the vent limit switch. Boiler in lockout. Consult service technician.
Defective or
disconnected hi-limit switch.
• Check wiring to hi-limit switch and control module.
• Check hi-limit switch. See Section 5.2.5.
• Check wiring to ensure sensor is properly connected to control module.
• Check for evidence of any damage to vent system.
• Push manual reset button, maintain constant watch during boiler operation to evaluate vent temperature at maximum operating settings to ensure no unsafe condition exists,
e.g. max ue temp. within allowable limits for
exhaust pipe material used.
5-6
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
SYMPTOM DIAGNOSIS REMEDY
TEMPERATURE SENSOR ERROR
Touch Screen Message:
Error - Max. In-Out Temp.
Exceed. -> Check water ow
Water temperature signal not within acceptable range.
Current outlet
temperature exceeds operating limit.
Defective or
disconnected temperature sensor.
Check water ow.
Check wiring to temperature sensor and
control module.
Check temperature sensor. See Section
5.2.1.
Potential ow or sensor failure.
Consult service technician.
MISCELLANEOUS
Touch Screen Message:
Check transformer; replace if damaged.
Check circuit board for visible damage.
Blank – screen dark, but fan
running Indicative of power­surge damage to appliance
5.3.2 Ignition Problems
SYMPTOM DIAGNOSIS REMEDY
NOISY SPARK WHEN IGNITING
Ignition lead is not
rmly connected.
Reconnect ignition lead.
BOILER RUMBLES WHEN IGNITING.
BOILER WILL NOT ATTEMPT TO IGNITE. FAN AND PUMP ARE OPERATING NORMALLY.
BOILER WILL NOT ATTEMPT TO IGNITE. FAN AND / OR PUMP ARE OFF DISPLAY NOT ILLUMINATED
Contaminants/
moisture on igniter
Ensure probe is dry by re-running post-purge; otherwise, clean or replace igniter probe.
probe/ame sensor.
Fluctuating gas
Check CO2 level via analyzer.
pressure/ gas pressure too high/too low.
Check for proper
Check pressure with manometer during ignition.
piping.
No power to ignition control module.
Igniter probe/ame
Check system wiring.
Check air reference tubing.
Reconnect probe.
sensor disconnected.
Blown fuse in ignition
Check fuse. If blown, replace.
module.
Defective Control
Check ignition output from control module.
Module.
No power to boiler. Check line voltage .
Defective transformer. Check transformer. Reconnect or replace as
needed.
TROUBLESHOOTING
5-7
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.3.3 Cycling Problems
SYMPTOM DIAGNOSIS REMEDY
RAPID CYCLING Improper values
entered via keypad.
Excess Condensate in venting.
Obstruction in
condensate trap.
Improper vent length
or improper slope to
vent.
Incorrect settings or
defective thermostat.
Air in system or
marginal water ow.
Slow combustion air blower.
Dirty burner/heat exchanger.
Check load maximum temps are above target temps, by 1/2 of the selected boiler differential. Ensure boiler differential is OK (16-30°F is generally adequate)
Check venting slopes on horizontal runs. Look for sags.
Inspect and clean condensate trap.
Check venting. Compare vent length and diameter to Table 4: Maximum Venting.
Check operation. Refer to manufacturer’s instructions. Check setting with ammeter.
Bleed/purge system as required. Conrm
adequate pump size and temp rise in HX
Check that CO2 level is OK per Tabel 8.
Check pressure drop.
Insufcient water
Refer to recommended piping in Section 1.6
ow due to improper
piping.
Insufcient water ow
due to undersized
Check manufacturer’s rating charts/check temperature differential across heat exchanger.
pump.
Insufcient water ow
due to restrictions in
Check temperature differential across zone/heat exchanger.
water pipe.
Insufcient radiation. Check actual amount of radiation per zone and
refer to manufacturer’s rating tables.
Unit over-red. Clock gas meter/check gas pressure with
manometer/ check CO2 level.
Unit Oversized. Check load calculation vs. min. boiler output.
Improperly set or
Check operation with ohmmeter/voltmeter.
defective operating/
safety controls.
5-8
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.3.4 Temperature Problems
SYMPTOM DIAGNOSIS REMEDY
INSUFFICIENT HEAT
Operating
Increase temperature target.
temperature too low.
Priority parameters
Review load conguration parameters.
or load conguration
improperly set up.
Unit undersized. Refer to Load Calculation vs. Boiler Output.
Air trapped within
Bleed system as required.
system.
Improper system
Refer to recommended piping in Section 1.6
piping.
System pump undersized.
Check pump manufacturer’s data/check temp differential across heat exchanger.
Poor gas/air mixing. Check CO2 level.
Defective thermostat. Refer to manufacturer’s instructions.
Obstruction in
Inspect and clean condensate drain.
condensate drain.
Unit cycling on
Check operation with Ohmmeter/Voltmeter.
operating/ safety controls.
TEMPERATURE EXCEEDS THERMOSTAT SETTING
ONE OR MORE ZONES DO NOT HEAT PROPERLY
System radiation undersized.
Incorrect anticipator
Check manufacturer’s rating tables for capacity per foot.
Check with Ammeter.
setting.
Thermostat not level. Check level.
Air trapped within
Vent system/zone as required.
zone(s) piping
Insufcient radiation/ excessive heat loss.
Insufcient ow rate
Check actual length of pipe using radiation / heat loss calculation.
Check temperature drop across zone.
to zone(s).
Defective zone valve/
Check operation per manufacturer’s instructions.
zone circulator.
TROUBLESHOOTING
5-9
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
5.3.5 Miscellaneous
SYMPTOM DIAGNOSIS REMEDY
FUMES AND HIGH HUMIDITY
Improperly installed
Refer to installation/operation instructions
condensate trap
Leak in vent piping Inspect using soap solution
BOILER STUCK ON INITIALIZE
TOUCH SCREEN MESSAGE:
Unknown Error
ERROR: WATER HIGH LIMIT / LOW WATER CUT-OFF WON’T CLEAR.
DHW TAKING TOO LONG TO HEAT.
BOILER OUTPUT NOT MODULATING UP TO MAXIMUM DESPITE TARGET NOT BEING REACHED.
Flue gas leak within
Visually inspect all mechanical connections
boiler
Fan board failure Replace fan.
Temperature sensor
input problem.
Test each temperature sensor for appropriate readings and replace defective temperature sensor.
Boiler is in 1 hour safety lockout.
Sensor may be under­reading actual water temp.
Reset safety device and cycle boiler power off and on to reset error.
Check sensor engagement; note well is 15cm / almost 6 inches deep and sensor must be fully set to back. Check programmed settings boiler temp set too close to the required DHW temp
Possible ow issue: check for 35 or 40
degree F temperature
Conrm that primary pump is able to overcome
head loss of boiler and primary loop piping at the
required ow rate.
difference between boiler supply and return water temperatures
(evokes electronic fence).
PRIMARY PUMP RUNS DURING PARALLEL-PIPED DHW CALL.
Load denition as DHW. On Touch Screen Controllers set the boiler pump
to off in the Installer Set-up Menu.
5-10
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
6.0
DIAGRAMS
6.1 - VFC 15-150 PARTS DIAGRAMS
6.2 - VFC 45-225 PARTS DIAGRAMS
6.3 - ADDITIONAL PARTS DIAGRAMS
6.4 - WIRING DIAGRAMS
6.5 - SEQUENCE OF OPERATION
DIAGRAMS
6-1
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
6.1 VFC 15-150 PARTS DIAGRAM
Diagram 6.1-1: Boiler Assembly – VFC 15-150
6-2
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
ITEM# DESCRIPTION PART# QTY
6 FAN, RG130 240-040 1
11 GASKET, FAN - FAN ADAPTER 250-310 1
15 FAN ADAPTER PLATE 180-023 1
20 SCREW, M4 x 10, FLAT HEAD,
3
EQUIPPED w/240-040
25 AIR INTAKE, BASE 180-017 1
30 SWIRL PLATE 180-020 1
35 AIR INTAKE, COVER 180-018 1
40 GAS VALVE 180-022 1
45 SPACER, #8, 1/8” THICK, 1/4”
150-092 3
O.D.
50 SCREW, M4 x 30, TAPPING,
3
EQUIPPED w/180-022
55 SCREW, #10-32 x 7/8”, HEX
150-110 4
HEAD
61 GASKET, FAN - FAN
250-311 1
COUPLER
70 NUT, #10-32, w/EXTERNAL
150-111 4
TOOTH WASHER
75 SWITCH, SNAP DISK,
240-030 1
MANUAL RESET, 230F
80 SWITCH, SNAP DISK, AUTO-
240-032 1
RESET, 203F
85 MOUNTING PLATE, SNAP
250-333 1
DISK
90 IGNITION MODULE
240-004C 1 (ALTERNATE CAPABLE CONTROLS 240-049)
95 SCREW, SHEET METAL, #8
150-021 2 x 3/4”
100 SENSOR, WATER PRESSURE 240-006 2
105 ENCLOSURE 250-312 1
111 GAS VALVE MOUNTING
250-314 1 BRACKET
115 SENSOR, AIR PRESSURE 240-003 1
120 TRANSFORMER 240-008 1
125 SIDE COVER, CONTROLLER 250-327 1
130 SCREW, #6-32 x 3/8”, PAN
150-014 6 HEAD
135 CHASSIS, CONTROLLER PCB 250-583 1
140 PCB, CONTROLLER V10.0 230-002 1
145 SPACER, MALE - FEMALE,
150-096 4 #6-32 x 3/4”
150 FRONT COVER,
250-591 1 CONTROLLER
155 PIPE CLAMP 150-039 3
160 2” ABS AIR INTAKE
1
ASSEMBLY
165 CLIP NUT, M10, 19mm
150-105 4 CENTER
170 HEAT EXCHANGER 170-009 1
ITEM# DESCRIPTION PART# QTY
175 REFRACTORY, OUTER 250-287 1
180 REFRACTORY, INNER 250-306 1
185 GASKET, HEAT EXCHANGER
250-328 1
LID
190 LID, HEAT EXCHANGER 250-284 1
195 SCREW, M10 x 55, HEX HEAD 150-106 4
200 WASHER, FENDER, M10 150-104 4
205 IGNITOR 240-002 1
210 GASKET, IGNITOR 250-050 1
215 SCREW, M4 x 10, PAN HEAD 150-013 4
220 SIGHT GLASS HOLDER 250-309 1
225 GASKET, SIGHT GLASS 250-060 2
230 SIGHT GLASS 250-059 1
235 GASKET, BURNER 250-308 2
240 BURNER 180-021 1
245 V-CLAMP 150-071 1
250 FAN COUPLER 250-280 1
270 FRONT COVER, VFC 150 250-313 1
Diagram 6.1-1 (Parts List)
Diagram 6.1-2: Door Assembly – VFC 15-150
DIAGRAMS
6-3
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
6.2 VFC 45-225 PARTS DIAGRAM
Diagram 6.2-1: Boiler Assembly – VFC 45-225
6-4
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
ITEM# DESCRIPTION PART# QTY
5 FAN, NRG 137 240-048 1
10 O-RING 150-073 1
15 FAN ADAPTER PLATE 180-023 1
20
SCREW, M4x10 TAPPING,
3
FLAT HEAD, EQUIPPED w/FAN
25 AIR INTAKE, BASE 180-017 1
30 SWIRL PLATE 180-020 1
35 AIR INTAKE, COVER 180-018 1
40 GAS VALVE 180-022 1
45 SPACER, #8, 1/8” THICK, 1/4”
150-092 3 O.D.
50 SCREW, M4 x 30, TAPPING,
3
EQUIPPED w/GAS VALVE
55 SCREW #10-32 x 7/8” HEX
150-110 4 HEAD
60 GASKET, FAN - FAN
250-381 2 COUPLER
65 FAN COUPLER SPACER 250-370 1
70 NUT, #10-32, w/EXTERNAL
150-111 4 TOOTH WASHER
75 SWITCH, SNAP DISK,
240-030 1 MANUAL RESET, 230F
80 SWITCH, SNAP DISK, AUTO-
240-032 1 RESET, 203F
85 MOUNTING PLATE, SNAP
250-333 1 DISK
90 IGNITION MODULE
240-004C 1 (ALTERNATE CAPABLE CONTROLS 240-049)
95 SCREW, SHEET METAL, #8
150-021 2 x 3/4”
100 SENSOR, WATER PRESSURE 240-006 2
105 ENCLOSURE 250-312 1
110 MOUNTING BRACKET, GAS
250-316 1 VALV E
115 SENSOR, AIR PRESSURE 240-003 1
120 TRANSFORMER 240-008 1
125 SIDE COVER, CONTROLLER 250-327 1
130 SCREW, #6-32 x 3/8” 150-014 6
135 CHASSIS, CONTROLLER PCB 250-583 1
140 PCB, CONTROLLER V10.0 230-002 1
145 SPACER, MALE - FEMALE,
150-096 4 #6-32 x 3/4”
150 FRONT COVER,
250-591 1 CONTROLLER
155 PIPE CLAMP 150-039 3
160 2” ABS AIR INTAKE
1
ASSEMBLY
165 CLIP NUT, M10, 19mm
150-105 4 CENTER
170 HEAT EXCHANGER 170-009 1
ITEM# DESCRIPTION PART# QTY
175 REFRACTORY, OUTER 250-287 1
180 REFRACTORY, INNER 250-306 1
185 GASKET, HEAT EXCHANGER
250-328 1
LID
190 LID, HEAT EXCHANGER 250-284 1
195 SCREW, M10 x 55, HEX HEAD 150-106 4
200 WASHER, FENDER, M10 150-104 4
205 IGNITOR 240-002 1
210 GASKET, IGNITOR 250-050 1
215 SCREW, M4 x 10, PAN HEAD 150-013 4
220 SIGHT GLASS HOLDER 250-309 1
225 GASKET, SIGHT GLASS 250-060 2
230 SIGHT GLASS 250-059 1
235 GASKET, BURNER 250-308 2
240 BURNER 180-021 1
245 V-CLAMP 150-071 1
250 FAN COUPLER 250-280 1
280 FRONT COVER, VFC 225 250-315 1
Diagram 6.2-1 (Parts List)
Diagram 6.2-2: Door Assembly – VFC 45-225
DIAGRAMS
6-5
Diagram 6.3-1: Vent high limit
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
6.3 ADDITIONAL PARTS DIAGRAMS
51 TRAP/EXHAUST KIT
Diagram 6.3-2: Intake Air Filter (order separately)
Diagram 6.3-4: Accessory parts kit (shipped with boiler)
ITEM # DESCRIPTION PART #
47 Pressure Relief Valve 180-005
49 Outdoor Temperature Sensor 240-025
51(a) Trap/Exhaust Kit VFC15-150 P-150
51(b) Trap/Exhaust Kit VFC45-225 P-151
66 Washer, #10, External Tooth 150-085
67 Screw, #10-32 x 1/2" 150-084
75 Switch, Snap disk, Manual Reset, 230F 240-030
100 Sensor, Water Pressure 240-006
101 Pressure Sensor Bushing 250-023
103 Intake Air Filter Element 180-103
104 Intake Air Filter Housing 180-104
PARTS BELOW - NOT SHOWN
68 Ignition Cable 210-001
69 Fuse Kit (10 pack) P-114
71 8 Position Terminal Block - Green 240-019
72 22 Position Terminal Block - Orange 240-020
73 DC to AC Fan Harness Conversion Kit 71-ACDC
74 Acid Neutralization Tank 180-029
102 Ignitor Kit w/Gasket P-142
Diagram 6.3-3: Water pressure sensor group
6-6
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
6.4 WIRING DIAGRAMS
Diagram 6.4-1: Ladder wiring diagram
DIAGRAMS
6-7
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
Diagram 6.4-2: Internal wiring diagram
6-8
INSTALLATION AND OPERATION INSTRUCTIONS
VFC 15-150, VFC 45-225 MODULATING GAS BOILERS
6.5 SEQUENCE OF OPERATION
Diagram 6.5-1: Sequence of operation diagram
DIAGRAMS
6-9
INSTALLATION & COMMISSIONING REPORT
Boiler Details:
Model Number _____________________ Serial Number ______________________________________________
Date of Installation ______________ Address of installation __________________________________________
_____________________________________________________________________________________________
User contact information _______________________________________________________________________
Installer Information Company ___________________________________________________________________
Address ______________________________________________________________________________________
Phone/Fax/E mail ____________________________________________________________________________ __
Fuel Natural Gas Propane
Gas Supply Pressure (high re) _______ Inches w.c. Measured Rate of Input (high re) ____________ Btu/hr
Installation instructions have been followed and completed (Section 1 of Installation and Operating Instructions).
Check-out procedures have been followed and completed (Section 3 of Installation and Operating Instructions).
Leak testing completed gas piping venting system Fan and combustion components
System Cleaned and Flushed (type of cleaner used) ________________________________________________
System Filled (type/concentration of any glycol/chemicals used) _______________________________________
Air purge completed
Relief Valve correctly installed and piped Relief valve “try lever” test performed
Condensate trap lled
Ignition Safety Shutoff test completed. Flame current reading - High re _______ µA - Low re _______ µA
Owner advised and instructed in the safe operation and maintenance of the boiler and system.
Information regarding the unit and installation received and left with owner
Condensate drain clear and free owing Condensate Neutralization? Yes/No
Combustion Readings:
CO
_____________ % O2 ______________ % CO ____________ ppm
2
Flue temperature _________ Return water temperature (measure simultaneously with ue temp.) _______________
Installers: send this completed sheet - Fax to 604 877 0295 - or - scan and Email to info@ibcboiler.com, and earn an extra year’s Parts Warranty coverage (User to submit corresponding Installation Record from User Guide).
Commissioning has been completed as listed on this report - Installer Signature _____________________________
INSTALLER SET-UP
Load Denition - Load #1 _______________________________________________________________________
Load Conguration - Load #1
_____________________________________________________________________________________________
Load Denition - Load #2 _______________________________________________________________________
Load Conguration - Load #2
_____________________________________________________________________________________________
Load Denition - Load #3 _______________________________________________________________________
Load Conguration - Load #3
_____________________________________________________________________________________________
Load Denition - Load #4 _______________________________________________________________________
Load Conguration - Load #4
_____________________________________________________________________________________________
SERVICE RECORD
DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE
NOTES
NOTES
NOTES
IMPORTANT
This Boiler is equipped with a feature that saves energy by reducing the boiler water
temperature as the heating load decreases. This feature is equipped with an override
which is provided primarily to permit the use of an external energy management system
that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT
LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is installed that reduces the boiler
water temperature as the heating load decreases.
This boiler is not used for any space heating.
This boiler is part of a modular or multiple boiler system having a total input
of 300,000 BTU/hr or greater.
This boiler is equipped with a tankless coil (not applicable to IBC’s VFC boilers).
US installers should contact IBC for any further information required.
REVISION HISTORY
R1 (SEPTEMBER 2005) Initial release
R2 (JULY 2007) Venting requirements (Canada) to ULC-S636; internal wiring diagram and warranty
details added
R3 (MARCH 2010) VFC 45-225-SL variant added (with new NRG-137 fan); warranty removed to separate document
R4 (SEPTEMBER 2012) Polypropylene venting, detachable lid heat exchanger and US Energy Act disclosures added; VFC 45-225-SL designation merged within base VFC 45-225 model
R5 (SEPTEMBER 2014) Disclosures updated to CSA 4.9-2014 / ANSI Z21.13-2014 Standard; Touch Screen Controller added
R6 (MAY 2015) Address update
IBC Technologies Inc.
8015 North Fraser Way Burnaby, BC Canada V5J 5M8
Tel: 604.877.0277 Fax: 604.877.0295
www.ibcboiler.com
120-100E-A-R6
May 2015
© IBC Technologies Inc. 2015
Loading...