If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
Do not store or use gasoline or other flammable vapors and liquids or other combustible
materials in the vicinity of this or any other appliance.
If you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a nearby phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fire department. Installation and service must
be performed by a qualified installer, service agency or the gas supplier.
Operating Manual
EX SERIES
Commercial Boilers
Water quality
Warning
Water quality has a significant impact on the lifetime and performance of a boiler's heat exchanger.
Improperly prepared water in a heating circuit may cause damage to the heat exchanger through
fouling or corrosion. Repeated or uncontrolled water fills will increase the potential for damage.
High levels of dissolved solids or minerals may precipitate out of the fluid onto the hottest part of the
heat exchanger, impairing heat transfer and resulting in overheating and premature failure. The
amount of solids that may form on the heat exchanger will depend on the degree of hardness and
the total water volume in the system. A high water volume system with a low hardness count may
cause as much damage as a system with less volume and higher hardness, so it is recommended
to treat water so as to remove all dissolved solids. Other water chemistry allowable limits are as
follows:
Acidity pH is to be between 6.6 and 8.5
Chloride is to be less than 125 mg/l
Iron is to be less than 0.3 mg/l
Cu less than 0.1 mg/l
Conductivity is to be less than 400μS/cm (at 77°F [25°C])
Hardness is to be 7 grains per gallon or less / 120 ppm or less
Important: Ensure that these limits are acceptable for the other water-side components in the
system.
Shipped with the boiler:
4 x anchor brackets (installed on pallet)
Condensate trap IBC # P-1221
Tridicator IBC # P-1234
Relief valve IBC # P-1205
2 x Inlet gas pressure test fittings, IBC part # 190-206
2 x spare air filters, IBC # P-381
Outdoor sensor, IBC part 240-025
1
Contents
Safety information5
Manual safety markings5
Important safety instructions5
Known contaminants6
Specifications7
Connection specifications8
Cabinet dimensions9
1.0 Introduction11
1.1 Standard features and benefits12
1.2 Warranty12
2.0 Before installation13
3.0 Installation15
3.1 Code requirements15
3.2 Determining location of the unit15
3.2.1 Factors to consider for best installation conditions16
3.3 Unpacking a boiler17
3.4 Installation clearances18
3.5 Exhaust venting and air intake venting18
3.5.1 Code19
3.5.2 Applications21
3.5.3 Exhaust vent material21
3.5.4 Vent travel22
3.5.5 Venting passage through ceiling and floor24
3.5.6 Rooftop vent termination25
3.5.7 Sidewall vent termination27
3.5.8 Direct vent combustion air intake piping32
3.5.9 Indoor air combustion air intake35
3.5.10 Combustion air filtration system36
3.6 Installing a condensate trap37
3.7 Installing a condensate neutralizer39
3.8 Water Piping41
3.8.1 General piping best practices43
3.8.2 System piping44
3.9 Gas piping54
3.9.1 Gas pressure54
3.10 Electrical connections55
3.10.1 Power quality and electrical protection55
3.10.2 120VAC line-voltage hook-up56
3.10.3 Other wiring59
3.10.4 Thermostat / sensor wiring59
3.10.5 Thermostat heat anticipator60
4.0 About the boiler controller61
4.1 Controller61
4.2 Control interface62
5.0 Before operating the boiler63
5.1 Important pre-ignition checks63
5.1.1 Checklist for electrical conditions, ducting and water connections63
6.0 Service and maintenance65
6.1 Maintenance checklists for manager of unit65
6.2 Maintenance checklists for heating contractor65
6.2.1 Venting66
6.2.2 Condensate trap66
6.2.3 Burner66
6.2.4 Heat exchanger67
6.2.5 Pump67
6.2.6 Gas piping67
6.2.7 Touchscreen boiler controller67
6.2.8 Water68
6.2.9 Freeze protection69
2
Section: Contents
6.2.10 Boiler treatment69
6.2.11 Relief valve - maintenance and testing69
6.3 Replacing the fan, gas valve, and burner70
6.3.1 Replacing the fan71
6.3.2 Replacing the gas valve72
6.3.3 Replacing the burner74
6.4 Replacing the air filter76
6.5 Cleaning a condensate trap77
7.0 Troubleshooting79
7.1 Preliminary checks79
7.2 Electronic components80
7.2.1 Temperature sensors80
7.2.2 Fan81
7.2.3 Air pressure sensor81
7.2.4 Water pressure sensor81
7.2.5 Gas pressure switches82
7.2.6 Safety and Ignition Module (SIM)82
7.3 Troubleshooting error messages85
7.3.1 Touchscreen error messages85
7.3.2 Maximum ignition trials error86
7.3.3 Hi/Low gas pressure switch error87
7.3.4 Hi Limit cut-off temperature error87
7.3.5 Low Water Cut-off error87
7.3.6 Aux. Interlock 1 or 288
7.4 Miscellaneous touchscreen controller errors88
7.4.1 Ignition issues89
7.4.2 Temperature issues90
7.4.3 Miscellaneous issues91
7.4.4 Cycling issues92
Appendices93
Wiring diagrams93
3
Installation & Commissioning Report96
Boiler parts diagram97
Revision history101
4
Section: Contents
5
Safety information
Danger
Points out an immediate hazardous
situation that must be avoided to
prevent serious injury or death.
Warning
Points out a potential hazardous situation
that must be avoided to prevent serious
injury or death.
Caution
Points out a potential hazardous
situation that must be avoided to
prevent possible moderate injury
and/or property damage.
Note
Points out installation, maintenance and
operational notes to enhance efficiency,
longevity and proper operation of the
boiler.
Danger
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other
appliance. If you smell gas vapors, do not try to operate any appliance - do not touch any
electrical switch or use any phone in the building. Immediately, call the gas supplier from a phone
located remotely. Follow the gas supplier’s instructions, or if the supplier is unavailable, contact
the fire department.
Warning
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury, or loss of life. Read and understand the entire manual before attempting
installation, start-up, operation, or service. Installation and service must be performed only by an
experienced, skilled installer or service agency.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all
instructions, including all those contained in component manufacturers’ manuals before installing,
starting up, operating, maintaining, or servicing the unit.
Manual safety markings
Important safety instructions
Installation, start-up and servicing of IBC boilers must be performed by competent, qualified, licensed and
trained heating technicians.
Failure to read and comply with all instructions and applicable national and local codes may result in
hazardous conditions that could result in property damage and injury to occupants, and in extreme cases to
death. Keep instructions near the air handling unit for future reference.
Warning
Disconnect power supply before any wiring/service is performed. Failure to do so could result
in damage to unit and/or electric shock.
Caution
The boiler must be installed so that electrical components are not exposed to water during
operation.
Known contaminants
Known Corrosive Contaminants to Avoid
Cements and glues
Paint or varnish removers
Adhesives used to fasten building products and other similar products
Chlorinated waxes or cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for snow and ice clearing
Sodium chloride or potassium chloride used for water softening
Refrigerant leaks from cracks in coils
Hydrochloric acid or muriatic acid used in household cleaning and stain removal
Chemicals in perming solutions
Chlorofluorocarbon chemicals found in spray cans
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Antistatic dryer sheets in clothes dryers
6
Section: Safety information
7
Specifications
EX 700EX 850
CSA Input (Natural Gas or Propane) - MBH70 - 70085 - 850
CSA Input (Natural Gas or Propane) - kW20.5 - 20524.9 - 249
CSA Output - MBH679824.5
CSA Output - kW199241.6
Thermal Efficiency97%97%
Minimum gas supply pressure (Natural Gas or Propane) - inch w.c.44
Maximum gas supply pressure (Natural Gas or Propane) - inch w.c.1414
Ambient temperature:
Low °F / °C
High °F / °C
32 / 0
122 / 50
32 / 0
122 / 50
Max. relative humidity (non-condensing)90%90%
Minimum water temp. °F / °C34 / 134 / 1
Maximum water temp. (electronic hi-limit) °F / °C190 / 88190 / 88
Maximum equivalent vent length Each side (Vent & Air Intake)) (Natural
Gas or Propane)
Air intake options: either direct vent or indoor supply
120'120'
*These alternative relief valves can be purchased: 30, 100, 125 and 150.
Flue Outlet6" Schedule 40
Combustion Air Inlet4" Schedule 40
Water Outlet2½" NPT-M
Water Inlet2½" NPT-M
Knock-outs (8)½"
Gas Inlet1" NPT-F
Condensate Outlet¾" Hose
8
Section: Specifications
Table 1 Specifications
Connection specifications
The following table displays the required connection specifications for each model.
Table 2 Connections
Cabinet dimensions
Figure 1 Frontal viewFigure 2 Top view
Figure 3 Back view
9
Cabinet dimensions
10
Section: Specifications
11
1.0Introduction
IBC's range of large commercial boilers is the solution for large-scale projects such as apartment buildings,
office buildings, big schools, hospitals, and hotels.
Figure 4 Front internal view
Figure 5 Back view of boiler
1.1 Standard features and benefits
12
Section: Introduction
High thermal efficiency
Built-in BACnet option
Turn-down ratio 10 to 1
Built-in 4-zone pump control
Multiple boilers: Up to 24 boilers can be connected without external controls
Maximum allowable ∆T=80 °F (44 °C)
50 psi relief valve (345 kPa)
Boiler pump control up to ¾ H.P. 120V or 208/240V
1.2 Warranty
IBC offers a 10-year warranty on the EX series heat exchanger and a 1-year warranty on all parts against
defects in materials or workmanship and failures due to thermal shock.
For more information and to obtain the EX series warranty form, go to ibcboiler.com.
13
2.0 Before installation
PrecautionsCheck
Care must be taken to properly size the boiler for its intended use.
Prolonged full fire run time, over-sizing or under-sizing, and incorrect flow rates through the boiler
can lead to increased maintenance costs, equipment stress and premature failure.
□
Ensure you install the boiler where the combustion air source is not subject to chemical fouling or
agricultural vapors.
Exposure to corrosive chemical fumes such as chlorinated and/or fluorinated hydrocarbons can
reduce the life of a boiler. Cleaners, bleaches, air fresheners, refrigerants, aerosol propellants, drycleaning fluids, de-greasers and paint-removers all contain vapors that can form corrosive acid
compounds when burned in a gas flame. Airborne chlorides such as those released with the use of
laundry detergents are also to be avoided.
□
Locate the boiler where water leakage will not result in damage to the area.
If there is no suitable location, install a suitable drain pan under the boiler. Do not install above
carpeting.
□
At a new construction site, or during renovations, protect the boiler from drywall dust or other
construction related contaminants.
Draw combustion air from a clean source (e.g., outdoors) and isolate the boiler from interior dust
sources. Do not seal boiler case openings directly when firing - allow for air circulation and
ventilation in the immediate area.
□
Place the exhaust outlet 12" minimum above the down-turned intake to avoid exhaust re-ingestion.
□
For sidewall venting options, place the inlet and exhaust terminations on the same side of the
building.
The elevation of both pipes can be raised in “periscope style” after passing through the wall to gain
required clearance above grade and snow level.
□
If using the indoor combustion air option, ensure combustion air openings to the boiler room
remain unblocked and free of obstructions.
□
Examine the condensate outlet to ensure proper disposal of condensate will occur during
operation. If condensates are to be discharged into building drain piping materials that are subject
to corrosion, a neutralization package must be used.
□
Ensure that the pressure relief valve is installed with no valves or other means of isolation between
its inlet and the boiler.
Make sure the relief valve outlet is piped with unobstructed piping (minimum 1" diameter) to a safe
□
Before installing the unit, it is important to review and observe the following checklist of precautions:
PrecautionsCheck
discharge location.
If the boiler is likely to be exposed to fluid temperatures below 34° F (1° C), a method of protection
to prevent freezing of condensate should be employed. Contact the factory for further information.
□
When the boiler is in operation, assess the impact of the steam plume normally at the exhaust
terminal of a condensing boiler.
Generally, intake and exhaust pipes should terminate at a rooftop or sterile wall location. Boiler
condensate is corrosive. Protective measures must be taken to prevent corrosion damage to metal
roofs or other metal building components in contact with the condensate. Keep exhaust plumes
well away from all building air intakes including those of neighboring properties.
□
Caution
Care must be taken to properly size the boiler for its intended use. Prolonged full fire run time,
over-sizing or under-sizing, and incorrect flow rates through the boiler can lead to increased
maintenance costs, equipment stress and premature failure.
14
Section: Before installation
15
3.0 Installation
The gas-fired modulating boilers are low pressure, fully condensing units having a variable input range.
Approved as “Category IV” vented appliances, the boilers use either Direct Vent (sealed combustion) or
indoor combustion air, providing a great degree of installation flexibility.
3.1 Code requirements
The boilers are tested and certified under CSA 4.9-2017 / ANSI Z21.13-2017. Below are the code
requirements for every installation.
CanadaUS
Conform to local codes, or in the absence of these,
with the latest editions of CAN/CGA B149.1 and the
Canadian Electrical Code Part 1 CSA C22.2 No. 1.
Where required by jurisdiction, installation must
conform to the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME
CSD-1.
If there is any conflict, follow the more stringent
regulations.
Table 3 Code requirements by country
Conform to the current National Fuel Gas Code ANSI
Z223.1 and the National Electrical Code ANSI/NFPA
70.
Where required by jurisdiction, installation must
conform to the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME
CSD-1.
If there is any conflict, follow the more stringent
regulations.
3.2 Determining location of the unit
The boilers are designed and approved for indoor installation in areas such as an alcove, basement, or utility
room. These areas should have a surrounding temperature of 32 °F (0°C) to 122 °F (50 °C) and less than
90% relative humidity.
Even though EX models are approved from installation on combustible floors, do not install them on carpet.
Warnings
Keep the area around a boiler clear of combustible materials, gasoline, and other
flammable vapors and liquids.
Ensure combustion air is not drawn from areas containing corrosive air such as
swimming pools or spas, including air directly next to outdoor pools and spas.
Ensure that a boiler is not exposed to water leaks from piping or components located
overhead, including condensation from uninsulated cold water lines overhead.
Protect the gas ignition system components from water (dripping, spraying, rain, etc.)
during appliance operation and when servicing (pump replacement, condensate trap
servicing, control replacement, etc.).
Ensure that combustible materials do not make contact with exposed water piping
and associated components (relief valves, circulators, etc.). Check local codes for
required clearances and/or provide adequate insulation.
3.2.1 Factors to consider for best installation conditions
16
Section: Installation
Install the boiler in areas where the combustion air source is not subject to chemical fouling or
agricultural vapors. Exposure to corrosive chemical fumes such as chlorinated and/or
fluorinated hydrocarbons can reduce the life of a boiler. See list of Known contaminants on page
6. For this reason, do not use the indoor air venting option (using air surrounding the boiler) in a
laundry room. Similarly, ensure any direct vent air source is not near a clothes dryer exhaust
terminal. Avoid agricultural applications where the boiler and/or the intake air source are
affected by ammonia and/or dust.
Avoid installing a boiler where water leakage will cause damage; for example, above carpeting.
If unavoidable, install a suitable drain pan under the appliance.
Other factors to consider:
The minimum clearance requirements for combustible materials (see Table 4 ).
For adequate servicing, we recommend a minimum 30" clearance at the front and 12" above the
boiler. Check local codes for additional access and service clearance requirements.
At a new construction site, or during renovations:
Take action to protect the boiler from drywall dust or other construction related
contaminants
Ensure combustion air is drawn from a clean source (e.g., outdoors)
Isolate the boiler from interior dust sources. Do not seal boiler case openings directly when
firing - allow for air circulation and ventilation in the immediate area.
3.2.1.1 Anchoring the boiler
17
3.3 Unpacking a boiler
Boiler weight – without water and any effect of system piping and components – is approximately 500 lbs /
225 kg.
Use the brackets provided to secure the boiler to the floor.
3.3 Unpacking a boiler
The boiler is shipped bolted to a pallet with four (4) anchor brackets and 3/8" Hex head bolts. Once the
anchor brackets are removed they can be used to secure the boiler to the floor.
Figure 6 Boiler packaging dimensions (inches)
3.4 Installation clearances
Warning
Exposed water piping and associated components (relief valves, circulators, etc., should not
be in contact with combustible materials. Check local codes for required clearances and / or
provide adequate insulation.
EX 700, 850
Surface
Minimum distance from
combustible surfaces
Recommended clearance for
installation and service
Front2"30"
Rear flue connection2"24"
Left side1"2"
Right side1"4"
Top6"
12"
(required for filter replacement)
Bottom00
Warning
Venting, condensate drainage, and combustion air systems for all IBC boilers must be
installed in compliance with all applicable codes and with instructions provided in the
respective installation manuals.
Inspect finished vent and air piping thoroughly to ensure all are airtight, and comply with the
instructions provided as well as with the requirements of applicable codes. Failure to comply
will result in severe personal injury or death.
18
Section: Installation
Table 4 Clearance distances for boiler mounting sites
3.5 Exhaust venting and air intake venting
When planning a boiler's installation, consider the appropriate vent materials, travel and termination.
An important consideration is managing the impact of the steam plume normally at the exhaust terminal of a
Danger
Do not common vent EX series modulating boilers with any other existing or new appliance.
19
3.5.1 Code
condensing boiler. Generally, intake and exhaust pipes should terminate at a rooftop or sterile wall location
to maximize customer satisfaction. Keep exhaust plumes well away from all building air intakes including
those of neighboring properties.
Flue gas exhaust to outdoors
Figure 7 Flue gas venting
3.5.1 Code
All venting must be installed in accordance with the requirements of the jurisdiction having authority: in
Canada, Part 8, Venting Systems of the B149.1-10 Code and any other local building codes are to be
followed. In the USA, the National Fuel Gas Code, ANSI 223.1, latest edition, prevails. Where there is a
discrepancy between the installation instructions provided, and the code requirements, apply the more
stringent.
Provisions for the combustion and air ventilation must be in accordance with the section “Air for
Combustion and Ventilation” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Clause 8.2, 8.3 or
8.4 of the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the
local building codes.
3.5.1.1 Important considerations when removing an existing boiler:
Warning
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.
20
Section: Installation
When an existing boiler is removed from a common venting system, the common venting system is
likely to be too large for proper venting of the appliances that remain connected to it. When resizing any
portion of the common venting system, use the minimum size according to the appropriate tables in the
National Fuel Gas Code, ANSI Z223.1 - latest edition. In Canada, use the B149.1 Installation Code.
At the time of removal of an existing boiler the following steps shall be followed with each appliance
remaining connected to the common venting system placed in operation, while the other appliances
remaining connected to the common venting system are not in operation:
Seal any unused opening in the common venting system.
Visually inspect the venting system for proper size and horizontal pitch. Determine that there is
no blockage or restriction, leakage, corrosion and other deficiencies that could cause an unsafe
condition.
(Where practical) Close all building doors and windows such as doors adjacent to appliances
remaining connected to the common venting system and other spaces of the building.
Turn on clothes dryers and any appliance not connected to the common venting system.
Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
Place in operation the appliance being inspected.
Follow the lighting instructions.
Adjust the thermostat so that the appliance operates continuously.
After determining that each appliance remaining connected to the common venting system
properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace
dampers and any other gas-burning appliance to their previous condition.
Any improper operation of the common venting system should be corrected, so the installation
conforms with the National Fuel Gas Code, ANSI Z223.1 - latest edition. In Canada, all
installations must conform with the current CAN/CGA - B149.1-10 Installation Code and/or local
codes.
3.5.2 Applications
Warning
Condensate can cause corrosion of metal roofing components and other roofing materials.
Check with the builder or roofing contractor to ensure that materials are resistant to acidic
condensate. pH levels can be as low as 3.0.
21
3.5.2 Applications
All EX series boilers are approved with alternative venting options: either 2-pipe Direct Vent or Vent pipe
with Indoor Air. With the Direct Vent case, combustion air is piped directly to the boiler’s air intake from
outdoors (see Vent termination clearance on page 30) for air intake piping requirements. Using the indoor
air alternative, air for combustion is drawn from the indoor air surrounding the boiler.
Provided the maximum overall vent length limit is not exceeded, the boiler may be vented through the wall,
directly through the roof, or upward using an existing -- but otherwise unused - chimney as a vent raceway.
3.5.3 Exhaust vent material
Exhaust vent material – CANADA
Use PVC, CPVC, Polypropylene (PPs), or Stainless Steel (SS) vent component systems approved under
ULC-S636 Standard for Type BH Gas Venting Systems, or stainless steel Type BH venting systems*. The
vent temperature is limited by the boiler controller with the use of a flue temperature sensor to ensure the
maximum temperature of the PVC venting material is not exceeded.
Exhaust vent material – USA
PVC, CPVC, PPs, or SS venting materials are approved for use with these boilers in most of the USA.
Check local codes to determine if any materials are prohibited. The vent temperature is limited with the use
of the flue temperature sensor and software to ensure that the maximum temperature of the PVC venting
material is not exceeded. PVC venting material shall be certified to Sch. 40 ASTM D1785 or D2665. CPVC
material shall be certified to Sch. 40/ASTM F441.
Exhaust vent material
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in venting
systems is prohibited.
Do not use ABS or any cellular core pipe for exhaust venting.
The exhaust fitting has a 6" PVC (schedule 40) connection. Use fittings to adapt to either PPs or SS venting
material. Insert exhaust venting directly into the 6" female stainless steel fitting, and secure with the built-in
clamp (see Figure 8 ).
For PPs material, use the 6" transition / adaptor fitting (Sch 40 to PPs) offered by the respective PPs
Warning
Ensure that you lubricate the gasket with silicone grease before inserting the venting
material. Fully insert the approved venting material into the boiler's exhaust outlet, and
tighten clamp to ensure the venting connection is locked in place (as shown below).
Warning
Do not mix PPs venting materials from different manufacturers. These venting materials are
designed to be installed as part of a complete system. Failure to comply may result in severe
personal injury or death.
22
Section: Installation
manufacturers Centrotherm / InnoflueTM (their part # ISAAL0606) or M&G Dura Vent / PolyProTM (#
6PPS-06PVCM-6PPF [10004281]), (# 4PPs-AD). For PPs material exposed to outdoor weather, follow
the venting supplier’s recommendations on UV protection.
For SS material, use the 6" transition / adaptor fitting offered by the SS manufacturers M&G Dura Vent (#
FSA-6PVCM-6FNSF [300538]) or Heat Fab (Saf-T-Vent) 9601PVC.
Figure 8 Securing the vent connection
Venting must be supported in accordance with the applicable code and instructions supplied by the
manufacturers.
3.5.4 Vent travel
PVC/CPVC (Schedule 40), PPs (Rigid Single Wall), or SS approved piping are the standard venting
options that can be sited up to 120 equivalent feet from the vent termination.
Warning
Follow all installation instructions supplied by the pipe and fitting manufacturer.
The actual vent travel allowance is reduced for fittings as shown in the following tables:
EX 700, EX 850
Exhaust Pipe SizeMaximum Equivalent Length
Sched.40; Rigid PPs
6" PVC/CPVC / Rigid PPs/SS120' (each side)
90° vent elbowallow 5' equivalent
45° elbowallow 3' equivalent
PPs 87-90° elbowsuse 5' equivalent
For example, for an EX 850 using 6 x 90º CPVC vent elbows, the maximum lineal measure of pipe
allowed is 90 feet (120' – (6 x 5' = 30) = 90').
Note
Unused intake travel cannot be added to the exhaust. Unequal intake and exhaust piping is
allowed.
23
3.5.4 Vent travel
Table 5 Maximum Exhaust Venting Length for EX 700, 850
Exhaust venting must slope down towards the boiler with a pitch
of at least 1/4" per foot (PP vent: follow PP manufacturer
requirements for slope), so condensate runs back towards the
trap. Support should be provided for intake and vent piping,
particularly for horizontal runs (follow local code).
Figure 9 Pipe and fitting beveling
Check that material meets local codes including fire stopping requirements. Some local jurisdictions
require a minimum initial length of pipe be exposed or accessible for inspection. Pipe clearances -
no IBC requirements; follow local codes. All piping must be liquid and pressure tight.
Ensure all venting components are clear of burrs/debris prior to assembly. Clear plastic debris
24
Section: Installation
left in the combustion air piping to avoid intake into the fan.
Secure joints using appropriate solvent cement to bond the respective pipe material (Canada:
CPVC cement approved under ULC-S636, in accordance with its manufacturer instructions;
USA: PVC (ASTM D2564), or PVC/ABS (D2235) - Use transition glue anywhere that PVC and
CPVC are joined. Follow the cement manufacturer’s instructions closely when joining various
components. For PPs, connections shall be secured using approved retainer clips supplied by
the respective PPs manufacturer.
Check that vent connections are liquid and pressure tight. Prior to firing the boiler, and before
any of the venting run is concealed by the building construction, the installer must test the
exhaust joints under fan pressure with the vent blocked, using a soap and water solution .the
installer must fill the condensate trap prior to testing.
To drive the fan into manual high speed operation for vent leak testing, from the touchscreen controller
Main Menu go to Diagnostics>Test Operation>Set Vent Test to On. Paint all joints with an approved
leak test solution just as you would joints in a gas line, and make sure there are no leaks. We suggest
attaching a tag on the vent line near the condensate drain tee with the type of test, the date and the
installer’s name.
3.5.5 Venting passage through ceiling and floor
Confirm material meets local codes including fire stopping requirements.
Check the local jurisdiction on the minimum initial length of pipe that should be exposed or
accessible for inspection.
Follow the local codes for pipe clearances - no IBC requirements.
Ensure that piping is liquid and pressure tight.
3.5.6 Rooftop vent termination
Warning
Condensate can cause corrosion of metal roofing components and other roofing materials.
Check with the builder or roofing contractor to ensure that materials are resistant to acidic
condensate. pH levels can be as low as 3.0.
Figure 10 Rooftop vent terminal
configurations
Figure 11 Rooftop vent termination with
sidewall combustion air
25
3.5.6 Rooftop vent termination
a. Rooftop vents must terminate as follows:
The exhaust pipe can terminate in an open vertical orientation without concern about rain
infiltration; rain will drain away through the condensate trap.
Optional bird screen may be placed in a termination fitting. Leave unglued, and hold in
place with a short nipple. This permits easy access for cleaning.
Do not exhaust vent into a common venting system.
b. For rooftop direct vent systems:
Rooftop, two pipe, direct vent configurations, including typical clearance requirements are
shown below in the following images.
Vent screen retainer
Exhaust
Vent screen
Inlet
Flashing
Figure 12 Rooftop vent terminal vent screen and retainer
Best Practice: To reduce the possibility of expansion noise, allow a ¼" gap
around the exhaust and air intake piping.
26
Section: Installation
The intake air pipe is not typically drained, so it must be terminated with a down-turned
elbow as shown.
The intake pipe does not need to penetrate the roof at the same elevation as the exhaust
(as shown); lower down on the roof is acceptable.
For roof top venting of multiple boiler sets, group all intake terminals together for a common
Caution
Vent termination clearances in this section are code minimum, or IBC recommended minimum
requirements, and may be inadequate for your installation. Building envelope details must be
examined carefully. Take action to avoid moisture entering building structures. Serious structural
damage may occur if adequate precautions and clearances are not allowed for. These
precautions apply to neighboring structures as well as to the structure the boiler(s) are installed
in.
27
3.5.7 Sidewall vent termination
penetration through a custom cap. Alternatively, place close together using commonly
available pipe flashing. Similarly, group the exhaust pipes and place the two separate
groups of pipes at least 3' apart (the closest intake and exhaust pipes shall be 36", or more,
apart). Use the same 12" (minimum) vertical separation for all termination options. For
alternate group terminations, contact the IBC Factory for written guidance.
Roof top termination kits are approved for use with the boiler model. Installation of the
vertical roof top termination must follow the installation instructions supplied with the venting
material manufacturer. Care must be taken to install the termination kit a minimum horizontal
distance of 10' (305 cm) away from any portion of the building and a minimum of 2' (61 cm)
above the roof line plus the anticipated snow line.
3.5.7 Sidewall vent termination
Figure 13 Minimum clearances from vent/air inlet terminations (see legend on adjacent page)
DescriptionUS Installations
1
1
Canadian
Installations
2
2
A Clearance above grade, veranda, porch, deck, or
balcony
1' (30 cm)1' (30 cm)
B Clearance to window or door that may be opened4' (1.2 m) below or to
side of opening
3' (91 cm)
C Clearance to permanently closed window
*
*
28
Section: Installation
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
2
In accordance with the current CAN/ CSA-B149 Inst allation C odes.
*
Clearances in acc ordance wit h local installation codes and the requirements of the gas supplier.
DescriptionUS Installations
1
1
Canadian
Installations
2
2
D Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2' (61 cm)
from the center line of the terminal
5' (1.5 m)*
E Clearance to unventilated soffit**
F Clearance to outside corner6' (1.83 m)*6' (1.83 m)*
G Clearance to inside corner6' (1.83 m)6' (1.83 m)*
H Clearance to each side of center line extended above
meter/regulator assembly
*3' (91 cm) within a
height 15' above the
meter/ regulator
assembly
IClearance to service regulator vent outlet*6' (1.83 m)
J Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance
4' (1.2 m) below or to
side of opening; 1'
(30 cm) above
opening
3' (91 cm)
K Clearance to mechanical air supply inlet*6' (1.83 m)
L Do not terminate above paved sidewalk or paved
driveway
Slip hazard due to
frozen condensate
Slip hazard due to
frozen condensate
M Clearance under veranda, porch, deck or balcony*12" (30 cm)
3
Warning
Important!: Maintain at least the minimum separation of exhaust vent termination from boiler
intake air as illustrated in Figure 14 , Figure 15 , Figure 16 and Figure 17 . Failure to do so can
result in a dangerous situation where exhaust gasses are re-ingested with combustion air.
Damage to the boiler can result from a failure to maintain these separations. Third party vent
termination kits and concentric wall penetration kits that do not maintain these minimum
separations shall not be used. Improper installation will void the warranty. Do not use proprietary
InnoFlue or PolyPro PPs terminals without specific approval from IBC.
29
3.5.7 Sidewall vent termination
Table 6 Vent/air inlet termination clearances
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
2
In accordance with the current CAN/ CSA-B149 Inst allation C odes.
3
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and t op of terminal, and underside of
veranda, porch, deck or balcony is greater than 1' (30 cm).
Sidewall direct vent with separate vent and air pipes shall be terminated as follows:
Caution
When the outdoor temperature drops below 5°F/-15°C, take care installing Concentric Side
Wall Termination kits. Possible blockage of the combustion air intake can occur when the
outdoor temperature drops below this temperature.
In areas of high snowfall, users must be advised to check side wall vent and air intake
terminations on a regular basis to ensure blockage does not occur.
3.5.8 Direct vent combustion air intake piping
Known Corrosive Contaminants to Avoid
Cements and glues
Paint or varnish removers
Adhesives used to fasten building products and other similar products
Chlorinated waxes or cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for snow and ice clearing
Sodium chloride or potassium chloride used for water softening
Refrigerant leaks from cracks in coils
Hydrochloric acid or muriatic acid used in household cleaning and stain removal
Chemicals in perming solutions
Chlorofluorocarbon chemicals found in spray cans
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Antistatic dryer sheets in clothes dryers
32
Section: Installation
The direct vent option uses piping from the outside to supply combustion air directly to the boiler’s
combustion air connection. Combustion air piping - if used - is inserted directly into the 4" PVC-sized
fitting, and increased immediately to 6".
At a new construction site, or during renovations, action must be taken to protect the boiler from drywall
dust or other construction related contaminants; combustion air should be drawn from a clean source
(e.g. outdoors) and the boiler should be isolated from interior dust sources. Do not seal boiler case
openings directly when firing - allow for air circulation and ventilation in the immediate area.
Warnings
In addition to preventing ingestion of chemical contaminants, ensure air intake
terminals are not installed in locations where contamination might occur due to
ingestion of particulate foreign material (dust, dirt and debris).
Configure intake air openings, so that rain or other forms of moisture cannot enter the
air intake piping system. Otherwise serious damage to the boiler may result.
Do not use
bushing
Flue gas exhaust to outdoors (connection at
rear of boiler)
Flue gas exhaust to outdoors
Combustion air from outdoors. "Direct Vent"
installation: check air intake outside is clear
of obstructions.
Combustion air from outdoors. Use reducing
coupling to transition from 4" connection to 6"
venting before first elbow.
Boiler supply
Boiler return
Figure 18 Direct vent combustion air intakeFigure 19 Combustion air intake - side view
33
3.5.8 Direct vent combustion air intake piping
Combustion air from outdoors
Flue gas exhaust to outdoors
Boiler supply connection at rear of boiler
Boiler return connection at rear of boiler
Figure 20 Rear view - combustion air intake
Notes
When installing air intake piping, ensure that a “trap” is not formed in the piping
causing a build-up of water and blockage of intake air. Such blockages will cause a
boiler safety shut-down.
Filters require checking and cleaning or replacing on a regular schedule based on
the severity of the problem.
34
Section: Installation
EX 700, EX 850
Note
Unused intake travel cannot be added to the exhaust. Unequal intake and exhaust piping is
allowed.
Warning
When using indoor air options, supply adequate combustion air to the boiler room according to
the requirements of all applicable codes.
35
3.5.9 Indoor air combustion air intake
Intake Pipe SizeMaximum Equivalent Length
Sched.40; Rigid PPs
6" PVC/CPVC / Rigid PPs/SS120' each side
90° vent elbowallow 5' equivalent
45° elbowallow 3' equivalent
PPs 87-90° elbowsuse 5' equivalent
Table 7 Maximum intake pipe venting length for EX 700, 850
For the inlet air – 6" Schedule 40 PVC, CPVC, ABS, PPs or SS piping of any type is permitted.
Ensure that adequate separation is maintained between the air intake inlet and the vent terminal. Refer to
the vent terminal configuration drawings in the Vent Termination section above.
Use support for intake piping, particularly for horizontal runs (follow local codes).
3.5.9 Indoor air combustion air intake
An “Indoor Combustion Air installation” can be described as air for combustion that is taken from the air
surrounding the boiler.
Flue gas exhaust to outdoors
Combustion air from boiler room. For indoor air installation, check air intake and boiler room
combustion air opening(s) to ensure they are clear of obstructions.
Figure 21 Indoor combustion air intake
36
Section: Installation
To support combustion, an ample air supply is required. This may require direct openings in the boiler
room to the outside. If the boiler is not in a room adjacent to an outside wall, air may be ducted from
outside wall openings.
Provisions for combustion and ventilation air must be made as follows:
in the USA, in accordance with the National Fuel Gas Code, ANSI Z223.1 (latest edition), or
applicable provisions of the local building codes
in Canada, in compliance with B149.1 (latest edition).
3.5.10 Combustion air filtration system
A built-in combustion air filter system is supplied with the boiler, and is located at the top of the unit. The
boilers use a 10" x 10" x 1" (MERV 8) filter.
End users will need to be instructed on how to maintain the filter in the boiler.
37
3.6 Installing a condensate trap
For instructions on how to replace the filter, see Replacing the air filter on
page 76.
Figure 22 Filter door - top view of boiler
3.6 Installing a condensate trap
IBC’s specified vent configuration promotes the safe drainage of moisture from the boiler and exhaust
venting without flowing liquids back through the heat exchanger (as done by some other condensing
boilers).
Reliable system operation requires:
1. Proper design and installation of exhaust
venting to allow condensate to run back to the
drain/trap.
Installing a condensate neutralizer on page 39.
2. Acid neutralization as appropriate.
To achieve these:
Allow a minimum ¼" per foot slope back to the
vent connection, with appropriate hangers to
maintain that gradient. For PPs venting, follow
the manufacturer's requirements. This will
ensure proper drainage and prevent
condensate from clogging.
Ensure the supplied trap is correctly installed
and filled with water.
When required, add (and maintain in good
condition) a neutralization tank. For information
on installing a condensate neutralizer, see
The condensate trap must be installed on the drain connection at the base of the boiler. The condensate
1.
Slide the union nut onto the elbow. The union
nut must include an embedded O-ring. Ensure
that the O-ring seal is in place on the heat
exchanger's stainless steel outlet tube.
2.
Attach the elbow and union nut firmly
to the boiler's outlet tube, making
sure that you rotate the elbow
sideways.
3.
Fill the condensate trap with water and insert
the trap into the hole of the metal plate.
4.
Rotate the elbow, and tighten the union
nut, so that the elbow and condensate
trap are secured. Ensure the union nut
O-ring is included. Check for leaks.
38
Section: Installation
drain must be piped to within 1" of a drain or connected to a condensate pump. The drainage line must
slope down to the drain at a pitch of ¼" per foot so condensate runs towards the drain.
Warning
Fill the trap with water before initially firing the boiler to prevent exhaust fumes from entering the
room. Never operate the boiler unless the trap is filled with water. Failure to comply will result in
severe personal injury or death.
3.7 Installing a condensate neutralizer
Warning
After installing a condensate neutralization package, the pH of the condensate discharge must be
measured on a regular schedule to ensure the neutralizing agent is active and effective.
Flue gas exhaust (connection at rear of boiler): condensate, and potentially rain water, flow back from
the venting system.
39
3.7 Installing a condensate neutralizer
If discharging condensate into building drain piping materials that are subject to corrosion, use a
neutralization package.
Figure 23 Condensate neutralization tank
Air intake piping: Warning - Risk of damage to appliance. Ensure rain water is prevented from
entering.
Free flow of condensate from venting systems and the pressure vessel must be maintained at all
times. Trap and condensate drain piping must be accessible to allow regular inspection and cleaning.
Condensate water line: Warning - Risk of damage to appliance. All condensate discharge lines,
including neutralization tank inlet, must be at a lower elevation than the condensate water line of the
appliance.
Condensate neutralizer: Drain materials subject to corrosion must be protected by acid neutralization.
Warning - Risk of injury. Tank fluid can be highly acidic. Do not use hands to stir material. Refer to the
neutralization instructions of the manufacturer. Access to the discharge, before the drain, is necessary
for proper maintenance in order to check the effectiveness of the neutralizing agent. A simple pH test
should be performed annually to ensure neutralizing agent is still effective. If the pH falls below 6.5
the neutralizing material should be replaced. The agent (limestone chips with a minimum calcium
carbonate content of 85%) can be purchased from a local supplier.
1" FPT inlet and outlet. Unions for ease of maintenance (ships with shown model NT-25, IBC part 180-
048).
To drain. Confirm slope. Slope the condensate hose and drain piping toward the drain and secure to
prevent accidental dis-assembly.
Danger
The water in the condensate neutralizer can cause severe burns to the skin. Wear protective
gloves and eye wear when servicing the condensate neutralizer.
40
Section: Installation
3.8 Water Piping
Warning
Water quality has a significant impact on the lifetime and performance of a boiler's heat
exchanger.
Improperly prepared water in a heating circuit may cause damage to the heat exchanger through
fouling or corrosion. Repeated or uncontrolled water fills will increase the potential for damage.
High levels of dissolved solids or minerals may precipitate out of the fluid onto the hottest part of
the heat exchanger, impairing heat transfer and resulting in overheating and premature failure.
The amount of solids that may form on the heat exchanger will depend on the degree of hardness
and the total water volume in the system. A high water volume system with a low hardness count
may cause as much damage as a system with less volume and higher hardness, so it is
recommended to treat water so as to remove all dissolved solids. Other water chemistry allowable
limits are as follows:
Acidity pH is to be between 6.6 and 8.5
Chloride is to be less than 125 mg/l
Iron is to be less than 0.3 mg/l
Cu less than 0.1 mg/l
Conductivity is to be less than 400μS/cm (at 77°F [25°C])
Hardness is to be 7 grains per gallon or less / 120 ppm or less
Important: Ensure that these limits are acceptable for the other water-side components in the
system.
Boiler Head Loss - EX 700, 850
Flow rate (gpm)2030405060708090100
Head @ flow (ft)2.62.93.23.74.24.85.56.47.2
41
3.8 Water Piping
Table 8 Boiler Head Loss - EX 700, 850
Ensure that the pump is rated for the design circulating water temperatures; some pumps have a minimum
water temperature rating above the low temperature potential of the boiler. Following installation, confirm the
actual performance by measuring Δ°T (under high and low flow conditions) after establishing the correct
firing rate.
To use legacy heat, we recommend water flow after burner shutdown. This is significant due to the mass
Warning
Do not use automotive-type ethylene or other types of automotive glycol antifreeze, or
undiluted antifreeze of any kind. This may result in severe boiler damage. Installers must
ensure that glycol solutions are formulated to inhibit corrosion in hydronic heating systems of
mixed materials. Improper mixtures and chemical additives may cause damage to ferrous and
non-ferrous components as well as non-metallic, wetted components, normally found in
hydronic systems. Ethylene glycol is toxic, and may be prohibited for use by codes applicable
to your installation location. For environmental and toxicity reasons, IBC recommends only
using non-toxic propylene glycol.
42
Section: Installation
of the heat exchanger plus its internal water volume. Default load settings will run the boiler’s primary
pump for up to 5 minutes (300 seconds) after burner shutdown. Secondary pumps can be set to run up to
15 minutes after burner shutdown (for the last calling load). As shipped, the default settings will run the
Load pump for 5 minutes to place the legacy heat where it is useful. Any secondary pump can be set to
run for 0 – 900 seconds in the heat purge mode. Guard against deadheading pumps when all zone
valves are closed by setting the load Pump Post Purge (sec) to '0'.
The primary pump must be under the control of the boiler to allow pump purge after burner shut-down.
Installers must conform to the piping design configurations provided to simplify the control application,
promote good loads and flow management.
Propylene glycol usage
Propylene glycol solution is commonly used in a closed loop where freeze protection is required. Its
density is lower than that of water, resulting in lower thermal performance at a given flow and pressure.
Generally, a 50%:50% solution of propylene glycol and water requires an increased system circulation
rate (gpm up 10%), and system head (up 20%) to provide performance equivalent to straight water.
These boilers are designed for use within a closed loop, forced circulation, low pressure system. A 50 psi
pressure relief valve (¾" NPT inlet, 1" NPT outlet) is supplied for field installation in the relief valve fitting
on top of the boiler. An optional relief valve, with a rating of up to 150 psi, can be used where required on
closed loop systems. Relief valve discharge piping must terminate between 6" (15 cm) and 12" (30 cm)
above the floor or per local code.
Warning
During operation, the relief valve may discharge large amounts of steam and/or hot water. To
reduce the potential for bodily injury and property damage, install a discharge line that:
Is connected from the valve outlet with no intervening valve and directed downward to a
safe point of discharge.
Allows complete drainage of both the valve and the discharge line.
Is independently supported and securely anchored, so as to avoid applied stress on the
valve.
Is as short and straight as possible.
Terminates freely to atmosphere where any discharge will be clearly visible and is at no
risk of freezing. terminates with a plain end which is not threaded.
Is constructed of a material suitable for exposure to temperatures of 375° F or greater.
Is, over its entire length, of a pipe size equal to or greater than that of the valve outlet (1"
NPT).
Do not cap, plug or obstruct the discharge pipe outlet.
3.8.1 General piping best practices
Caution
Contact local water purveyors about the suitability of the supply for use in hydronic heating
systems.
If unsure about water quality, request testing and assessment (and treatment, if required) from a
local water treatment expert.
Alternatively, water or hydronic fluid of known quality can be brought to the site.
43
3.8.1 General piping best practices
Primary/secondary piping, or the use of a hydraulic separator (such as the Caleffi 549 SEP4™ 4-in-1
Magnetic Hydraulic Separators) is recommended for maximum flexibility in multi-load applications. Piping
loads in parallel is also encouraged in systems that only have two loads, or when loads are operating
simultaneously. The extremely low pressure drop through the heat exchanger of the EX series affords more
flexible options unavailable in other designs.
3.8.2 System piping
Warning
Close the fill valve after any addition of water to the system, to reduce risk of water
escapement.
Example: In these EX models, the minimum flow rate required through the heat exchanger is 18
or 21 gpm (depending on model) and a maximum of 100 gpm is allowed. Primary/Secondary
piping ensures adequate flow and de-couples Δ°T issues (boiler vs. distribution). Aim for a 20°
to 30° F Δ°T across the heat exchanger at high fire (there is a boiler protection throttle fence
limiting the Δ°T to 80°F).
44
Section: Installation
System piping is connected to the boiler using 2½" NPT-Male threaded fittings. To simplify servicing, we
recommend using unions or flanged fittings, gate or ball valves at the boilers supply and return water
connections. You must install un-insulated hot water pipes with a minimum ¼" clearance from
combustible materials.
Fluid fill is most often accomplished by using a boiler regulator & fill valve set at 12 psig or more, with
the appropriate backflow prevention device as required by local code. This is acceptable in areas
where municipal water or well water has been treated and filtered to remove excessive minerals and
sediment, and water chemistry is known to be suitable for closed loop hydronic systems. In areas where
water quality is in question, or when chemical treatment or glycol is required, other options should be
considered. Follow the applicable codes and good piping practice.
There are a number of boiler feed and pressurization devices on the market today that may be a better
choice than a raw water fill from the mains. When regular maintenance requires relief valve blow-off, the
discharge may be directed back into the pressurization unit for recycling of boiler fluid and chemicals
back into the system. In buildings that may be unoccupied for long periods of time, pressurization units
are useful to prevent flood damage should leakage occur from any component in the system. An
additional benefit is that backflow prevention devices are not required when using these devices.
Do not place any water connections above the boiler; leaks can damage the fan and controls. If
needed, create a shield over the top of the cover, but allow clearance for airflow and service access.
For best results, use a Primary/Secondary piping system, with a pumped boiler loop using 2½" piping.
Refer to Table 8 for boiler head loss information.
Check valves or thermal traps should be used to isolate both the supply and return piping for each load
- to avoid thermal siphoning and reverse flow.
To ensure adequate water flow through the boiler under high-head / single zone space heating
conditions, a pressure activated bypass or other means of bypass must be used on any load where the
flow rate might drop below minimum requirements (18 or 21 gpm - depending on model).
For further information and details, consult our Concept Drawings – which provide detail on specific single
Note
The piping drawings in this manual are simple schematic guides to a successful installation.
There are many necessary components not shown, and details such as thermal traps are left
out so the drawings have greater clarity. We require that our boilers be installed by licensed
and experienced trades people who are familiar with the applicable local and national codes.
System design is to be completed by an experienced hydronic designer or Engineer. It is
necessary to carefully read and follow these installation instructions along with the application
drawing that fits your system.
Low water cut-off (LWCO): the IBC EX series comes factory-equipped with an internally mounted
Certified Low Water Cut-Off. Sometimes an external device is required by local jurisdiction. These
devices have specific installation requirements not illustrated here. Consult the IBC factory or the
LWCO manufacturer for proper application of these devices.
Pressure relief valve (ships with boiler): no isolation valve permitted between boiler and relief valve.
Tridicator / external pressure and temperature gauge (ships with boiler).
45
3.8.2 System piping
and multiple boiler applications “Piping”, “Wiring” and “Settings”. (available at www.ibcboiler.com or from
your IBC Representative).
Optional external water high limit (manual reset). The IBC EX series comes factory-equipped with
an internally mounted manual reset mechanical water temperature high limit. It can be fitted with an
external manual reset mechanical water temperature high limit if required by local jurisdiction.
To supply manifold
From return manifold
Optional flow switch: follow manufacturer’s instructions. Typical requirements include installing on a
horizontal run, with at least five (5) pipe diameters of straight piping both upstream and downstream
of flow switch, and ensuring proper paddle engagement for the piping size.
Integrated boiler drain
Figure 24 Trim for multiple boiler installations
Pressure relief valve (shipped with boiler): no isolation valve is permitted between the boiler and
relief valve.
Tridicator or external pressure and temperature gauge (shipped with boiler).
46
Section: Installation
Hydraulic separator (low-loss header) provides primary/secondary hydraulic separation, a
microbubble air eliminator and a dirt separator. Air eliminator is installed at the most effective
point, where the fluid is at the highest temperature and lowest pressure.
Secondary pumps to multiple loads or zones. All receive identical temperatures. Note integrated
check valves.
Return lines from loads.
Expansion tank connection (point of no pressure change)should be on the suction side of the
circulator.
Primary pump or boiler circulator into connection at rear of boiler.
Fill station with isolation valve closed, or fill tank.
Figure 25 Primary/Secondary piping concept with hydraulic separator
Pressure relief valve (field-supplied): no isolation valve is permitted between the boiler and relief
valve.
Tridicator or external pressure and temperature gauge (field-supplied).
Microbubble air eliminators are best installed where the fluid is at the highest temperature and
lowest pressure.
Expansion tank connection (point of no pressure change) should be on the suction side of the
circulator.
47
3.8.2 System piping
Primary pump or boiler circulator.
Closely-spaced tees to or from load 1.
Closely-spaced tees to or from load 2.
Fill station with isolation valve closed, or fill tank.
Dirt separator recommended.
Figure 26 Boiler trim options - single boiler
48
Section: Installation
Closely-spaced tees: To avoid induced flow, install each set of tees with straight piping a minimum
of 8 pipe diameters upstream and 4 pipe diameters downstream. Avoid using elbow or other
component that may create turbulent flow. Position tees as close together as possible (maximum 4
pipe diameters apart) and ensure that there are no restrictions between the fittings that would result
in a pressure drop.
Heat migration: On secondary loops that extend vertically to a load that is above the primary loop,
steps must be taken such as fabricating a thermal trap in the return piping - minimum 18" (46 cm)
drop - to prevent thermal siphoning and heat migration to the load when there is no demand for heat
to that loop. Alternatively, use check valves on both supply and return of secondary piping.
Figure 27 Important Primary/Secondary piping details with closely-spaced tees
49
3.8.2 System piping
DHW indirect tank
Air handler
Low temperature radiant protected by a mixing valve for simultaneous heating during higher
temperature air handler operation. Boiler can return to lower supply temperature when radiant
alone is operating.
Figure 28 Primary/Secondary piping concept with simultaneous heating calls
50
Section: Installation
DHW indirect tank
Air handler
Check valves (may be integral to pumps - not shown)
51
3.8.2 System piping
Figure 29 Two pump, two load - parallel piping concept
The boilers can supply multiple heating loads with compatible supply temperature requirements.
Check valve (typical of each boiler - may be integral to pump).
Tridicator (shipped with boiler) typical of each boiler.
Pressure relief valve (shipped with boiler) typical of each boiler.
Boiler pump into rear connection (typical of each boiler).
Low-loss header / hydraulic separator (shown) or closely-spaced tees 'bridge' to load piping.
52
Section: Installation
Always ensure that loads sensitive to high temperatures are protected using means such as mixing
valves.
Figure 30 Multiple boiler piping
Pressure relief valve (shipped with boiler) typical of each boiler.
Tridicator (shipped with boiler) typical of each boiler.
Check valve (typical of each boiler)
Boiler pump into rear connection (typical of each boiler)
Low-loss header / hydraulic separator (shown) or closely-spaced tees 'bridge' to load piping
Check valve for opt-out circuit.
Opt-out pump into rear side (opt-out boiler(s) only)
Opt-out load piping in reverse-return for balanced flows
Figure 31 Multiple boiler opt-out piping
53
3.8.2 System piping
3.9 Gas piping
Note
Due to the precision of modern modulating boilers it is important to pay special attention to
gas pressure regulation.
Important: Check gas supply pressure to each boiler with a manometer or other high-quality
precision measuring device. Pressure should be monitored before firing the boiler, during
operation throughout the boiler's full modulation range, and after the call when the regulator is
in a "lock-up" condition.
Pay special attention to retrofit situations where existing regulators may have an over-sized
orifice and/or worn seats, causing pressure “creep” and high lock-up pressures.
A high quality regulator will maintain constant pressure above the boiler’s minimum
specification at all firing rates, and will not exceed the boiler’s maximum pressure rating when
locked-up with no load.
54
Section: Installation
3.9.1 Gas pressure
The boilers require a minimum inlet gas supply pressure of 4.0" w.c. for natural gas or propane during
high fire operation. For either fuel, the inlet pressure shall be no greater than 14.0" w.c. Confirm this
pressure range is available with your local gas supplier.
The inlet gas connection to the boiler is 1" NPT (female).
The high gas pressure switch setpoint is set at 14" wc and the low gas pressure setpoint is set at 3.5" wc.
To locate the switches on the boiler, see EX 700, 850 - gas valve and fan components.
Adequate gas supply piping must be installed with no smaller than 1¼" Schedule 40 (e.g. Iron Pipe Size
(IPS) and using a 1" w.c. pressure drop, in accordance with the following chart.
Maximum Gas Pipe Length (ft)
Model1¼" IPS1½" IPS2" IPS2½" IPS
EX 700 (Natural Gas)50'100'350'800'
EX 700 (Propane)150'300'900'2000'
EX 850 (Natural Gas)40'80'250'600'
EX 850 (Propane)100'200'700'1600'
Table 9 Maximum Gas Pipe Length (ft)
55
3.10 Electrical connections
Gas piping must have a sediment trap ahead of the boiler’s gas valve. A manual shutoff valve must be
located outside the boiler, in accordance with local codes or standards. All threaded joints in gas piping
should be made with an approved piping compound resistant to the action of natural gas or propane. Use
proper hangers to support gas supply piping as per applicable codes.
The boiler must be disconnected or otherwise isolated from the gas supply
during any pressure testing of the system at test pressures in excess of ½
psig. Dissipate test pressure prior to reconnecting. The boiler and its gas
piping shall be leak tested before being placed into operation.
The gas valve is provided with pressure taps to measure gas pressure
upstream (supply pressure) and downstream (manifold pressure) of the gas
valve (see Figure 2 on page 1). Note that manifold pressure varies slightly in
accordance with firing rates with the modulating series boilers, but will always
be close to 0" wc. An adapter fitting is supplied with the boiler.
Figure 32 Typical gas piping
3.10 Electrical connections
All electrical wiring to the boiler (including grounding) must conform to local
electrical codes and/or to the National Electrical Code, ANS/NFPA No. 70 –
latest edition, or to the Canadian Electrical Code, C22.1 - Part 1.
3.10.1 Power quality and electrical protection
In areas of unreliable power, appropriate surge protectors and or power conditioning equipment should be
installed in power supply wiring circuits.
Note
The IBC boiler (like any modern appliance that contains electronic equipment) must have a
“clean” power supply, and is susceptible to power surges and spikes, lightning strikes and
other forms of severe electrical “noise”. Power conditioning equipment (surge protectors,
APC or UPS devices) may be required in areas where power quality is suspect.
3.10.2 120VAC line-voltage hook-up
Caution
The on-board controller load pump relays are protected with 5 Amp fuses. The maximum
recommended load on each fuse is 4 Amps (80% of rating). The maximum combined pump
load is 10 Amps. Isolation relays or contactors must be used if the loads exceed these
maximums.
56
Section: Installation
Line-voltage wiring is done within the field-wiring box (see Wiring diagrams on page 93). Connect the
boiler to the grid power using a separate, fused circuit and on/off switch within sight of the boiler. Use 14gauge wire in BX cable or conduit properly anchored to the boiler case for mains supply and pump
circuits.
Figure 33 Line voltage load pump terminals
Connect a 120VAC / 15 amp supply to the “AC IN” tagged leads in the wiring box.
3.10.2.1 Load pumps
The 120VAC power supply to the load pumps (P/V1, P/V2, P/V3, and P/V4) is factory installed and
connected to P/V-L and P/V-N for your convenience. If you use the P/V relay connections for zone valves,
you need to remove and cap off the 120VAC connections at P/V-L and P/V-N. The 24VAC can then be
applied using an external transformer to supply power to zone valves. The upper 4 pairs of contacts on
the connector strip are then powered to manage up to 4 load pumps – the top pair for Load 1, the second
pair for #2 etc. Once the controller is programmed for the respective loads, the boiler manages all the
loads without need of further relays (for loads up to ⅓ HP; for more – use a protective relay).
3.10.2.2 Boiler pump
Power in - black wire.
To boiler - yellow wire.
57
3.10.2 120VAC line-voltage hook-up
The boiler (primary) pump is powered by the yellow wire from the pair labeled "Boiler Pump". Wire the
pump's neutral to the white wire labeled "AC In". Do not attempt to connect the boiler pump to the pump/zone
valve terminal block along the controller’s right edge as this is reserved for the secondary pumps and/or zone
valves only.
Figure 34 Electrical box with boiler pump relay - black and yellow wires
If the total boiler amperage drawn is less than 12 amps and the boiler pump is 120V, you can connect the
black wire from the relay to the line voltage mains supplied to the boiler. For 120 volt boiler pumps, the black
wire can be connected to the line voltage mains and the yellow wire connected to boiler pump. For 208/240
volt boiler pumps, the black wire can be one leg of the 208/240 voltage mains and the yellow wire connected
to the boiler pump. The boiler pump relay may require connection to a second electrical circuit (amperage
greater than 4 amps). The boiler pump relay is rated for a maximum amperage load of ¾ horsepower. A
disconnect switch should be installed to isolate the boiler pump and the boiler pump relay power supply.
Pumps can be switched on/off using the touchscreen controller, so there is no need for temporary pump
58
Section: Installation
wiring during system filling / air purging. If pumps are hard-wired to the panel during the system fill/purge
phase, re-wire the boiler pump to the primary pump leads inside the wiring box so the primary pump
purge function is active.
In a new construction application, use a construction thermostat, or jumper with an in-line on/off switch –
for on/off management of the boiler. Do not just turn off power from the unit, or its moisture management
routine will be interrupted (fan turns at ultra low rpm for 90 minutes after burner shutdown). Treat it like a
computer, where you do not just pull the plug when done. If a "low airflow / check vent" error signal
shows, check for (and remove) any water in the clear vinyl air reference tubes. This has been seen
occasionally at construction sites where the boiler has been repeatedly de-powered wet.
The combined current of all load pumps connected through the on-board pump relays should not exceed
10 amps. The control circuit board is protected using on-board field replaceable fuses. Each pump is
fused with a separate 5 Amp fuse. The Alarm contact is fused with a 5 Amp fuse and the 24VAC boiler
control circuit is protected with a 2 Amp fuse.
3.10.2.3 Variable speed boiler pumps
Variable speed boiler pumps are for connecting and managing speed in pumps that accept 0-10VDC on
4-20 mA input signal.
Figure 35 Electrical box with new variable speed connection
3.10.3 Other wiring
Danger
Do not connect sensors to “Therm” terminals. Overheating components can result in serious
personal injury and/or property damage.
Note
Sensors connected to any sensor input contacts must be of the NTC Thermister type with a
resistance of 10,000 ohms at 77°F (25°C) and β = 3892. We do not recommend using 3rd party
supplied sensors. Compatible water temperature sensors and outdoor sensors can be
supplied by your IBC distributor.
59
3.10.3 Other wiring
Other optional low voltage connections to the control board include:
Two auxiliary Interlocks - for external safety devices as may be required by some jurisdictions, such
as an external low-water cutoff.
Contacts for indoor and outdoor temperatures sensors associated with reset heating. A 10K ohm
thermister (resistor dependent on temperature) for outdoor reset sensing is supplied with the boiler
for improved comfort and combustion efficiency.
One pair for a DHW tank sensor. Connect to "DHW S" (not the respective Therm. 1,2,3,4 location)
and the boiler automatically detects and calls a smart DHW routine.
One pair of contacts for remote secondary loop temperature control.
One pair (marked BoilerNet) for network connection – this is used for connecting multiple IBC
modulating units for autonomous staging.
The bottom pair of contacts (labeled 'External Control') receives a 0-10VDC (default) or 4-20 mA
signal from an external boiler controller for direct throttle control. The boiler’s own sensors act as
high limits only. The user must enter maximum and minimum boiler supply temperatures.
3.10.4 Thermostat / sensor wiring
Each of the four loads has dry contacts for thermostats as marked on the lower connector strip (e.g., “Therm
1”). Gang lines from a multiple-zoned load (e.g., off the end-switches for each radiant floor zone) present a
common thermostat signal to the controller. Ensure that there are no disturbing influences on the call-forheat lines - for example, that there are no coils to switch an air handler motor. Most power stealing
thermostats can be connected directly to the Therm terminals. Consult the Controller manual for more
detailed instructions.
3.10.5 Thermostat heat anticipator
60
Section: Installation
IBC “Therm” contacts draw no power, so an anticipator setting for the thermostat is not applicable with
the EX modulating series boilers. For a heat load where zone valves are used to manage
thermostatically controlled zones, each room's thermostat heat anticipator should be adjusted to the
current draw of its associated zone valve.
Figure 36 Electric wiring connections
61
4.0 About the boiler controller
Note
Use only a stylus or a clean finger to interact with the touchscreen. Using sharp or metallic objects
will cause damage.
This boiler is equipped with a touchscreen controller for programming the boiler. For detailed instructions on
using the controller, see the Touchscreen Controller manual.
The controller is equipped to provide:
Control of up to 5 pumps – 1 boiler pump + 4 separate load pumps
Outdoor Reset control
Set Point temperature regulation
Domestic Hot Water (DHW)
External control via 0-10VDC or 4-20mA signaling
Manual control of firing rate for gas valve calibration
Alarm dry contacts
Zoning - simultaneous operation of up to four pumps
Load Combining – simultaneous operation of two similar water temperature loads
Programmable setback / override schedule
The control can manage or operate in a network of up to 24 IBC boilers without additional controller.
Some of the new features available in the touchscreen control include:
Express Setup Menu for simple, quick programming
Portal connectivity for remote monitoring and programming
Superior warning messages while setting up the control
Advanced Error messages with visual display on the Home Screen
Internet/LAN connectivity
BACnet (with activation)
4.1 Controller
When the boiler is first energized, the controller will go through a power up sequence that will take
approximately 90 seconds. During this time the controller is completing a self- diagnostic and loading all
previous settings. In the event of a power interruption the boiler will automatically resume operation when
power is restored with all the previously stored values. The controller provides overall management of the
boiler operations including:
Burner operation, safety management systems, Call for Heat
management and Load Priority
Real time boiler data
Temperature and throttle operation
Maintenance of operational and error service logs
2-way communication between other IBC boilers and controls
Internet connection and communication
Operational and historical data may be accessed at any time using the
System Status and Load Profiles sections of the control. Error logs are
available in the Diagnostics section and the controller is capable of
recording any or all errors since original power-up complete with the date and time of the error.
4.2 Control interface
The control interface is provided through a 2¼ x 4 inch, color touchscreen display. The touchscreen
responds to a light finger touch on the screen. You can also use a stylus, pencil, or similar device to
operate the touch controls. Do not use a sharp or metallic object such as a screw driver to operate the
control as it could damage the touchscreen.
The controller display is divided into two areas, the screen active area and the boiler status bar. All
screens have an active area consisting of the screen title bar at the top and a border surrounding the
active area. At the bottom of the display there is space reserved for the boiler status bar.
Prior to any interaction with the touchscreen, the display shows the Home screen details of the current
boiler status. If the controller has been left on the Home screen long enough (user adjustable, 10 minutes
by default) the display will be dimmed to save power.
The control will automatically return to the home screen if left unattended. The screens will step back one
screen at a time in 10 minute increments if the touchscreen has not been touched. The pop-up windows
will also step back automatically in 2 minute intervals.
The boiler status bar indicates if the boiler is in a normal, warning or alarm state. When no warning or
alarm state is present, the bar will be green and the time will be displayed inside the green area. The bar
can also be yellow or red corresponding a warning or alarm state. Text inside the bar will indicate the
specific warning or alarm present. If more than one alarm is present the text display will slowly change,
rotating though whatever alarms that are present.
63
5.0 Before operating the boiler
Danger
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other
appliance. If you smell gas vapors, do not try to operate any appliance - do not touch any
electrical switch or use any phone in the building. Immediately, call the gas supplier from a phone
located remotely. Follow the gas supplier’s instructions, or if the supplier is unavailable, contact
the fire department.
Do not use this boiler if any part has been under water. Immediately call a qualified service
technician to inspect the boiler and to replace any part of the control system and any gas control
that has been under water.
Should overheating occur or the gas supply fails to shut off, do not turn off or disconnect the
electrical supply to the pump. Instead shut off the gas supply at a location external to the
appliance.
Checking electrical conditionsCheck
Check all line voltage electrical connections to ensure all connections are correct and tight.
□
Check thermostat connections.
□
Thermostat in a suitable location.
□
Checking piping connectionsCheck
Ensure venting system is complete and seal tested.
Confirm any common venting system at the installation site is isolated and independent of the EX
boiler.
Also confirm that any holes left from the removal of a previous boiler have been sealed, and that
any resizing of the old flue has been done.
□
5.1 Important pre-ignition checks
Once installation of the unit is completed, and before operating the unit, it is important to review the following
checklist of precautions:
5.1.1 Checklist for electrical conditions, ducting and water
connections
Checking piping connectionsCheck
Check that the water piping system is fully flushed and charged, and that all air has been
discharged through loosened bleed caps.
Note it is possible to switch all pumps on/off from the touchscreen – without a call for heat. This
simplifies system filling and air bleeding (go to Installer Setup, System Settings, Site Settings,
change Manual Pump Purge to "ON". When complete, return to "OFF", or this will automatically
occur with a call for heat). Use a minimum water pressure of 12 psig. And confirm that the pressure
relief valve is installed and safely drained.
□
Check to see that adequate gas pressure is present at the inlet gas supply test port.
Open the test port by turning its center-screw one full turn counterclockwise, using a small (1/8" or 3
mm) flat screwdriver.
Connect a manometer and open the gas control valve. Requirements are minimum 4" w.c and
maximum 14" w.c.
Check that there are no gas leaks.
□
All connections are pressure tested and leak free.
□
All piping flushed to ensure all air is removed.
□
Check valve is installed and the external pump is flowing in the correct direction.
□
Checking ducting connectionsCheck
All connections are pressure tested and leak free.
□
All duct work is sized correctly and joints are sealed.
□
All supply air dampers and registers are opened.
□
Powering on the boilerCheck
Perform a final check of electrical wiring, and provide power to the boiler to initialize operation.
Warning
Fill the condensate trap with water before you first fire the boiler to prevent exhaust
fumes from entering the room. Never operate the boiler unless the trap is filled with
water. Failure to comply will result in severe personal injury or death.
□
64
Section: Before operating the boiler
65
6.0 Service and maintenance
Caution
The owner is responsible for general care of the boiler. Improper maintenance of the boiler may
result in a hazardous condition.
Maintenance Required for VentingFrequency Check
Check and replace filter as needed. Site conditions will determine how often the filter
will need to be replaced. For replacement instructions, see Replacing the air filter on
page 76
As needed
□
Inspect system for unusual noises. Call your local heating contractor for service if
needed
As needed
□
Keep vent terminals clear of obstructions (snow, dirt, etc.).As needed
□
Inspection of the boiler is to be performed annually by a qualified service technician.Annually
□
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper
and dangerous operation.
Maintenance RequiredCheck
Remove any obstructions (e.g. leaves, dust, other debris) from vent terminals
□
Check and clean or replace intake air filters or screens as required.
□
Check for holes or leaks in venting. Replace venting as needed.
□
Examine for any signs of moisture caused by sweating intake air pipes; insulate as required.
□
Ensure proper resealing or re-installation of venting on each servicing.
□
Inspection of the boiler is to be performed annually by a qualified service technician.
6.1 Maintenance checklists for manager of unit
Managers of EX series boilers should arrange follow-up inspections and simple maintenance procedures
according to IBC's suggested servicing guidelines below.
6.2 Maintenance checklists for heating contractor
6.2.1 Venting
Maintenance Required for VentingFrequency Check
Check and replace filter as needed. For replacement instructions, see Replacing
the air filter on page 76
Monthly
□
Have your local heating contractor inspect the unit annually.
Annually
□
Inspect system for unusual noises. Call your local heating contractor for service if
needed
As needed
□
Keep vent terminals clear of obstructions (snow, dirt, etc.).As needed
□
Inspection of the boiler is to be performed annually by a qualified service
technician.
Annually
□
Maintenance Required for Condensate TrapFrequency Check
Examine every two months to see if cleaning is necessary (see Maintaining a
condensate trap).
Ensure that the trap has been re-filled completely before firing boiler.
Bi-monthly
□
If condensate neutralization is used, check the pH level of condensate discharge.
Annually
□
Maintenance Required for BurnerFrequency Check
Remove the burner to inspect for extent of fouling (see Replacing the burner on
page 74).
a. Wash the burner from outside with a domestic water pressure, and dry
using compressed air.
b. Evaluate the magnitude of clearing required, and establish a reasonable
burner inspection schedule. Some boiler / locations may call for annual
service, others showing clean burners will only need attention every 2 – 5
years.
c. Reassemble. Visually inspect the burner through sight glass. Ensure the
flame is stable, without excessive fluttering. Normal flame pattern is evenly
distributed over the burner surface.
Annually
□
66
Section: Service and maintenance
6.2.2 Condensate trap
6.2.3 Burner
Maintenance Required for BurnerFrequency Check
If the burner is operating improperly, remove and clean or replace. Use a CO
2
analyzer to determine proper combustion. See Combustion test target ranges -
CO2 / Maximum CO for correct values.
Annually
□
Warning
When removing the burner for inspection or boiler servicing, examine the sealing gaskets and
replace if damaged. Upon re-assembly, test all sealing areas to ensure there is no leakage of
combustible gas/air premix.
6.2.4 Heat exchanger
Maintenance Required for Heat ExchangerFrequency Check
In areas of poor gas quality, there may be a build-up of black plaque (typically sulfur).
Other fouling agents include: airborne dust, debris and volatiles.
With the burner removed, examine the heat exchanger for signs of contamination
and clean if necessary. Refer to instructions in Replacing the burner on page 74 for
access to the combustion chamber and heat exchanger.
Annually
□
Maintenance Required for PumpFrequency Check
Check that the pump is on in normal operation and that the water Δ°T is reasonable
for a given firing rate.
Annually
□
Maintenance Required for Gas PipingFrequency Check
Check for damage or leaks and repair as needed.
Annually
□
Maintenance Required for Boiler ControllerFrequencyCheck
Check that boiler operation is consistent with the steps in the Touchscreen
Boiler Controller Manual.
Annually
□
67
6.2.4 Heat exchanger
6.2.5 Pump
6.2.6 Gas piping
6.2.7 Touchscreen boiler controller
Maintenance Required for Boiler ControllerFrequencyCheck
Check that water temperature targets and setpoint is satisfactory and have
not been adversely amended.
Annually
□
Check the operating history using the boilers Logs menu and Error Logs
menu.
The controller tracks the duty cycle of the boiler in each of the 4 loads
separately. This information can be used to adjust the water temperatures
of each load.
□
If a problem exists with the controller, consult the section Troubleshooting
on page 79.
6.2.8 Water
Checks for Water in the BoilerFrequency Check
Check water pressure and temperature.
There should be no noticeable change if boiler is functioning normally. Check for
any noise in the system.
Annually
□
Check water piping for damage or leaks and repair as needed.
Annually
□
Check the water pressure. Pressure should be stable when the boiler is firing and
the water temperature is rising.
If pressure rises sharply, consider replacement of expansion tank.
Annually
□
Check also for noise at high fire, which may signal water quality problems.Annually
□
Water chemistry shall be of a quality generally accepted as suitable for hydronic
applications.
Annually
□
Ensure any direct “city fill” water connections are left in the closed position to
minimize exposure to leaks and flooding.
Annually
□
Caution
Installers should inquire of local water purveyors as to the suitability of their supply for use in
hydronic heating systems.
If water quality is questionable, a local water treatment expert must be consulted for testing,
assessment and, if required, treatment.
Alternatively, water or hydronic fluid of known quality can be brought to the site.
68
Section: Service and maintenance
6.2.9 Freeze protection
Maintenance to prevent freezingFrequency Check
Check the freeze protection. Use only antifreeze made specifically for hydronic
systems. Inhibited propylene glycol is recommended. Antifreeze volume must be
between 25% and 50% of the total volume of water in the system.
Annually
□
Warning
Do not use automotive-type ethylene or other types of automotive glycol antifreeze, or undiluted
antifreeze of any kind. This may result in severe boiler damage. It is the responsibility of the
Installer to ensure that glycol solutions are formulated to inhibit corrosion in hydronic heating
systems of mixed materials. Improper mixtures and chemical additives may cause damage to
ferrous and non-ferrous components as well as non-metallic, wet components, normally found in
hydronic systems. Ethylene glycol is toxic, and may be prohibited for use by codes applicable to
your installation location. For environmental and toxicity reasons, IBC recommends only using
non-toxic propylene glycol.
Maintenance for Boiler TreatmentFrequency Check
Check consistency of any boiler treatment used, for appropriate mixture. Chemical
inhibitors are consumed over time, lowering their density.
Annually
□
Verify proper operation after servicing.
Annually
□
Caution
Installers should inquire of local water purveyors as to the suitability of their supply for use in
hydronic heating systems.
If water quality is questionable, a local water treatment expert must be consulted for testing,
assessment and, if required, treatment.
Alternatively, water or hydronic fluid of known quality can be brought to the site.
69
6.2.9 Freeze protection
6.2.10 Boiler treatment
6.2.11 Relief valve - maintenance and testing
The relief valve manufacturer requires that under normal operating conditions a “try lever test” must be
performed every two months.
Under severe service conditions, or if corrosion and/or deposits are noticed within the valve body, testing
must be performed more often. A “try lever test” must also be performed at the end of any non-service period.
Maintenance for Relief valveFrequency Check
Test at or near the maximum operating pressure by holding the test lever fully
open for at least 5 seconds to flush the valve seat free of sediment and debris.
Then release the lever and allow the valve to snap shut.
If the lever does not activate, or if there is no sign of discharge, discontinue use of
equipment immediately and contact a licensed contractor or qualified service
personnel.
If the relief valve does not completely seal, and fluid continues to leak from the
discharge pipe - perform the test again to try and flush any debris that may be
lodged in the valve. If repeated tries fail to stop the leakage, contact a licensed
contractor or qualified service personnel to replace the valve.
While performing a “try lever test”, a quantity of heat transfer fluid will be
discharged from the piping system and the system pressure will drop. This fluid
must be replaced. To refill and pressurize your system, we recommend using a
system pressurization unit such as an Axiom Industries model SF100 series.
Capture the discharged fluid in a container and recycle it by returning it to the
system feeder unit. This is particularly important when your system contains
treatment chemicals or glycol solutions. If the system employs plain water, the
boiler auto fill valve must be turned on in order to recharge the lost fluid.
Annually
□
6.3 Replacing the fan, gas valve, and burner
70
Section: Service and maintenance
Fan
Mixing device
High pressure switch
Inlet gas pressure test port (location of)
Low pressure switch
Low fire adjustment (zero-offset)
High fire adjustment (on the side)
Manifold gas pressure test port
Shutoff valve
6.3.1 Replacing the fan
71
6.3.1 Replacing the fan
Figure 37 EX 700, 850 - gas valve and fan components
1. Turn off the electric power and gas supply to the boiler.
2. Ensure the boiler cools down to the surrounding temperature. Do not drain the boiler unless
freezing conditions are expected during this procedure.
3. Remove the front cover, and then remove the boiler's top panel by removing the Torx screws on the
top panel of the boiler.
A ladder or step may be required to have a clear vertical view of the work area. Do not attempt to
reach from the front without a clear view, as damage to connectors, screws or refractory may occur.
4. Unplug both the upper and lower electrical connectors from the fan.
5. Position the harnesses out of the way of the heat exchanger lid.
Remove the four 5/16" hex head bolts that attach the gas valve to the mixing device. (Seeon
6.
Figure 38 .) These bolts should be first loosened slightly in a cross sequence to prevent deformation
of the mating parts.
7. Carefully move aside the gas valve assembly, and retain the O-ring for re-installing.
8. Remove the four (4) ¼" hex bolts that connect the mixing device to the air filter box. The gasket
should remain attached to the air filter box.
9. Remove the four (4) hex bolts that attach the fan to the heat exchanger lid. An open-ended
Unscrew four (4) bolts to separate the gas valve from the mixing device. Keep gasket and bolts
for re-assembly.
Location of high gas pressure switch.
Gas valve inlet: Unscrew the four (4) bolts of the flange to separate gas valve from the gas
valve. Keep gasket and bolts for re-assembly.
Low gas pressure switch.
72
Section: Service and maintenance
wrench or socket is required.
10. With the mixing device still attached, remove the fan by pulling straight up ensuring that no wires
are caught and that the gas line remains in place. Place the removed components in a clean,
dry area.
11. Note how the mixing device is positioned on the fan before removing it from the fan. Remove the
six (6) 6 mm screws to separate the mixing device from the fan.
12. Attach the mixing device to the new fan.
13. Re-install the components in reverse order of the steps above.
6.3.2 Replacing the gas valve
Gas valve electrical connector
Gas valve outlet: Unscrew the four (4) bolts of the flange to separate gas valve from the gas
valve. Keep gasket and bolts for re-assembly.
Figure 38 Accessing the gas valve - EX 700, 850
73
6.3.2 Replacing the gas valve
1. Turn off the electric power and gas supply to the boiler.
2. Ensure that the boiler cools down to the surrounding temperature. Do not drain the boiler unless
freezing conditions are expected during this procedure.
3. Remove the front cover, and then remove the boiler's top panel by removing the four Torx head
screws on the top panel of the boiler.
4. A ladder or step may be required to have a clear vertical view of the work area. Do not attempt to
reach from the front without a clear view, as damage to connectors, screws or refractory may occur.
5. Remove the screw and pull off the electrical connector from the gas valve, and disconnect the three-
(3) wire Molex plug from the the gas pressure switches.
6. Unscrew the four (4) bolts of the flange to separate the gas valve inlet from the gas line. Keep gasket
and bolts for re-assembly. (See lon Figure 38 .)
7. Unscrew the four (4) bolts of the flange to separate the gas valve outlet from the gas line. Keep gasket
and bolts for re-assembly. (See o on Figure 38 .)
8. Re-install the components in reverse order of the steps above.
9. Tune the gas valve. For instructions, see Adjusting the gas valve on page 1.
6.3.3 Replacing the burner
Warning
The IBC heat exchanger has a small amount of combustion chamber insulation (refractory),
which contains ceramic fibers.
When exposed to extremely high temperatures, the ceramic fibers that contain crystalline
silica can be converted into cristobalite, classified as a possible human carcinogen.
Avoid disturbing or damaging the refractory. If damage occurs, contact the factory for
directions.
Avoid breathing and contact with skin and eyes and follow these precautions:
1. For conditions of frequent use or heavy exposure, respirator protection is required.
Refer to the “NIOSH Guide to the Selection and Use of Particulate Respirators
Certified under 42 CFR 84” for selection and use of respirators certified by NIOSH.
For the most current information, NIOSH can be contacted at 1-800-356-4676 or on the
web at www.cdc.gov/niosh.
2. Wear long sleeved, loose fitting clothing, gloves and eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes separately from other laundry and rinse
washing machine thoroughly.
6. Discard used insulation in an air tight plastic bag.
NIOSH stated first aid:
Eye contact - Irrigate and wash immediately.
Breathing - Provide fresh air.
74
Section: Service and maintenance
1. Turn off the electric power and gas supply to the boiler.
2. Ensure that the boiler cools down to the surrounding temperature. Do not drain the boiler unless
freezing conditions are expected during this procedure.
3. Remove the front cover, and then remove the boiler's top panel by removing the four Torx head
screws on the top panel of the boiler.
4. A ladder or step may be required to have a clear vertical view of the work area. Do not attempt to
reach from the front without a clear view, as damage to connectors, screws or refractory may
occur.
5. Remove the screw and pull off the electrical connector from the gas valve, and disconnect the three-
Warning
After removing a burner, it is imperative that you perform a gap analysis on the ignitor.
75
6.3.3 Replacing the burner
(3) wire Molex plug from the the gas pressure switches.
6. Unscrew the four (4) bolts of the flange to separate the gas valve inlet from the gas line. Keep gasket
and bolts for re-assembly. (See l on Figure 38 .)
7. Remove the four 5/16" hex head bolts that attach the gas valve assembly to the mixing device. (See
j on Figure 38 .) These bolts should be first loosened slightly in a cross sequence to prevent
deformation of the mating parts.
8. Carefully move aside the gas valve assembly, and retain the O-ring for re-installing.
9. Remove the four (4) ¼" hex bolts that connect the mixing device to the air filter box. The gasket should
remain attached to the air filter box.
10. Remove the four (4) 10 mm hex bolts that attach the fan to the heat exchanger lid. An open-ended
wrench or socket is required.
11. With the mixing device still attached, remove the fan by pulling straight up ensuring that no wires are
caught and that the gas line remains in place. Place the removed components in a clean, dry area
12. Unplug the ignitor from the lid and place in a safe place.
13. Loosen the eight (8) 5 mm Allen lid fasteners securing the lid to the heat exchanger. Mark the
orientation of the lid onto the heat exchanger with a marker.
14. Carefully lift up on the lid and remove. Be careful not to damage the refractory insulation. Place the lid
and burner assembly in a clean dry area.
15. Carefully loosen the burner cap screws and remove. Keep the cap screws for re-installation.
16. Separate the burner from lid. Replace the burner gasket upon re-installaion.
17. Re-install the components in reverse order of the steps above.
6.4 Replacing the air filter
1.
Remove the two screws of the air filter lid, and
set aside.
2.
Remove the air filter, and replace
with a new one.
76
Section: Service and maintenance
Two replacement filters are shipped with each boiler. The air filter should be inspected and/or replaced
monthly. When replacing the air filter in the unit, use a MERV 8 filter sized at 10" x 10" x 1".
6.5 Cleaning a condensate trap
Warning
If condensate neutralization is used, check the pH
level of condensate discharge.
Never operate the boiler unless the trap is filled with
water. Failure to comply will result in severe personal
injury or death.
1.
Unscrew the union nut.
2.
Rotate the elbow sideways, so that you
can remove the condensate trap base.
77
6.5 Cleaning a condensate trap
Condensate traps should be checked every two months, cleaned
and refilled as necessary. Before cleaning the condensate trap,
you must turn off the power to the boiler, and allow it to cool down.
Important: Installers or service contractors should ensure that the
end user is instructed on cleaning and refilling the trap.
3.
Clean and flush out the debris in the condensate
trap base.
4.
Fill the condensate trap to the top
with water.
5.
Reinsert the condensate trap through the metal
plate.
6.
Rotate the elbow, and tighten the union
nut, so that elbow and condensate trap
are secured. Ensure the union nut O-ring
is included. Check for leaks.
78
Section: Service and maintenance
79
7.0 Troubleshooting
Note
The boilers are equipped with a blocked vent shutoff system, which closes the gas supply upon
detection of an irregular venting condition. In such an event, the electronic controller automatically
carries out a reset/ retry every 5 minutes.
Preliminary Troubleshooting ChecksCheck
Confirm power to the boiler: check that the touchscreen controller display is on (e.g., display is lit.
The touchscreen controller’s display will be fully functional in 90 seconds after power is restored
to the boiler.)
□
Check that the boiler is not in a safety lockout.
□
Ensure wiring is clean and secure.
□
Check that gas is reaching the unit.
□
Check the gas pressure switches.
□
Confirm that the water system is properly charged to 12 psi minimum, and that the pump is
serviceable.
□
This section includes various conditions as well as possible solutions related to the EX unit.
The troubleshooting section is divided into 3 sections:
Preliminary checks
Electronic components
Troubleshooting error messages
Often, a problem can be identified and solved through simple checks of the basics: confirming the electrical
power supply, gas flow and resetting the thermostat control.
7.1 Preliminary checks
The first step in troubleshooting this system should be a review of the touchscreen controller. There are a
number of diagnostic features incorporated in the software that evaluate system integrity, display error
conditions and provide initial remedial actions.
In addition to checking the display, the following list is a guideline for troubleshooting:
7.2 Electronic components
80
Section: Troubleshooting
This section details the method for troubleshooting the non-standard electronic components on the boiler.
7.2.1 Temperature sensors
The resistance of the temperature sensors varies inversely with temperature. To test, measure the
temperature of the sensed environment and compare with the value derived from the measurement of the
resistance (obtained by connecting a good quality test meter capable of measuring up to 5,000 kΩ
(5,000,000Ω) at the controller end of the sensor lead).
To obtain a resistance reading, remove power to the boiler. For the supply water, return water, and vent
temperature sensors, remove the wire leads by disconnecting their respective Molex connectors. Place
multi-meter probes into the sensor’s female Molex connector socket. Do not apply voltage to the sensor
as damage may result.
The supply water and vent temperature sensors each contain two separate circuits. Test each pair. Both
circuits must deliver accurate (although not necessarily identical) readings. Note that failures may occur
only within certain temperature ranges.
Temp. °F/°C
0 / -1885,362100 / 385,828
5 / -1572,918105 / 415,210
10 / -1262,465110 / 434,665
15 / -953,658115 / 464,184
20 / -742,218120 / 493,760
25 / -439,913125 / 523,383
30 / -134,558130 / 543,050
35 / 229,996135 / 572,754
40 / 426,099140 / 602,490
45 / 722,763145 / 632,255
50 / 1019,900150 / 662,045
55 / 1317,436155 / 681,857
60 / 1615,311160 / 711,689
Resist.
Ω – Ohm
Temp. °F/°C
Ω – Ohm
Resist.
65 / 1813,474165 / 741,538
Temp. °F/°C
81
7.2.2 Fan
70 / 2111,883170 / 771,403
75 / 2410,501175 / 791,281
80 / 279,299180 / 821,172
85 / 298,250185 / 851,073
90 / 357,334190 / 88983
95 / 356,532195 / 91903
Table 10 Temperature sensor resistance values - 10K ohms
Resist.
Ω – Ohm
Temp. °F/°C
Resist.
Ω – Ohm
7.2.2 Fan
Operating power is provided by means of a separate 120 VAC connector (white/black/green). Control of the
fan is provided via a four-lead connector. This connector feeds a PWM control signal (black wire) from the
controller and provides a tachometer signal (white wire) back from the fan. Unplugging the control connector
will cause the fan to go to high speed and trigger a “Blocked Vent Error” within 6 seconds if the boiler is
operating.
7.2.3 Air pressure sensor
The air pressure sensor monitors air flow in the venting system. If airflow through the combustion air intake or
the exhaust vent becomes too restricted for safe operation, the boiler will stop firing, and display a "Fan
Pressure Error". Also, to prevent avoidable Fan Pressure Errors, the system decreases the fan speed if the
reading from the sensor nears the error threshold.
7.2.4 Water pressure sensor
The water pressure sensor ensures that there is adequate pressure in the heating system for safe operation.
The pressure is displayed in PSI as the default. If the system pressure should drop below 8PSI the firing rate
of the boiler is reduced. If the pressure drops to 4PSI or lower, the boiler will not fire.
Check the operation of the sensor by isolating the boiler from its system piping, and close the system fill
valve, and then crack the pressure relief valve. The pressure displayed should reflect declining pressure. If it
remains “fixed”, drain the boiler and replace the sensor, or dislodge any blocking debris from the sensor inlet
channel and reinsert.
7.2.5 Gas pressure switches
Warning
Do not attempt to adjust the High or Low pressure switch.
82
Section: Troubleshooting
The high and low gas pressure switches help protect the boiler from gas pressures outside of the
acceptable range of operation. To view the location of the pressure switches on the EX series boilers, see
Figure 38
The low gas pressure switch is pre-calibrated, and will trip when the inlet gas pressure falls below
3.5" w.c.
The high gas pressure switch is pre-calibrated and will trip when the inlet gas pressure rises
above 15" w.c.
You must reset the low gas pressure switch after the gas to the boiler is connected and turned on. To
“reset” either the low or high gas pressure switch, press on the clear plastic cover above the Red button.
If either the high or low gas pressure switch trips, the boiler controller will show a Red bar at the bottom of
the screen and indicate “Low/High Gas Pressure”.
7.2.6 Safety and Ignition Module (SIM)
The SIM is a safety control used in EX. It is certified to conform to the UL 60730-5-5 and ANSI Z21.202014 • CAN/CSA-C22.2 No. 60730-2-5-14 standards.
The module controls the boiler’s gas valve, including:
Direct spark automatic ignition
Flame detection and current measurement
Supply water temperature sensing
Flue gas temperature sensing
Supply water maximum temperature shutdown
Flue gas maximum temperature shutdown
Low water cut-off.
The SIM continuously communicates with the boiler’s main controller reporting sensor readings and
status. The sensor readings and error status, if any are displayed on the boiler controller’s screen.
7.2.6.1 Table showing LED operating status
83
7.2.6 Safety and Ignition Module (SIM)
Its two status LEDs indicate the operating status as shown in the table below.
SIM Status Indicators
LED 1LED 2State
Rapid flashPower up or resetting startup checks and initialization
OffOffStandby
OffOnPre-purge or inter-
purge
OnOnHeating
Rapid flashOnIgniting
OffFlashingLockout
Flash alternately with
LED 2
Table 11 SIM LED status Indicators
Flash alternately with
LED 1
Fail-safeBoiler requires a power cycle
Description, LED status
indication
LED 1 Off=flame or sparking
LED 2 = Burner-on call state
LED 1 Off=no flame or sparking
LED 2 = Burner-on call state
7.2.6.2 Low water cutoff function: reset and test
The low water cutoff (LWCO) function provides continuous protection against a low water incident.
If the SIM detects a low water incident, the boiler goes into a lockout condition. To clear the lockout condition
in the controller, go to Diagnostics>Advanced Diagnostics>Clear Errors. To test the LWCO on the boiler,
you can also manually place the boiler in a lockout condition.
7.2.6.3 Resetting the boiler after a LWCO lockout
Before you reset the boiler, ensure that the boiler is pressurized and that the air has been removed.
1. On the touchscreen controller, tap the Home screen.
2. On the Main Menu, tap the Diagnostics button.
3. Tap the Advanced Diagnostics button.
84
Section: Troubleshooting
4. Tap the Clear Errors button.
5. Tap the Yes radio button, and then tap OK.
The system clears the errors, and resets the boiler.
7.2.6.4 Testing the LWCO function
1.
Press and hold the LWCO Test button for 5 seconds (located on top of the electrical box).
A message on the screen indicates that the boiler is in lockout mode.
2. On the touchscreen controller, select the Reset button.
The message: "The SIM Module has been reset" is displayed.
3. Tap the Close button, and then tap the Back button until you return to the Home screen.
7.2.6.5 Water Temperature function: reset and test
The hi-limit temperature function monitors the hi-limit temperature set in the SIM. If the water temperature
exceeds the hi-limit temperature, the boiler goes into a lockout condition (locks), requiring a manual reset.
You can test the hi-limit cutoff temperature function on the boiler.
Resetting the boiler after a Hi-Limit lockout
Before you reset the boiler, ensure that the boiler is pressurized and that the air has been removed.
1. On the touchscreen controller, tap the Home screen.
2. On the Main Menu, tap the Diagnostics button.
3. Tap the Advanced Diagnostics button.
4. Tap the Clear Errors button.
5. Tap the Yes button, and then tap OK.
The system clears the errors, and resets the boiler.
Testing the Hi-Limit cutoff temperature function
1. On the touchscreen controller, tap the Home screen.
2. On the Main Menu, tap the Diagnostics button.
3. Tap the SIM Module button.
4. Tap the Hi-Limit Test button.
Warning
Never attempt to repair the control module (circuit board). If the control module is defective,
replace it immediately.
85
7.3 Troubleshooting error messages
You will need to enter a cutoff temperature below the Supply Temp. value currently displayed. For
example, if the Supply Temp. value is 180°F, enter 170°F in the Cut Off Temp. box.
5. Tap inside the Cut-Off Temp. box, and then tap a number value.
6.
Tap the OK button.
The message: "Hi-Limit Detected" is displayed.
7.
To reset the boiler, select the Reset button. The cutoff value reverts to normal upon reset.
The message: "The SIM module has been reset" is displayed.
8. Tap the Close button, and then tap the Back button until you return to the Home screen.
7.3 Troubleshooting error messages
Errors shown on the touchscreen controller are described below as well as diagnoses and fixes.
7.3.1 Touchscreen error messages
The bottom line of the touchscreen displays the boiler's error status. The following colors represent the
boiler's operating status:
Green – Normal
Yellow – Warning
Red – Alarm
The text inside the bar will indicate the specific warning or alarm. If there is more than one alarm present the
text will scroll slowly through all current alarm conditions. Besides the errors listed below, see also
Miscellaneous touchscreen controller errors on page 88.
7.3.2 Maximum ignition trials error
Maximum Ignition Trials Error
IssueDiagnosisFix
Error – Ignition Failure after 3
tries boiler has failed to ignite
on 3 successive attempts.
Boiler is in lockout for 1 hour,
then repeats 3-try sequence.
Consult service technician if
error recurs.
No spark when igniting.
Ignition probe/flame
sensor disconnected.
Check that ignition lead is secure at the
control module and at the probe.
Manual gas shutoff is
closed or gas line not
fully purged.
Check for gas flow. Open manual gas
shutoff and reset boiler.
Gap between ignition
probe rods is too large
or too small.
Adjust ignition probe rod gap between ⅛
and 3/16th (3.2-4.7 mm).
Spark, but no ignition.Check spark module is sending power to
gas valve – close gas supply, then
disconnect (black) electric housing from
face of gas valve, gently spread plastic tabs
to open, and look for 24vac voltage during
an ignition cycle. Replace module if no
current detected
Boiler ignites, but shuts
off at the end of the
ignition trial. Improperly
grounded pressure
vessel/burner or
unserviceable ignition
lead or spark module.
Ensure the pressure vessel is grounded.
Check the ignition probe/flame sensor is
electrically isolated from the vessel, and its
ceramic insulator is intact. Replace ignition
lead Replace spark module.
86
Section: Troubleshooting
7.3.3 Hi/Low gas pressure switch error
87
7.3.3 Hi/Low gas pressure switch error
High/Low Gas Press Error
IssueDiagnosisFix
Error – High/Low Gas PressInlet gas pressure has risen
above 15" w.c. or has fallen below
3.5" w.c.
7.3.4 Hi Limit cut-off temperature error
Hi Limit cutoff temperature Error
IssueDiagnosisFix
Error – Water High-Limit
Exceeded
Water temperature exceeds hi-limit. Boiler is in hard
lockout mode.
7.3.5 Low Water Cut-off error
Measure the inlet gas pressure.
Reset the switch.
See Water
Temperature
function:
reset and
test on page
84.
Low Water Cutoff Error
IssueDiagnosisFix
Error - Low Water CutoffThe Safety and Ignition module
has detected a low water
condition.
See Low water cutoff function:
reset and test à la page 83.
7.3.6 Aux. Interlock 1 or 2
88
Section: Troubleshooting
IssueDiagnosisFix
Aux. Interlock 1 or 2
Interlock 1 or 2 terminals are
open.
Jumper lead is loose or
compromised.
External safety is in an alarm state. Inspect the external safety
Gas Supply Pressure (high fire) ____ Inches w.c. Measured Rate of Input (high fire) _____Btu/hr
□Leak testing completed □ Gas piping □ Venting system □ Fan □ combustion components
□System Cleaned and Flushed (type of cleaner used) __________________________________
□System Filled (type/concentration of any glycol/chemicals used) _________________________
□Air purge completed
□Relief Valve correctly installed and piped Relief valve “try lever” test performed
□Condensate trap filled Condensate drain clear and free flowing Condensate Neutralization.
□Ignition Safety Shutoff test completed. Flame current reading - High fire _____ µA - Low fire _____ µA
□Owner advised and instructed in the safe operation and maintenance of the boiler and system.
□Information regarding the unit and installation received and left with owner
Combustion Readings:
CO2_____________ % O2______________ % CO ____________ ppm
Flue temperature ___ Return water temperature (measure simultaneously with flue temp.) _____
Commissioning has been completed as listed on this report - Installer Signature _____________
Installers: send this completed sheet - Fax to 604 877 0295 - or - scan and Email to info@ibcboiler.com.
Boiler parts diagram
Item
Number
DescriptionPart NumberReplacement Kit Numbers
10Door500-134P-1209
20Controller500-044P-242
30Safety Ignition Module500-105P-270
40Top panel251-030P-1227
50Controller module chassis251-042P-1228
60Gas valve relay240-165P-1233
70Boiler pump relay240-165P-1233
80Transformer240-008P-9059
90Air pressure sensor (behind
controller)
240-162P-1210
100Vessel high limit switch (behind
controller)
240-030P-9070
97
Boiler parts diagram
Item
Number
DescriptionPart NumberReplacement Kit Numbers
Wiring harness (not shown)P-1232
Item NumberDescriptionPart NumberReplacement Kit Number
150Fan240-156P-1212
160Fan gasket255-126
98
Section: Appendices
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.